RAB RBAY17S Field Adjustable LED High Bay Instructions

June 9, 2024
RAB

RAB RBAY17S Field Adjustable LED High Bay Instructions
RAB RBAY17S Field Adjustable LED High Bay

IMPORTANT

READ CAREFULLY BEFORE INSTALLING FIXTURE. RETAIN THESE INSTRUCTIONS FOR FUTURE REFERENCE.

RAB fixtures must be wired in accordance with the National Electrical Code and all applicable local codes. Proper grounding is required for safety. THIS PRODUCT MUST BE INSTALLED IN ACCORDANCE WITH THE APPLICABLE INSTALLATION CODE BY A PERSON FAMILIAR WITH THE CONSTRUCTION AND OPERATION OF THE PRODUCT AND THE HAZARDS INVOLVED.

WARNING: Make certain power is OFF before installing or maintaining fixture. No user serviceable parts inside. Suitable for damp locations

FOR V-HOOK / CHAIN MOUNTING

Mount Housing to sturdy ceiling structure as follows:

  1. V-Hook (2) and 3.28ft Chain (2) are provided for mounting. Secure V-Hooks through Side Slots on housing as shown in Fig. 1 and 2. Secure Chain to V-Hooks as shown in Fig. 2 and 3.
  2. Remove Access Plate ( See Fig. 2 for AR17S & AR17M, see Fig. 3 for AR17L) and feed supply wires with strain relief connector. Make electrical connections as shown in wiring diagram (Fig. 14). Use approved wiring connectors and wire to local NEC codes. Push all wires back into Housing. Be careful not to pinch wires.
  3. Reinstall Access Plate and secure with supplied Screw (1).
    Mounting Instruction

RBAY17S / RBAY17M PENDANT MOUNTING

(Accessory ordered separately – Model# PMKRBAY17S and PMKRBAY17M)

  1. Choose length of a 3/4” NPS Pendant Stem (by others).

  2. Install Pendant Junction Box (ordered separately) to Pendant Stem ( by others) and secure with Locknuts (by others) as shown in Fig. 5.

  3. Mount Housing onto the Pendant Junction Box by securing with Hook feature and tightening (2) Screws (provided) as shown in Fig. 6.
    Mounting Instruction

  4. Remove the Knockout from Side Panel ( Fig. 6). Pull supply wires through side Knockout and feed supply wires through Flex Conduit (provided) as shown in Fig. 6. Secure Flex Conduit to Side Panel and secure Side Panels with (2) Screws (provided) as shown in Fig. 4. Wire the Housing leads to supply wires using UL listed wire connectors according to NEC and local codes.

  5. Push all wires back into Housing. Be careful not to pinch wires.

  6. Secure Flex Conduit to Access Plate (Fig. 6).
    Mounting Instruction

RBAY17L PENDANT MOUNTING

(Accessory ordered separately – Model# PMKRBAY17L)

  1. Choose length of a 3/4” NPS Pendant Stem (by others).

  2. Install Pendant Junction Box (ordered separately) to Pendant Stem ( by others) and secure with Locknuts (by others) as shown in Fig. 7.

  3. Pull supply wires and connect to Housing leads using UL listed wire connectors according to EC and local codes.
    Mounting Instruction

  4. Push all wires back into Housing and secure Access Plate with provided Screw (1).

  5. Mount Housing onto the Pendant Junction Box by securing into the Hook feature and tightening (2) Screws (provided) as shown in Fig. 8

  6. Install Side Panels with provided (2) Screws (provided) (Fig. 8). Be careful not to pinch wires.
    Mounting Instruction

RBAY17S / RBAY17M SURFACE MOUNTING

Mount Surface Mounting Bracket to sturdy structure as follows:
(Accessory ordered separately – Model# SMKRBAY17S and SMKRBAY17)

  1. Install Surface Mounting Bracket (ordered separately) to sturdy surface with Fastener (by others) as shown in Fig. 9.
  2. Wire the Housing leads to supply wires using UL listed wire connectors according to NEC and local codes. Secure Access Plate with (1) Screw (provided).
  3. Mount Housing onto the Surface Mounting Bracket by securing with Hook (4) feature and (2) Screws (provided) as shown in Fig. 10.
    Mounting Instruction

RBAY17L SURFACE MOUNTING

Mount Surface Mounting Bracket to sturdy surface as follows:
(Accessory ordered separately – Model# SMKRBAY17)

  1. Install Surface Mounting Bracket (ordered separately) to sturdy surface with Screws (by others) as shown in Fig. 9.
  2. Wire the Housing leads to supply wires using UL listed wire connectors according to NEC and local codes. Secure Access Plate with (1) Screw (provided).
  3. Mount Housing onto the Surface Mounting Bracket by securing with Hook (4) feature and (2) Screws (provided) as shown in Fig. 11.
    Mounting Instruction

FIELD ADJUSTMENT

Follow instructions below to change the Fixture Power (W) and/or Color Temperature (CCT) from factory settings:

Factory Settings:

  • RBAY17S 130/100/80W 130W / 4000K
  • RBAY17M 260/220/160W 260W / 4000K
  • RBAY17L 400/320/260W 400W / 4000K
  1. Locate the selector switches located on the side of the housing as shown (RBAY17S, RBAYM Fig. 12, RBAY17L Fig. 13).
    Field Adjustment
    Field Adjustment

  2. Select Color Temperature (CCT) and/or Power (W) by sliding the respective switch to the desired value.

MVS/PIR SENSOR INSTALLATION

For units ordered with MVS or PIR Sensor follow directions below.

  1. Remove Sensor Base Plug located on the Housing as shown in Fig. 14.
  2. Insert MVS or PIR Sensor into the Sensor Base Plug and turn to secure as shown in Fig. 15.
  3. See MVS/PIR Sensor instructions for pre-sets and programmable settings.
  4. Use optional remote ordered separately Model# MSR1, (formally REMOTE-OD2) for user programming.
    Field Adjustment
    Field Adjustment

0-10V DIMMABLE WIRING

Universal voltage driver permits operation at 120V through 277V, 50 or 60 Hz. Units ordered with /480 suffix are 480V, 50 or 60Hz only. For 0-10V dimming, follow the wiring directions as shown in Fig. 16.
Dimmable Wiring

  1. Connect the black fixture lead to the LINE supply lead.
  2. Connect the white fixture lead to the COMMON supply lead.
  3. Connect the GROUND wire from fixture to supply ground.
  4. Connect the purple fixture lead to the (V+) DIM lead.
  5. Connect the pink fixture lead to the (V-) DIM lead.

NOTE: Do not connect DIM V+ (purple)/ DIM V- (pink) to line voltage or supply ground.

CLEANING & MAINTENANCE

CAUTION: Be sure fixture temperature is cool enough to touch. Do not clean or maintain while fixture is energized.

  1. Lens can be washed only after removing from fixture and only in a solution of warm water and any mild, non-abrasive household detergent, rinsed with clean water and wiped dry.
    Do not use chemicals to clean Lens or fixture.

  2. Do not open fixture to clean the LED. Do not touch the LED.

Note: These instructions do not cover all details or variations in equipment nor do they provide every possible situation during installation, operation or maintenance.

TROUBLESHOOTING

  1. Check that the line voltage at the fixture is correct.
  2. Be sure the fixture is grounded properly

Note: These instructions do not cover all details or variations in equipment nor do they provide for every possible situation during installation, operation or maintenance.

Support

Easy Answers
rablighting.com
Visit our website for product info

Tech Help Line
Call our experts: 888 722-1000

e-mail
Answered promptly – sales@rablighting.com

Free Lighting Layouts
© 2022 RAB LIGHTING Inc. Answered online or by request

RBAY17 S-M-L – IN – 0922

RAB WARRANTY : RAB’s warranty is subject to all terms and conditions found at rablighting.com/warranty. P-100141

Documents / Resources

| RAB RBAY17S Field Adjustable LED High Bay [pdf] Instructions
RBAY17S, RBAY17L, RBAY17M, Field Adjustable LED High Bay, LED High Bay, Field Adjustable High Bay, High Bay, Bay
---|---

References

Read User Manual Online (PDF format)

Read User Manual Online (PDF format)  >>

Download This Manual (PDF format)

Download this manual  >>

Related Manuals