SENECA Z-4AI 4-Channel Analog Input Module Instruction Manual

June 9, 2024
SENECA

SENECA Z-4AI 4-Channel Analog Input Module

PRELIMINARY WARNINGS

The word WARNING preceded by the symbol indicates conditions or actions that put the user’s safety at risk.
The word ATTENTION preceded by the symbol indicates conditions or actions that might damage the instrument or the connected equipment. The warranty shall become null and void in the event of improper use or tampering with the module or devices supplied by the manufacturer as necessary for its correct operation, and if the instructions contained in this manual are not followed.

  • WARNING: The full content of this manual must be read before any operation. The module must only be used by qualified electricians. Specific documentation is available via QR-CODE shown on page 1.
  • The module must be repaired and damaged parts replaced by the Manufacturer. The product is sensitive to electrostatic discharges. Take appropriate measures during any operation.
  • Electrical and electronic waste disposal (applicable in the European Union and other countries with recycling). The symbol on the product or its packaging shows the product must be surrendered to a collection centre authorized to recycle electrical and electronic waste.

SENECA s.r.l.; Via Austria, 26 – 35127 – PADOVA – ITALY; Tel. +39.049.8705359 – Fax +39.049.8706287

CONTACT INFORMATION

Technical support: [email protected]

Product information: [email protected]

This document is the property of SENECA srl. Copies and reproduction are prohibited unless authorised. The content of this document corresponds to the described products and technologies.
Stated data may be modified or supplemented for technical and/or sales purposes.

MODULE LAYOUT

Dimensions LxHxD: 17.5 x 102.5 x 111 mm; Weight: 110 g; Enclosure: PA6, black

SIGNALS VIA LED ON FRONT PANEL

LED STATUS LED meaning
PWR Green ON The device is powered correctly
FAIL yellow Flashing Anomaly or fault
RX Red Flashing Receipt of packet completed
RX Red ON Anomaly / Check connection
TX Red Flashing Transmission of packet completed

TECHNICAL SPECIFICATIONS

CERTIFICATIONS

|

https://www.seneca.it/products/z-4ai/doc/CE_declaration

---|---

INSULATION

|

WARNING
the maximum working voltage between any
terminal and ground must be less
than 50Vac / 75Vdc

____

ENVIRONMENTAL CONDITIONS

| Temperature: __ -10 ÷ + 65°C

Humidity: __ 30% ÷ 90% non condensing.

Altitude: __ Up to 2000 m above sea level

Storage temperature: -20 ÷ + 85°

Protection rating: IP20.

ASSEMBLY| IEC EN60715, 35mm DIN rail in vertical position.

CONNECTIONS

| 3-way removable screw terminals, pitch 5 mm Rear connector IDC10 for DIN bar 46277 front micro USB
POWER SUPPLY| Voltage: 10 ÷ 40Vdc; 19 ÷ 28Vac 50 ÷ 60Hz Absorption: Typical: 0.5W @ 24Vdc, Max: 3.5W
INPUTS

Voltage input:| Bipolar with F.S. programmable at +2Vdc and +10Vdc Input impedance >100kOhm
Current input:| Bipolar with F.S. Programmable at +20mA with 50Ohm internal shunt selectable via DIP-switch. Available power supply: 90 + 90mA at 13Vdc.
Number of channels:| 4
Input resolution:| 15 bit + sign.
Input protection:| ± 30Vdc or 25mA
Voltage and current precision:| Starting: 0.1 % of full scale Linearity: 0.03% of scale. Zero: 0.05% of scale.

TC: 100 ppm, EMI: <1 %

Sampling time| 120ms/channel or 60ms/channel
Measurement update times| –  250ms for 4 channels with ADC speed 1 sample every 60ms

–  500ms for 4 channels with ADC speed 1 sample every 120ms

Filter| configurable from 0 to 6

CONFIGURATION OF FACTORY SETTINGS

All DIP-switches in| OFF|  |
---|---|---|---
Communication parameters of ModBUS protocol:| 38400 8, N, 1 Address 1
Communication parameters of micro USB front port| 2400 8, N, 1 Address 1
Channel input from 1 to 4| VOLTAGE ± 10 Vdc
Numerical representation of the input measurement:| ± 10000 mV
Sampling time:| 120 ms

ModBUS CONNECTION RULES

  1. Install the modules in the DIN rail (120 max)
  2. Connect the remote modules using cables of an appropriate The following table shows cable length data:
  3. Bus length: maximum length of the Modbus network according to the Baud Rate. This is the length of the cables that connect the two farthest modules (see Diagram 1).
  4. Derivation length: maximum length of a derivation 2 m (see Diagram 1).

SENECA Z-4AI 4-Channel Analog Input Module-fig7For maximum performance, it is recommended to use special shielded cables, such as BELDEN 9841

IDC10 CONNECTOR

Power supply and Modbus interface are available using the Seneca DIN rail bus, via the IDC10 rear connector, or the Z-PC-DINAL2-17.5 accessory.

Rear Connector (IDC 10)
The meaning of the various pins on the IDC10 connector is shown in the figure if you wish to supply signals directly via it.

SETTING THE DIP-SWITCHES

The position of the DIP-switches defines the Modbus communication parameters of the module: Address and Baud Rate The following table shows the values of the Baud Rate and the Address according to the setting of the DIP-switches:

SENECA Z-4AI 4-Channel Analog Input Module-fig9

Note: When DIP switches 3 to 8 are OFF, the communication settings are taken from programming (EEPROM).
Note 2: The RS485 line must be terminated only at the ends of the communication line.
The settings of the dip-switches must be compatible with the settings on the registers.
The description of the registers is available in the USER MANUAL.

ANALOGUE INPUT SETTING VIA DIP-SWITCH:
DIP-Switch SW2 defines the type of input for each individual channel. Channels 1 to 4 can be set in current or voltage.
For the settings, refer to the SW2 table on the side.

ELECTRICAL CONNECTIONS

Power supply
The upper limits must not be exceeded as this can seriously damage the module. If the power supply source is not protected against overload, a safety fuse with a 2.5A max permissible value must be installed in the power supply line.

ModBus RS485
Connection for RS485 communication using the MODBUS master system as an alternative to the Z-PC-DINx bus.
N.B. The indication of the RS485 connection polarity is not standardised and in some devices may be inverted.

INPUTS

SENECA Z-4AI 4-Channel Analog Input Module-fig13

  • A) Voltage input with sensor supply from the MODULE (13 Vdc)
  • B) Voltage input with sensor supply NOT coming from the MODULE
  • C) Current input with sensor supply NOT coming from the MODULE
  • D) Current input with sensor supply from the MODULE (13 Vdc)
  • E) Current input with EXTERNAL sensor supply

ATTENTION
The upper power supply limits must not be exceeded, as this might cause serious damage to the module. Switch the mod-ule off before connecting inputs and outputs.
To meet the electromagnetic immunity requirements:

  • use shielded signal cables;
  • connect the shield to a preferential instrumentation earth system;
  • separate shielded cables from other cables used for power installations (inverters, motors, induction ovens, etc…).
  • make sure that the module is not supplied with a supply voltage higher than that indicated in the technical specifications in order not to damage it.