Phason FC-1T-1F Fixed-Stage Fan or Heater Controller User Manual
- June 9, 2024
- Phason
Table of Contents
FC-1T-1F Fixed-Stage Fan or Heater
Controller
User Manual
FC-1T-1F Fixed-Stage Fan or Heater Controller
FC-1T-1F user manual
The FC-1T-1F automatically controls the temperature in a room by switching
fans, lamps, or heaters on or off as the temperature drops below or exceeds
the temperature set point. When the SSC-1 D is in cooling mode, it switches on
the fans when the temperature exceeds the set point. When the control is in
heating mode, it switches on the lamps or heaters when the temperature drops
below the set point.
Features
- One solid-state relay
- Heat and cool modes
- Adjustable temperature set point, 32 to 99°F (0 to 37°C)
- Fahrenheit and Celsius display
- Six-foot temperature sensor (extendable)
- Error code display for troubleshooting
- Overload protection fuse
- Rugged, NEMA 4X enclosure (corrosion resistant, water resistant, and fire retardant)
- CSA approval
- Two-year limited warranty
Installation
- **** Switch OFF the power at the source before connecting the incoming power wires.
- DO NOT switch on the power until you have finished all wiring and verified all equipment is properly connected and free of obstructions.
Electrical ratings
- Input: 120/230 VAC, 50/60 Hz
- Relay: 10 A at 120/230 VAC, general-purpose (resistive) 1/3 HP at 120 VAC, 1/2 HP at 230 VAC 360 W tungsten at 120 VAC
- Fuse. 15 A, 250 VAC ABC-type ceramic
Temperature display units
Mode of operation
- Set the voltage switch to the correct position for the line voltage used, 120 or 230 VAC.
- Connect the wires as shown in the diagram.
Startup When the control powers up:
- 88 will display for 0.25 seconds (start-up).
- 00 will display for 1 second (self-test).
- 60 will display for 1 second. The 60 means that the frequency is 60 Hz.
- The display will flash between the temperature and PF (power failure). Dick the switch to the right to clear the message.
Display alerts
| The temperature sensor cable has short circuited.
---|---
| The temperature sensor is damaged or the connecting wire is broken.
| The Temperature knob has been tumed. The display will alternately flash and
the ambient temperature. The control will not Es accept the new setting until
the switch is cocked to the set position.
OR
The voltage switch Is set to 230 but the Incoming power is 120 volts. Make
sure the voltage switch is in the correct position.
| There has been a power failure. The display will flash between the
temperature and Click the switch to the right to clear the r message.
Programming
Switch position | Function | |
---|---|---|
CENTER | Displays the ambient temperature | |
RIGHT | Allows you to view and adjust the temperature set point o Clears |
alarms
LEFT| | Allows you to verify if the control is in heating or cooling mode
Allows you to verify if the control is displaying Fahrenheit or Celsius
Temperature set point
The FC-1T-1 F controls the temperature in a room by switching fans, lamps, or
heaters on or off as the temperature drops below or exceeds the temperature
set point. The set point is the desired room temperature and can be set
between 32 and 98°F (0 and 38°C).
♦ In cooling mode, the control switches on the load when the temperature
exceeds the set point.
♦ In heating mode, the control switches on the load when the temperature drops
below the set point.
To adjust the setpoint
- Click the switch to the right and hold.
- Adjust the TEMPERATURE knob to the desired setting.
NOTE
You must hold the switch in the set position while turning the TEMPERATURE
knob. If this is not done correctly, the display will flash between t 5 and
the temperature display, indicating the knob has accidentally been turned. The
control will not accept the new setting until the switch is clicked to the
right.
FC Series model| Replaced models| Interface| Fixed stages|
Variable stages| Control
---|---|---|---|---|---
FC-1VAC| MSC-4| Dial| 0| 1| Manual
FC-1T-1VAC| MTC-4C| Dial| 0| 1| Temperature
FC-1T-1VDC| SSV – DC| 3-digit LED. dial| 0| 1(DC)| Temperature
FC-1T-1F| SSC -ID| 2-digit LED. dial| 1- heat or cool| 0| Temperature
FC-1T-IVAC-1F| FHC-ID| 2-digit LED. dial| 1- heat only| 1| Temperature
FC-1T-2VAC-3F| SEC-HD PEC TVS| 4-digit LED. button| 3| 2| Temperature
PhasonControls.com
sales@phason.ca
International: 204-233-1400
Toll-free North America: 800-590-9338
FC-1T-1F 10940000