HYTRONIK HBIR29-SV PIR Standalone Motion Sensor Instruction Manual

June 9, 2024
HYTRONIK

HYTRONIK HBIR29-SV PIR Standalone Motion Sensor

HYTRONIK-HBIR29-SV-PIR-Standalone-Motion-Sensor-prodact-
img

Installation and Instruction Manual

PIR Standalone Motion Sensor with BLUETOOTH

Technical Specifications

Operation frequency 2.4 GHz – 2.483 GHz
Transmission power 4 dBm
Range (Typical indoor) 10~30m
Protocol  Mesh
Operating voltage 220~240VAC 50/60Hz
Stand-by power <0.65W (Empty load)
Switched power Max. 40 devices, 80mA
Warming-up 5s
Sensor principle PIR detection
Detection range (Max.)* HBIR29/SV Installation Height : 6m Detection Range

(Ø) :9m
Detection range (Max.)*

HBIR29/SV/R

| Installation Height : 6m

Detection Range (Ø) :10m

Detection range (Max.)* HBIR29/SV/H

| Installation height:15m (forklift)

12m (person)

Detection range (Ø):24m

Detection range (Max.)* HBIR29/SV/RH| Installation height:20m (forklift)

12m (person)

Detection range (Ø):40m

Detection angle| 360O
Operation temperature| Ta:-20OC~+50OC
IP rating| IP20

Standard compliance

| EN300328, EN301489-1, EN301489-17, EN62479, EN55015, EN61547, EN60669-1, EN60669-2-1,

EN62493

Certification| CB, CE , EMC, RED, RCM

Download the App

The access to Silvair apps

Installation

Mechanical Structure & Dimensions

HYTRONIK-HBIR29-SV-PIR-Standalone-Motion-Sensor-fig-2

  1. Ceiling (drill hole φ66~68mm)
  2. Carefully prise off the cable clamps.
  3. Make connections to the pluggable terminal blocks.
  4. Insert plug connectors and secure using the provided cable clamps, then clip terminal covers to the base.
  5. Fit detection blind (if required) and desired lens.
  6. Clip fascia to body.
  7. Bend back springs and insert into ceiling.

HYTRONIK-HBIR29-SV-PIR-Standalone-Motion-Sensor-fig-3

Wire Preparation

Pluggable screw terminal. It is recommended to make connections to the terminal before fitting to the sensor.

  1. 200 metres (total) max. for 1mm² CSA (Ta = 50℃)
  2. 300 metres (total) max. for 1.5mm² CSA (Ta = 50℃)

Wiring Diagram

HYTRONIK-HBIR29-SV-PIR-Standalone-Motion-Sensor-fig-5

Mesh Factory Reset

The device HBIR29/SV can be reset by placing a strong magnet (e.g. N38 neodymium magnet, d=10mm*h=4mm) near the sensor lens for 5 seconds. Once the factory reset is done successfully, the luminaire flashes and then permanent on, then the device is being able to be re-commissioned by SILVAIR app.

Status LED blinking Sequence

HBIR29/SV Unprovisioned| 30ms ON| 300ms OFF
HBIR29/SV Provisioned| 15ms ON| 2,000ms OFF
Factory reset| 500ms ON| 1,000ms OFF
Factory reset (initial burst)| 100ms ON| 1,000ms OFF
MESH package received| 30ms ON| 50ms OFF
Attention (from network)| 500ms ON| 500ms OFF

Reprovision

Place a strong magnet on the site of the Reset/Hall effect sensor (see diagram 4 below). To trigger the reset the magnet must be held in position for 5 seconds.

Diagram

Note: When change the lens part of HBIR29/SV, please kindly make sure that the lens fits the right location, where the “Reset dot” and “BLE dot”matches with the physical location on the PCB.

Big and small silicon gasket used to make IP54 degree protection when HBIR29/SV series device mounted into HA03 housing for ceiling mount

Small silicon water-proof gasket dimension(size:mm)

Big silicon water-proof gasket dimension(size:mm)

Placement Guide and Typical Range

Smart Phone to Device Range

The smart device with the App installed will have a typical range of 10m, but varies from device to device. During commissioning, the installer will need to be in range of the devices when searching for devices to add to the network. Once the devices have been added to the network via the App, the devices will start communicating within the wireless mesh. This means that once the network is complete, all devices are accessible from the smart device when in a 20m range of a single point.

Detection Pattern & Optional Accessories

HBIR29/SV (Low-bay)

HBIR29/SV: Low-bay flat lens detection pattern for single person @ Ta = 20ºC (Recommended ceiling mount installation height 2.5m-6m)

HYTRONIK-HBIR29-SV-PIR-Standalone-Motion-Sensor-fig-10

Optional Accessory — Ceiling/Surface Mount Box: HA03

HYTRONIK-HBIR29-SV-PIR-Standalone-Motion-Sensor-fig-11

Optional Accessory — Blind Insert for Blocking Certain Detection Angles

HYTRONIK-HBIR29-SV-PIR-Standalone-Motion-Sensor-fig-12

HBIR29/SV/R (Reinforced Low-bay)

HBIR29/SV/R: Low-bay convex lens detection pattern for single person @ Ta = 20ºC (Recommended ceiling mount installation height 2.5m-6m)

HYTRONIK-HBIR29-SV-PIR-Standalone-Motion-Sensor-fig-13

Optional Accessory — Ceiling/Surface Mount Box: HA03

HYTRONIK-HBIR29-SV-PIR-Standalone-Motion-Sensor-fig-14

Optional Accessory — Blind Insert for Blocking Certain Detection Angles

HYTRONIK-HBIR29-SV-PIR-Standalone-Motion-Sensor-fig-15

HBIR29/SV/H (High-bay)

HBIR29/SV/H: High-bay lens detection pattern for forklift @ Ta = 20ºC (Recommended ceiling mount installation height 10m-15m)

HYTRONIK-HBIR29-SV-PIR-Standalone-Motion-Sensor-fig-16

HBIR29/SV/H: High-bay lens detection pattern for single person @ Ta = 20ºC (Recommended ceiling mount installation height 2.5m-12m)

HYTRONIK-HBIR29-SV-PIR-Standalone-Motion-Sensor-fig-17

Optional Accessory — Ceiling/Surface Mount Box: HA03

HYTRONIK-HBIR29-SV-PIR-Standalone-Motion-Sensor-fig-18

Optional Accessory — Blind Insert for Blocking Certain Detection Angles

HYTRONIK-HBIR29-SV-PIR-Standalone-Motion-Sensor-fig-19

HBIR29/SV/RH (Reinforced High-bay with 3-Pyro)

HBIR29/SV/RH: Reinforced high-bay lens detection pattern for forklift @ Ta = 20ºC (Recommended ceiling mount installation height 10m-15m)

HYTRONIK-HBIR29-SV-PIR-Standalone-Motion-Sensor-fig-20

HBIR29/SV/RH: Reinforced high-bay lens detection pattern for single person @ Ta = 20OC (Recommended ceiling mount installation height 2.5m-12m)

HYTRONIK-HBIR29-SV-PIR-Standalone-Motion-Sensor-fig-21

Optional Accessory — Ceiling/Surface Mount Box: HA03

HYTRONIK-HBIR29-SV-PIR-Standalone-Motion-Sensor-fig-22

Additional Information / Documents

  1. Regarding precautions for PIR Sensors installation and operation, please kindly refer to www.hytronik.com/download->knowledge->PIRSensors-Precautions for Product Installation and Operation
  2. Data sheet is subject to change without notice. Please always refer to the most recent release on www.hytronik.com/products/bluetoottechnology->Partnership
  3. Regarding Hytronik standard guarantee policy, please refer to www.hytronik.com/download->knowledge->Hytronik Standard Guarantee Policy

References

Read User Manual Online (PDF format)

Loading......

Download This Manual (PDF format)

Download this manual  >>

HYTRONIK User Manuals

Related Manuals