Nexa Thermostatic Radiator Valve ZRT-106 Manual

June 8, 2024
NEXA

Nexa

Thermostatic Radiator Valve

SKU: ZRT-106

Quickstart

This is a
secure
HVAC-Thermostat
for
.

Please make sure the internal battery is fully charged.

Important safety information

Please read this manual carefully. Failure to follow the recommendations in this manual may be dangerous or may violate the law.
The manufacturer, importer, distributor and seller shall not be liable for any loss or damage resulting from failure to comply with the instructions in this manual or any other material.
Use this equipment only for its intended purpose. Follow the disposal instructions.

Do not dispose of electronic equipment or batteries in a fire or near open heat sources.

What is Z-Wave?

Z-Wave is the international wireless protocol for communication in the Smart Home. This
device is suited for use in the region mentioned in the Quickstart section.

Z-Wave ensures a reliable communication by reconfirming every message ( two- way
communication
) and every mains powered node can act as a repeater for other nodes
( meshed network ) in case the receiver is not in direct wireless range of the
transmitter.

This device and every other certified Z-Wave device can be used together with any other
certified Z-Wave device regardless of brand and origin
as long as both are suited for the
same frequency range.

If a device supports secure communication it will communicate with other devices
secure as long as this device provides the same or a higher level of security.
Otherwise it will automatically turn into a lower level of security to maintain
backward compatibility.

For more information about Z-Wave technology, devices, white papers etc. please refer
to www.z-wave.info.

Product Description

Thermostatic Radiator Valves (TRVs) sense the air temperature around them and regulate the flow of water through the radiator which they are fitted to.They can be set at a level that gives you the room temperature you want. These settings may have to be different in each room, and you can set the TRVs to suit each room and then leave them to do their job.The device can be set temperature by manual or by gateway.

Prepare for Installation / Reset

Please read the user manual before installing the product.

In order to include (add) a Z-Wave device to a network it must be in factory default
state.
Please make sure to reset the device into factory default. You can do this by
performing an Exclusion operation as described below in the manual. Every Z-Wave
controller is able to perform this operation however it is recommended to use the primary
controller of the previous network to make sure the very device is excluded properly
from this network.

Inclusion/Exclusion

On factory default the device does not belong to any Z-Wave network. The device needs
to be added to an existing wireless network to communicate with the devices of this network.
This process is called Inclusion.

Devices can also be removed from a network. This process is called Exclusion.
Both processes are initiated by the primary controller of the Z-Wave network. This
controller is turned into exclusion respective inclusion mode. Inclusion and Exclusion is
then performed doing a special manual action right on the device.

Quick trouble shooting

Here are a few hints for network installation if things dont work as expected.

  1. Make sure a device is in factory reset state before including. In doubt exclude before include.
  2. If inclusion still fails, check if both devices use the same frequency.
  3. Remove all dead devices from associations. Otherwise you will see severe delays.
  4. Never use sleeping battery devices without a central controller.
  5. Dont poll FLIRS devices.
  6. Make sure to have enough mains powered device to benefit from the meshing

Association – one device controls an other device

Z-Wave devices control other Z-Wave devices. The relationship between one device
controlling another device is called association. In order to control a different
device, the controlling device needs to maintain a list of devices that will receive
controlling commands. These lists are called association groups and they are always
related to certain events (e.g. button pressed, sensor triggers, …). In case
the event happens all devices stored in the respective association group will
receive the same wireless command wireless command, typically a ‘Basic Set’ Command.

Association Groups:

Group NumberMaximum NodesDescription

1| 1| -When the unit is powered up first time, the unit will send a Notification Report and Clock report to the node of Group 1.-When the battery level of the unit drops to an unacceptable level, the unit will emit Battery report to the nodes of Group 1.-When performing Factory Reset the unit will send Device Reset Locally Notification to the node of Group1.-The unit will send Sensor Multilevel Report to the node of Group 1 every two hours.-When changing mod of the unit, it will send Thermostat Mode Report to the node of Group 1.-When changing target value of temperature, the unit will send Thermostat Setpoint Report to the node of Group 1.-When changing the state of button lock, the unit will send Protection Report to the node of Group
---|---|---

Configuration Parameters

Z-Wave products are supposed to work out of the box after inclusion, however
certain configuration can adapt the function better to user needs or unlock further
enhanced features.

IMPORTANT: Controllers may only allow configuring
signed values. In order to set values in the range 128 … 255 the value sent in
the application shall be the desired value minus 256. For example: To set a
parameter to 200 it may be needed to set a value of 200 minus 256 = minus 56.
In case of a two byte value the same logic applies: Values greater than 32768 may
needed to be given as negative values too.

Parameter 1: Parameter 1

Temperature Auto Report period setting
Size: 2 Byte, Default Value: 120

SettingDescription

1 – 255 minutes

Parameter 10: Parameter 10

Manual Override takeover period
Size: 1 Byte, Default Value: 8

SettingDescription

1 – 48 1~48, means 30mins to 24hrs (8=4hrs)

Parameter 2: Parameter 2

Temperature offset for internal sensor
Size: 1 Byte, Default Value: 0

SettingDescription

-80 – 80 -80~+80 Offsets the measured temperature by -8.0~+8.0

Parameter 3: Parameter 3

Maximum Set point value
Size: 1 Byte, Default Value: 35

SettingDescription

5 – 35 5~35 for 5~35

Parameter 4: Parameter 4

Minimum Set point value
Size: 1 Byte, Default Value: 5

SettingDescription

5 – 35 5~35 for 5~35

Parameter 5: Parameter 5

Frost protection temperature
Size: 1 Byte, Default Value: 5

SettingDescription

5 – 15 5~15 for 5~15

Parameter 6: Parameter 6

Open window detect function
Size: 1 Byte, Default Value: 0

SettingDescription

0 – 1 0: Disable 1: Enable

Parameter 7: Parameter 7

Open window detect time period
Size: 1 Byte, Default Value: 15

SettingDescription

2 – 30 minutes

Parameter 8: Parameter 8

Open window detect temperature drop setting
Size: 1 Byte, Default Value: 4

SettingDescription

4 – 8 4=2 , 5=2.5 6= 3, 7=3.5, 8=4

Parameter 9: Parameter 9

Open window detect delay time select
Size: 1 Byte, Default Value: 30

SettingDescription

10 – 60 minutes

Technical Data

Hardware Platform SD3502
Device Type Thermostat – HVAC
Network Operation Listening Sleeping Slave
Firmware Version HW: 1 FW: 1.01:00.00
Z-Wave Version 6.81.03
Certification ID ZC10-22067099
Z-Wave Product Id 0x0060.0x0015.0x0001
Thermostat Modes Energy Save HeatHeat
Thermostat HVAC Systems Supported Heat Only
Thermostat Power Source Battery
Firmware Updatable Updatable by Consumer by RF
Security V2 S2_UNAUTHENTICATED ,S2_AUTHENTICATED
Frequency XXfrequency
Maximum transmission power XXantenna

Supported Command Classes

  • Association Grp Info
  • Association V2
  • Basic
  • Battery
  • Clock
  • Configuration
  • Device Reset Locally
  • Firmware Update Md V4
  • Manufacturer Specific V2
  • Sensor Multilevel V5
  • Notification V8
  • Powerlevel
  • Protection
  • Security
  • Security 2
  • Supervision
  • Thermostat Mode V3
  • Thermostat Setpoint V3
  • Transport Service V2
  • Version V3
  • Zwaveplus Info V2

Explanation of Z-Wave specific terms

  • Controller — is a Z-Wave device with capabilities to manage the network.
    Controllers are typically Gateways,Remote Controls or battery operated wall controllers.

  • Slave — is a Z-Wave device without capabilities to manage the network.
    Slaves can be sensors, actuators and even remote controls.

  • Primary Controller — is the central organizer of the network. It must be
    a controller. There can be only one primary controller in a Z-Wave network.

  • Inclusion — is the process of adding new Z-Wave devices into a network.

  • Exclusion — is the process of removing Z-Wave devices from the network.

  • Association — is a control relationship between a controlling device and
    a controlled device.

  • Wakeup Notification — is a special wireless message issued by a Z-Wave
    device to announces that is able to communicate.

  • Node Information Frame — is a special wireless message issued by a
    Z-Wave device to announce its capabilities and functions.

Read User Manual Online (PDF format)

Read User Manual Online (PDF format)  >>

Download This Manual (PDF format)

Download this manual  >>

Related Manuals