RAB A17 Area Light Installation Guide
- June 9, 2024
- RAB
Table of Contents
A17 Area Light
Installation Guide
A17 Area Light
IMPORTANT
READ CAREFULLY BEFORE INSTALLING FIXTURE. RETAIN THESE INSTRUCTIONS FOR
FUTURE REFERENCE.
RAB fixtures must be wired in accordance with the National Electrical Code and
all applicable local codes. Proper grounding is required for safety. THIS
PRODUCT MUST BE INSTALLED IN ACCORDANCE WITH THE APPLICABLE INSTALLATION CODE
BY A PERSON FAMILIAR WITH THE CONSTRUCTION AND OPERATION OF THE PRODUCT AND
THE HAZARDS INVOLVED.
WARNING: Make certain power is OFF before installing or maintaining
fixture. No user serviceable parts inside.
WARNING: Do not use an electric generator to test LED fixtures.
WARNING: Min 75°C SUPPLY CONDUCTORS.
MOUNTING THE UNIVERSAL ARM ON THE FIXTURE
- Remove the Arm Cover from the Arm by loosening Arm Cover Screws as shown in Fig. 1.
- Feed wires from fixture into Arm.
- Line up Arm and fixture. Tighten screws inside the Arm and tighten securely to housing.
- Replace the Arm Cover and secure with Screws as shown in Fig. 2.
Square Pole Mount
-
Place the Bolster Plate inside the Pole as shown in Fig. 3.
-
Remove the Round Pole Adaptor Plate.
-
Fix Arm to Square Pole with Bolt.
-
Open the Arm Cover and pull the wires into the junction box.
-
Feed supply wires from the Pole to connect to the Arm.
Make appropriate wire connections per NEC in an approved enclosure (Fig. 7). -
Use bolts to tighten to the Pole.
Round Pole Mount
- Place the Bolster Plate inside the Pole as shown in Fig. 3.
- Fix Arm to Round Pole with Bolt.
- Open the Arm Cover and pull the wires into the junction box.
- Feed supply wires from the Pole to connect to the Arm. Make appropriate wire connections per NEC in an approved enclosure (Fig. 7).
- Use bolts to tighten to the Pole.
SLIPFITTER MOUNT
NOTICE: Adjustable angle is 90°.
- Place the Slipfitter over the Tenon and secure the Fixture with set Screws on the side of the Slipfitter as shown in Fig. 5.
- Feed wires from Fixture through Slipfitter and supply wires from pole. Make the necessary connections in the Slipfitter and knot wires for strain relief.
- To adjust the angle of the Slipfitter, losen the Locking Bolt and swivel Fixture to desired angle. The graduation of the Slipfitter cover plate can be used as guidelines to adjust the angle.
- Tighten the Locking Bolt (Fig. 6).
0-10V DIMMABLE WIRING
Universal voltage driver permits operation at 120V thru 277V, 50 or 60 Hz.
Units ordered with /480 suffix operate at 480V, 50 or 60Hz.
For 0-10 Dimming, follow the wiring directions as shown in Fig. 7.
-
Connect the black/brown fixture lead to the LINE supply lead.
-
Connect the white/blue fixture lead to the COMMON supply lead.
-
Connect the green/yellow wire from fixture to supply ground.
Do NOT connect the GROUND of the dimming fixture to the output. -
Connect the purple fixture lead to the DIM V+ lead.
-
Connect the pink/gray fixture lead to the DIM V- lead.
-
Cap the yellow fixture lead, if present. Do NOT connect.
CLEANING & MAINTENANCE
CAUTION: Do not open or remove Respirator Plug as shown in Fig. 8. Be
sure fixture temperature is cool enough to touch.
Do not clean or maintain while fixture is energized.
- Clean Polycarbonate lens with non-abrasive glass cleaning solution.
- Do not open the fixture to clean the LED. Do not touch the LED.
Note: These instructions do not cover all details or variations in equipment nor do they provide for every possible situation during installation, operation or maintenance.
Microwave Motion Sensor
PERFORMANCE
Operating voltage | 12 ± 2V DC |
---|---|
Operating current | 30mA |
Output | DIM 0-10V |
Stand-by power | <0.5W |
Brightness | 70%/80%/90%/100% |
Detection area | 20%/50%/75%/100% |
Hold time | 10s/1min/10min/30min |
Daylight threshold | 10Lux/30Lux/50Lux/100Lux/Disable |
Stand-by period | 1min/30min/60min/+∞ |
Stand-by dimming level | 10%/20%/30%/50% |
Microwave frequency | 5.8GHz ± 75MHz |
Microwave power | <0.5mW |
Detection angle | 30-150° |
Control line | Black/White:12V+ ; Purple: DIM+ ; Pink: 12V-/DIM- |
Mounting height | Max 15M (ceiling mounted) |
Detection range | Max Ø15m (ceiling mounted) Max 20m(wall mounted) |
Operating temperature | -25°C~+60°C |
IP rating | IP65 |
MVS SENSOR FACTORY SETTINGS
BRIGHTNESS | 100% |
---|---|
HOLD TIME | 1 Minute |
DAYLIGHT | Disabled |
SENSITIVITY | 50% |
STAND-BY DIMMING LEVEL | 20% |
STAND-BY TIME | 1 Minute |
DIMENSIONS
Weight: 0.14lb
WIRING DIAGRAM
DETECTION COVERAGE
LUX ON-OFF
Sensor automatically turns off light when ambient brightness exceeds preset
lux level. Following preconditions apply to use the Lux On Off function:
- Stand-by period : +∞
- Stand-by dimming level : 10%, 20%, 30% or 50%
- Daylight threshold : 10Lux, 30Lux, 50Lux or 100Lux
When ambient brightness is lower than preset lux level, light automatically turns on| When motion detected while ambient brightness is insufficient, light DIMs 100%| Light dims to stand-by level when there is no motion detection after hold time| When ambient brightness is higher than preset lux level, light automatically turns off
INSTRUCTIONS REMOTE-OD
RAB Lighting is committed to creating high-quality, affordable, well-designed
and energy-efficient LED lighting and controls that make it easy for
electricians to install
and end users to save energy. We’d love to hear your comments. Please call the
Marketing Department at 888-RAB-1000 or email:
marketing@rablighting.com
REMOTE-OD
PROGRAMMING GUIDELINES
- If you want to send a setting, it will only work if the remote control is on. If you do not press any button within 10 seconds, the indicator light will go out.
- When using “ON/OFF” button, the rest of the buttons except the “ON/OFF”, “BRIGHTNESS” and “SEND” buttons will be disabled.
- When using “TEST” button, the rest of the buttons except the “TEST”, “SENSITIVITY” and “SEND” button will be disabled.
- Every change requires you to press the “SEND” button to save.
- Because of the power supply DIMMING ratio diff erence, when using diff erent power, “BRIGHTNESS” and “STANDBY DIM” adjust percentage of the power will have diff erence with the measured power.
© 2022 RAB LIGHTING Inc.
REMOTE-OD
REMOTE CONTROL – IN – 0322
73724-RAB
Easy Answers
rablighting.com
Visit our website for product info
Tech Help Line
Call our experts: 888 722-1000
e-mail
Answered promptly – sales@rablighting.com
Free Lighting Layouts
Answered online or by request
References
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>