DELTA DVP04PT06PT-S Temperature Measurement Instructions

June 8, 2024
Delta

Table of Contents

DELTA DVP04PT06PT-S Temperature Measurement

DELTA-DVP04PT06PT-S-Temperature-Measurement-PRODUCT

Thank you for choosing Delta DVP series PLC. DVP04/06PT-S is able to receive 4/6 points of RTDs and convert them into 16-bit digital signals. Through FROM/TO instructions in DVP Slim series MPU program, the data can be read and written. There are many 16-bit control registers (CR) in modules. The power unit is separate from it and is small in size and easy to install.
DVP04/06PT-S is an OPEN-TYPE device. It should be installed in a control cabinet free of airborne dust, humidity, electric shock and vibration. To prevent non-maintenance staff from operating DVP04/06PT-S, or to prevent an accident from damaging DVP04/06PT-S, the control cabinet in which DVP04/06PT-S is installed should be equipped with a safeguard. For example, the control cabinet in which DVP04/06PT-S is installed can be unlocked with a special tool or key.

  • DO NOT connect AC power to any of I/O terminals, otherwise serious damage may occur. Please check all wiring again before DVP04/06PT-S is powered up. After
  • DVP04/06PT-S is disconnected, Do NOT touch any terminals in a minute. Make sure that the ground terminal on
  • DVP04/06PT-S is correctly grounded in order to prevent electromagnetic interference.

Product Profile & Dimension

DELTA-DVP04PT06PT-S-Temperature-Measurement-
FIG-2DELTA-DVP04PT06PT-S-Temperature-
Measurement-FIG-3

  • I/O Terminal LayoutDELTA-DVP04PT06PT-S-Temperature-Measurement-FIG-4

External WiringDELTA-DVP04PT06PT-S-Temperature-Measurement-
FIG-5

  • Note1 : Use only the wires that are packed with the temperature sensor for analog input and separate them from other power line or any wire that may cause noise.
    Note 2: 3-wire RTD sensor provides a compensation loop that can be used to subtract the wire resistance while 2-wire RTD sensor has no mechanism to compensate. Use cables (3-wired) with the same length (less than 200 m) and wire resistance of less than 20 ohm.

  • Note3: If there is noise, please connect the shielded cables to the system earth point, and then ground the
    system earth points or connect it to the distribution box.
    Note 4: Please keep wires as short as possible when connecting the module to a device whose temperature is going to be measured, and keep the power cable used as far away from the cable connected to a load as possible to prevent noise interference.

  • Note 5: Please connect a power supply module and on the temperature module to a system
    ground, and then ground the system ground or connect the system ground to a distribution box.

Electrical Specifications

Max. rated power consumption 2W
Operation/storage Operation: 0°C~55°C (temp.), 5~95% (humidity), pollution

degree 2

Storage: -25°C~70°C (temp.), 5~95% (humidity)

Vibration/shock resistance| International standards: IEC61131-2, IEC 68-2-6 (TEST Fc)/ IEC61131-2 & IEC 68-2-27 (TEST Ea)

Series connection to DVP-PLC MPU

| The modules are numbered from 0 to 7 automatically by their distance from MPU. No.0 is the closest to MPU and No.7 is the furthest. Maximum

8 modules are allowed to connect to MPU and will not occupy any digital I/O points.

Functional Specifications

DVP04/06PT-S Celsius (°C) Fahrenheit (°F)
Analog input channel 4/6 channels per module
Sensors type 2-wire/3-wire Pt100 / Pt1000 3850 PPM/°C (DIN 43760 JIS

C1604-1989)

/ Ni100 / Ni1000 / LG-Ni1000 / Cu100 / Cu50/ 0~300Ω/ 0~3000Ω

Current excitation| 1.53mA / 204.8uA
Temperature input range| Please refer to the temperature/digital value characteristic curve.
Digital conversion range| Please refer to the temperature/digital value characteristic curve.
Resolution| 0.1°C| 0.18°F
Overall accuracy| ±0.6% of full scale during 0 ~ 55°C (32 ~ 131°F)
Response time| DVP04PT-S: 200ms/channel; DVP06PT-S: 160/ms/channel
Isolation method

(between digital and analog circuitry)

| There is no isolation between channels.

500VDC between digital/analog circuits and Ground 500VDC between analog circuits and digital circuits 500VDC between 24VDC and Ground

Digital data format| 2’s complement of 16-bit
Average function| Yes (DVP04PT-S: CR#2 ~ CR#5 / DVP06PT-S: CR#2)
Self diagnostic function| Every channel has the upper/lower limit detection function.
RS-485 Communication Mode| Supported, including ASCII/RTU mode. Default communication format: 9600, 7, E, 1, ASCII; refer to CR#32 for details on the communication format.

Note1: RS-485 cannot be used when connected to CPU series PLCs. Note2: Refer to Slim Type Special Module Communications in the appendix E of the DVP programming manual for more details on RS-485 communication setups.

---|---

The unit of temperature would be displayed as 0.1°C/0.1°F. If the temperature unit is set to be Fahrenheit, the second decimal place would not be shown.

Control Register

CR# Address Latched Attribute Register content Description
#0 H’4064 O R Model name

(Set up by the system)

| DVP04PT-S model code= H’8A DVP06PT-S model code = H’CA

1

|

H’4065

|

X

|

R/W

|

CH1~CH4 Mode setting

| b15~12| b11~8| b7~4| b3~0
CH4| CH3| CH2| CH1
Take CH1 mode (b3,b2,b1,b0) for example.

1. (0,0,0,0): Pt100 (default)

2. (0,0,0,1): Ni100

3. (0,0,1,0): Pt1000

4. (0,0,1,1): Ni1000

5. (0,1,0,0): LG-Ni1000

6. (0,1,0,1): Cu100

7. (0,1,1,0): Cu50

8. (0,1,1,1): 0~300 Ω

9. (1,0,0,0): 0~3000 Ω

10. (1,1,1,1)The channel is disabled.

Mode 8 and 9 are only available for DVP04PT-S V4.16 or later and DVP06PT-S V4.12 or later.

2

|

H’4066

|

O

|

R/W

|

DVP04PT-S:

CH1 average number

| Number piece of readings used for the calculation of “average” temperature on CH1.

Setting range: K1~K20. Default setting is K10.

|

DVP06PT-S:

CH1~CH6 average number

| Number piece of readings used for the calculation of “average” temperature on CH1 ~ 6.

Setting range: K1~K20. Default setting is K10.

3

|

H’4067

|

O

|

H’4067

|

DVP04PT-S:

CH2 average number

| Number piece of readings used for the calculation of “average” temperature on CH2.

Setting range: K1~K20. Default setting is K10.

4

|

H’4068

|

O

|

H’4068

|

DVP04PT-S:

CH3 average number

| Number piece of readings used for the calculation of “average” temperature on CH3.

Setting range: K1~K20. Default setting is K10.

5

|

H’4069

|

O

|

H’4069

|

DVP04PT-S:

CH4 average number

| Number piece of readings used for the calculation of “average” temperature on CH4.

Setting range: K1~K20. Default setting is K10.

6| H’406A| X| R| CH1 average degrees| DVP04PT-S:

Average degrees for CH1 ~ 4 DVP06PT-S:

Average degrees for CH1 ~ 6 Unit: 0.1°C, 0.01 Ω (0~300 Ω),

0.1 Ω (0~3000 Ω)

7| H’406B| X| R| CH2 average degrees

8| H’406C| X| R| CH3 average degrees

9| H’406D| X| R| CH4 average degrees

10| —| X| R| CH5 average degrees

11| —| X| R| CH6 average degrees

12| H’4070| X| R| CH1 average degrees| DVP04PT-S:

Average degrees for CH1 ~ 4 DVP06PT-S:

Average degrees for CH1 ~ 6 Unit: 0.1°C, 0.01 Ω (0~300 Ω),

0.1 Ω (0~3000 Ω)

13| H’4071| X| R| CH2 average degrees

14| H’4072| X| R| CH3 average degrees

15| H’4073| X| R| CH4 average degrees

16| —| X| R| CH5 average degrees

17| —| X| R| CH6 average degrees

18| H’4076| X| R| Present temp. of CH1| DVP04PT-S:

Present temperature of CH 1~4

19| H’4077| X| R| Present temp. of CH2

CR#| Address| Latched| Attribute| Register content| Description|
---|---|---|---|---|---|---

20| H’4078| X| R| Present temp. of CH3| DVP06PT-S:

Present temperature of CH1~6 Unit: 0.1°C, 0.01 Ω (0~300 Ω),

0.1 Ω (0~3000 Ω)

|

21| H’4079| X| R| Present temp. of CH4|

22| —| X| R| Present temp. of CH5|

23| —| X| R| Present temp. of CH6|

24| H’407C| X| R| Present temp. of CH1|

DVP04PT-S:

Present temperature of CH 1~4 DVP06PT-S:

Present temperature of CH 1~6 Unit: 0.1°C, 0.01 Ω (0~300 Ω),

0.1 Ω (0~3000 Ω)

|

25| H’407D| X| R| Present temp. of CH2|

26| H’407E| X| R| Present temp. of CH3|

27| H’407F| X| R| Present temp. of CH4|

28| —| X| R| Present temp. of CH5|

29| —| X| R| Present temp. of CH6|

29

|

H’4081

|

X

|

R/W

|

DVP04PT-S:

PID mode setup

| Set H’5678 as PID mode and other values as normal mode

Default value is H’0000.

|

30

|

H’4082

|

X

|

R

|

Error status

| Data register stores the error status. Refer to the error code chart for details.|

31

|

H’4083

|

O

|

R/W

| DVP04PT-S:

Communication address setup

| Set up the RS-485 communication address; setting range: 01~254. Default: K1|

|

X

|

R/W

| DVP06PT-S:

CH5~CH6 Mode setting

| CH5 mode: b0 ~ b3 CH6 mode: b4 ~ b7 See CR#1 for reference|

32

|

H’4084

|

O

|

R/W

|

DVP04PT-S:

Communication format setting

| For baud rate, the settings are 4,800/9,600/19,200/38,400/57,600/

115,200 bps.

Communication format:

ASCII: 7,E,1 / 7,O,1 / 8,E,1 / 8,O,1 / 8,N,1

RTU: 8,E,1 / 8,O,1 / 8,N,1

Factory default : ASCII,9600,7,E,1 (CR#32=H’0002)

Refer to ※CR#32 communication

format settings at the end of this

table for more information.

|

|

X

|

R/W

|

DVP06PT-S: CH5~CH6

Error LED indicator setting

| b15~12| b11~9| b8~6| b5~3| b2~0|
ERR LED| reserved| CH6| CH5|
b12~13 correspond to CH5~6, when bit is ON, the scale exceeds

the range, and the Error LED indicator flashes.

|

33

|

H’4085

|

O

|

R/W

| DVP04PT-S: CH1~CH4

Reset to default setting And Error LED indicator setting

| b15~12| b11~9| b8~6| b5~3| b2~0|
ERR LED| CH4| CH3| CH2| CH1|
If b2~b0 are set to 100, all the setting values of CH1 will be reset to the defaults. To reset all channels to defaults, set b11~0 to H’924 (DVP04PT-S supports single and all channels reset; DVP06PT-S supports all channels reset only). b12~15 correspond to CH1~4, when bit is ON, the scale exceeds

the range, and the Error LED indicator flashes.

|

|

X

|

R/W

|

DVP06PT-S:

CH1~CH4 Reset to default setting And CH1~CH4 Error LED indicator setting

|

34| H’4086| O| R| Firmware version| Display version in hexadecimal. ex:

H’010A = version 1.0A|

35 ~ #48 For system use|

Symbols: O means latched. (Supported with RS485, but does not support when connecting to MPUs.) X means not latched. R means can read data by using FROM instruction or RS-485.

W means can write data by using TO instruction or RS-485.

|

  1. Added the RESET function is only for 04PT-S modules with firmware V4.16 or later and not available for 06PT-S. Connect the module power input to 24 VDC and write H’4352 into CR#0 and then turn the power off and on again; all parameters in modules, including communication parameters are restored to factory defaults.
  2. If you want to use Modbus address in decimal format, you can transfer a hexadecimal register to decimal format and then add one to have it become a decimal Modbus register address. For example transferring the address “H’4064” of CR#0 in hexadecimal format to decimal format, to have the result 16484 and then adding one to it, you have 16485, the Modbus address in decimal format.
  3. CR#32 communication format settings: for DVP04PT-S modules with firmware V4.14 or previous versions, b11~b8 data format selection is not available. For ASCII mode, the format is fixed to 7, E, 1 (H’00XX) and for RTU mode, the format is fixed to 8, E, 1 (H’C0xx/H’80xx). For modules with firmware V4.15 or later, refer to the following table for setups. Note that the original code H’C0XX/H’80XX will be seen as RTU, 8, E, 1 for modules with firmware V4.15 or later.
b15 ~ b12 b11 ~ b8 b7 ~ b0

ASCII/RTU,

exchange low and high byte of CRC check code

|

Data format

|

Baud rate

Description
H’0| ASCII| H’0| 7,E,1*1| H’01| 4800 bps

H’8

| RTU,

do not exchange low and

high byte of CRC check code

| H’1| 8,E,1| H’02| 9600 bps
H’2| reserved| H’04| 19200 bps

H’C

| RTU,

exchange low and high byte of CRC check code

| H’3| 8,N,1| H’08| 38400 bps
H’4| 7,O,1*1| H’10| 57600 bps
 | H’5| 8.O,1| H’20| 115200 bps

  • *Note 1:** This is only available for ASCII format.
  • Ex: Write H’C310 into CR#32 for a result of RTU, exchange low and high byte of CRC check code, 8,N,1 and baud rate at 57600 bps.
  • RS-485 function codes: 03’H is for reading data from registers. 06’H is for writing a data word to registers. 10’H is for writing multiple data words to registers.
  • CR#30 is the error code register.

Note : Each error code will have a corresponding bit and should be converted to 16-bit binary numbers (Bit0~15). Two or more errors may happen at the same time. Refer to the chart below:

Bit number 0 1 2 3

Description

| Power source abnormal| The contact is not connected to

anything.

|

Reserved

|

Reserved

Bit number| 4| 5| 6| 7
Description| Reserved| Reserved| average number error| Instruction error
Bit number| 8| 9| 10| 11
Description| CH1 Abnormal conversion| CH2 Abnormal conversion| CH3 Abnormal conversion| CH4 Abnormal conversion
Bit number| 12| 13| 14| 15
Description| CH5 Abnormal conversion| CH6 Abnormal conversion| Reserved| Reserved

  1. Temperature/Digital Value Characteristic Curve

The mode of measuring Celsius (Fahrenheit) temperature:

Sensor Temperature range Digital value conversion range
°C (Min./Max.) °F (Min./Max.) °C (Min./Max.)
Pt100 -180 ~ 800°C -292 ~ 1,472°F
Ni100 -80 ~ 170°C -112 ~ 338°F
Pt1000 -180 ~ 800°C -292 ~ 1,472°F
Ni1000 -80 ~ 170°C -112 ~ 338°F
LG-Ni1000 -60 ~ 200°C -76 ~ 392°F
Cu100 -50 ~ 150°C -58 ~ 302°F
Cu50 -50 ~ 150°C -58 ~ 302°F
Sensor Input resistor range Digital value conversion range
0~300Ω 0Ω ~ 320Ω K0 ~ 32000
0~3000Ω 0Ω ~ 3200Ω K0 ~ 32000
  1. When CR#29 is set to H’5678, CR#0 ~ CR#34 can be used for PID settings with DVP04PT-S version V3.08 and above.

PID Mode description

CR#| Keep| R/W|  | CR#| Keep| R/W|

0| O| R| Model name| #24| O| R/W| CH1 KD

---|---|---|---|---|---|---|---

1| X| R/W| CH1~CH4 Mode setting| #25| O| R/W| CH2 KD

2| X| R| PID Output % at CH1| #26| O| R/W| CH3 KD

3| X| R| PID Output % at CH2| #27| O| R/W| CH4 KD

4| X| R| PID Output % at CH3|  |  |  | Run/Stop & Auto tuning

Bit0:CH1 PID Run/Stop Bit1:CH2 PID Run/Stop Bit2:CH3 PID Run/Stop Bit3:CH4 PID Run/Stop 0=PID Stop,1=PID Run

Bit4:CH1 Auto tuning Bit5:CH2 Auto tuning Bit6:CH3 Auto tuning Bit7:CH4 Auto tuning

1: The auto tuning function is enabled. After the auto tuning is complete, the value becomes 0.

5| X| R| PID Output % at CH4|  |  |

CR#2~CR#5: 0~1000; Unit: 0.1%|  |  |

6| X| R| Average temperature (0C) at CH1|  |  |

7| X| R| Average temperature (0C) at CH2|  |  |

8| X| R| Average temperature (0C) at CH3|  |  |

9| X| R| Average temperature (0C) at CH4| #28| X| R/W

CR#6~CR#9:Unit: 0.1%|  |  |

10| O| R/W| Set temperature at CH1|  |  |

11| O| R/W| Set temperature at CH2|  |  |

12| O| R/W| Set temperature at CH3|  |  |

13| O| R/W| Set temperature at CH4|  |  |

CR#10~CR#13: Set the PID target value (SV)|  |  |

14| O| R/W| CH1 KP|

29

|

X

|

R/W

|

Enter PID mode(H’5678) K0: Exit the PID mode

15| O| R/W| CH2 KP

16| O| R/W| CH3 KP| #30| X| R| Error code

17| O| R/W| CH4 KP| #31| O| R/W| CH1 Sampling time

19| O| R/W| CH1 KI| #32| O| R/W| CH2 Sampling time

20| O| R/W| CH2 KI| #33| O| R/W| CH3 Sampling time

21| O| R/W| CH3 KI| #34| O| R/W| CH4 Sampling time

22| O| R/W| CH4 KI| CR#31~CR#34: 1~30; Unit: 1s

Note: CR#29 must be set to H’5678 so as to enter the PID mode before configuring settings on other control registers.

Read User Manual Online (PDF format)

Loading......

Download This Manual (PDF format)

Download this manual  >>

Related Manuals