MEAN WELL RST-15K-HV 15KW Input With High Voltage Output Instruction Manual
- June 9, 2024
- MEAN WELL
Table of Contents
MEAN WELL RST-15K-HV 15KW Input With High Voltage Output
Features
- 3ψ 3-wire / △196~305VAC or 3ψ 4-wire / Y 340~530VAC
- High efficiency up to 94%
- Forced air cooling
- Output voltage and constant current level programmable
- Wide voltage adjustment range 1~120%
- Active current sharing up to 2 units(28.5KW)
- Built-in remote ON-OFF control / Alarm signal
- Protections: Short circuit / Overload / Over voltage / Over temperature / Fan fail
- 5 years warranty
Applications
Energy & power system
- U.V or laser diode application
- Electrolysis system
- Factory control or automation apparatus
- Burn-in facility
- RF application
·EV charging station
- Description
RST-15K-HV is a 15KW 3ψinput enclosed type AC/DC power supply. This series operates for the wide range three phase AC input and offers the models with the high voltage DC output(115V/230V/380V) that mostly demanded from the industry. This series provides models with forced air cooling, that can be working at ambient temperature up to 70℃. Moreover, RST-15K-HV provides vast design flexibility by equipping various built-in functions such as the output programming, active current sharing, remote ON- OFF control, alarm signals. etc.
- Model Encoding
SPECIFICATION
MODEL | RST-15K-115 | RST-15K-230 | RST-15K-380 |
---|---|---|---|
OUTPUT | DC VOLTAGE (factory default) | 115V | 230V |
CURRENT (factory default) | 130A | 64.8A | 39.55A |
CURRENT RANGE | 0 ~ 130A | 0 ~ 69A | 0 ~ 45A |
RATED POWER | 14950W | 14904W | 15030W |
FULL POWER VOLTAGE RANGE | 115 ~ 138V | 216 ~ 260V | 334 ~ 400V |
RIPPLE & NOISE (max.) **Note.2** | 1Vp-p | 2Vp-p | 4Vp-p |
VOLTAGE ADJ. RANGE | 90 ~ 138V | 170 ~ 260V | 260 ~ 400V |
Can be adjusted via built-in potentiometer
VOLTAGE TOLERANCE Note.3| ±1.0%| ±1.0%| ±1.0%
LINE REGULATION| ±0.5%| ±0.5%| ±0.5%
LOAD REGULATION| ±0.5%| ±0.5%| ±0.5%
SETUP, RISE TIME| 3000ms, 200ms at full load
HOLD UP TIME (Typ.)| 16ms 230VAC/400VAC at 75% load 10ms /
230VAC/400VAC at full load
INPUT| VOLTAGE RANGE| 3ψ 3W/△196~305VAC or 3ψ 4W/Y 340~530VAC
FREQUENCY RANGE| 47 ~ 63Hz
POWER FACTOR (Typ.)| ≧0.98/230VAC(400VAC)/≧0.97/277VAC(480VAC) at full
load
EFFICIENCY (Typ.) **Note.7| 93%| 94%| 94%
AC CURRENT (Typ.)| 45A/230VAC(3ψ 3-wire / △) 26A/230VAC(3ψ
4-wire / Y)
INRUSH CURRENT (Typ.)| 150A/230VAC(3ψ 3-wire / △)
100A/230VAC(3ψ 4-wire / Y)
LEAKAGE CURRENT| <3.5mA/Y 530VAC <21mA /△305VAC
PROTECTION| **
OVERLOAD
| 100 ~ 107% of rated current
Protection type : Constant current limiting, unit will shutdown after 5 sec.
re-power on to recover
OVER VOLTAGE
| 145 ~ 166V| 273 ~ 312V| 420 ~ 480V
Protection type : Shut down o/p voltage, re-power on to recover
OVER TEMPERATURE| Shut down o/p voltage, recovers automatically after
temperature goes down
FUNCTION| CURRENT SHARING| Up to 2 units. Please refer to the
Function Manual
OUTPUT VOLTAGE PROGRAMMABLE| Adjustment of output voltage is
allowable between 1 ~ 120% of nominal output voltage. Please refer to the PV
curve Function Manual
CONSTANT CURRENT LEVEL PROGRAMMABLE| Adjustment of constant
current level is allowable between 20 ~ 100% of rated current. Please refer to
the Function Manual
REMOTE ON-OFF CONTROL| Please refer to the Function Manual
ALARM SIGNAL OUTPUT| AC fail, DC OK, fan fail, OTP. Please refer to the
Function Manual.
ENVIRONMENT| WORKING TEMP.| -30 ~ +70℃ (Refer to “Derating Curve”)
WORKING HUMIDITY| 20 ~ 90% RH non-condensing
STORAGE TEMP., HUMIDITY| -40 ~ +85℃, 10 ~ 95% RH non-condensing
TEMP. COEFFICIENT| ±0.03%/℃ (0 ~ 45℃)
VIBRATION| 10 ~ 500Hz, 2G 10min./1cycle, 60min. each along X, Y, Z axes
SAFETY & EMC
(Note 6,8)
| SAFETY STANDARDS| UL62368-1, CAN/CSA C22.2 No. 62368-1, TUV BS
EN/EN62368-1, EAC TP TC 004 approved
WITHSTAND VOLTAGE| I/P-O/P:4.3KVDC I/P-FG:2.8KVDC O/P-FG:2.8KVDC
ISOLATION RESISTANCE| I/P-O/P, I/P-FG, O/P-FG:100M Ohms / 500VDC /
25℃/ 70% RH
EMC EMISSION| Parameter| Standard| Test Level / Note
Conducted| BS EN/EN55032 (CISPR32) / BS EN/EN55011 (CISPR11)| Class B
Radiated| BS EN/EN55032 (CISPR32) / BS EN/EN55011 (CISPR11)| Class A
Harmonic Current| BS EN/EN61000-3-12| —–
Voltage Flicker| BS EN/EN61000-3-3| —–
EMC IMMUNITY| BS EN/EN55024 , BS EN/EN61204-3, BS EN/EN61000-6-2
Parameter| Standard| Test Level / Note
ESD| BS EN/EN61000-4-2| Level 3, 8KV air ; Level 2, 4KV contact
Radiated| BS EN/EN61000-4-3| Level 3
EFT / Burst| BS EN/EN61000-4-4| Level 3
Surge| BS EN/EN61000-4-5| Level 4, 4KV/Line-Earth ; Level 3, 2KV/Line-Line
Conducted| BS EN/EN61000-4-6| Level 3
Magnetic Field| BS EN/EN61000-4-8| Level 4
Voltage Dips and Interruptions| BS EN/EN61000-4-11| >95% dip 0.5 periods, 30%
dip 25 periods,
95% interruptions 250 periods
OTHERS
| MTBF| 121.9K hrs min. Telcordia SR-332 (Bellcore) ; 16.2K hrs
min. MIL-HDBK-217F (25℃)
DIMENSION| 54042483.5mm (LWH)
PACKING| 25Kg; 1pcs/25Kg/2.82CUFT
NOTE|
- All parameters NOT specially mentioned are measured at △230VAC(Y 400VAC) input, rated load and 25℃ of ambient temperature.
- Ripple & noise are measured at 20MHz of bandwidth by using a 12″ twisted pair-wire terminated with a 0.1uf & 47uf parallel capacitor.
- Tolerance :includes set up tolerance, line regulation and load regulation.
- Derating may be needed under low input voltages. Please check the derating curve for more details.
- If use PV signal to adjust Vo, under creatin operation conditions, ripple noise of Vo might go over rating defined in this specification.
- Need additional EMI filter to meet regulations of EMC conducted and radiated emission. Characteristics of EMI filter please refer to the table, Minimum Insertion Loss.
- The efficiency is measured at △: 230VAC/Y: 400VAC input. The efficiency level is measured at output voltage 115V(115V model)/230V(230V model)/ 380V(380V model).
- The power supply is considered a component which will be installed into a final equipment. All the EMC tests are been executed by mounting the unit on a 600mm*900mm metal plate with 1mm of thickness. The final equipment must be re-confirmed that it still meets EMC directives. For guidance on how to perform these EMC tests, please refer to “EMI testing of component power supplies.” (as available on http://www.meanwell.com)
- The ambient temperature derating of 3.5℃/1000m with fanless models and of 5℃/1000m with fan models for operating altitude higher than 2000m(6500ft).
- An unstable O/P voltage is expected in the first 300ms after power on. A minimum load of 5% is suggested if fast load change is required at power on phase.
- Product Liability Disclaimer:For detailed information, please refer to https://www.meanwell.com/serviceDisclaimer.aspx
Block Diagram DERATING CURVE
STATIC CHARACTERISTICS EFFICIENCY VS LOAD (380V MODEL)
AC Power Connection
Fig 1.2
◎3ψ3-wire /△196~305VAC ψ 3 4-wire / Y 340~530VAC
Note : RST-15K can also be
operated by 1ψ2-wire 196~305VAC input. Please refer to the connection diagram
below.
Operating with 1ψ2-wire may lead to certain characteristics different from the
specification, such as the larger Ripple and Noise. Should there be any
issues, please contact MEAN WELL.
Function Manual
- Output Voltage Programming (or, PV / remote voltage programming / remote adjust / margin programming / dynamic voltage trim)
- Default by potentiometer (SVR)
* Have the DIP switch position-3 set as
* Output voltage can be trimmed by SVR.
2. **By Output Voltage Programming**
* Have the DIP switch position-3 set as
* The output voltage can be trimmed to 1~120% by applying EXTERNAL VOLTAGE between PV+ and PV- on CN26 or CN27.![MEAN-WELL-RST-15K-HV-15KW-Input-With-High-Voltage-Output-07](https://manuals.plus/wp-content/uploads/2023/02/MEAN-WELL-RST-15K-HV-15KW-Input-With-High-Voltage-Output-07.png)![MEAN-WELL-RST-15K-HV-15KW-Input-With-High-Voltage-Output-08](https://manuals.plus/wp-content/uploads/2023/02/MEAN-WELL-RST-15K-HV-15KW-Input-With-High-Voltage-Output-08.png)
* The 100% output voltage is 115/216/334V.
* When PV signal to adjust voltage under Vo<11.5V(115V model) / 21.6V(230V model) / 33.4V(380V model) with dynamic load condition, the Vo overshoot & undershoot might go over rating.![MEAN-WELL-RST-15K-HV-15KW-Input-With-High-Voltage-Output-09](https://manuals.plus/wp-content/uploads/2023/02/MEAN-WELL-RST-15K-HV-15KW-Input-With-High-Voltage-Output-09.png)
* The rated current should change with the Output Voltage Programming accordingly.
* Maximum output current is Based on rated power wattage.
- Constant Current Programming (or, PC / remote current programming / dynamic current trim)
- Default Overload Protection(OLP) 100~107% of rated current
* Have the DIP switch position-2 set as
* Output current is set default value.
2. by Constant Current Level Programming
* Have the DIP switch position-2 set as
* The constant current level can be trimmed to 20~100% of the rated current by applying EXTERNAL VOLTAGE between PC+ and PC- on CN26 or CN27.
EXTERNAL VOLTAGE (DC)
Fig 2.2
3. Select Overload Protection (OLP) Mode
(1) Default Continuous Constant Current mode
Have the DIPswitch position-1 set as ,and RST-15K will work in continuous
constant current mode when the output is overloaded andthe output voltage is
greater than 50% of the rated output voltage.
Delay Shutdown mode
Have the DIPswitch position-1 set as ,and RST-15K will shut down after 5
seconds of constant current operation, when the output is overloaded or short-
circuited.
Remote ON-OFF Control
- The power supply can be turned ON-OFF by using the “Remote ON-OFF” function.
Between Remote ON-OFF(CN25 pin5) and 12V-AUX(CN25 pin1)| Output Status
---|---
Switch close (Short)| power supply ON
Switch open (Open)| power supply OFF
Table 4.1
5. Alarm Signal Output
※ There are 4 alarm signals on CN22, and each signal can select two types of
output circuit.
(1)Relay contact output {OTP1, OTP1-GND) ; (DC-OK1, DC-OK1-GND) ; (AC-
FAIL1-GND, AC-FAIL1) ; (FAN-FAIL1-GND, FAN-FAIL1)} Normally open contact.
“Short” when the alarm arises. Relay contact rating(maximum) is 30V/1A
resistive.(2)Open collector output {DC-
OK2-GND, DC-OK2) ; (AC-FAIL2-GND, AC-FAIL2) ; (OTP2, OTP2-GND) ; (FAN-FAIL2,
FAN-FAIL2-GND)} An external voltage source is required for this function that
is shown in Fig 5.2. These signals are isolated from output. The maximum sink
current is 10mA and the maximum external voltage is 20V (there is a built-in
24V zener diode in inner circuitry).6. Current Sharing
RST-15K has the built-in active current sharing function and can be connected
in parallel, up to 2 units, to provide higher output power as exhibited below
:
※ The voltage difference among each output should be minimized that less than
0.2V is required.
※ The total output current must not exceed the value determined by the
following equation.
Maximum output current at parallel operation=(The rated current per
unit)x(Number of unit)x0.95
※ When the total output current is less than 5% of the total rated current, or
say (5% of Rated current per unit)×(Number of unit)
the current shared among units may not be fully balanced. CS+, CS- and RC+, RC- are connected mutually in parallel.
Mechanical Specification
Mounting Instruction
Hole No.| Recommended Screw Size| MAX. Penetration Depth L| Recommended
mounting torque
---|---|---|---
1| M4| 5mm| 7~10Kgf-cm
Control Pin No. Assignment CN26,CN27(): HRS DF11-06DP-2DS or equivalent 15
Mating Housing | HRS DF11-06DS or equivalent |
---|---|
Terminal | HRS DF11-**SC or equivalent |
CN26 and CN27 are connected internally.
Pin No. | Function | Description |
---|---|---|
1 | CS- | Current sharing signal. When units are connected in parallel, the CS |
pins of the units should be connected to allow current balance between units.
2| CS+
3| PC-| Connection for output current programming.
4| PV-| Connection for output voltage programming.
5| PC+| Connection for output current programming.
6| PV+| Connection for output voltage programming.
Control Pin No. Assignment CN22(): HRS DF11-16DP-2DS or equivalent 1 15
Mating Housing | HRS DF11-16DS or equivalent |
---|---|
Terminal | HRS DF11-**SC or equivalent |
Pin No. | Function | Description |
---|---|---|
1 |
DC-OK1
| Alarm signal of DC-OK.
Normally open contact. “Short” when the PSU turns on. Relay contact rating(maximum) is 30V/1A resistive.
2| AC-FAIL1| Alarm signal of AC-fail.
Normally open contact. “Short” when the PSU input voltage is too low. Relay contact rating(maximum) is 30V/1A resistive.
3
|
DC-OK1-GND
| Alarm signal of DC-OK.
Normally open contact. “Short” when the PSU turns on. Relay contact rating(maximum) is 30V/1A resistive.
4| AC-FAIL1-GND| Alarm signal of AC-fail.
Normally open contact. “Short” when the PSU input voltage is too low. Relay contact rating(maximum) is 30V/1A resistive.
5| DC-OK2| Alarm signal of DC-OK.
Open collector signal. Low when the PSU turns on. The maximum sink current is
10mA and the maximum external voltage is 20V.
6| AC-FAIL2| Alarm signal of AC fail.
Open collector signal. Low when the PSU input voltage is too low. The maximum
sink current is 10mA and the maximum external voltage is 20V.
7| DC-OK2-GND| Alarm signal of DC-OK.
Open collector signal. Low when the PSU turns on. The maximum sink current is
10mA and the maximum external voltage is 20V.
8| AC-FAIL2-GND| Alarm signal of AC fail.
Open collector signal. Low when the PSU input voltage is too low. The maximum
sink current is 10mA and the maximum external voltage is 20V.
9| OTP1| Alarm signal of OTP.
Normally open contact. “Short” when the PSU over temperature protection
occurs. Relay contact rating(maximum) is 30V/1A resistive.
10| FAN-FAIL2| Alarm signal of fan fail.
Open collector signal. Low when the internal fan fails. The maximum sink
current is 10mA and the maximum external voltage is 20V.
11| OTP1-GND| Alarm signal of OTP.
Normally open contact. “Short” when the PSU over temperature protection occurs. Relay contact rating(maximum) is 30V/1A resistive.
12|
FAN-FAIL2-GND
| Alarm signal of fan fail.
Open collector signal. Low when the internal fan fails. The maximum sink
current is 10mA and the maximum external voltage is 20V.
13| OTP2| Alarm signal of OTP.
Open collector signal. Low when the PSU over temperature protection occurs.
The maximum sink current is 10mA and the maximum external voltage is 20V.
14| FAN-FAIL1| Alarm signal of fan fail.
Normally open contact. “Short” when the internal fan fails. Relay contact
rating(maximum) is 30V/1A resistive.
15| OTP2-GND| Alarm signal of OTP.
Open collector signal. Low when the PSU over temperature protection occurs.
The maximum sink current is 10mA and the maximum external voltage is 20V.
16| FAN-FAIL1-GND| Alarm signal of fan fail.
Normally open contact. “Short” when the internal fan fails. Relay contact
rating(maximum) is 30V/1A resistive.
Control Pin No. Assignment (CN25) : HRS DF11-08DP-2DS or equivalent 1 7
Mating Housing | HRS DF11-08DS or equivalent |
---|---|
Terminal | HRS DF11-**SC or equivalent |
Pin No. | Function | Description |
---|
1,3
|
12V-AUX
| Auxiliary voltage output, 11.4~12.6V, referenced to pin 2,4(GND-AUX). Only for remote on-off control & Alarm signal. The maximum load current is 0.1A. This output is not controlled by the “Remote ON/OFF” function.
2,4
|
GND-AUX
| Auxiliary voltage output GND.
The signal return is isolated from the output terminals (+V & -V).
5,7
|
RC+
|
The output can be turned ON-OFF in association with RC+ and RC-.
6,8
|
RC-