When connecting to pipe work do not use the actuator for leverage. Do not over
tighten.
Put the AUTO/MAN lever in MAN position only for servicing (filling, venting or draining). The lever is not designed for intensive use, it must be operated smoothly with moderate force, only if the mechanism is seated on the valve body.
OVERVIEW
Thank you for choosing one of our products. These 2 port spring return zone valves have been designed to be used on central heating systems which when wired with room thermostat, cylinder thermostat and programmer will control the water flow from the boiler to hot water and central heating.
DIAGRAM
INSTALLATION OF THE VALVE
WARNINGS AND PRECAUTIONS
The valve must be installed with the arrow in the direction of the flow.
Failure to do so will result in water hammer and potential premature
failure.Do not over tighten. The
valve can be mounted vertically or horizontally but must not be mount- ed so
that valve head is below the horizontal level of pipe work. WIRING
All controls must be earthed. All valves must have a means of disconnection
from electrical mains supply which incorporates a contact separation of at
least 3mm in all poles.
All wiring must be carried out to IEE Regulations by a competent Electrician.
The system must be appropriately fused.
Blue: | Neutral |
---|---|
Brown: | Live |
Green & yellow: | Earth |
Orange: | End switch out (auxilliary) |
Grey: | End switch in (auxiliary) |
Typical circuit using two zone Valves Programmer, Room and Cylinder Thermostat as control elements
Br | Brown |
---|---|
Gr | Grey |
O | Orange |
G/Y | Green/Yellow |
B | Blue |
SCHEMATIC DIAGRAM REPLACING ACTUATOR
REMOVAL
-
Remove the locking screw and then remove actuator cover and lock the lever in “MAN” position.
-
Lift actuator from valve body.
-
Loosen the 2 securing screws. RE-FITTING
-
Ensure valve stem is in parallel position as indicated.
-
Seat the actuator over the valve body and tighten the 2 securing screws (see above).
-
Replace the cover and screw.Release lever and allow to travel back to“AUTO”: do not force the travel by hand.
DIMENSIONAL SPECIFICATIONS
Dimensions (in mm):
| MTV222 : 22mm compression fittings| MTV228 : 28mm compression fittings
---|---|---
A| 87| 87
B| 55| 55
C| 60| 60
D| 112| 117
E| 108| 108
TECHNICAL SPECIFICATIONS
- Voltage: 230V~ 50Hz.
- Power consumption: 6W.
- Cable lenth: 1m, 5 core.
- Valve is normally closed when there is no power.
- Max. differential pressure for 22mm = 1Bar.
- Max. static pressure 10.0 Bar.
Environment :
- Fluid temperature : +5°C to +80°C.
- Max ambient temperature : +50°C.
Hereby, NEOMITIS Limited declares that MTV222a and MTV228a are in compliance
with :
Safety Regulations 2016 (2016 No.1101), EMC Regulations 2016 (2016 No.1091)
and RoHS Regulations 2012 (2012 No.3032).
The full text of the UKCA declaration of conformity is available at the
following internet address: www.neomitis.com.
Hereby, Imhotep Creation, declares that the products mentioned in this manual
are in compliance with :
The full text of the EU declaration of conformity is available at the
following internet address :
www.imhotepcreation.com.
Directives 2014/35/EU, 2014/30/EU and 2011/65/EU. Neomitis Ltd and Imhotep
Creation belong to Axenco Group.
The symbol , affixed on the product indicates that you must dispose of it at
the end of its useful life at a special recycling point, in accordance with
European Directive WEEE 2012/19/EU. If you are replacing it, you can also
return it to the retailer from which you buy the replacement equipment. Thus,
it is not ordinary household waste. Recycling products enables us to protect
the environment and to use less natural resources.
MTV322A
3 PORT ZONE MID-POSITION
VALVE, 22mm COMPRESSION FITTING
MTV328A
3 PORT ZONE MID-POSITION
VALVE, 28MM COMPRESSION FITTING
OVBERVIEW
Thank you for choosing one of our products.
This 3 port zone valve mid position have been designed to be used on central
heating systems which when wired with room thermostat, cylinder thermostat and
programmer
will control the water flow from the boiler to either to hot water only,
heating only or both simultaneously.
DIAGRAM
INSTALLATION OF THE VALVE
WARNINGS AND PRECAUTIONS
**** The valve must be installed according to instructions:
AB = Flow from boiler
A = Radiator circuit
B = Hot water circuit The valve can be mounted vertically or horizontally but
must not be mounted so that valve head is below the horizontal level of pipe
work.When connecting to pipe work do not use
the actuator for leverage. Do not over tighten.
Put the AUTO/MAN lever in MAN position only for servicing (filling, venting or
draining). The lever is not designed for intensive use, it must be operated
smoothly with moderate force, only if the mechanism is seated on the valve
body. WIRING
All controls must be earthed. All valves must have a means of disconnection
from electrical mains supply which incorporates a contact separation of at
east 3mm in all poles.
All wiring must be carried out to IEE Regulations by a competent Electrician.
The system must be appropriately fused.
Blue: | Neutral |
---|---|
White: | Heating on |
Grey: | Hot water off |
Green & yellow: Orange: | Earth |
Orange: | Boiler and pump live |
To use as diverter valve, isolate orange, connect white and grey together. Mid
position Valve
Typical circuit showing Programmer, Room and Cylinder Thermostat as control
elements
W | White |
---|---|
Gr | Grey |
O | Orange |
G/Y | Green/Yellow |
B | Blue |
SCHEMATIC DIAGRAM REPLACING ACTUATOR
REMOVAL
-
Remove the locking screw and then remove the actuator cover and lock the lever in “MAN” position.
-
Loosen 2 securing screws.
-
Lift actuator from valve body. RE-FITTING
-
Ensure valve stem in parallel position as indicated.
-
Seat the actuator over the valve body and tighten the 2 securing screws (seeabove).
-
Replace the cover and screw.Release lever and allow to travel back to “AUTO”: do not force the travel by hand.
IMENSIONAL SPECIFICATIONS
Dimensions (in mm):
| MTV322 : 22mm compression fittings
---|---
A| 87
B| 55
C| 60
D| 117
E| 133
TECHNICAL SPECIFICATIONS
- Voltage: 230V~ 50Hz.
- Power consumption: 6W.
- Cable lenth: 1m, 5 core.
- Port A is normally closed when there is no power.
- Max. differential pressure for 22mm = 1Bar.
- Max. static pressure 10.0 Bar.
Environment :
- Fluid temperature: +5°C to +80°C.
- Max ambient temperature: +50°C.
The full text of the EU declaration of conformity is available at the
following internet address :
www.imhotepcreation.com.
Hereby, Imhotep Creation, declares that the products mentioned in this manual
are in compliance with :
Directives 2014/35/EU, 2014/30/EU and 2011/65/EU.
Hereby, NEOMITIS Limited declares that MTV322a and MTV328a are in compliance
with:
Safety Regulations 2016 (2016 No.1101), EMC Regulations 2016 (2016 No.1091)
and RoHS Regulations 2012 (2012 No.3032).
The full text of the UKCA declaration of conformity is available at the
following internet address: www.neomitis.com.
Neomitis Ltd and Imhotep Creation belong to Axenco Group.
The symbol , affixed on the product indicates that you must dispose of it at
the end of its useful life at a special recycling point, in accordance with
European Directive WEEE 2012/19/EU. If you are replacing it, you can also
return it to the retailer from which you buy the replacement equipment. Thus,
it is not ordinary household waste. Recycling products enables us to protect
the environment and to use less natural resources.
www.neomitis.com NEOMITIS®
LIMITED – 16 Great Queen Street, Covent Garden, London, WC2B 5AH UNITED
KINGDOM
Registered in England and Wales No: 9543404
Tel: +44 (0) 2071 250 236 –
Fax: +44 (0) 2071 250 267 –
E-mail: contactuk@neomitis.com
References
- Imhotep Creation : Fabricant de produits OEM-ODM mécatroniques, de systèmes et d'interfaces homme-machine de régulation
- Néomitis® : solutions pour le confort thermique : radiateurs - panneaux rayonnants - sèche serviettes – panneaux acier – ballons d'eau chaude thermodynamiques – gestion d’énergie
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>