LITHONIA LIGHTING LED Combo Exit and Emergency Light Instruction Manual
- June 9, 2024
- LITHONIA LIGHTING
Table of Contents
INSTALLATION INSTRUCTIONS
LED COMBO EXIT & EMERGENCY LIGHT
READ AND FOLLOW ALL SAFETY INSTRUCTIONS
WARNING: FAILURE TO FALLOW THESE INSTRUCTIONS AND WARNINGS MAY RESULT IN
DEATH, SERIOUS INJURY OR SIGNIFICANT PROPERTY DAMAGE. For your protection,
read and follow these warnings and instructions carefully before installing or
maintaining this equipment. These instructions do not attempt to cover all
installation and maintenance situations. If you do not understand these
instructions or additional information is required, contact LITHONIA or your
local LITHONIA distributor.
WARNING: RISK OF ELECTRIC SHOCK – NEVER CONNECT TO, DISCONNECT FROM, OR
SERVICE WHILE EQUIPMENT IS ENERGIZED.
WARNING: RISK OF FIRE. Lamps are hot. Keep combustible material away from
hot parts. Observe lamp manufacture’s warnings, recommendations and
restrictions on lamp operation and maintenance. Make sure lamps are correctly
installed.
CAUTION: The battery in this unit may not be fully charged. After
electricity is connected to unit, let battery charge for at least 24 hours,
then normal operation of this unit should take effect. To check, press the
TEST button. The lamps on the unit should turn on.
IMPORTANT SAFEGUARDS: When using electrical equipment, basic safety
precautions should always be followed, including the following:
- Do not use outdoors.
- Consult local building code for approved wiring and installation.
- Disconnect AC power before servicing and installation.
- Do not mount near gas or electric heaters.
- Do not use this equipment for anything other than its intended use.
- The use of accessory equipment not recommended by the manufacturer will void product listing and warranty and may cause an unsafe condition.
- Any service on this equipment should be performed by qualifi ed personnel only.
- Equipment should be mounted in locations and at heights where it will not be subject to tampering by unauthorized personnel.
- Use caution when servicing batteries.
- Cap unused wires with enclosed wire nuts or other approved method.
- Make sure wire terminations are secure and leads are properly tucked in appropriate wire channels
NOTE: Max mounting height is 8.5 ft to achieve at least 1 ft-candle of
illuminance in emergency mode.
INSTALLATION INSTRUCTIONS (back mount):
- Remove EXIT stencil from housing, set aside.
- Drill or knock out appropriate knockouts on back plate to fi t junction box mounting points.
- Drill or knock out center hole in back plate for EXIT supply wire leads.
- Route EXIT supply wires through center hole of the back plate and make wiring connection. For 120V, use black and white wires and for 277V, use red and white wires. WARNING: Properly insulate the unused lead with a wire nut (provided) or other approved means.
- Secure back plate to junction box (hardware not included).
- Remove proper chevron(s) as required. When removing chevrons it may be helpful to remove the color diffuser panel to allow easier access to the chevrons. If removing color diffuser panel it is important to remember to reinstall the diffuser panel, securing with diffuser retention caps once chevron(s) have been removed.
- Connect battery only after continuous AC power can be provided to the unit.
- Apply continuous AC power and press “TEST” button to check operation.(See operation (battery back-up) for testing procedures)
SAVE THESE INSTRUCTIONS
and deliver to owner after installation
INSTALLATION INSTRUCTIONS (top mount):
-
Remove EXIT stencil from housing, set aside.
-
Place screws (provided) in holes on the canopy.
-
Remove the mounting hole plug located on the top of the housing.
-
Route EXIT supply wires through mounting hole in top of the housing. Route EXIT supply wires through mounting canopy. Dress wires carefully through housing.
-
Route wires from junction box through metal mounting plate. Secure mounting plate to junction box (hardware not included).
-
Make wiring connection. For 120V, use black and white wires and for 277V, use red and white wires.
WARNING: Properly insulate the unused lead with a wire nut (provided) or other approved means. -
Push wire connections through middle metal plate and into the J-Box.
-
Secure the canopy to the steel mounting plate with screws installed in step 2.
-
Remove proper chevron(s) as required. When removing chevrons it may be helpful to remove the color diffuser panel to allow easier access to the chevrons. If removing color diffuser panel it is important to remember to reinstall the diffuser panel, securing with diffuser retention caps once chevron(s) have been removed.
-
Connect battery only after continuous AC power can be provided to the unit.
-
Secure face plate(s) to the housing.
-
Apply continuous AC power and press “TEST” button to check operation.(See operation (battery back-up) for testing procedures)
INSTALLATION INSTRUCTIONS (side mount):
-
Remove EXIT stencil from housing, set aside.
-
Place screws (provided) in holes on the canopy.
-
Remove the lamp head from the housing on the desired mounting position. Disconnect the lamp head wires from the lamp pc board. Set lamp head aside.
-
Route EXIT supply wires through mounting hole in side of the housing where the lamp head was removed. Route EXIT supply wires through mounting canopy. Dress wires carefully through housing.
-
Route wires from junction box through metal mounting plate. Secure mounting plate to junction box (hardware not included).
-
Make wiring connection. For 120V, use black and white wires and for 277V, use red and white wires.
WARNING: Properly insulate the unused lead with a wire nut (provided) or other approved means. -
Push wire connections through middle metal plate and into the J-Box.
-
Secure the canopy to the steel mounting plate with screws installed in step 2.
-
Remove proper chevron(s) as required. When removing chevrons it may be helpful to remove the color diffuser panel to allow easier access to the chevrons. If removing color diffuser panel it is important to remember to reinstall the diffuser panel, securing with diffuser retention caps once chevron(s) have been removed.
-
Connect battery only after continuous AC power can be provided to the unit.
-
Secure face plate(s) to the housing.
-
Apply continuous AC power and press “TEST” button to check operation.(See operation (battery back-up) for testing procedures)
INSTALLATION (relocation of lamp head to top of housing):
- Remove the mounting hole plug located on the top of the housing.
- Snap lamp head that was removed from the side of the housing into the mounting hole plug located on the top of the housing.
- Route lamp head wires through housing channels and make connection on the lamp pc board.
OPERATION (battery backup):
- Apply AC power to the unit. The LED indicator will be RED.
- After the battery has been left to charge for 24 hours, test the unit by pushing the switch. The LED indicator turns OFF and the LED board stays ON.
- When the switch is released, the LED indicator turns back to RED and the LED board stays ON.
MAINTENANCE:
CAUTION: Always turn off AC power to the equipment before servicing.
Servicing should be performed only by a qualified service technician. Use only
MANUFACTURER supplied replacement parts.
BATTERY: The battery supplied with the EL model requires no maintenance.
However, it should be tested periodically and replaced when it no longer
operates the connected sign for the duration of a 30-second or 90-minute test.
The battery supplied in this sign has a typical life of 5 years when used in a
normal ambient temperature of 72° F.
WIRING DIAGRAM:
Lithonia Emergency
One Lithonia Way, Conyers GA 30012
Phone: 800-334-8694
www.lithonia.com
Part #EMCSA00802 Rev. F
2018.10.31
References
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>