HORMANN FST MZ OD Fire and Smoke Tight Sliding Door Instruction Manual

June 4, 2024
HORMANN

HORMANN FST MZ OD Fire and Smoke Tight Sliding Door

HORMANN-Fire-and-Smoke-Tight-Sliding-Door-PRODUCT

TOOL REQUIRED

HORMANN-Fire-and-Smoke-Tight-Sliding-Door-FIG1

INSTRUCTION

HORMANN-Fire-and-Smoke-Tight-Sliding-Door-FIG2

Dissemination, as well as duplication of this document and the use and communication of its content, are prohibited unless explicitly permitted. Noncompliance will result in damage compensation obligations. All rights reserved in the event of patent, utility model or design model registration. Subject to changes. These instructions are original operating instructions as outlined in EC Directive 2006/42/EC and are divided into a text and illustrated section. The instructions contain important information on the product, and especially safety instructions and warnings.

Read through the instructions carefully. Keep these instructions in a safe place.
For the initial start-up, the fitting instructions for the operator and any other external control devices are required.

Warnings used

DANGER
Indicates a danger that immediately leads to death or serious injuries.

CAUTION
Indicates a danger that can lead to minor or moderate injuries.

ATTENTION
Indicates a danger that can lead to damage or destruction of the product.

Symbols used

HORMANN-Fire-and-Smoke-Tight-Sliding-Door-FIG3 HORMANN-Fire-and-Smoke-Tight-Sliding-Door-FIG4

Abbreviations used

  • Fire protection category
  • Finished floor leve
  • Multi-purpose sliding door
  • Clear passage height
  • Clear passage width

In this document, the terms door and sliding door will be used in lieu of the terms fire and smoke-tight sliding door.

Scope

  • FST 30 OD
  • FST 120 OD
  • FST 60 OD
  • FST MZ OD
  • FST 90 OD

Safety instructions

Danger
Danger to life when fitting the fire sliding door elements The door/door frame can fall over during fitting and may cause injury to persons.

  • Secure both against falling over before and during fitting.
  • Only specialists in accordance with EN 12635 may fit, service, repair and disassemble sliding door FST.
  • Electrical work may only be carried out by trained specialists.
  • Do not make any alterations through attachments and conversions.
  • Take precautionary measures when cauterizing, grinding, and welding.
  • Intumescent materials must not react as a result of heat input.

Intended use
EN 13241 specifies the application for installation, fitting and use.

  • Observe the operating and maintenance instructions.
  • Comply with the inspection and maintenance conditions.
  • Only operate the sliding door if it is technically sound and in perfect working order.
  • Only commission the manufacturer or specialist companies for repairs and maintenance on the sliding door.
  • Comply with the respective national regulations and approvals.

Non-intended use
The fire and a smoke-tight sliding door are not suited:

  • As an external door
  • As a cold-storage door
  • As a wet room door

Safety instructions for operation

WARNING
The danger of injury due to door run

  • The area of travel of the door system must always be kept free from obstructions.
  • No persons or objects are allowed within the danger area of the door.
  • Secure the sliding door immediately in case of damage. Repairs may only be carried out by trained specialists.
  • As per EN 12604, a gravity-driven sliding door must be equipped with a visual-acoustic warning device. The visual-acoustic warning must accompany the door closing process.

Approved walls, wall thicknesses, fastenings, and fitting
Determine the height of the concrete lintel, depending on the door height, with ≥ 255 mm or ≥ 295 mm. Before fitting, make sure there are no gaps > 20 mm between the fire sliding door frame and wall components (see Figure 2)

HORMANN-FST-MZ-OD-Fire-and-Smoke-Tight-Sliding-Door-
FIG3

Approved walls and components Minimum thickness [mm]
EI 230 EI 260 / EI290
A Reinforced concrete acc. to EN 1992-1-1

B

| Brickwork acc. to EN 771-1, compression strength min. M12, apparent density class min. 0.9, mortar acc. to 998-2, min. compression strength M5|

175

|

175

|

240

C

| Sand-lime brickwork acc. to

EN 771-2, compression strength min. M12, apparent density class min. 0.9, mortar acc. to 998-2, min. compression strength M5,

  • max. LDB 3500 × 3500 mm

|

175 *(150)**

|

175

|

240

D

| Gas concrete acc. to EN 771-4, compression strength min. M4, min. apparent density class 0.5, mortar acc. to DIN EN 998-2, min. compression strength M3|

175

|

240

|

E

| Timber partition wall with OSB boards, cladded timber partition wall as per described structure, min. thickness 110 mm,

max. LDB 5000 x 4500 mm

|

110

|

|

F

| Steel girders, fire-proof encased steel components

(Static requirements)

| min . REI30|

min . REI90

| min . REI120
Approved fastenings|
---|---
A| Steel anchor Ø 10 × ≥ 80| Yes
Bonded anchor with steel bolt M10 × ≥ 80 mm| Yes

B

| Through-bolt fixing M10 with hex nut and counterplate| Yes
Anchoring bolt 10 × 90 mm| Yes

C

| Through-bolt fixing M10 with hex nut and counterplate| Yes
Plastic dowels with steel screws Ø 10 × ≥ 120 mm| Only on side

D

| Steel anchor Ø 10 × 80 mm| Yes
Through-bolt fixing M10 with hex nut and counterplate| Only on side
E| Hexagon screws M10 × 100 mm| Yes
Hexagon screws M8 × 80 mm| Only on side
F| Steel screw M10 × 60 mm| Yes
Steel screw M8 × 60 mm| Only on side

Fitting

Overview

No . Description (see illustrated section)
1a Single-leaf handle element, telescopic handle element

Double-leaf handle element
2| Normal element| 3| Connection element
4a| Labyrinth element| 4b| Telescopic labyrinth element
5| Wicket door| 6| Pull connection, threaded rod
7| Guiding profile| 8| Weight box on guiding profile:

Normal guiding variant

No . Description (see illustrated section)
9 Weight box in parking area: Normal guiding, weight diverted or
flush guiding variant 10
11 Closing weight
13 Track
15 Floor buffer
17 Magnet 24 V DC
19 Support bracket
21 Cable clamp plate
23 Cladding
25 Travel limit damper

Fitting on tiles is possible. Increase the anchoring length of the dowels by the thickness of the tiles.

Floor condition, floor clearance
The door opening and floor of the building must be prepared before fitting the sliding door. After fitting the concrete floors, the slab edges may lift (curling). This does not constitute grounds for a complaint regarding the sliding door. Incorrectly fitted sliding doors, the floor clearance can change such that proper function is no longer guaranteed. The floor of the sliding door FST-90 OD must not be flammable (class A1 according to EN 13501-1). On both sides of the door leaf surface, the fireproof area must be at least 150 mm. With FST-30 OD, parquet or carpet flooring of class CFL-S1 according to EN 13501-1 can be used. With smoke-tight doors, the floor must be seamless. Carpet flooring is not permitted.
Permissible floor clearance:

  • Fire door 15 mm ± 7 mm
  • Smoke-tight door 15 mm + 5 mm / – 7 mm

Doors with smoke protection functions require a seamless floor or a stainless steel floor rail (not included in the standard delivery).

Higher fitting position for fire sliding doors
A higher fitting position means a one-sided downward offset of over 500 mm, e.g. in an installation shaft or offset hall levels. In this case, the door leaf edge must be at least 200 mm away from this offset. You have to fit a smoke-tight seal on 4 sides.

Door guiding variants (Figure 1a / 1c)

HORMANN-FST-MZ-OD-Fire-and-Smoke-Tight-Sliding-Door-
FIG2• Normal guiding (A):
The weight box with the closing weight is located on the inlet side. The
weight box is combined with the guiding profile.
• Normal and flush guiding with diverted closing weight (B), (C), (D):
The weight box with closing weight is located at the end of the track in
the parking area. The cable is diverted.
3.5 Track fitting variants (Figure 2/5/6)

HORMANN-FST-MZ-OD-Fire-and-Smoke-Tight-Sliding-Door-
FIG3HORMANN-FST-MZ-OD-Fire-and-Smoke-
Tight-Sliding-Door-FIG7 HORMANN-FST-
MZ-OD-Fire-and-Smoke-Tight-Sliding-Door-FIG8 HORMANN-FST-MZ-OD-Fire-and-Smoke-Tight-Sliding-Door-
FIG9 HORMANN-FST-MZ-OD-Fire-and-Smoke-
Tight-Sliding-Door-FIG10 HORMANN-FST-
MZ-OD-Fire-and-Smoke-Tight-Sliding-Door-FIG11 HORMANN-FST-MZ-OD-Fire-and-Smoke-Tight-Sliding-Door-
FIG12HORMANN-FST-MZ-OD-Fire-and-Smoke-
Tight-Sliding-Door-FIG13 HORMANN-FST-
MZ-OD-Fire-and-Smoke-Tight-Sliding-Door-FIG14 HORMANN-FST-MZ-OD-Fire-and-Smoke-Tight-Sliding-Door-
FIG15 HORMANN-FST-MZ-OD-Fire-and-Smoke-
Tight-Sliding-Door-FIG16 HORMANN-FST-
MZ-OD-Fire-and-Smoke-Tight-Sliding-Door-FIG17

  • Wall fitting
    For wall fitting, fit the track to the wall via support brackets.

  • Direct fitting to the ceiling
    For ceiling fitting, fit the track right to the ceiling.

  • Suspended ceiling fitting
    For suspended ceiling fitting, fit the track on the ceiling via a suspension bracket.

  • Fitting to the ceiling with a false lintel:
    If there is no lintel in the opening area on-site, you can fit a cladded- shaped tube construction to the ceiling (false lintel).

Fixing the door frame

ATTENTION
Fastening elements
High dynamic forces occur when the sliding door is opened and closed. Strong deformation may result in case of a fire.

  • Fastening elements must be able to reliably absorb forces.

Fixing of the track, guiding profile, weight box and labyrinth profile is dependent on the construction subsurface.

  • Only use fasteners from Table 2.5 or fasteners with similar properties. Plastic dowels with Fischer FUR 10 steel screw or equivalent. Steel anchor MKT B 10 / 15 or equivalent. Heavy-duty anchor MKT SZ-S steel or equivalent. Anchoring bolt HUS3-H or similar.
  • Bolt the product through the wall using M 10 threaded rods and counter plates.
  • Use suitable fixing material for the construction subsurface when fitting the recess flaps.

Go through the work steps in order.

Suspending and joining the door elements
ATTENTION
Incorrect fitting of the door elements
Incorrect fitting of the door elements can lead to them being bent.

  • Position the door elements vertically during fitting (see Figure 7.3).HORMANN-FST-MZ-OD-Fire-and-Smoke-Tight-Sliding-Door-FIG18
  • Make sure that the door elements are firmly connected.
  • Only tighten the tensioning nuts moderately (Figure 7.9).

HORMANN-FST-MZ-OD-Fire-and-Smoke-Tight-Sliding-Door-
FIG22

Note:
To prevent fires and increased temperatures from impairing the room partition, close the gaps between wall-side profiles and uneven wall surfaces.

  • Gaps ≤ 5 mm:
    • Only have to be sealed with silicone/acrylic in case of smoke-tight function.
  • Gaps > 5 – 20 mm: (not uniform over the entire profile length)
    • Backfill with mineral wool of building materials class A1.

Non-paintable parts
The following parts must not be painted:

  • Track / rollers
  • Cable and return pulleys
  • Electric magnet
  • Toothed belt
  • Hydraulic track control
  • Door closers
  • Travel limit damper
  • Lever handle / recessed lever handle/folding ring
  • Floor buffer / roller

Door lock (optional)
Optionally, the sliding door can be equipped with a curved bolt lock or a hook catch lock. The locks are already fitted at the factory. The lock plate height can be set in the guiding profile.

ATTENTION
Damage to the curved bolt lock
Due to closing the sliding door with the bolt extended.

  • Do not lock the open sliding door.
  • First adjust the closing speed of the door, then activate the lock system.

ATTENTION
Damage to the hook catch lock
Due to opening the locked sliding door.

  • Do not open a locked sliding door.
  • First adjust the closing speed of the door, then activate the lock system.
  • The door leaf must not bounce back after closing.
  • Adjust the travel limit dampers and closing speed.

Installing the hold-open device
The fitting of the hold-open device is determined by the fitting instructions and the manufacturer’s construction technique permit if applicable. Please inquire about any short-notice changes to the fitting conditions if necessary.
Installing the electric opening aid
Observe the manufacturer’s installation instructions.
Installing the optical/ acoustic alarm system
Observe the manufacturer’s installation instructions.

Initial start-up

Before completing the fitting, check that the sliding door is functioning properly. Check the following:

  • Track-bearing surfaces may not be painted.
  • Fit the track in a horizontal position when switched off at the mains.
  • The door leaf must pass walls, lintels, and recesses without any contact.
  • The door must be able to close independently from any position.
  • The closing weight in the weight box must not make contact, block or hit the upper or lower end in any end-of-travel position of the sliding door.
  • The closing weight cable may not chafe at any point.
  • Return pulleys must be easy to move.
  • The closing speed of the door leaf must be between 0.08 m/s and 0.20 m/s. This results in a travel time of 5 –12 s/m (Figure 12)HORMANN-FST-MZ-OD-Fire-and-Smoke-Tight-Sliding-Door-FIG42
  • Doors with smoke protection functions require a seamless floor or a stainless steel floor rail (not included in the standard delivery).

Operation

Caution
The danger of injury due to door run

  • Objects and persons, especially children, must not be in the door system’s range of motion or opening.
  • When moving to the end-of-travel position and for doors with compensator function, use the grip handle, and not the recessed handle.
  • For doors with a compensator function, the door leaf is decoupled from the closing weight and can be moved very easily.
  • Open the door slowly by hand.
  • High opening speeds can cause damage to the floor buffer and the magnet support bracket.

Opening (without electric operator):

  • Open the door leaf up to the stop / hold-open device by hand.

The hold-open device in the Door open position:
The hold-open device consists of a telescopic anchor and an electric magnet (24 V DC). The electric magnet is wired to a smoke detector.
The leaves are released by

  • Push button
  • Smoke detector
  • Power failure

Closing (without electric operator):

ATTENTION
Exceeding the closing speed
Accelerating the closing speed may damage the closing device and the guiding profile.

  • Do not exceed the set closing speed of the sliding door (for example by pushing manually). The steel cable will become trapped and damaged. The correct closing of the door can then no longer be ensured. The steel cable may break.

The closing weight closes the released door leaf. The closing weight is connected to the labyrinth element via a pull cord.

  • The closing speed of 0.08 m/s to 0.2 m/s or a travel time of 5 – 12 s/m can be set on the hydraulic track control (Figure 12).

Checking and maintenance

The owner or a person authorized by the owner is responsible for proper maintenance of the sliding door in the specified intervals.

  • Functional parts, particularly safety components, may only be exchanged by specialists.
  • Document maintenance.

At least 1 × monthly:

  • General visual inspection of the door leaf and frame for damage/changes
  • Check the function of the fire alarm system (smoke detector), self-closing mechanism, hold-open device (electric magnet)
  • Check the seals (with the smoke-tight door version) for wear and correct position
  • Replace defective parts using original spare parts
  • Check closing speed
  • Lock plates for the locks/latches must be free of obstacles

At least 1 × a year:
Check fixings:

  • Check the connections between the track, guiding profile, weight box and labyrinth profile to the wall
  • All fitting screws

Track:

  • Check for cleanliness and clean if necessary.
  • Apply a thin layer of multi-purpose grease (NLGI class 2, water-resistant, acid-free) to the track-bearing surfaces.

Door travel properties:

  • Checking for a perfect door travel
  • Check for unusual noises when opening and closing

Cable:
Check for wear, corrosion, chafing, creasing and wire tearing
Cable fastening:
Check the cable fastening on the door leaf and in the weight box
Cable pulleys and hydraulic track control:

  • Cable pulleys are easy to move
  • Function of the hydraulic track control

Floor guide roller:
Function of the floor guide roller

Information signs and ID plates:
Legibility of all information signs and ID plates

Fire sliding doors with wicket door
Check fastening and function:

  • Closers
  • Hinges
  • Lock

Note:
Shorten the maintenance intervals in case of excessive dust, dirt, moisture, chemicals, etc. For fire sliding doors with opening aids (see Figure 16) you also have to set the closing speed of the door via the hydraulic track control in the weight box. Set the track control on the opening aid to the minimum resistance.

Cleaning and care

Clean and oil all mechanical parts with suitable cleaning agents depending on the wear and as required, but at least 1 × a year.

ATTENTION
Unsuitable cleaning agents and incorrect cleaning

  • Do not use any high-pressure cleaners, lyes and acids for cleaning.
  • Do not rub hard.
  • Never use abrasive sponges containing metal, steel wool or steel brushes, products that contain chloride, particularly hydrochloric acid products, bleach or silver polish.

Surface treatment
Galvanized surfaces

  • Use clear water.
  • Use warm water together with a neutral, non-abrasive cleaning agent (household detergent, pH value°7) if more heavily soiled.

When using mildly acidic, neutral or alkaline degreasing agents, immediately clean the surface with water. The residue-free removal of the degreasing agent prevents chemical damage to the zinc surface.
Removal of white rust from galvanized surfaces

  • Remove white rust residue-free by using hard nylon brushes.
  • Wire brushes are not suitable.
  • Dark spots or tinting usually left after brushing adapts to the environment with time.

Contact a specialist painting company in case of repeated white rust formation.
Powder-coated surfaces
The surface of the door leaf and frame consists of a primer powder coating based on epoxy resin and polyester.

  • Clearwater is sufficient for cleaning and care.
  • Use warm water together with a neutral, non-abrasive cleaning agent (household detergent, pH value°7) if more heavily soiled.

Stainless steel surfaces
Conduct an initial passivation of the stainless steel door construction after completion of the construction work. Contact the supplier for further information. When using stainless steel doors first make sure that the quality of the stainless steel is suitable for the application. Stainless steel may rust. To prevent corrosion, remove the protective film completely right after fitting, however no later than 3 months.

  • Clean stainless steel surfaces with a damp cloth or shammy.
  • For heavier soiling, use a common (non-ferrous) sponge.
  • Remove fingerprints, as well as oily and greasy contamination, with a special cleaning agent (e.g. NIRO-Brillant).

Recommendations for material selection
Fire sliding doors can be optimized for their application by selecting the appropriate materials. Under certain conditions, stainless steel products may be affected by surface corrosion, pitting or crevice corrosion or stress corrosion cracking. More information is available directly from the manufacturing factory.

Dismantling

Dismantle the door in accordance with these fitting instructions in the logically correct reverse order.

Disposal
Disassemble the sliding door into individual parts after dismantling. Recycle or dispose of the components in accordance with local official regulations.

Malfunctions and troubleshooting

Malfunction Possible cause Remedy View|
---|---
1| Sliding door does| Electric magnet does not release the door| ▶| Check push button and wiring.| ––|
| not fully close|
Track not fitted horizontally| ▶| Align the track horizontally.| 6a .4| HORMANN-FST-MZ-OD-Fire-and-Smoke-Tight-Sliding-Door-
FIG9
| | Track hangs forward| ▶| Align the track horizontally.| 6a .4| HORMANN-FST-MZ-OD-Fire-and-Smoke-Tight-Sliding-Door-
FIG9
| | Track fitted in waves| ▶| Align the track horizontally.| 6a .4| HORMANN-FST-MZ-OD-Fire-and-Smoke-Tight-Sliding-Door-
FIG9
| | Track fitted in a distorted manner| ▶| Adjust the track fixing bracket correctly.| 6a .4| HORMANN-FST-MZ-OD-Fire-and-Smoke-Tight-Sliding-Door-
FIG9
| | Track is dirty| ▶| Clean the track bearing surfaces.| 7 .1| HORMANN-FST-MZ-OD-Fire-and-Smoke-Tight-Sliding-Door-
FIG18
| | Door elements are distorted| ▶| Loosen the tensioning nuts. Re-align the elements.| 7 .9| HORMANN-FST-MZ-OD-Fire-and-Smoke-Tight-Sliding-
Door-FIG22
| | Rollers incorrectly fitted| ▶| Check the position of rollers (concave, straight) and that fitting on the axle is correct.| 7 .5| HORMANN-
FST-MZ-OD-Fire-and-Smoke-Tight-Sliding-Door-FIG19
| | Door leaf scrapes against the floor| ▶| Adjust the door leaf to the correct floor clearance.| 7 .7| HORMANN-FST-MZ-OD-Fire-and-Smoke-
Tight-Sliding-Door-FIG22
| | Door leaf touches the brickwork in the parking area| ▶| Increase the wall spacing by refitting the sliding door.| ––|
| | Cable is jammed| ▶| Check the cable guide and the return pulleys.| ––|
| | Closing weight does not move| ▶| Check vertical fitting of the weight box.| 4| HORMANN-FST-MZ-OD-Fire-and-Smoke-Tight-Sliding-Door-
FIG5
| | | ▶| Check the weight box for damage.| ––|
| | | ▶| Check fitting of the anti-rotation safeguard.| 11a.3| HORMANN-FST-MZ-OD-Fire-and-Smoke-Tight-Sliding-Door-
FIG36
| | ▶| Shorten the cable so that the weight does not touch the floor prematurely.| 11a.3| HORMANN-FST-MZ-OD-Fire-and-Smoke-Tight-Sliding-
Door-FIG36
| | Door leaf touches the guiding profile| ▶| Align the guiding profile.| 4| HORMANN-FST-MZ-OD-Fire-and-Smoke-Tight-Sliding-Door-
FIG5
| | Guidance damper adjusted too strongly| ▶| Adjust the guidance damper.| 9 .6a| HORMANN-FST-MZ-OD-Fire-and-Smoke-Tight-Sliding-Door-
FIG26
| | Door leaf is slowed down by the wall labyrinth| ▶| Move the wall labyrinth.| 9 .2| HORMANN-FST-MZ-OD-Fire-and-Smoke-Tight-Sliding-
Door-FIG27
| | Increased frictional resistance due to a rough bottom| ▶| Process the bottom surface.| ––|
| | surface for the ST seal|
▶| Adjust the door leaf to the correct floor clearance. Increase the closing weight.| 15 .3| HORMANN-FST-MZ-OD-Fire-and-Smoke-Tight-Sliding-
Door-FIG53
2| Door closing speed| Hydraulic track control damping is too large| ▶| Adjust the damping.| 12 .1| HORMANN-FST-MZ-OD-Fire-and-
Smoke-Tight-Sliding-Door-FIG42
| too slow|
The bearing above the brake roller (= cable skip| ▶| Adjust the bearing so that no pressure is exerted on the cable| ––|
| | safety) is pressing against the brake roller| | or brake roller.| |
| | Hydraulic track control damping is correct:| ▶| Search for the error under malfunction 1.| ––|
3| Door closing speed| Hydraulic track control damping is too small| ▶| Adjust the damping.| 12 .1| HORMANN-FST-MZ-OD-Fire-and-
Smoke-Tight-Sliding-Door-FIG42
| too fast|
Track fitted with slope in the direction of the guiding| ▶| Align the track horizontally.| 6a .4| HORMANN-FST-MZ-OD-Fire-and-Smoke-Tight-Sliding-
Door-FIG12
| | profile| | | |
| | Closing weight too high| ▶| Reduce the closing weight.| ––|
| | The operational direction of the brake roller was not| ▶| Turn the brake roller.| 11a.2| HORMANN-FST-MZ-OD-Fire-and-Smoke-Tight-Sliding-Door-
FIG36
| | adjusted on-site| | | |
4| Not enough track fixing brackets supplied| Different fitting distance of the lintel and parking area was not taken into account| ▶| Fit the support brackets according to the specified distance.| 5| HORMANN-FST-
MZ-OD-Fire-and-Smoke-Tight-Sliding-Door-FIG7
5 Cable tear Cable sags or is not under tension| ▶| Adjust the track horizontally.| ––|
▶| Do not close the door by hand.| ––|
▶| Closing weight is slowed down in the weight box. See malfunction 1.| ––|
6| Unusual noises when opening and closing| Rollers touch in the track| ▶| Adjust the track fixing brackets correctly. If the track is distorted, see malfunction 1.| 6a .4| HORMANN-FST-MZ-OD-Fire-and-Smoke-
Tight-Sliding-Door-FIG12
▶| Align the track horizontally. If the track hangs forward, see malfunction 1.| 6a .4| HORMANN-FST-MZ-OD-Fire-and-Smoke-Tight-Sliding-Door-
FIG12
Track is dirty| ▶| Clean the track bearing surfaces.| 7 .1| HORMANN-FST-MZ-OD-Fire-and-Smoke-Tight-Sliding-Door-
FIG18
Door leaf scrapes against the floor| ▶| Adjust the floor clearance correctly.| 7 .7| HORMANN-FST-MZ-OD-Fire-and-Smoke-Tight-Sliding-Door-
FIG20
Door leaf touches the brickwork in the parking area| ▶| Increase the wall spacing by refitting the sliding door.| ––|
Door elements touch the track| ▶| Door elements are distorted. Loosen the tensioning nuts. Re-align the elements. See malfunction 1.| 7 .9| HORMANN-FST-MZ-OD-Fire-and-Smoke-Tight-Sliding-Door-
FIG22
Closing weight does not move fault-free| ▶| Check vertical fitting of the weight box.| 4| HORMANN-FST-MZ-OD-Fire-and-Smoke-Tight-Sliding-Door-
FIG5
▶| Check for damage to the weight box.| ––|
▶| Check fitting of the anti-rotation safeguard.| 11a.3| HORMANN-FST-
MZ-OD-Fire-and-Smoke-Tight-Sliding-Door-FIG36
▶| Shorten the cable so that the weight does not touch the floor.| 11a.3| HORMANN-FST-MZ-OD-Fire-and-Smoke-Tight-Sliding-Door-
FIG36
7| Open sliding door cannot be fixed| Electric magnet does not fix| ▶| Check push button and wiring.| |
▶| Check the electric magnets.| |
▶| Check the power supply.| |