EZPAN® FA 1×4, 2×2, 2×4 INSTALLATION
RAB Lighting is committed to creating high-quality, affordable, well-designed and energy-efficient LED lighting and controls that make it easy for electricians to install and end users to save energy. We’d love to hear your comments. Please call the Marketing Department at 888-RAB-1000 or email: marketing@rablighting.com

RAB-EZPAN-FA-1x4-2x2-2x4-01

IMPORTANT
READ CAREFULLY BEFORE INSTALLING FIXTURE. RETAIN THESE INSTRUCTIONS FOR FUTURE REFERENCE.
RAB fixtures must be wired in accordance with the National Electrical Code and all applicable local codes. Proper grounding is required for safety.
THIS PRODUCT MUST BE INSTALLED IN ACCORDANCE WITH THE APPLICABLE INSTALLATION CODE BY A PERSON FAMILIAR WITH THE CONSTRUCTION AND OPERATION OF THE PRODUCT AND THE HAZARDS INVOLVED.
WARNING: Make certain power is OFF before installing or maintaining fixture.
WARNING: Risk of fire or electric shock. Suitable for damp locations.
WARNING: Suitable for 9/16” or 15/16” flat tee grid in both insulated ceilings and non-insulated ceilings. Access above ceiling required.
WARNING: Do not handle energized fixture when hands are wet, when standing on wet or damp surfaces, or in water.
WARNING: Vapor barrier must be suitable for 90° C.
WARNING: Fixture to be independently supported to building structure.

RECESSED CEILING MOUNTING

The fixture is suitable only for INDOOR RECESSED CEILING application. Above ceiling access required.
To mount in an insulated or non-insulated ceiling – 9/16” or 15/16” exposed flat tee grid ceiling follow the steps below.

  1. Firmly bend the pre-installed Grid Clips up and out as shown in Fig. 1.

  2. Rotate and slide the Fixture as required to fit through the Tee-Grid Bar and place it as indicated by the directional arrow as shown in Fig. 2.
    Secure the Fixture to the Tee-Grid Bar.

  3. Support wires are required by installation codes. Support the Fixture to the building structure by Support Wires (supplied by others) through the Grid Clip Hole as shown in Fig. 3.

  4. Make sure that the orientation of the Splice Box and Access Plate faces an accessible tile to make electrical splices.

  5. Loosen Access Plate Screw and remove the Access Plate. Knock out appropriate Conduit Knockouts on the Access Plate to route input conduit.
    Use appropriate conduit connectors as required by code (Fig. 4).

  6. Connect wires as shown in wiring diagram. Push all wires back into the Splice Box. Use appropriate UL-approved wire connectors as required by code to complete wiring. Be careful not to pinch wires.
    WARNING: To prevent wiring damage or abrasion, do not expose wiring to edges of sheet metal or other sharp objects.

  7. Replace Access Plate and tighten Access Plate Screw.

0-10V DIMMABLE WIRING

Universal voltage driver permits operation at 120V thru 277V, 50 or 60 Hz. For 0-10V Dimming, follow the wiring directions as shown in Fig. 5.

  1. Connect the black fixture lead to the LINE supply lead.
  2. Connect the white fixture lead to the COMMON supply lead.
  3. Connect the GROUND wire from fixture to supply ground.
  4. Connect the purple fixture lead to the (V+) DIM lead.
  5. Connect the pink (or gray) fixture lead to the (V-) DIM lead.

NOTE: Do not connect DIM V+ (purple)/ DIM V- (pink/gray) to line voltage or supply ground.

FIELD ADJUSTMENT

Follow instructions below to change the fixture wattage or color temperature from the factory settings.
Factory Settings: 4000K, 30W (1X4, 2X2), (40W (2X4)

  1. Locate the Selector Switches on the side of the driver.
  2. Select a wattage and color temperature by sliding the respective switch to the desired value.
  3. After the switches are positioned to the desired settings insert the Silicone Cover to lock the switches in place.

RAB-EZPAN-FA-1x4-2x2-2x4-07

CLEANING & MAINTENANCE

CAUTION: Be sure fixture temperature is cool enough to touch.

Do not clean or maintain while fixture is energized.

  1. Clean polystyrene lens & fixture with non-abrasive cleaning solution.
  2. Do not open fixture to clean the LEDs. Do not touch the LEDs.

BATTERY BACKUP MODELS

WIRING

  • CAUTION: FOR BATTERY BACKUP FIXTURE. Voltage can be present in BATTERY.
  • To prevent high voltage from being present on output leads, Inverter connector must be open. Do not join
  • BATTERY connector until installation is complete and AC power is supplied to the emergency driver. (Fig. 6)RAB-EZPAN-FA-1x4-2x2-2x4-08
  • NOTE: Make sure that the necessary branch circuit wiring is available. An UNSWITCHED AC source of power is required.
  • The emergency driver must be fed from the same branch circuit as the LED driver.
  • CAUTION: Do not use any supply voltage other than 120-277V 50/60 HZ.
  1. Connect UNSWITCHED HOT fixture lead to HOT AC supply line.
  2. If using an UNSWITCHED circuit, connect UNSWITCHED and SWITCHED lines together.
  3. If using a SWITCHED circuit, connect SWITCHED HOT AC fixture lead to the external
  4. Connect the pink (or gray) fixture lead to the (V-) DIM lead.
  5. For 0-10V Dimming, connect DIM (+) and DIM (-) to the supply ground. Do not connect GROUND to the output leads.
  6. All unused leads must be capped and insulated.
  7. After installation is complete, supply AC power to the fixture and connect the BATTERY.
  8. When power is on, the fixture should be on and the Charging Indicator Light should illuminate to indicate the battery is charging.
  9. Once the BATTERY has charged for at least one hour, a short duration test may be performed by pressing the test button.
  10. After the battery has charged for 24 hours, a long duration test can be performed by shutting power to the fixture.
OPERATION
  1. When AC power is applied, the charging indicator light is illuminated, indicating that the BATTERY is being charged.
  2. When AC power fails , the standby power automatically switches to emergency mode (internal battery), operating at reduced illumination for a minimum of 90 minutes.
  3. When AC power is restored, the emergency driver automatically returns to charging mode.

MAINTENANCE
Although no routine maintenance is required to keep the emergency driver functional, it should be checked periodically to ensure that it is working.

The following schedule is recommended:

  1. Visually inspect the charging indicator light monthly. It should be illuminated
  2. Test the emergency operation of the fixture at 30-day intervals for a minimum of 30 seconds.
  3. Conduct a 90-minute discharge test once a year. Fixture would operate at reduced illumination for a minimum of 90 minutes.

TROUBLESHOOTING

  1. Is the fixture grounded properly?
  2. If the charging indicator light does not illuminate after pressing the test button, check if battery is connected properly.
  3. Is the Battery Backup Dip Switch Position set to 4?

Battery Backup Setting

RAB-EZPAN-FA-1x4-2x2-2x4-15

Note: These instructions do not cover all details or variations in equipment nor do they provide for every possible situation during installation, operation or maintenance.

Welcome
Luminaire Sensor
WE’ RE HERE TO HELP:
1 (844) LIGHTCLOUD
or 1 844-544-4825

Hello
The Light cloud Luminaire Sensor is a dual-technology motion detector and closed loop daylight harvester that can switch and dim both local and remote circuits. The Luminaire Sensor requires a compatible light cloud controller or fixture.

Specifications

PART NUMBER

  • Edge: LCLCSENSE/EG
  • Standard: LCLCSENSE/SH
  • High Bay: LCLCSENSE/HB
  • INPUT
  • 5VDC

OPERATING TEMPERATURE

  • -40°C to 40°C

DIMENSIONS

  • Ceiling Mount: 2.25”W x 1.74”H x 2.25”D
  • Edge: 1.30”W x 0.99”H x 2.34”D
  • Standard: 1.20”W x 1.05”H x 1.20”D
  • High Bay: 1.75”W x 1.08”H x 1.75”D

SENSOR COVERAGE

  • Edge: 20 ft. diameter at 9 ft.
  • Standard: 30 ft. diameter at 9 ft.
  • High Bay: 40 ft. diameter at 30 ft.
  • 50 ft. diameter at 45 ft.

MOUNTING HEIGHT

  • Edge: 8 to 12 ft.
  • Standard: 8 to 12 ft.
  • High Bay: 25 to 45 ft.

CONNECTOR

  • RJ9 (RJ22)

RATING

  • Standard and High Bay: IP66

Setup & Installation

  1. Remove Bezel
    Twist counter-clockwise.

  2. Prepare Mounting Hole
    Use knockout or cut hole for sensor.
    Holes have +/- 1/8 in. tolerance.RAB-EZPAN-FA-
1x4-2x2-2x4-10

  3. Installing the Sensor

  4. Ceiling Mount
    Place gasket and sensor into ceiling mount.
    Screw bezel onto sensor from below ceiling. RAB-EZPAN-FA-
1x4-2x2-2x4-11Fold up tabs on ceiling mount and push through hole cut in step 2.

  5. In-Fixture Mounting
    Place gasket and sensor through the hole cut in step 2RAB-EZPAN-FA-
1x4-2x2-2x4-12

  6. Connect the Sensor
    Controller: Use the adapter to connect the sensor to the Controller.
    Light cloud Driver: Plug the sensor into the sensor port on the driver ..RAB-EZPAN-FA-1x4-2x2-2x4-12

If a longer cable is needed, an extension cable (RJ9) up to 10 ft. can be used.

Configuration
To configure the Luminaire Sensor, please login to the Web App at control.lightcloud.com or call Light cloud Support at 1(844) Light cloud.
For additional startup information, please visit lightcloud.com/start.

RAB-EZPAN-FA-1x4-2x2-2x4-14