Phason Plus Touch Series Advanced Ventilation Control User Guide
- June 9, 2024
- Phason
Table of Contents
Phason Plus Touch Series Advanced Ventilation Control
OVERVIEW
(A) Display cable
Disconnect the cable during installation. Reconnect it when done.
(B) Voltage switch
Set the switch to the correct line voltage.
(C) Incoming power
Connect the incoming power from the panel.
(D) Temperature probe (TEMP1 to TEMP4)
Connect the primary temperature probe to TEMP1. Connect any
additional probes to the other terminals.
(E) Actuator feedback (ACT-1 and ACT-2)
Connect the feedback potentiometer from the actuator.
(F) Alarm relay
Connect an external alarm system or siren.
(G) General-purpose relays (STG-1 to STG-6)
Connect single-speed/stage heating/cooling equipment.
(H) Variable stages (VAR-1 and VAR-2)
Connect variable speed fans
(I) Fuses (F1 and F2)
The fuses are for the variable stages. F1 is for VAR-1 F2 is for VAR-2.
(J) USB
Connect a USB drive when saving or loading settings, or updating
firmware.
(K) OUTDOOR
Connect a Phason 3K Temperature Sensor for measuring outdoor temperature.
(L) +5V
Can provide +5 VDC
(M) DOL (M: AUX1 to AUX3)
Connect DOL119 Carbon Dioxide or DOL 53 Ammonia Sensors. Place the jumpers on
the correct pins.
(N) DOL 114 (TEMP / HUM)
Connect a DOL 114 Temperature and Humidity Sensor. BPlace the jumpers on the
correct pins.
(O) Pulse counter (COUNT)
Not available, used for future development.
Electrical ratings
Input power
120/230 VAC, 50/60 Hz
Variable stages (2: VARI-1, VARI-2)
10 A at 120/230 VAC, general-purpose (resistive) 7 FLA at 120/230 VAC, PSC
motor 1/2 HP at 120 VAC, 1 HP at 230 VAC, PSC motor
Fuses (2: F1and F2)
15 A, 250 VAC ABC-type ceramic
Relay stages (6: STG-1 to STG-6)
10 A at 120/230 VAC, general-purpose (resistive) 1/3 HP at 120 VAC, 1/2 HP at
230 VAC 360 W tungsten at 120 VAC
Alarm relay
0.4 A at 125 VAC; 2 A at 30 VDC, resistive load 0.2 A at 125 VAC; 1 A at 30
VDC, inductive load
MOUNTING HOLES AND ORIENTATION
CUSTOMER SUPPORT
www.phason.ca
sales@phason.ca
International: 204-233-1400 Toll-free
North America: 800-590-9338
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>