LITHONIA LIGHTING SQRS5S Remote Station Instruction Manual

June 9, 2024
LITHONIA LIGHTING

SQRS5S Remote Station

DISCONTINUED

Installation Instructions
1. Always disconnect all power.
2. This device is supplied by a Class 2 low voltage transformer. Install in accordance with appropriate codes.
3. Do not mix control and power conductors in the same conduit.
4. Excessive dust may damage this remote station. Install during final finish work.
5. Use only as intended.
6. Use only accessories recommended by Lithonia Control Systems.
Important Remote Station Mounting and Location Notes
1. Ambient Conditions: Maximum Ambient Temperature: 104°F/40° C Minimum Ambient Temperature: 32°F/0°C Relative Humidity: 10-90% Non condensing

SQRS5S – Remote Station
Rough In Mounting and Wiring Instructions
1. Install a 2″ wide single gang masonry box (RACO #690, Steel City #GW125C) or square corner ring (RACO #782) at the desired location. Remote station frame must be mounted to a grounded back box, or a separate ground conductor must be added. For cut-in locations do not use “F clips”, use 2″ wide box equal to Caddy MPLS to avoid the circuit board shorting to box.
2. Connect this remote to a single Sequel Series Control Station (SQCS, SQMPCS, SQIDC) or a single Remote Station Interface (SQRSI, SQMPRSI) with (6) Class 2 #18 AWG conductors. Add a spare conductor to this run if total length exceeds 250 feet (80m).
3. Remotes which have the same function can be wired in a daisy chain, or may be home run separately and connected under the same terminal at the control station or interface. See figure 1.
4. Refer to figure 1 (below left) for typical one line wiring details, and to figures 3 – 5 for Lithonia typical interconnection wiring details. Refer to “As Built” drawings for project specific wiring details.
Quantity of Class 2 low voltage individual #18 AWG wires as indicated in the symbol. If multiconductor cable is desired, use Belden 83653, 83662 shielded, low capacitance, (not twisted) control cable or equal. A spare conductor is shown in each run to the left for applications with a total wire length of greater than 250 feet (80m).

Figure 1 LIGHTING CONTROL SYSTEMS

Part No. CDCS000118 Rev F 1/99

Installation Instructions

SQRS5S – Remote Station

DISCONTINUED

Figure 3 – Sequel Control Station to SQRS5S Remote Control Station Interconnection Wiring Details Note: See SQRSI Installation Instruction to connect this station to interfaces.

Part No. CDCS000118 Rev F 1/99

LIGHTING CONTROL SYSTEMS
ONE LITHONIA WAY, DECATUR, GEORGIA 30035, TELEPHONE 770-987-4200, FAX 770-987-1002 IN CANADA: 1100 50TH AVE., LACHINE, QUEBEC H8T 2V3, A UNIT OF N.S.I. HOLDINGS, INC.

Installation Instructions

SQRS5S – Remote Station

DISCONTINUED

LIGHTING CONTROL SYSTEMS

Part No. CDCS000118 Rev F 1/99

Installation Instructions

SQRS5S – Remote Station

DISCONTINUED

Part No. CDCS000118 Rev F 1/99

LIGHTING CONTROL SYSTEMS
ONE LITHONIA WAY, DECATUR, GEORGIA 30035, TELEPHONE 770-987-4200, FAX 770-987-1002 IN CANADA: 1100 50TH AVE., LACHINE, QUEBEC H8T 2V3, A UNIT OF N.S.I. HOLDINGS, INC.