Phason AutoFlex Connect II Control System User Guide

June 9, 2024
Phason

Phason Auto Flex Connect II Control System User Guide
Phason AutoFlex Connect II Control System

Mounting guidelines

  • Mount the control on a sheltered, vertical surface
  • Mount the control with the electrical knockouts facing down.
  • Mount the control away from sources of moisture and heat

Mounting guidelines

For the larger Auto Flex Connect:

  • Mount high-voltage modules (ACT-1, ACT-1T, ACT-1V, RM 2, RM-2-3PH, RM-4, VAC-1, and LOOP-DRIVE) next to the trough, and then run the cabling through the trough.
  • Mount low-voltage modules (IN-4, VDC-4, VCM-DC, and LOOP-SENSE) at the outer positions and run the cabling along the inside of the enclosure.

Installing modules

  1. Position the module over the connector (A) and then press straight on to the connector.
  2. Fasten the module in place using all four screws (B) provided.
    Installing modules
Electrical ratings
Control power 85 to 264 VAC, 50/60 Hz
Alarm relay 0.4 A at 125 VAC; 2 A at 30 VDC, resistive load 0.2 A at 125 VAC;

1 A at 30 VDC, inductive load
ACT-1 ACT-1V| 15 A at 120/230 VAC, general-purpose (resistive) 1/2 HP at 120 VAC, 1 HP at 230 VAC 0-10 V DC signal feedback (ACT-1V only)
ACT-1T LOOP-DRIVE RM-2| 20 A at 120/230 VAC, general-purpose (resistive) 1 HP at 120 VAC, 2 HP at 230 VAC
RM-2-3PH| 1 HP at 120 VAC, 2 HP at 230 VAC 230 VAC coil, 70 VA inrush, pilot duty
RM-4| 15 A at 120/230 VAC, general-purpose (resistive) 1/2 HP at 120 VAC, 1 HP at 230 VAC
VAC-1| 7 A at 120/230 VAC, general-purpose (resistive) 4.9 FLA at 120/230 VAC, PSC motor 1/2 HP at 120 VAC, 1 HP at 230 VAC 800 W @ 120 VAC, 1600 W @ 230 VAC
VCM-DC VDC-4| 0 to 10 VDC, 2K Ω load

  • You can connect more than one piece of equipment to a variable stage or relay if they are the same type (such as fans) and the total current draw and horsepower does not exceed the limit.
  • The maximum wire gauge for all terminals is 12 AWG, solid or stranded.
  • Immediately after powering up the control, remove the battery tab from the power supply on the back of the display
    Installing modules

Incoming power

Incoming power

Alarm relay

Each AutoFlex control has an alarm relay connection on the inside of the cover. For complete installation information, read Connecting an alarm system in the AutoFlex Connect II installation guide.

Input Module

The IN-4 is a Smart Module that has connections for four analog sensors, dry contact switches, or dry contact pulse outputs. For complete installation information and a list of supported sensors, read Connecting sensors to IN-4 modules in the AutoFlex Connect II installation guide.

Place the shunts in the proper positions for the type of sensor you are connecting. For each sensor, there are four shunts to position.
Input Module
Input Module
Input Module
Input Module

RM-2, RM-2-3PH, and RM-4 modules

The RM-2, RM-2-3PH, and RM-4 are Smart Modules that precisely control the equipment connected to them.

  • The RM-2 has two high-capacity relays. Each relay has an integrated current sensor.
  • The RM-2-3PH has two high-capacity relays and two pilot relays for controlling three-phase motors and equipment. The relays operate as pairs, with one high-capacity and one pilot relay in each pair. The highcapacity relays each have an integrated current sensor.
  • The RM-4 has four relays. The RM-4 does not have current sensors.

For complete installation information, read Connecting equipment to RM-2, RM-2-3PH, and RM-4 modules in the Auto Flex Connect II installation guide.

Wiring instructions are the same for the RM-2 and the RM-4 Relay Modules. The following examples use the RM-4.

ACT-1, ACT-1T, and ACT-1V modules

Actuator Modules are Smart Modules that have one OPEN and one CLOSE relay specifically for actuator and curtain control. The ACT-1 uses potentiometer feedback ACT-1T uses timed feedback, and ACT-1V uses 0-10 V DC-signal feedback.

For complete installation information, read Connecting equipment to ACT-1, ACT-1T, and ACT-1V modules in the AutoFlex Connect II installation guide.

  •  Do not run actuator feedback wires in or along the same conduit as AC-power lines.
  • If you are unsure of the potentiometer wiring for your actuator, read  Determining correct actuator feedback wiring in the AutoFlex Connect II installation guide.
  • If you are measuring AC power with a digital multimeter (DMM) and a limit switch opens the circuit, the DMM measures voltage after the relay switch even if the relay  is open

AC-powered actuators

AC-powered actuators

DC-powered actuators

DC-powered actuators

VAC-1 module

The VAC-1 is a single-output Smart Module with a current sensor that can control variable-speed fans, heat mats, and lights. A temperature probe connector is included for heat mat control. For complete installation information, read Connecting equipment to VAC-1 modules in the Auto Flex Connect II installation guide.

Heat mats
Heat mats

VLX-20 Variable Load Expansion Box

The VLX-20 has a 20 A variable AC stage that allows you to increase the capacity of the VAC-1. The VLX-20 is ideal for controlling loads such as heat mats, heat lamps, and incandescent  lights.

The VAC-1 and VLX-20 must be on the same phase.
VAC-1 module

VDC-4 module

The VDC-4 is a Smart Module that has four outputs for controlling variable frequency drives (VFD), Fan DRIVEs, or other equipment requiring a 0 to 10 V DC signal. For complete installation information, read Connecting equipment to VDC-4 modules in the Auto Flex Connect II installation guide.
VDC-4 module

The disconnect relay for the variable frequency drive is a relay on an RM-4 module. Configure the relay to follow the variable DC output. For more information, refer to the online help at the Auto Flex Connect display

AutoFle Logo

Read User Manual Online (PDF format)

Loading......

Download This Manual (PDF format)

Download this manual  >>

Related Manuals