ADP CP180 Soffit Mount Compact Ceiling mount Air Handlers
Nomenclature
Product Features
General Features
- Available in uncased or factory-installed cased configurations.
- Designed for drop ceiling or Fur-Down application.
- Constructed of heavy-gauge, corrosion-resistant galvanized steel.
- Left hand refrigerant connections.
- Condensate drain connections on left and right side of air handler.
- Decorative panel available as accessory.
- Air pressure leak tested.
- Suitable for free air-return installation (non-ducted return).
Coil Features
- Available in copper or aluminum construction.
- AC or HP applications; R-22 & R-410A compatible.
- Field or factory installed threaded expansion valve.
- Lanced fin design.
- Rifled copper tubing.
Electrical Features
- ECM Constant Torque motor or PSC motor available.
- Easy to service electric heat section.
- Pull disconnect line voltage connection standard on all factory-installed heat models.
- Patented condensate drain pan safety float switch available as accessory.
- Includes thermostat connections, time delay, & motor speed settings (PSC motor uses control board; functions are built into the ECM Constant Torque motor).
Physical Data
| Unit Size
---|---
CP18| CE18| CP19| CE19| CP23| CE23| CP24|
CE24| CP25| CE25| CP29| CE29| CP30| CE30
Available Voltages| 208/240 V, 60 Hz, 1 Phase
Maximum Elec. Heat available (kW)| 8| 8| 8| 8| 8| 8| 10| 10| 10| 10| 10|
10| 10| 10
Transformer Size and Type| 40VA, Class 2
Blower Data:
2-Speed PSC Motor
| Motor H.P.| 1/8| —| 1/8| —| 1/3| —| 1/3| —| 1/3| —| 1/3| —| 1/3| —
F.L.A. @ 240 V| 1.25| —| 1.25| —| 1.9| —| 1.9| —| 1.9| —| 1.9| —| 1.9| —
Blower Data:
ECM Constant Torque
| Motor H.P.| —| 1/4| —| 1/4| —| 1/4| —| 1/4| —| 1/4| —| 1/4| —| 1/4
F.L.A. @ 240 V| —| 2| —| 2| —| 2| —| 2| —| 2| —| 2| —| 2
Nominal CFM| 600| 600| 600| 600| 800| 800| 800| 800| 800| 800| 1000|
1000| 1000| 1000
Refrigerant Conn. (IDS) Suction| 3/4″
Refrigerant Conn. (IDS) Liquid| 3/8″
R-410A Piston Size (in)| 0.049| 0.049| 0.049| 0.049| 0.053| 0.053|
0.053| 0.053| 0.053| 0.053| 0.059| 0.059| 0.059| 0.059
Pallet Quantity (min order per model)| 8
Max Unit Weight (uncased)| 60| 63| 65| 68| 63| 63| 65| 68| 70| 73| 68|
70| 70| 73
Max Shipping Weight (uncased)| 63| 66| 68| 71| 66| 66| 68| 71| 73| 76|
71| 73| 73| 76
Max Unit Weight (cased)| 89| 92| 97| 100| 92| 92| 97| 100| 105| 108|
103| 105| 105| 108
Max Shipping Weight (cased)| 92| 95| 100| 103| 95| 95| 100| 103| 108|
111| 106| 108| 108| 111
Blower Performance
2-Speed PSC Motor
Unit Size| Blower Speed Setting| Airflow (CFM) vs. External
Static Pressure (inches W.C.) ***
---|---|---
0.1| 0.2| 0.3| 0.4| 0.5*
18, 19| Low – Red| 610| 536| 468| 392| 316
^ High -Black| 680| 607| 532| 456| 368
23| Low – Red| 846| 777| 702| 627| 546
^ High -Black| 902| 830| 755| 667| 589
24, 29| Low – Red| 833| 781| 725| 658| 580
^ High -Black**| 1039| 976| 903| 825| 728
25, 30| Low – Red| 839| 771| 706| 644| 553
* ^ High -Black| 1050| 975| 901| 820| 744
-
Factory setting for cooling.
^ Factory setting for heating.
*** All airflow data is with a dry coil & electric heat.- Heating speeds should not be reduced below factory setting.
- Different speeds can be set for cooling mode; see installation instructions.
- When matched with heat pump, and the room thermostat calls for second stage heat (electric heat strips), the first stage (heat pump) operation must be lockedout. See parts sheet for Heat Pump Relay Kit – Part #76701444.
ECM Constant Torque Motor
Unit Size| Blower Speed Setting| **Airflow (CFM) vs. External
Static Pressure (inches W.C.) ***
---|---|---
0.1| 0.2| 0.3| 0.4| 0.5**
18, 19| Tap 1 (G)| 604| 514| 453| 437| 301
Tap 2 (DS)| 604| 514| 453| 437| 301
Tap 3 (Y1)| 735| 651| 577| 506| 444
Tap 4 (Y2)| 890| 826| 764| 700| 605
^ Tap 5 (W1)| 890| 826| 764| 700| 605
23, 24, 29| Tap 1 (G)| 618| 547| 464| 344| 270
Tap 2 (DS)| 617| 547| 469| 351| 273
Tap 3 (Y1)| 779| 720| 633| 549| 441
Tap 4 (Y2)| 940| 876| 812| 750| 675
^ Tap 5 (W1)| 937| 875| 812| 750| 674
25, 30| Tap 1 (G)| 630| 557| 485| 380| 277
Tap 2 (DS)| 630| 556| 483| 378| 277
Tap 3 (Y1)| 803| 719| 640| 576| 521
Tap 4 (Y2)| 981| 909| 833| 766| 705
^ Tap 5 (W1)| 984| 909| 837| 769| 709
Factory setting for heating.
*** All airflow data is with a dry coil & electric heat.
Uncased Dimensions
Air Handler | A (in) | B (in) | C (in) |
---|---|---|---|
18, 23 | 37 | 19.5 | 10.5 |
19, 24, 29 | 43 | 20.5 | 10.5 |
25, 30 | 49 | 20.5 | 10.5 |
Cased Dimensions
Air Handler Size| A (in)| B (in)| C (in)| D (in)|
E (in)
---|---|---|---|---|---
18, 23| 39.7| 24| 11| 30.5| 7
19, 24, 29| 45.7| 24| 11| 36.5| 7
25, 30| 51.7| 24| 11| 42.5| 7
Electrical Data
Unit Size (All have electric heat)| Heating Capacity| Blower
Amps
---|---|---
kW| BTUH| PSC| ECM
240V [ 1 l| 240 V [ 1 l| 208 V| 240V| 208 V|
240V
18, 19| 3.0| 10,236| 1.25| 1.25| 2.00| 2.00
5.0| 17,060| 1.25| 1.25| 2.00| 2.00
6.0| 20,472| 1.25| 1.25| 2.00| 2.00
8.0| 27,296| 1.25| 1.25| 2.00| 2.00
23, 24,29| 3.0 121| 1 0,236| 1.90| 1.90| 2.00| 2.00
5.0| 17,060| 1.90| 1.90| 2.00| 2.00
6.0| 20,472| 1.90| 1.90| 2.00| 2.00
8.0| 27,296| 1.90| 1.90| 2.00| 2.00
10 13]| 34 ,120| 1.90| 1.90| 2.00| 2.00
25,30| 5.0| 17,060| 1.90| 1.90| 2.00| 2.00
6.0| 20,472| 1.90| 1.90| 2.00| 2.00
8.0| 27,296| 1.90| 1.90| 2.00| 2.00
100| 34 120| 1.90| 1.90| 2.00| 2.00
[1] For 208 Volts use .751 correction factor for kW & MBTUH.
[2] 3kW not available in -25 model
[31 10kW not available in -23 model
Unit Size (All have electric heat)| Heat Capacity| Minimum
Circuit Ampacity| Pull Disconnect Amps Per Stage
---|---|---|---
kW| PSC| ECM
240 V [ 1 l| 208 V| 240V| 208V| 240V
18, 19| 0.0| 1.6| 1.6| 2.6| 2.5| 15
3.0| 15.1| 17.2| 16.0| 18.1| 30
5.0| 23.2| 26.6| 24.1| 27.5| 30
6.0| 28.6| 32.8| 29.5| 33.8| 45
8.0| 37.6| 43.2| 38.5| 44.2| 45
23, 24,29| 0.0| 2.5| 2.4| 2.6| 2.5| 15
3 (2]| 15 .9| 18.0| 16.0| 18.1| 30
5.0| 24.0| 27.4| 24.1| 27.5| 30
6.0| 29.4| 33.6| 29.5| 33.8| 45
8.0| 38.4| 44.0| 38.5| 44.2| 45
10 13]| 41.4| 54.4| 41.6| 54.5| 60
25,30| 0.0| 2.5| 2.40| 2.6| 2.5| 15
5.0| 24.0| 27.4| 24.1| 27.5| 30
6.0| 29.4| 33.6| 29.5| 33.8| 45
8.0| 38.4| 44.0| 38.5| 44.2| 45
100| 41.4| 54.4| 41.6| 54.5| 60
[ 1 ] For 208 Volts use .751 correction factor for kW & MBTUH.
[2] 3kW not available in -25 model
[3] 10kW not available in -23 model
Electrical Connections
- Determine the number of circuits needed to supply the heater with electrical power (1 or 2 circuits). See the air handler Accessory Kit label for number of circuits and ratings.
- Disconnect all power supplies.
- Remove the control panel.
- Using the pre-punched wiring holes, install UL listed wires and fittings.
- Connect appropriate size wire to the pull disconnect terminals.
- Connect green ground wire(s) (1 or 2) to the ground terminal(s) (1 or 2) marked “GND”.
- Install conduit-opening plugs in any unused openings.
- Reinstall the air handler control panel.
- Reconnect power.
- Dispose of all remaining parts.