BLAUBERG EVH Duct Heater For Supply Air Pre-Heating With External Control User Manual
- June 8, 2024
- BLAUBERG
Table of Contents
BLAUBERG EVH Duct Heater For Supply Air Pre-Heating With External Control
User’s manual
This user’s manual is a main operating document intended for technical, maintenance, and operating staff. The manual contains information about purpose, technical details, operating principle, design, and installation of the EVH unit and all its modifications. Technical and maintenance staff must have theoretical and practical training in the field of ventilation systems and should be able to work in accordance with workplace safety rules as well as construction norms and standards applicable in the territory of the country. The information in this user’s manual is correct at the time of the document’s preparation. The Company reserves the right to modify the technical characteristics, design, or configuration of its products at any time in order to incorporate the latest technological developments. No part of this publication may be reproduced, stored in a retrieval system, or transmitted, in any form or by any means in any information search system or translated into any language in any form without the prior written permission of the Company.
SAFETY REQUIREMENTS
- Please read the user’s manual carefully prior to installing and operating the unit.
- All user’s manual requirements as well as the provisions of all the applicable local and national construction, electrical, and technical norms and standards must be observed when installing and operating the unit.
- The warnings contained in the user’s manual must be considered most seriously since they contain vital personal safety information.
- Failure to follow the rules and safety precautions noted in this user’s manual may result in an injury or unit damage.
- After a careful reading of the manual, keep it for the entire service life of the unit.
- While transferring the unit control, the user’s manual must be turned over to the receiving operator.
UNIT INSTALLATION AND OPERATION SAFETY PRECAUTIONS
- Disconnect the unit from power mains prior to any installation operations.
- The unit must be grounded
- Do not change the power cable length at your own discretion.
- Do not bend the power cable. Avoid damaging the power cable.
- Do not put any foreign objects on the power cable.
- Do not use damaged equipment or cables when connecting the unit to power mains.
- Do not touch the unit controls with wet hands.
- Do not carry out the installation and maintenance operations with wet hands.
- Do not allow children to operate the unit.
- The unit is allowed to be used by children aged from 8 years old and abOve and persons with reduced physical, sensory, or mental capabilities or no experience and knowledge provided that they have been given supervision or instruction regarding safe use of the unit and understand the risks involved.
- Do not store any explosive or highly flammable substances in close proximity to the unit.
- Do not open the unit during Operation.
- Do not block the air duct when the unit is switched on.
- Do not sit on the unit and avoid placing foreign objects on it.
- Disconnect the unit from power mains prior to any technical maintenance.
- When the unit generates unusual sounds, odour, or emits smoke, disconnect it from power supply and contact the Seller.
- Do not direct the air flow produced by the unit towards open flame or ignition sources.
- In case of continuous operation of the unit, periodically check the security of mounting.
- Use the unit only for its intended purpose.
PURPOSE
The heater is designed for integration into a ventilation system and joint operation with an air handling unit equipped with a control system regulating the heater operation. The heater maintains the duct air temperature at a point that prevents the heat exchanger freezing.
DELIVERY SET
NAME | NUMBER |
---|---|
Heater | 1 pc. |
Connecting cable with DB-9M connectors | 1 pc. |
User’s manual | 1 pc. |
Packing box | 1 pc. |
DESIGNATION KEY
TECHNICAL DATA
- The heater is rated for indoor application with the ambient temperature ranging from -30 °C up to +40 °C and relative humidity up to 80 %.
- The heater is rated for connection to single-phase ac 230 V/50 (60) Hz.
- The recommended minimum air flow speed in the air duct is 1.5 m/s.
- The heater is rated as a class I electric appliance.
- Ingress Protection (IP) rating from solid objects and liquids IP40.
- The heater design is regularly improved, so some models may slightly differ from those ones described in this manual
Model
| Technical data| Dimensions [mm]
---|---|---
Power consumption of electric heating elements [kW]|
Current [A]
| ****
Ø D
| ****
В
| ****
H
| ****
L
| ****
L1
EVH 125-0,6-1| 0,6| 2,6| ****
124
| ****
155
| ****
251
| ****
306
| ****
192
EVH 125-0,8-1| 0,8| 3,5
EVH 125-1,2-1| 1,2| 5,2
EVH 150-0,8-1| 0,8| 3,5| ****
149
| ****
170
| ****
282
| ****
306
| ****
192
EVH 150-1,2-1| 1,2| 5,2
EVH 150-1,7-1| 1,7| 7,4
EVH 150-2,0-1| 2,0| 8,7
EVH 160-0,8-1| 0,8| 3,5| ****
159
| ****
175
| ****
293
| ****
306
| ****
192
EVH 160-1,2-1| 1,2| 5,2
EVH 160-1,7-1| 1,7| 7,4
EVH 160-2,0-1| 2,0| 8,7
EVH 200-1,2-1| 1,2| 5,2| ****
199
| ****
195
| ****
337
| ****
306
| ****
192
EVH 200-1,7-1| 1,7| 7,4
EVH 200-2,0-1| 2,0| 8,7
EVH 250-1,2-1| 1,2| 5,2| ****
247
| ****
287
| ****
388
| ****
307
| ****
192
EVH 250-2,0-1| 2,0| 8,7
EVH 250-3,0-1| 3,0| 13,0
DESIGN AND OPERATING PRINCIPLE
- The control box is rigidly fixed to the heater casing and covered with a detachable cover. The control box incorporates:
- fasteners for the electric heating element
- electric components for connection to power supply
- ground screw clamp
- manual reset thermal switch TK-90
- automatic reset thermal switch TK-50
- The electric cable gland for power cable as well as the connector for connection to the air handling unit are located on the front panel of the control box.
- The tubular electric heating element is incorporated inside of the heater casing.
- The casing, the connecting box and the heater cover are made of galvanized steel.
- The heater casing is heat-insulated with 20 mm mineral wool layer.
INSTALLATION AND SET-UP
Do not remove the plugs before the heaters are connected to the air handling unit. Make sure to cover the socket connector with the plugs after dismantling of the connecting cable. If only one heater is connected, do not remove the plugs from the other socket connector that is not in use. If the socket connectors are not covered with plugs for any reasons, the ventilation unit does not start during connection to power supply and the control panel displays DI1 and DI3 errors for EVH. Turn the unit off and cover the socket connectors with the plugs to troubleshoot the errors.
- Air duct connection to the heater
- The heater is designed for inline mounting in the air duct both horizontally and vertically.
- Heater connection to the air handling unit
- Connect the heater and the air handling unit using the cable with DB-9M connectors through DB-9F external connectors. The external connector of the heater must be connected to the external connector of the air handling unit prior to connection of the heater and the unit to power mains! ****
Heater position
In case of horizontal mounting position the control box cover must be
directed upwards only. The maximum deviation angle is 90°. The control box
cover may not be positioned downwards!
CONNECTION TO POWER MAINS
- Heater connection to the air handling unit
- The connection must be completed prior to connection of the heater and the air handling unit to power mains!
- The electric heater an the air handling unit must be connected via the cable with the prewired connectors DB-9F.
- Heater connection to power mains
- Connect the heater to AC single-phase 230 V / 50 (60) Hz power mains using a pre-wired power cable with a Euro Plug.
Design. | Name | Type |
---|---|---|
ТК-50 | Contacts of manual reset thermal switch with response temperature +50 | |
°C | N0 | |
ТК-90 | Contacts of manual reset thermal switch with response temperature +90 | |
°C | N0 | |
Heating signal | Heater control triac input signal | VAC |
MAINTENANCE
The heater maintenance includes:
- Inspection of screw connections as well as rivet and welded joints.
- Inspection of tightening of ground screw clamps and electric connections.
- Inspection of the wire terminal connections.
- Cleaning of the electric heating elements of dust and dirt.
STORAGE AND TRANSPORTATION REGULATIONS
- Store the unit in the manufacturer’s original packaging box in a dry closed ventilated premise with temperature range from +5 °C to + 40 °C and relative humidity up to 70 %.
- Storage environment must not contain aggressive vapors and chemical mixtures provoking corrosion, insulation, and sealing deformation.
- Use suitable hoist machinery for handling and storage operations to prevent possible damage to the unit.
- Follow the handling requirements applicable for the particular type of cargo.
- The unit can be carried in the original packaging by any mode of transport provided proper protection against precipitation and mechanical damage. The unit must be transported only in the working position.
- Avoid sharp blows, scratches, or rough handling during loading and unloading.
- Prior to the initial power-up after transportation at low temperatures, allow the unit to warm up at operating temperature for at least 3-4 hours.
WARRANTY
MANUFACTURER’S WARRANTY
The product is in compliance with EU norms and standards on low voltage guidelines and electromagnetic compatibility. We hereby declare that the product complies with the provisions of Electromagnetic Compatibility (EMC) Directive 2014/30/EU of the European Parliament and of the Council, Low Voltage Directive (LVD) 2014/35/EU of the European Parliament and of the Council and CE-marking Council Directive 93/68/EEC. This certificate is issued following test carried out on samples of the product referred to above. The manufacturer hereby warrants normal operation of the unit for 24 months after the retail sale date provided the user’s observance of the transportation, storage, installation, and operation regulations. Should any malfunctions occur in the course of the unit operation through the Manufacturer’s fault during the guaranteed period of operation, the user is entitled to get all the faults eliminated by the manufacturer by means of warranty repair at the factory free of charge. The warranty repair includes work specific to elimination of faults in the unit operation to ensure its intended use by the user within the guaranteed period of operation. The faults are eliminated by means of replacement or repair of the unit components or a specific part of such unit component.
The warranty repair does not include:
- routine technical maintenance
- unit installation/dismantling
- unit setup
The manufacturer’s warranty does not apply to the following cases:
- User’s failure to submit the unit with the entire delivery package as stated in the user’s manual including submission with missing component parts previously dismounted by the user.
- Mismatch of the unit model and the brand name with the information stated on the unit packaging and in the user’s manual.
- User’s failure to ensure timely technical maintenance of the unit.
- External damage to the unit casing (excluding external modifications as required for installation) and internal components caused by the user.
- Redesign or engineering changes to the unit.
- Replacement and use of any assemblies, parts and components not approved by the manufacturer.
- Unit misuse.
- Violation of the unit installation regulations by the user.
- Violation of the unit control regulations by the user.
- Unit connection to power mains with a voltage different from the one stated in the user’s manual.
- Unit breakdown due to voltage surges in power mains.
- Discretionary repair of the unit by the user.
- Unit repair by any persons without the manufacturer’s authorization.
- Expiration of the unit warranty period.
- Violation of the unit transportation regulations by the user.
- Violation of the unit storage regulations by the user.
- Wrongful actions against the unit committed by third parties.
- Unit breakdown due to circumstances of insuperable force (fire, flood, earthquake, war, hostilities of any kind, blockades).
- Missing seals if provided by the user’s manual.
- Failure to submit the user’s manual with the unit purchase date stamp.
- Missing payment paperwork certifying the unit purchase.
CERTIFICATE OF ACCEPTANCE
Unit Type | Duct heater for supply air pre-heating with external control |
---|---|
Model | EVH __ |
Serial Number | |
Manufacture Date |
Quality Inspector’s Stamp
|
SELLER INFORMATION
Seller|
---|---
Address|
Phone Number|
E- mail|
Purchase Date|
This is to certify acceptance of the complete unit delivery with the user’s
manual. The warranty terms are acknowledged and accepted.
Customer’s Signature|
INSTALLATION CERTIFICATE
The EVH __ unit is installed pursuant to the requirements stated in the present user’s manual.
Company name|
Address|
Phone Number|
Installation Technician’s Full Name|
Installation Date:| Signature:
The unit has been installed in accordance with the provisions of all the
applicable local and national construction, electrical and technical codes and
standards. The unit operates normally as intended by the manufacturer.
Signature:|
WARRANTY CARD
Unit Type | Duct heater for supply air pre-heating with external control |
---|---|
Model | EVH __ |
Serial Number | |
Manufacture Date | |
Purchase Date | |
Warranty Period | |
Seller |