SAFETY INSTRUCTIONS
General
Please familiarize yourself with the safety features and instructions by
first reading the documentation supplied with this product before using the
equipment. This product has been designed and tested in accordance with
international standards. The equipment must be used exclusively for the
purpose for which it was designed.
WARNING: ELECTRIC SHOCK HAZARD.
The product is used in conjunction with a permanent energy source (battery).
Input and/or output terminals may still be dangerously energized, even when
the equipment is
switched off. Always switch off the AC supply and the battery before carrying
out maintenance or servicing the product.
The product has no internal user-serviceable components. Do not remove the
front plate or operate the product if any panels have been removed. All
servicing must be undertaken by qualified personnel.
Never use the product where there is a risk of gas or dust explosions. Consult
the battery manufacturer’s information to ascertain that the product is
intended for use in conjunction with the battery. Always comply with the
battery manufacturer’s safety instructions.
WARNING: Do not lift heavy loads without assistance.
Installation
Read the installation instructions in the installation manual before
installing the equipment.
This is a Safety Class I product (supplied with a protective grounding
terminal). The chassis must be grounded. A grounding point is located on the
outside of the product. Whenever it is likely that the grounding protection
has been damaged, the product must be turned off and secured against
unintended operation; please contact qualified service staff.
Ensure that the DC and AC input cables are fused and fitted with circuit
breakers. Never replace a safety component with a different type. Consult the
manual to determine the correct component.
Before applying power, ensure that the available power source matches the
configuration settings of the product as described in the manual.
Ensure that the equipment is used under the correct ambient conditions. Never
operate the product in a wet or dusty environment. Ensure there is adequate
free space for
ventilation around the product and check that the ventilation vents are not
blocked.
Ensure that the required system voltage does not exceed the product’s
capacity.
Transport and Storage
Ensure that the mains power and battery leads have been disconnected before
storing or transporting the product.
No liability can be accepted for any transport damage if the equipment is
shipped in nonoriginal packaging.
Store the product in a dry environment; the storage temperature must be
between -20 °C and 60 °C.
Consult the battery manufacturer’s manual in respect of transport, storage,
charging, recharging and disposal of the battery.
DESCRIPTION
2.1 General
SinusMax – Superior engineering
Developed for professional duty, the Phoenix range of inverters is suitable
for the widest range of applications. The design criteria have been to produce
a true sine wave inverter with optimised efficiency but without compromise in
performance. Employing hybrid HF technology, the result is a top-quality
product with compact dimensions, light in weight and capable of supplying
power, problem-free, to any load.
Extra start-up power
A unique feature of the SinusMax technology is very high start-up power.
Conventional high frequency technology does not offer such extreme
performance. Phoenix inverters, however, are well suited to power up difficult
loads such as compressors, electric motors and similar appliances.
Parallel and 3-phase operation capability
Up to 6 inverters can operate in parallel to achieve higher power output.
Operation in 3-phase configuration is also possible.
To transfer the load to another AC source: the automatic transfer switch
If an automatic transfer switch is required, we recommend to using the
MultiPlus or Quattro instead. The switch is included in these products and the
charger function of the MultiPlus/Quattro can be disabled. Computers and other
electronic equipment will continue to operate without disruption because the
MultiPlus/Quattro features a very short switchover time (less than 20
milliseconds).
Programmable relay
The Phoenix Inverter is equipped with a programmable relay, which by default
is set as an alarm relay. The relay can be programmed for all kinds of other
applications however, for example as a starter relay for a generating set.
Programmable with DIP switches, VE.Net panel or personal computer
The Phoenix Inverter is supplied ready for use. Three features are available
for changing certain settings if desired:
- The most important settings can be changed in a very simple manner, using DIP switches.
- All settings, with exception of the programmable relay, can be changed with a VE.Net panel.
- All settings can be changed with a PC and free of charge software, downloadable from our website www.victronenergy.com.
OPERATION
3.1 On/Off Switch
When switched to “on”, the product is fully functional. The inverter will
come into operation and the LED “inverter on” will light up.
3.2 Remote control
Remote control is possible with a simple on/off switch or with a Phoenix
Inverter Control panel.
3.3 LED Indications
| LED off
---|---
| LED flashes
| LED illuminated
The inverter is switched on and supplies power to the load. Battery operation.
The inverter is switched on and
supplies power to the load.
Pre alarm: overload, or battery voltage low, or inverter temperature high
The inverter is switched off.
Alarm: overload, or battery voltage low, or inverter temperature high, or
DC ripple voltage on battery terminal was too high.
The inverter is switched on “eco mode” and supplies power to the load.
INSTALLATION
This product should be installed by a qualified electrician.
4.1 Location
The product must be installed in a dry and well-ventilated area, as close
as possible to the batteries. There should be a clear space of at least 10cm
around the appliance for cooling.
| Excessively high ambient temperature will result in the following:
Reduced service life.
Reduced charging current.
Reduced peak capacity, or shutdown of the inverter.
Never mount the appliance directly above the batteries.
---|---
The product is suitable for wall mounting. For mounting see appendix A.
The appliance can be mounted horizontally as well as vertically; vertical
mounting is preferable. The vertical position offers optimum cooling.
The interior of the product must remain accessible after installation.
Try and keep the distance between the product and the battery to a minimum in
order to minimize cable voltage losses.
For safety purposes, this product should be installed in a heat-resistant
environment if it is used with equipment where a substantial amount of power
is to be converted. You should prevent the presence of e.g. chemicals,
synthetic components, curtains or other textiles, etc., in the immediate
vicinity.
4.2 Connection of Battery cables
In order to fully utilize the full capacity of the product, batteries with
sufficient capacity and battery cables with sufficient cross section should be
used. See table.
| 24/2000| 12/2000
---|---|---
Recommended cross section (mm²)| |
→ 6 m| 50| 70
| 24/2000| 12/2000
Recommended battery capacity (Ah)| 200 – 500| 350 – 1000
Remark: Internal resistance is the important factor when working with low-
capacitybatteries. Please consult your supplier or the relevant sections of
our book “electricity on board”, downloadable from our website.
Procedure
Proceed as follows to connect the battery cables:
Use an insulated box spanner in order to avoid shorting the battery.
Avoid shorting the battery cables.
Connect the battery cables: the + (red) and the – (black), to the battery see
appendix A.
Reverse polarity connection (+ to – and – to +) will cause damage to the
product. (Safetyfuse inside the Phoenix Inverter Compact can be damaged)
Secure the nuts tightly in order to reduce the contact resistance as much as
possible.
4.3 Connection of the AC cabling
This is a Safety Class I product (supplied with a protective grounding
terminal).
The neutral wire of the AC output of this inverter is connected to the
chassis.
This is to ensure proper functioning of a GFCI (or RCCB) to be installed in
the AC output of the Inverter.
The chassis of the product must be connected toground, to the frame (of a
vehicle) or the ground plate or hull (of a boat).
Procedure
The terminal points are indicated clearly. From left to right: “PE” (earth),
“L” (phase) and “N” (neutral).
4.4 Optional Connections
A number of optional connections are possible:
4.4.1 Remote on/off switch & remote Control panel
The product can be remotely controlled in two ways.
- With an external switch (connection terminal H, see appendix A). Operates only if the switch on the Inverter is set to “on”.
- With a Phoenix Inverter Control panel (connected to one of the two RJ45 sockets C, see appendix A). Operates only if the switch on the inverter is set to “on”.
Only one remote control can be connected, i.e. either a switch or a remote
control panel.
4.4.2. Programmable relay
The inverters are equipped with a multi-functional relay that by default is
programmed as an alarm relay. (VEConfigure3 software needed to change relay
functionality).
Near the connection terminals an LED illuminates when the relay is activated
(refer to S, see appendix A).
4.4.3 Parallel Connection
The inverters can be connected in parallel with several identical devices. To
this end, a connection is established between the devices by means of standard
RJ45 UTP cables.
The system (one or more inverters plus optional control panel) will require
subsequent configuration (see Section 5).
In the event of connecting inverters in parallel, the following requirements
must be met:
- A maximum of six units connected in parallel.
- Only identical devices may be connected in parallel.
- The DC connection cables to the devices must be of equal length and cross-section.
- If a positive and a negative DC distribution point is used, the cross-section of the connection between the batteries and the DC distribution point must at least equal the sum of the required cross-sections of the connections between the distribution point and the inverters.
- Place the inverters close to each other, but allow at least 10 cm for ventilation purposes under, above and beside the units.
- UTP cables must be connected directly from one unit to the other (and to the remote panel). Connection/splitter boxes are not permitted.
- Only one remote control means (panel or switch) can be connected to the system.
4.4.4 Three-phase operation
The Phoenix Inverter can also be used in 3-phase wye (Y) configuration. To
this end, a connection between the devices is made by means of standard RJ45
UTP cables (the same as for parallel operation). The system (Inverters plus an
optional control panel) will require subsequently configuration (see Section
5).
Pre-requisites: see Section 4.4.3.
Note: the Phoenix Inverter is not suitable for 3-phase delta (Δ)
configuration.
CONFIGURATION
| Settings may only be changed by a qualified engineer.
Carefully read the instructions before changes are made.
Batteries should be placed in a dry and well-ventilated area during charging.
---|---
5.1 Standard settings: ready for use
On delivery, the Phoenix inverter is set to standard factory values. In
general, these settings are suitable for stand-alone operation.
Standard factory settings
Inverter frequency | 50 Hz |
---|---|
Inverter voltage | 230 VAC |
Stand-alone/parallel/3-phase | stand-alone |
Search mode | off |
Programmable relay | alarm function |
5.2 Explanation of settings
Inverter frequency
Output frequency
Adjustability: 50 Hz; 60 Hz
Inverter voltage
Adjustability: 210 – 245 V
Stand-alone/parallel operation/2-3 phase setting
Using several devices, it is possible to:
- Increase total inverter power (several devices in parallel).
- Create a split-phase system.
- Create a 3-phase system.
The standard product settings are for standalone operation. For parallel, three phase or split phase operation see section 4.4.3 and 4.4.4.
Search Mode (Applicable in stand-alone configuration only)
If search mode is “on”, the power consumption in no-load operation is
decreased by approx. 70 %. In this mode the Compact, when operating in
inverter mode, is switched off in case of no load or very low load, and
switches on every two seconds for a short period. If the output current
exceeds a set level, the inverter will continue to operate. If not, the
inverter will shut down again.
The Search Mode can be set with a DIP switch.
The Search Mode “shut down” and “remain on” load levels can be set with
VEConfigure3.
The standard settings are:
Shut down: 40 Watt (linear load).
Turn on: 100 Watt (linear load).
AES (Automatic Economy Switch)
Instead of the search mode, the AES mode can also be chosen (with help of
VEConfigure3 only).
If this setting is turned “on”, the power consumption in no-load operation and
with low loads is decreased by approx. 20 %, by slightly “narrowing” the
sinusoidal voltage.
Not adjustable with DIP switches.
Applicable in stand-alone configuration only.
Programmable relay
By default, the programmable relay is set as an alarm relay, i.e. the relay
will de-energise in the event of an alarm or a pre-alarm (inverter almost too
hot, ripple on the input almost too high, battery voltage almost too low).
Not adjustable with DIP switches.
Near the connection terminals an LED illuminates when the relay is activated
(refer to S, see appendix A).
5.3 Configuration by computer
All settings can be changed by means of a computer or with a VE.Net panel
(except for the multi-functional relay and the VirtualSwitch when using
VE.Net).
Some settings can be changed with DIP switches (see Section 5.2).
For changing settings with the computer, the following is required:
- VEConfigure3 software: can be downloaded free of charge at www.victronenergy.com.
- A MK3-USB (VE.Bus to USB) interface.
Alternatively, the Interface MK2.2b (VE.Bus to RS232) can be used (RJ45 UTP
cable needed).
5.3.1 VE.Bus Quick Configure Setup
VE.Bus Quick Configure Setup is a software program with which one Compact unit
or systems with a maximum of three Compact units (parallel or three phase
operation) can be configured in a simple manner. VEConfigure3 forms part of
this program.
The software free can be downloaded free of charge at
www.victronenergy.com.
5.3.2 VE.Bus System Configurator
For configuring advanced applications and/or systems with four or more
inverters, VE.Bus System Configurator software must be used. The software can
be downloaded free of charge at
www.victronenergy.com. VEConfigure3 forms part
of this program.
5.4 Configuration with a VE.Net panel
To this end, a VE.Net panel and the VE.Net to VE.Bus converter are
required.
With VE.Net you can set all parameters, with the exception of the multi-
functional relay and the VirtualSwitch.
5.5 Configuration with DIP switches
Some settings can be changed with DIP switches
Procedure:
a) Turn the Compact on, preferably without load.
b) Set the dipswitches as required.
c) Store the settings by moving Dip switch 8 to “on” and back to “off”.
5.5.1. DIP switch 1 and 2
Default setting: to operate the product with the “On/Off/Charger Only”
switch
ds 1: “off”
ds 2: “on”
The default setting is required when using the “On/Off/Charger Only” switch in
the front panel. This setting should also be used in setups with a GX device
or VE.Bus Smart dongle when no additional Digital Multi Control panel or
VE.Bus BMS is connected. When a Digital Multi Control panel or a VE.Bus BMS is
included please refer to the settings below.
Setting for remote operation with a Multi Control Panel or a VE.Bus BMS:
ds 1: “on”
ds 2: “off”
This setting is required when a Multi Control Panel and/or a VE.Bus BMS is
connected. The Multi Control panel must be connected to one of the two RJ45
sockets B, see appendix A.
Setting for remote operation with a 3-way switch:
ds 1: “off”
ds 2: “off”
This setting is required when a 3-way switch is connected.
The 3-way switch must be wired to terminal L, see appendix A.
Only one remote control can be connected, i.e. either a switch or a remote
control panel.
In both cases the switch on the product itself should be “on”.
5.5.2 Exemplary settings
Example 1 is the factory setting (since factory settings are entered by
computer, all DIP switches of a new product are set to “off”, except for
DS-2).
Example 1: (factory setting)
1 No panel connected
2 No panel connected
5 Frequency: 50 Hz
6 Search mode off
8 store setting: off→ on→ off
Example 2
1 No panel connected
2 No panel connected
5 Frequency: 50 Hz
6 Search mode off
8 store setting: off→ on→ off
Example 3
1 Panel connected
2 Panel connected
5 Frequency: 60 Hz
6 Search mode on
8 store setting: off→ on→ off
Store the settings (DS3-DS7) by changing switch ds-8 from off to on, and then
back to off.
The LED’s “Inverter” and “eco mode” and “alarm” will flash four times to
indicate acceptance of the settings.
MAINTENANCE
The Compact does not require specific maintenance. It will suffice to check all connections once a year. Avoid moisture and oil/soot/vapours, and keep the device clean.
TROUBLE SHOOTING TABLE
Proceed as follows for quick detection of common faults.
Consult your Victron Energy dealer if the fault cannot be resolved.
Problem | Cause | Solution |
---|---|---|
The inverter fails to operate when switched on. | The battery voltage is too | |
high or too low. | Ensure that the battery voltage is within the correct value. | |
The inverter fails to operate | Processor in no function-mode. | Switch Front |
switch off, wait 4 seconds Switch front switch on.
The alarm LED flashes.| Pre-alarm alt. 1: The DC input voltage is low.| Charge
the battery or check the battery connections.
The alarm LED flashes| Pre-alarm alt. 2: The ambient temperature is too high.|
Place the inverter in a cool and well-ventilated room or reduce the load.
The alarm LED flashes.| Pre-alarm alt. 3: The load on the inverter is higher
than the nominal load.| Reduce the load.
The alarm LED flashes.| Pre-alarm alt. 4: Voltage ripple on the DC input
exceeds 1,25 Vrms.| Check the battery cables and terminals.
Check the battery capacity; increase if necessary.
The alarm LED flashes intermittantly.| Pre-alarm alt. 5. Low battery voltage
and excessive load.| Charge the batteries, reduce the load or install
batteries with a higher capacity. Use shorter and/or thicker battery cables.
The alarm LED is on| The inverter did cut out following a pre-alarm.| Check
the table for the appropriate course of action.
TECHNICAL DATA
Phoenix Inverter | C 12/2000 230 V | C 24/2000 230 V |
---|
INVERTER
Input voltage range (VDC)| 9,5 – 17 V| 19 – 33 V
Output| Output voltage: 230 VAC ± 2 % Frequency: 50 Hz ± 0,1 % (1)
Cont. output power at 25 °C (VA) (3)| 2000| 2000
Cont. output power at 25 °C (W)| 1600| 1600
Cont. output power at 40 °C (W)| 1450| 1450
Cont. output power at 65 °C (W)| 1000| 1000
Peak power (W)| 3500| 3500
Maximum efficiency (%)| 92| 92
Zero-load power (W)| 9| 11
Zero load power in search mode (W)| 3| 4
GENERAL
Programmable relay (4)| yes
Protection (2)| a – g
Common Characteristics| Operating temp. range: -40 to +65 °C (fan assisted
cooling)
Humidity (non condensing): max 95%
ENCLOSURE
Common Characteristics| Material & Colour: aluminium (blue RAL 5012)
Protection category: IP 21
Battery-connection| Bolts M8
230 VAC-connection| connector 6 mm², 10 AWG
Weight (kg)| 12
Dimensions (hxwxd in mm)| 520 x 255 x 125
STANDARDS
Safety| EN 60335-1, EN 60335-2-29
Emission/Immunity| EN 55014-1, EN 55014-2, EN 61000-3-3
-
Can be adjusted to 60 Hz and to 240 V
-
Protection
a) Output short circuit
b) Overload
c) Battery voltage too high
d) Battery voltage too low
e) Temperature too high
f) 230 VAC on inverter output
g) Input voltage ripple too high -
Non linear load, crest factor 3:1
-
Programmable relay which can be set for general alarm, DC undervoltage or genset start signal function
Appendix A: overview connections
B | 2x RJ45 connector for remote panel and/or parallel and 3-phase operation. |
---|---|
C | AC output line (L) and neutral (N). |
F | M8 battery minus connection. |
H | Terminals for (left to right): temperature sensor positive, temperature |
sensor minus.
I| M8 battery positive connection.
L| Connector for remote switch:
Short right and middle terminal to switch “on”.
Short left and middle terminal to switch to “charger only”.
M| DIP switches for set-up mode.
P| Terminals for (left to right): Multi-functional relay NO – COM – NC
Q| Cabinet GND terminal
R| PE (ground) terminals
S| Indicator Programmable relay
LED illuminates when relay is activated
Appendix B: installation information
This ground wire “G” connects the output neutral to ground. It must be cut/removed if a floating output is required or reposition to “dummy” terminal.
E | Output |
---|---|
F | Connected to chassis |
G | Output Neutral to PE connection |
I | DC fuse |
J | Converter |
L | Chassis on output ground terminals should be permanently connected to |
ground
Appendix C: parallel connection
Appendix D: three-phase connection
Victron Energy Blue Power