PEERLESS PEE0103001 SERIES MI-e Gas Boilers User Manual

June 9, 2024
Peerless

PEERLESS PEE0103001 SERIES MI-e Gas Boilers

PEERLESS-PEE0103001-SERIES-MI-e-Gas Boilers-PRODUCT-
IMAGE

SERIES MI-e ® GAS BOILERS

TO THE INSTALLER: This manual is the property of the owner and must be affixed near the boiler for future reference.

TO THE OWNER: This boiler should be inspected annually by a Qualified Service Agency.

WARNING
If the information in this manual is not followed exactly, a fire or explosion may result causing property damage, personal injury or loss of life.

  • Do not store or use gasoline or other flammable vapors and liquids in the vicinity of this or any other appliance.
  • WHAT TO DO IF YOU SMELL GAS
    • Do not try to light any appliance.
    • Do not touch any electrical switch; do not use any phone in your building.
    • Immediately call your gas supplier from a neighbor’s phone. Follow the gas supplier’s instructions.
    • If you cannot reach your gas supplier, call the fire department.
  • Installation and service must be performed by a qualified installer, service agency or the gas supplier.
TO BE COMPLETED BY THE INSTALLER

Service Agency
Phone No.
Address____

Boiler Model No.__
Serial No.

Date of Installation:___

Basic Operation

WARNING
Service on this boiler should be undertaken only by trained and skilled personnel from a qualified service agency.

CAUTION
Should overheating occur or the gas supply fail to shut off, do not turn off or disconnect the electrical supply to the pump. Instead, shut off the gas supply at a location external to the appliance.
Do not use this boiler if any part has been under water. Immediately call a qualified service agency to inspect the boiler and to replace any part of the control system and any gas control which has been under water.

General

This water boiler is a natural draft appliance and is equipped with controls for proper operation. All controls must be in proper working order. Contact a qualified service agency to provide annual maintenance as specified in Installation, Operation and Maintenance Manual.

  1. Limit. See Figure 1. A device which automatically interrupts boiler operation when the water temperature exceeds the set point. Maximum allowable temperature is 240°F (115°C).
    Boiler operation is interrupted when system temperature reaches cut-out temperature. Boiler operation resumes automatically when system temperature falls approximately 15°F (8°C) below the cut-out temperature. See also Figure 5 for limit sequence of operation.
    A. Limit Control may incorporate a low water cut-off feature that will interrupt boiler operation upon loss of water in the boiler. If the low water cut-off function is activated to interrupt boiler operation, follow the instructions TO TURN OFF GAS TO THE APPLIANCE (see Figures 2, 3 & 4) and contact a qualified service agency.

  2. Flame Rollout Switch. See Figure 1. A device which automatically interrupts boiler operation when flames or excessive heat are present in the combustion area. The control is a single use device. If the control is activated to interrupt boiler operation, do not attempt to place boiler in operation. Contact a qualified service agency.

  3. Blocked Vent Switch (Vent Safety Shutoff Switch). See Figure 1. A device which automatically interrupts boiler operation when there is a blockage in the vent pipe or chimney. The control is a manual reset device. The control is located on the draft hood relief opening. If the control was activated to interrupt boiler operation, do not attempt to place boiler in operation. Contact a qualified service agency.

  4. Pilot. The pilot provides the ignition source for the main burners. Your boiler has an intermittent pilot. The intermittent pilot ignites only when there is a call for heat and extinguishes when the call for heat ends. See Figure 6.

  5. Gas Valve. The gas valve regulates gas flow to the burners and pilot. See Figure 1.

  6. Safety Relief Valve. A device which protects the boiler against excessive pressure. The safety relief valve can discharge a large amount of hot water – the installer should provide piping to discharge water near floor at a floor drain. If the safety relief valve discharges water, follow instructions TO TURN OFF GAS TO APPLIANCE (see Figures 2, 3 & 4), and contact a qualified service agency.

PEERLESS-PEE0103001-SERIES-MI-e-Gas Boilers-01Figure 1: Control Locations

  • B. Instructions to place boiler in operation and to turn off the boiler are shown on the Operating or Lighting Instruction Label posted on the left side of the boiler. The instructions are also shown in Figures 2, 3 & 4.
  • C. The Sequence of Operation is shown in Figure 5.

PEERLESS-PEE0103001-SERIES-MI-e-Gas Boilers-06Figure 3: Intermittent Ignition Operating Instructions

FOR YOUR SAFETY READ BEFORE OPERATING

WARNING: If you do not follow these instructions exactly, a fire or explosion may result causing property damage, personal injury, or loss of life.

  • This appliance is equipped with an ignition device which automatically lights the pilot. Do not try to light the pilot by hand.

  • BEFORE OPERATING smell all around the appliance area for gas. Be sure to smell next to the floor because some gas is heavier than air and will settle on the floor. WHAT TO DO IF YOU DO SMELL GAS

    • Do not try to light any appliance.
      Do not touch any electric switch; do not use any phone in your building.

    • Immediately call your gas supplier from a neighbor’s phone. Follow the gas supplier’s instructions.
      If you cannot reach your gas supplier, call the fire department.

  • C. Use only your hand to slide the gas control switch.
    Never use tools. If the switch will not slide by hand, don’t try to repair it, call a qualified service technician. Force or attempted repair may result in a fire or explosion.
    D. Do not use this appliance if any part has been under water. Immediately call a qualified service technician to inspect the appliance and to replace any part of the control system and any gas control which has been under water.

OPERATING INSTRUCTIONS
  1. STOP! Read the safety information above on this label.
  2. Set the thermostat to lowest setting.
  3. Turn off all electric power to the appliance.
  4. This appliance is equipped with an ignition device which automatically lights the pilot. Do not try to light the pilot by hand.PEERLESS-PEE0103001-SERIES-MI-e-Gas Boilers-03
  5. If the gas valve is not visible, remove control access panel.
  6. If the gas control knob is not in the “OFF” position, turn the knob clockwise  to “OFF”.
  7. Wait five (5) minutes to clear out any gas. If you then smell gas, STOP! Follow “B” in the safety information above on this label. If you don’t smell gas, go to the next step.
  8. Turn the gas control knob counterclockwise to “ON”.
  9. Replace control access panel, if applicable.
  10. Turn on all electrical power to the appliance.
  11. Set thermostat to desired setting.
  12. If the appliance will not operate, follow the instructions “To Turn Off Gas To Appliance” and call your service technician or gas supplier.

TO TURN OFF GAS TO APPLIANCE

  1. Set the thermostat to lowest setting.
  2. Turn off all electric power to the appliance if service is to be performed.
  3. If the gas valve is not visible, remove the control access panel.
  4. Turn the gas control knob clockwise to “OFF”.
  5. Replace control access panel, if applicable.

Figure 4: Operating Instructions – Robershaw Gas Valve

PEERLESS-PEE0103001-SERIES-MI-e-Gas Boilers-04Figure 5: Intermittent Ignition Sequence of Operation

User Maintenance

WARNING
Product Safety Information
Refractory Ceramic Fiber Product
This appliance contains materials made from refractory ceramic fibers (RCF). Airborne RCF, when inhaled, have been classified by the International Agency for Research on Cancer (IARC), as a possible carcinogen to humans. After the RCF materials have been exposed to temperatures above 1800°F (980°C), they can change into crystalline silica, which has been classified by the IARC as carcinogenic to humans. If particles become airborne during service or repair, inhalation of these particles may be hazardous to your health.

Avoid Breathing Fiber Particulates and Dust

Suppliers of RCF recommend the following precautions be taken when handling these materials:

Precautionary Measures:
Provide adequate ventilation.
Wear a NIOSH/MSHA approved respirator.
Wear long sleeved, loose fitting clothing and gloves to prevent skin contact.
Wear eye goggles.
Minimize airborne dust prior to handling and removal by water misting the material and avoiding unnecessary disturbance of materials.
Wash work clothes separately from others. Rinse washer thoroughly after use.
Discard RCF materials by sealing in an airtight plastic bag.

First Aid Procedures:

  • Inhalation: If breathing difficulty or irritation occurs, move to a location with fresh clean air. Seek immediate medical attention if symptoms persist.
  • Skin Contact: Wash affected area gently with a mild soap and warm water. Seek immediate medical attention if irritation persists.
  • Eye Contact: Flush eyes with water for 15 minutes while holding eyelids apart. Do not rub eyes. Seek immediate medical attention if irritation persists.
  • Ingestion: Drink 1 to 2 glasses of water. Do not induce vomiting. Seek immediate medical attention.

WARNING
Service on this boiler should be undertaken only by trained and skilled personnel from a qualified service agency. Inspections should be performed at intervals specified in the Installation, Operation and Maintenance Manual and this User’s Information Manual. Maintain manuals in a legible condition.

Keep boiler area clear and free of combustible materials, gasoline and other flammable vapors and liquids.

Do not place any obstructions in boiler room that will hinder flow of combustion and ventilation air.

  • A. General Housekeeping (Continuous).
1. Keep boiler area clear and free of combustible materials and obstructions to the free flow of combustion and ventilation air to the boiler.
2. Do not store or use gasoline or other flammable vapors or liquids in the vicinity of the boiler or any other appliance.
3. Do not store or use sources of hydrocarbons in the vicinity of the boiler. Sources of hydrocarbons include bleaches, cleaners, chemicals, sprays, paint removers, fabric softeners and refrigerants.
  • B. Inspect Vent System (Monthly)
1. Vent pipe must be continuous to chimney with no separations, obstructions, or sags. Vent pipe must be supported at minimum 4 foot (122 cm) intervals and secured with sheet metal screws.
2. Chimney must not have signs of continuous wetness. If signs of continuous wetness are observed, contact a qualified service agency.
  • C. Inspect Pilot and Main Burner Flames (Monthly).
1. Adjust thermostat to lowest setting.
2. Remove control access panel (lower front jacket panel) by lifting and pulling out.
3. Adjust thermostat to highest setting. Verify operation follows Sequence of Operation (see Figure 5).
4. View flames through observation port. See Figure 1.
5. Check pilot flame. See Figure 6. The pilot flame should be medium blue covering approximately 3/8” to 1/2” (10 to 12 mm) of the sensing probe. If the flame is yellow and lazy, follow instructions TO TURN OFF GAS TO APPLIANCE (see Figures 2, 3 & 4) and contact qualified service agency.
6. Check main burner flames. See Figure 6. The flames should have clearly defined inner cones approximately 1- 1/2” (40 mm) high and should have a very sharp blue color characteristic. If the flame is yellow and lazy, follow instructions TO TURN OFF GAS TO APPLIANCE (see Figures 2, 3 & 4) and contact qualified service agency.
7. Adjust all thermostats to lowest setting to shut down boiler.
8. Replace control access panel.
9. Adjust thermostats to normal setting.
  • D. Controls
1. Safety Relief Valve. Conduct try lever test as outlined in manufacturer’s instruction tag on the safety relief valve.
2. Low Water Cut-off. Control manufacturer requires low water cut-off to be serviced every five years by a qualified service agency. See control manufacturer’s instructions for further information.
  • E. General Inspection and Maintenance (Annual). For continued safe operation a qualified service agency must provide a more detailed inspection of burners, heat exchanger and vent system, and provide maintenance as specified in the Installation, Operation and Maintenance Manual.

PEERLESS-PEE0103001-SERIES-MI-e-Gas Boilers-05 Figure 6: Intermittent Ignition Pilot Configuration and Flames

Controls maintenance may be part of annual inspection and maintenance by a qualified service agency if annual frequency is specified by controls manufacturer.

Read User Manual Online (PDF format)

Read User Manual Online (PDF format)  >>

Download This Manual (PDF format)

Download this manual  >>

Related Manuals