RAB Lighting is committed to creating high-quality, affordable, well-designed, and energy-efficient LED lighting and controls that make it easy for electricians to install and end users to save energy. We’d love to hear your comments. Please call the Marketing Department at 888-RAB-1000 or email: marketing@rablighting.com.

IMPORTANT

READ CAREFULLY BEFORE INSTALLING THE FIXTURE. RETAIN THESE INSTRUCTIONS FOR FUTURE REFERENCE.
RAB fixtures must be wired in accordance with the National Electrical Code and all applicable local codes. Proper grounding is required for safety. THIS PRODUCT MUST BE INSTALLED IN ACCORDANCE WITH THE APPLICABLE INSTALLATION CODE BY A PERSON FAMILIAR WITH THE CONSTRUCTION AND OPERATION OF THE PRODUCT AND THE HAZARDS INVOLVED.

  • WARNING: Make certain power is OFF before installing or maintaining the fixture. No user-serviceable parts inside.
  • CAUTION: For proper weatherproof function all gaskets must be seated properly and all screws inserted and tightened firmly. Apply weatherproof silicone sealant around the edge of the ceiling mounting box and/or junction box. This is especially important with an uneven ceiling surface. Silicone all plugs and unused conduit entries.

MOUNTING

CEILING MOUNTING

The fixture is suitable for outdoor applications in wet locations.

  1. Loosen Screws (2) to free Junction Box from LED Housing. Remove NPS Adaptor as marked (Fig. 2) if mounting directly to the ceiling surface without a junction box.
  2. Mount Junction Box to the ceiling by knocking out (4) Knock Out Locations as marked in Fig. 3. Use the appropriate mounting hardware for the mounting surface. May alternately be mounted to recessed junction boxes.
  3. For hands-free wiring, hang the fixture on the EZ Hang Hook as shown in Fig 1. Connect supply wires to Fixture Wires. Supply can come from the back or through either of four 1/2” Plugs to make electrical splices. Use appropriate UL-approved wire connectors as required by the code to complete wiring.
  4. Close the fixture and tighten Screws (2).
  5. If the mounting surface is irregular, use caulk to seal any gaps around Junction Box.
PENDANT MOUNTING

The fixture can be mounted to a 1/2” or 3/4” NPS Pendant. A 1/2” to 3/4” NPS Adaptor is included.

  1. Feed supply wires through Pendant (supplied by others)
  2. Loosen Screws (2) on LED Housing.
  3. Remove the 1/2” plug and mount Junction Box to Pendant. For the 3/4” Pendant, remove the plug and NPS Adaptor. Hang LED fixture with EZ Hang Hook as shown in Fig. 1
  4. Make supply connections wiring sections as shown in the Ceiling Mounting section above.
  5. Close the fixture and tighten the Screws (2).RAB-PORTO-Garage-Light-fig-1

KNOCK OUT LOCATIONS

RAB-PORTO-Garage-Light-fig-2

ON-OFF WIRING

Universal voltage driver permits operation at 120V thru 277V, 50 or 60 Hz. Units ordered with (/480V) suffix are 480V, 50Hz or 60Hz. For non-dimming, follow the wiring directions in Fig. 4.

  1. Connect the black fixture lead to the LINE supply lead.
  2. Connect the white fixture lead to the COMMON supply lead.
  3. Connect the GROUND wire from the fixture to the supply ground.

Note:
These instructions do not cover all details or variations in equipment nor do they provide for every possible situation during installation, operation or maintenance.

0-10V DIMMABLE WIRING

Universal voltage driver permits operation at 120V thru 277V, 50 or 60 Hz. Units ordered with (/480V) suffix are 480V, 50Hz or 60Hz. For 0-10V Dimming follow the wiring directions shown in Fig. 5.

  1. Connect the black fixture lead to the LINE supply lead.
  2. Connect the white fixture lead to the COMMON supply lead.
  3. Connect the GROUND wire from the fixture to the supply ground. Do NOT connect the GROUND of the dimming fixture to the output.
  4. Connect the purple fixture lead to the (V+) DIM lead.
  5. Connect the pink (or gray) fixture lead to the (V-) DIM lead.
  6. Cap the yellow fixture lead, if present. Do NOT connect.RAB-PORTO-Garage-Light-fig-4

TROUBLESHOOTING

  1. Check that the line voltage at the fixture is correct. Refer to wiring directions.
  2. Be sure the fixture is grounded properly.
  3. Is the photocell, if used, functioning properly?

CLEANING & MAINTENANCE

CAUTION:
Be sure the fixture temperature is cool enough to touch. Do not clean or maintain while the fixture is energized.

  1. Clean polycarbonate lenses with a non-abrasive cleaning solution.
  2. Do not open the fixture to clean the LEDs. Do not touch the LEDs.

Hello
The Lightcloud Luminaire Sensor is a dual-technology motion detector and closed-loop daylight harvester that can switch and dim both local and remote circuits. The Luminaire Sensor requires a compatible light cloud controller or fixture.

Specifications

PART NUMBER

  • Edge: LCLCSENSE/EG
  • Standard: LCLCSENSE/SH
  • High Bay: LCLCSENSE/HB

INPUT
5VDC

OPERATING TEMPERATURE
-40°C to 40°C

DIMENSIONS

  • Ceiling Mount: 2.25”W x 1.74”H x 2.25”D
  • Edge: 1.30”W x 0.99”H x 2.34”D
  • Standard: 1.20”W x 1.05”H x 1.20”D
  • High Bay: 1.75”W x 1.08”H x 1.75”D

SENSOR COVERAGE

  • Edge: 20 ft. diameter at 9 ft.
  • Standard: 30 ft. diameter at 9 ft.
  • High Bay:
    • 40 ft. diameter at 30 ft.
    • 50 ft. diameter at 45 ft.

MOUNTING HEIGHT

  • Edge: 8 to 12 ft.
  • Standard: 8 to 12 ft.
  • High Bay: 25 to 45 ft.

CONNECTOR
RJ9 (RJ22)

RATING

  • Standard and High Bay: IP66

Setup & Installation

  1. Remove Bezel
    Twist counter-clockwise.

  2. Prepare Mounting Hole
    Use knockout or cut hole for the sensor. Holes have +/- 1/8 in. tolerance .RAB-PORTO-Garage-Light-fig-6

  3. Installing the Sensor

  4. Ceiling Mount
    Place gasket and sensor into ceiling mount. Screw the bezel onto the sensor from below the ceiling.RAB-PORTO-Garage-Light-fig-7
    Fold up tabs on the ceiling mount and push through a hole cut in step 2.

  5. In-Fixture Mounting
    Place the gasket and sensor through the hole cut in step 2.RAB-PORTO-
Garage-Light-fig-8

  6. Connect the Sensor

    • Controller: Use the adapter to connect the sensor to the Controller.RAB-PORTO-Garage-Light-fig-9
    • Lightcloud Driver: Plug the sensor into the sensor port on the driver.RAB-PORTO-Garage-Light-fig-10

If a longer cable is needed, an extension cable (RJ9) up to 10 ft. can be used.

Configuration

To configure, the Luminaire Sensor, please log in to the Web App at control.lightcloud.com or call Lightcloud Support at 1(844) Lightcloud.

For additional startup information, please visit lightcloud.com/start.

Sensor Coverage

RAB-PORTO-Garage-Light-fig-11

© RAB Lighting, Inc. 2020
170 Ludlow Ave., Northvale, NJ 07647 Custom manufactured in China.

WE’RE HERE TO HELP:
1 (844) LIGHTCLOUD or 1 844-544-4825.

References

Read User Manual Online (PDF format)

Loading......

Download This Manual (PDF format)

Download this manual  >>

Related Manuals