SAMSUNG TGHQABU Essential R32 Air Conditioner User Manual
- June 9, 2024
- Samsung
Table of Contents
TGHQABU Essential R32 Air Conditioner
ARTGHQ**ME
Table of Contents
Safety Precautions …………………………………………………………………….05
User Manual Unit Specifications and Features…………………………………………………..10 10 1.
Indoor unit display…………………………………………………………………………………………………………. 11 2. Operating
temperature…………………………………………………………………………………………………… 12 3. Other features
……………………………………………………………………………………………………………… 13 4. Setting angle of
airflow………………………………………………………………………………………………….. 13 5. Manual operation (without
Remote)………………………………………………………………………………….
Care and Maintenance……………………………………………………………. 14
Troubleshooting……………………………………………………………………… 16
Installation Manual
Accessories……………………………………………………………………………… 19
Installation Summary – Indoor Unit …………………………………………. 20
Unit Parts…………………………………………………………………………………21
Indoor Unit Installation…………………………………………………………….22
22 1. Select installation location……………………………………………………………………………………………….. 22 2.
Attach mounting plate to wall………………………………………………………………………………………….. 23 3. Drill
wall hole for connective piping…………………………………………………………………………………… 24 4. Prepare
refrigerant piping………………………………………………………………………………………………… 24 5. Connect drain
hose………………………………………………………………………………………………………… 25 6. Connect signal
cable………………………………………………………………………………………………………. 26 7. Wrap piping and
cables………………………………………………………………………………………………….. 27 8. Mount indoor
unit………………………………………………………………………………………………………….
Outdoor Unit Installation……………………………………………………………….28
28 1. Select installation location……………………………………………………………………………………………….. 29 2.
Install drain joint……………………………………………………………………………………………………………. 29 3. Anchor
outdoor unit………………………………………………………………………………………………………. 31 4. Connect signal and
power cables………………………………………………………………………………………
Refrigerant Piping Connection………………………………………………… 32
32 A. Note on Pipe Length…………………………………………………………………………………………………….. 32 B.
Connection Instructions Refrigerant Piping………………………………………………………………………
32 1. Cut pipe………………………………………………………………………………………………………………… 33 2. Remove
burrs…………………………………………………………………………………………………………. 33 3. Flare pipe
ends……………………………………………………………………………………………………….. 33 4. Connect
pipes…………………………………………………………………………………………………………
Air Evacuation……………………………………………………………………….. 35 35 1. Evacuation
Instructions…………………………………………………………………………………………………. 36 2. Note on Adding
Refrigerant……………………………………………………………………………………………
Electrical and Gas Leak Checks……………………………………………….. 37
Test Run………………………………………………………………………………… 38
In using R-32 …………………………………………………………………………. 39
Remote manual
Remote controller Specifications ……………………………………………… 43 Operation buttons
………………………………………………………………….. 44 Indicators on LCD
……………………………………………………………………..47 How to use the buttons …………………………………………………………..
48 Auto operation ……………………………………………………………………….. 48 Cooling/Heating/Fan
operation ……………………………………………….. 48 Dehumidifying operation
………………………………………………………… 49 Timer operation ……………………………………………………………………… 50
Handling the remote controller ……………………………………………….. 54
Safety Precautions
Safety Precautions
Read Safety Precautions Before Operation and Installation
Incorrect installation due to ignoring instructions can cause serious damage
or injury. The seriousness of potential damage or injuries is classified as
either a WARNING or CAUTION.
WARNING
This symbol indicates the possibility of personnel injury or loss of life.
CAUTION
This symbol indicates the possibility of property damage or serious
consequences.
WARNING
This appliance can be used by children aged from 8 years and above and persons
with reduced physical, sensory or mental capabilities or lack of experience
and knowledge if they have been given supervision or instruction concerning
use of the appliance in a safe way and understand the hazards involved.
Children shall not play with the appliance. Cleaning and user maintenance
shall not be made by children without supervision EN Standard requirements
.
This appliance is not intended for use by persons(including children) with
reduced physical, sensory or mental capabilities, or lack of experience and
knowledge, unless they have been given supervision or instruction concerning
use of the appliance by a person responsible for their safety. Children should
be supervised to ensure that they do not play with the appliance(IEC Standard
requirements).
WARNINGS FOR PRODUCT USE
· If an abnormal situation arises (like a burning smell), immediately turn off
the unit and disconnect the power. Call your dealer for instructions to avoid
electric shock, fire or injury.
· Do not insert fingers, rods or other objects into the air inlet or outlet.
This may cause injury, since the fan may be rotating at high speeds.
· Do not use flammable sprays such as hair spray, lacquer or paint near the
unit. This may cause fire or combustion.
· Do not operate the air conditioner in places near or around combustible
gases. Emitted gas may collect around the unit and cause explosion.
· Do not operate your air conditioner in a wet room such as a bathroom or
laundry room. Too much exposure to water can cause electrical components to
short circuit.
· Do not expose your body directly to cool air for a prolonged period of time.
· Do not allow children to play with the air conditioner. Children must be
supervised around the unit at all times.
· If the air conditioner is used together with burners or other heating
devices, thoroughly ventilate
the room to avoid oxygen deficiency. · In certain functional environments,
such as kitchens, server rooms, etc., the use of specially
designed air-conditioning units is highly recommended.
Page 5
Safety Precautions
CLEANING AND MAINTENANCE WARNINGS
· Turn off the device and disconnect the power before cleaning. Failure to do
so can cause electrical shock.
· Do not clean the air conditioner with excessive amounts of water. · Do not
clean the air conditioner with combustible cleaning agents. Combustible
cleaning agents
can cause fire or deformation.
CAUTION
· Turn off the air conditioner and disconnect the power if you are not going
to use it for a long time. · Turn off and unplug the unit during storms. ·
Make sure that water condensation can drain unhindered from the unit. · Do not
operate the air conditioner with wet hands. This may cause electric shock. ·
Do not use device for any other purpose than its intended use. · Do not climb
onto or place objects on top of the outdoor unit. · Do not allow the air
conditioner to operate for long periods of time with doors or windows open,
or if the humidity is very high.
ELECTRICAL WARNINGS · Only use the specified power cord. If the power cord is
damaged, it must be replaced by the
manufacturer, its service agent or similarly qualified persons in order to
avoid a hazard. · Keep power plug clean. Remove any dust or grime that
accumulates on or around the plug. Dirty
plugs can cause fire or electric shock. · Do not pull power cord to unplug
unit. Hold the plug firmly and pull it from the outlet. Pulling
directly on the cord can damage it, which can lead to fire or electric shock.
· Do not modify the length of the power supply cord or use an extension cord
to power the unit. · Do not share the electrical outlet with other appliances.
Improper or insufficient power supply
can cause fire or electrical shock. · The product must be properly grounded at
the time of installation, or electrical shock may occur. · For all electrical
work, follow all local and national wiring standards, regulations, and the
Installation Manual. Connect cables tightly, and clamp them securely to
prevent external forces from damaging the terminal. Improper electrical
connections can overheat and cause fire, and may also cause shock. All
electrical connections must be made according to the Electrical Connection
Diagram located on the panels of the indoor and outdoor units. · All wiring
must be properly arranged to ensure that the control board cover can close
properly. If the control board cover is not closed properly, it can lead to
corrosion and cause the connection points on the terminal to heat up, catch
fire, or cause electrical shock. · If connecting power to fixed wiring, an
all-pole disconnection device which has at least 3mm clearances in all poles,
and have a leakage current that may exceed 10mA, the residual current
device(RCD) having a rated residual operating current not exceeding 30mA, and
disconnection must be incorporated in the fixed wiring in accordance with the
wiring rules.
TAKE NOTE OF FUSE SPECIFICATIONS
The air conditioner’s circuit board (PCB) is designed with a fuse to provide
overcurrent protection. The specifications of the fuse are printed on the
circuit board ,such as : Indoor unit: T3.15AL/250VAC, T5AL/250VAC,
T3.15A/250VAC, T5A/250VAC, etc. Outdoor unit: T20A/250VAC(<=18000Btu/h units)
T30A/250VAC(>18000Btu/h units) NOTE: For the units with R32 refrigerant , only
the blast-proof ceramic fuse can be used.
Page 6
Safety Precautions
WARNINGS FOR PRODUCT INSTALLATION
1. Installation must be performed by an authorized dealer or specialist.
Defective installation can cause water leakage, electrical shock, or fire.
2. Installation must be performed according to the installation instructions.
Improper installation can cause water leakage, electrical shock, or fire.
3. Contact an authorized service technician for repair or maintenance of this
unit. This appliance shall be installed in accordance with national wiring
regulations.
4. Only use the included accessories, parts, and specified parts for
installation. Using non-standard parts can cause water leakage, electrical
shock, fire, and can cause the unit to fail.
5. Install the unit in a firm location that can support the unit’s weight. If
the chosen location cannot support the unit’s weight, or the installation is
not done properly, the unit may drop and cause serious injury and damage.
6. Install drainage piping according to the instructions in this manual.
Improper drainage may cause water damage to your home and property.
7. For units that have an auxiliary electric heater, do not install the unit
within 1 meter (3 feet) of any combustible materials.
8. Do not install the unit in a location that may be exposed to combustible
gas leaks. If combustible gas accumulates around the unit, it may cause fire.
9. Do not turn on the power until all work has been completed. 10.When moving
or relocating the air conditioner, consult experienced service technicians for
disconnection and reinstallation of the unit. 11.How to install the appliance
to its support, please read the information for details in “indoor unit
installation” and “outdoor unit installation” sections .
Note about Fluorinated Gasses
1. Installation, service, maintenance and repair of this unit must be
performed by a certified technician.
2. Product uninstallation and recycling must be performed by a certified
technician. 3. For equipment that contains fluorinated greenhouse gases in
quantities of 5 tonnes of CO2
equivalent or more, but of less than 50 tonnes of CO2 equivalent, If the
system has a leakdetection system installed, it must be checked for leaks at
least every 24 months. 4. When the unit is checked for leaks, proper record-
keeping of all checks is strongly recommended.
Page 7
Safety Precautions
WARNING for Using R32 Refrigerant
When flammable refrigerant are employed, appliance shall be stored in a well
-ventilated area where the room size corresponds to the room area as specifiec
for operation. For R32 frigerant models: Appliance shall be installed,
operated and stored in a room with a floor area larger than 4m2. Appliance
shall not be installed in an unvertilated space, if that space is smaller than
4m 2 . When mechanical connectors are reused indoors, sealing parts shall be
renewed. When flared joints are reused indoors, the flare part shall be re-
fabricated. (IEC Standard Requirements)
Correct Disposal of This Product (Waste Electrical & Electronic Equipment)
(Applicable in countries with separate collection systems) This marking on the
product, accessories or literature indicates that the product and its
electronic accessories (e.g. charger, headset, USB cable) should not be
disposed of with other household waste at the end of their working life. To
prevent possible harm to the environment or human health from uncontrolled
waste disposal, please separate these items from other types of waste and
recycle them responsibly to promote the sustainable reuse of material
resources. Household users should contact either the retailer where they
purchased this product, or their local government office, for details of where
and how they can take these items for environmentally safe recycling. Business
users should contact their supplier and check the terms and conditions of the
purchase contract. This product and its electronic accessories should not be
mixed with other commercial wastes for disposal.
Correct disposal of batteries in this product This marking on the battery,
manual or packaging indicates that the batteries in this product should not be
disposed of with other household waste at the end of their working life. Where
marked, the chemical symbols Hg, Cd or Pb indicate that the battery contains
mercury, cadmium or lead above the reference levels in EC Directive 2006/66.
Page 8
WARNING In case of a malfunction, immediately stop operation of the air
conditioner and disconnect the entire power system. Then consult the
authorized service personnel.
CAUTION The product shall be stored in a room with no ignition sources
(e.g. open flames, gas appliance, electric heater, etc.). · Note that the
refrigerant has no odour.
When the air conditioner does not operate properly for cooling or heating,
there is a possibility of refrigerant leakage. If any leakage, stop operation,
ventilate the room, and consult your dealer immediately for recharging
refrigerant. The refrigerant is not harmful. However, if it comes in contact
with fire, it may generate harmful gases and there is risk of fire. During
transportation of the indoor unit, the pipe lines shall be covered with
brackets for protection. Do not move the product with holding the pipe lines.
· It may cause gas leakage.
Do not cut or burn the refrigerant container or pipings. Do not point the air
direction to the fireplace or heater.
Page 9
Unit Specifications and Features
Unit Specifications and Features
Indoor unit display
NOTE: Different models have different front panel and display window. Not all
the indicators describing below are available for the air conditioner you
purchased. Please check the indoor display window of the unit you purchased.
Illustrations in this manual are for explanatory purposes. The actual shape of
your indoor unit may be slightly different. The actual shape shall prevail.
Front Panel
Power Cable (Some Units)
Louver
Remote Control Remote Control Holder(Some Units)
Display window
” fresh ” when Fresh feature is activated(some units) “defrost” when defrost feature is activated. ” run ” when the unit is on. ” timer ” when TIMER is set.
” ” Displays temperature, operation feature and
Error codes:
Whe, nilEluCmOinfuantecstigorna(dsoumalelyuonnites)biys
activated, one as —
the
,
— –set temperature — …… in one second interval.
Display Code Meanings
” ” for 3 seconds when:
· TIMER ON is set (if the unit is OFF, ” ” remains on when TIMER ON is set ) ·
FRESH, SWING, TURBO, or SILENCE feature is turned on
” ” for 3 seconds when: · TIMER OFF is set · FRESH, SWING, TURBO, or SILENCE feature is turned off ” ” when anti-cold air feature is turned on ” ” when defrosting(cooling & heating units) ” ” when unit is self-cleaning(some units) ” ” when 8 C heating feature is turned on(some units)
Page 10
Unit Specifications and Features
Operating temperature
When your air conditioner is used outside of the following temperature ranges, certain safety protection features may activate and cause the unit to disable.
Inverter Split Type
COOL mode
Room Temperature
17°C – 32°C (62°F – 90°F)
Outdoor Temperature
0°C – 50°C (32°F – 122°F)
DRY mode 10°C – 32°C (50°F – 90°F)
0°C – 50°C (32°F – 122°F)
FOR OUTDOOR UNITS WITH AUXILIARY ELECTRIC HEATER
When outside temperature is below 0°C (32°F ), we strongly recommend keeping
the unit plugged in at all time to ensure smooth ongoing performance.
NOTE: Room relative humidity less than 80%. If the air conditioner operates in
excess of this figure, the surface of the air conditioner may attract
condensation. Please sets the vertical air flow louver to its maximum angle
(vertically to the floor), and set HIGH fan mode.
To further optimize the performance of your unit, do the following: · Keep
doors and windows closed. · Limit energy usage by using TIMER ON and TIMER OFF
functions. · Do not block air inlets or outlets. · Regularly inspect and clean
air filters.
Page 11
Unit Specifications and Features
Not all the functions are available for the air conditioner, please check the
indoor display and remote control of the unit you purchased.
Other Features
· Auto-Restart If the unit loses power, it will automatically restart with the
prior settings once power has been restored.
· Louver Angle Memory When turning on your unit, the louver will automatically
resume its former angle.
· Refrigerant Leakage Detection
The indoor unit will automatically display “EC” or “EL0C”or flash LEDS (model
dependent ) when it detects refrigerant leakage.
· Sleep Operation The SLEEP function is used to decrease energy use while you
sleep (and don’t need the same temperature settings to stay comfortable). This
function can only be activated via remote control. And the Sleep function is
not available in FAN or DRY mode.
Press the SLEEP button when you are ready to go to sleep. When in COOL mode,
the unit will increase the temperature by 1°C (2°F) after 1 hour, and will
increase an additional 1°C (2°F) after another hour.
The sleep feature will stop after 8 hours and the system will keep running
with final situation.
SLEEP Operation
Set temperature
Cool mode(+1 C/2 F) per hour for the first two hours
1hr
1hr
Keep running
Saving energy during sleep
Page 12
Unit Specifications and Features
· Setting Angle of Air Flow
Setting vertical angle of air flow
While the unit is on, use the SWING/ DIRECT button on remote control to set
the direction (vertical angle) of airflow. Please refer to the Remote Control
Manual for details.
NOTE ON LOUVER ANGLES When using COOL or DRY mode, do not set louver at too
vertical an angle for long periods of time. This can cause water to condense
on the louver blade, which will drop on your floor or furnishings. When using
COOL or HEAT mode, setting the louver at too vertical an angle can reduce the
performance of the unit due to restricted air flow.
Setting horizontal angle of air flow
The horizontal angle of the airflow must be set manually. Grip the deflector
rod (See Fig.B) and manually adjust it to your preferred direction. For some
units, the horizontal angle of the airflow can be set by remote control.
please refer to the Remote Control Manual.
Range
NOTE: Do not move louver by hand. This will
cause the louver to become out of sync. If this
occurs, turn off the unit and unplug it for a few
seconds, then restart the unit. This will reset the
louver.
Fig. A
CAUTION
Do not put your fingers in or near the blower and suction side of the unit.
The high-speed fan inside the unit may cause injury.
Manual Operation(without remote)
CAUTION
The manual button is intended for testing purposes and emergency operation
only. Please do not use this function unless the remote control is lost and it
is absolutely necessary. To restore regular operation, use the remote control
to activate the unit. Unit must be turned off before manual operation.
To operate your unit manually: 1. Open the front panel of the indoor unit. 2.
Locate the MANUAL CONTROL button on
the right-hand side of the unit. 3. Press the MANUAL CONTROL button one
time to activate FORCED AUTO mode. 4. Press the MANUAL CONTROL button again
to activate FORCED COOLING mode. 5. Press the MANUAL CONTROL button a third
time to turn the unit off. 6. Close the front panel.
Deflector rod
Fig. B
Manual control button
Page 13
Care and Maintenance
Care and Maintenance
Cleaning Your Indoor Unit
BEFORE CLEANING OR MAINTENANCE
ALWAYS TURN OFF YOUR AIR CONDITIONER SYSTEM AND DISCONNECT ITS POWER SUPPLY
BEFORE CLEANING OR MAINTENANCE.
CAUTION
Only use a soft, dry cloth to wipe the unit clean. If the unit is especially
dirty, you can use a cloth soaked in warm water to wipe it clean.
· Do not use chemicals or chemically treated cloths to clean the unit
· Do not use benzene, paint thinner, polishing powder or other solvents to
clean the unit. They can cause the plastic surface to crack or deform.
· Do not use water hotter than 40°C (104°F) to clean the front panel. This can
cause the panel to deform or become discolored.
6. Rinse the filter with fresh water, then shake off excess water.
7. Dry it in a cool, dry place, and refrain from exposing it to direct
sunlight.
8. When dry, re-clip the air freshening filter to the larger filter, then
slide it back into the indoor unit.
9. Close the front panel of the indoor unit.
Filter Tab
Cleaning Your Air Filter
A clogged air conditioner can reduce the cooling efficiency of your unit, and
can also be bad for your health. Make sure to clean the filter once every two
weeks.
1. Lift the front panel of the indoor unit. 2. First press the tab on the end
of filter to
loosen the buckle, lift it up, then pull it towards yourself. 3. Now pull the
filter out. 4. If your filter has a small air freshening filter, unclip it
from the larger filter. Clean this air freshening filter with a hand-held
vacuum. 5. Clean the large air filter with warm, soapy water. Be sure to use a
mild detergent.
Page 14
Care and Maintenance
CAUTION
· Before changing the filter or cleaning, turn off the unit and disconnect its
power supply.
· When removing filter, do not touch metal parts in the unit. The sharp metal
edges can cut you.
· Do not use water to clean the inside of the indoor unit. This can destroy
insulation and cause electrical shock.
· Do not expose filter to direct sunlight when drying. This can shrink the
filter.
Maintenance Pre-Season Inspection
After long periods of non-use, or before periods of frequent use, do the
following:
Check for damaged wires
Clean all filters
CAUTION
· Any maintenance and cleaning of outdoor unit should be performed by an
authorized dealer or a licensed service provider.
· Any unit repairs should be performed by an authorized dealer or a licensed
service provider.
Check for leaks
Replace batteries
Maintenance Long Periods of Non-Use
If you plan not to use your air conditioner for an extended period of time, do
the following:
Make sure nothing is blocking all air inlets and outlets
Clean all filters
Turn on FAN function until unit dries out completely
Turn off the unit and disconnect the power
Remove batteries from remote control
Page 15
Troubleshooting
Troubleshooting
SAFETY PRECAUTIONS
If ANY of the following conditions occurs, turn off your unit immediately!
· The power cord is damaged or abnormally warm · You smell a burning odor ·
The unit emits loud or abnormal sounds · A power fuse blows or the circuit
breaker frequently trips · Water or other objects fall into or out of the unit
DO NOT ATTEMPT TO FIX THESE YOURSELF! CONTACT AN AUTHORIZED SERVICE PROVIDER
IMMEDIATELY!
Common Issues
The following problems are not a malfunction and in most situations will not require repairs.
Issue
Unit does not turn on when pressing ON/OFF button
Possible Causes
The Unit has a 3-minute protection feature that prevents the unit from
overloading. The unit cannot be restarted within three minutes of being turned
off.
The unit changes from COOL/HEAT mode to FAN mode
The set temperature has been reached, at which point the unit turns off the compressor. The unit will continue operating when the temperature fluctuates again.
The indoor unit emits white mist
In humid regions, a large temperature difference between the room’s air and the conditioned air can cause white mist.
The indoor unit makes noises
A rushing air sound may occur when the louver resets its position.
A squeaking sound may occur after running the unit in COOL mode due to
expansion and contraction of the unit’s plastic parts.
Both the indoor unit and outdoor unit make noises
Low hissing sound during operation: This is normal and is caused by
refrigerant gas flowing through both indoor and outdoor units.
Low hissing sound when the system starts, has just stopped running, or is
defrosting: This noise is normal and is caused by the refrigerant gas stopping
or changing direction.
Squeaking sound: Normal expansion and contraction of plastic and metal parts
caused by temperature changes during operation can cause squeaking noises.
Page 16
Troubleshooting
Issue
The outdoor unit makes noises
Dust is emitted from either the indoor or outdoor unit
Possible Causes
The unit will make different sounds based on its current operating mode.
The unit may accumulate dust during extended periods of non-use, which will be
emitted when the unit is turned on. This can be mitigated by covering the unit
during long periods of inactivity.
The unit emits a bad odor
The unit may absorb odors from the environment (such as furniture, cooking,
cigarettes, etc.) which will be emitted during operations.
The unit’s filters have become moldy and should be cleaned.
The fan of the outdoor unit does not operate
Operation is erratic, unpredictable, or unit is unresponsive
During operation, the fan speed is controlled to optimize product operation.
Interference from cell phone towers and remote boosters may cause the unit to
malfunction. In this case, try the following: · Disconnect the power, then
reconnect. · Press ON/OFF button on remote control to restart operation.
NOTE: If problem persists, contact a local dealer or your nearest customer service center. Provide them with a detailed description of the unit malfunction as well as your model number.
Troubleshooting
When troubles occur, please check the following points before contacting a repair company.
Problem
Possible Causes
Solution
Temperature setting may be higher than ambient room temperature
Lower the temperature setting
Poor Cooling Performance
The heat exchanger on the indoor Clean the affected heat exchanger or outdoor unit is dirty
The air filter is dirty
The air inlet or outlet of either unit is blocked Doors and windows are open
Excessive heat is generated by sunlight
Remove the filter and clean it according to instructions
Turn the unit off, remove the obstruction and turn it back on
Make sure that all doors and windows are closed while operating the unit
Close windows and curtains during periods of high heat or bright sunshine
Too many sources of heat in the room (people, computers, electronics, etc.)
Low refrigerant due to leak or long-term use
Reduce amount of heat sources
Check for leaks, re-seal if necessary and top off refrigerant
Page 17
Troubleshooting
Problem
The unit is not working
The unit starts and stops frequently
Indicator lamps continue flashing Error code appears and begins with the
letters as the following in the window display of indoor unit: · E(x), P(x),
F(x) · EH(xx), EL(xx), EC(xx) · PH(xx), PL(xx), PC(xx)
Possible Causes Power failure
Solution Wait for the power to be restored
The power is turned off
Turn on the power
The fuse is burned out
Replace the fuse
Remote control batteries are dead Replace batteries
The Unit’s 3-minute protection has been activated
Timer is activated
Wait three minutes after restarting the unit
Turn timer off
There’s too much or too little refrigerant in the system
Check for leaks and recharge the system with refrigerant.
Incompressible gas or moisture Evacuate and recharge the system
has entered the system.
with refrigerant
The compressor is broken
Replace the compressor
The voltage is too high or too low
Install a manostat to regulate the voltage
The unit may stop operation or continue to run safely. If the indicator lamps continue to flash or error codes appear, wait for about 10 minutes. The problem may resolve itself. If not, disconnect the power, then connect it again. Turn the unit on. If the problem persists, disconnect the power and contact your nearest customer service center.
NOTE: If your problem persists after performing the checks and diagnostics above, turn off your unit immediately and contact an authorized service center.
Page 18
Accessories
The air conditioning system comes with the following accessories. Use all of the installation parts and accessories to install the air conditioner. Improper installation may result in water leakage, electrical shock and fire, or cause the equipment to fail. The items are not included with the air conditioner must be purchased separately.
Name of Accessories Q`ty(pc)
Shape
Name of Accessories Q`ty(pc)
Shape
Manual
2~3
Remote controller
1
Drain joint
(for cooling &
1
heating models)
Seal
(for cooling &
1
heating models)
Mounting plate
1
Anchor
Mounting plate fixing screw
5~8 (depending on models)
5~8 (depending on models)
Battery
2
Remote controller
holder(optional)
1
Fixing screw for
remote controller
2
holder(optional)
Small Filter
(Need to be installed on
the back of main air filter
1
by the authorized
technician while installing
the machine)
Name
Connecting pipe assembly
Shape
6.35( 1/4i n) – 9&12&18K Liquid side
9.52( 3/8in) – 24 K
Gas side
9.52( 3/8in) – 9K 12. 7( 1/ 2in) – 12&18K
15.9 ( 5 /8in) – 24 K
Quantity(PC)
Parts you must purc hase separately. Consult the dealer about the proper pipe
size of the unit you purchased.
Accessories
Page 19
Installation Summary – Indoor Unit
1
15cm (5.9in)
2
3
12cm (4.75in)
2.3m (90.55in)
12cm (4.75in)
Select Installation Location
44
Determine Wall Hole Position
5
6
Attach Mounting Plate
Installation Summary -Indoor Unit
Drill Wall Hole
7
Connect Piping
8
Connect Wiring
Prepare Drain Hose
Page 20
Wrap Piping and Cable
9
8 STEP
Mount Indoor Unit
Unit Parts
NOTE: The installation must be performed in accordance with the requirement of
local and national standards. The installation may be slightly different in
different areas.
1
2 4
5
3 2
4 6
5 7
8
9
10
1 Air-break switch 3
6 7 8
Unit Parts
11
11
c1
1 Wall Mounting Plate 2 Front Panel 3 Power Cable (Some Units) 4 Louver
c2
5
Functional Filter (On Back of Main Filter – Some Units)
6 Drainage Pipe
7 Signal Cable 8 Refrigerant Piping
9 Remote Controller
10 Remote controller Holder (Some Units)
11 Outdoor Unit Power Cable (Some Units)
NOTE ON ILLUSTRATIONS
Illustrations in this manual are for explanatory purposes. The actual shape of
your indoor unit may be slightly different. The actual shape shall prevail.
Page 21
Indoor Unit Installation
Installation Instructions Indoor unit
PRIOR TO INSTALLATION
Before installing the indoor unit, refer to the label on the product box to
make sure that the model number of the indoor unit matches the model number of
the outdoor unit.
Step 1: Select installation location Before installing the indoor unit, you
must choose an appropriate location. The following are standards that will
help you choose an appropriate location for the unit.
Proper installation locations meet the following standards:
Good air circulation Convenient drainage Noise from the unit will not disturb
other
people Firm and solid–the location will not vibrate Strong enough to support
the weight of the
unit A location at least one meter from all other
electrical devices (e.g., TV, radio, computer)
DO NOT install unit in the following locations:
Near any source of heat, steam, or combustible gas
Near flammable items such as curtains or clothing
Near any obstacle that might block air circulation
Near the doorway
In a location subject to direct sunlight
NOTE ABOUT WALL HOLE:
If there is no fixed refrigerant piping:
While choosing a location, be aware that you should leave ample room for a
wall hole (see Drill wall hole for connective piping step) for the signal
cable and refrigerant piping that connect the indoor and outdoor units. The
default position for all piping is the right side of the indoor unit (while
facing the unit). However, the unit can accommodate piping to both the left
and right.
Refer to the following diagram to ensure proper distance from walls and
ceiling:
15cm (5.9in) or more
12cm (4.75in) or more
12cm (4.75in) or more
2.3m (90.55in) or more
Step 2: Attach mounting plate to wall The mounting plate is the device on
which you will mount the indoor unit.
Take out the mounting plate at the back of the indoor unit.
Secure the mounting plate to the wall with the screws provided. Make sure that
mounting plate is flat against the wall.
NOTE FOR CONCRETE OR BRICK WALLS:
If the wall is made of brick, concrete, or similar material, drill 5mm-
diameter (0.2in-diameter) holes in the wall and insert the sleeve anchors
provided. Then secure the mounting plate to the wall by tightening the screws
directly into the clip anchors.
Indoor Unit Installation
Page 22
Step 3: Drill wall hole for connective piping
1. Determine the location of the wall hole based on the position of the
mounting plate. Refer to Mounting Plate Dimensions.
2. Using a 65mm (2.5in) or 90mm(3.54in) (depending on models )core drill,
drill a hole in the wall. Make sure that the hole is drilled at a slight
downward angle, so that the outdoor end of the hole is lower than the indoor
end by about 5mm to 7mm (0.2-0.275in). This will ensure proper water drainage.
3. Place the protective wall cuff in the hole. This protects the edges of the
hole and will help seal it when you finish the installation process.
Type A
39mm (1.5in)
285mm (11.2in)
230mm(9.1in)
411mm(16.2in) 246mm(9.7in)
Indoor unit outline
39mm (1.5in)
47mm (1.85in)
47mm (1.85in)
Left rear wall hole 65mm (2.5in) 45mm(1.7in) 185mm(7.3in)
139mm(5.5in) 107mm(4.2in)
805mm(31.7in)
Right rear wall hole 65mm (2.5in)
model A (AR(05,09,12)TGH**)
302mm (11.88in)
CAUTION
When drilling the wall hole, make sure to avoid wires, plumbing, and other
sensitive components.
36mm (1.4in)
285mm(11.2in)
458mm(18in) 243mm(9.57in)
Indoor unit outline
36mm (1.4in)
47mm (1.85in)
(1.85in)
47mm
Wall
Indoor
Outdoor
Left rear wall hole 65mm (2.5in)
45mm(1.7in) 240mm(9.5in)
958.3mm(37.7in)
143mm(5.6in) 100mm(3.9in)
model B (AR18TGH**)
Right rear wall hole 65mm (2.5in)
264mm(10.4in)
559mm(22in) 344mm(13.5in)
(1.85in) (2.16in)
55mm
55mm (2.16in)
324.9mm (12.79in)
5-7mm (0.2-0.275in)
47mm
(1.85in)
45mm(1.77in)
45mm(1.77in)
47mm
MOUNTING PLATE DIMENSIONS
Left rear wall hole 65mm (2.5in)
219mm(8.6in)
1037.6mm(40.85in)
299mm(11.8in)
Right rear wall hole 65mm (2.5in)
Different models have different mounting plates.
model C (AR24TGH**)
For the different customization requirements, the shape of the mounting plate may be slightly different. But the installation dimensions are the same for the same size of indoor unit.
NOTE: When the gas side connective pipe is
15.9mm(5/8in) or more, the wall hole should
be 90mm(3.54in).
See Type A and Type B for example:
Correct orientation of Mounting Plate
Indoor Unit Installation
Page 23
Step 4: Prepare refrigerant piping The refrigerant piping is inside an
insulating sleeve attached to the back of the unit. You must prepare the
piping before passing it through the hole in the wall. 1. Based on the
position of the wall hole relative
to the mounting plate, choose the side from which the piping will exit the
unit. 2. If the wall hole is behind the unit, keep the knock-out panel in
place. If the wall hole is to the side of the indoor unit, remove the plastic
knock-out panel from that side of the unit. This will create a slot through
which your piping can exit the unit. Use needle nose pliers if the plastic
panel is too difficult to remove by hand.
Knock-out Panel
3. If existing connective piping is already embedded in the wall, proceed
directly to the Connect Drain Hose step. If there is no embedded piping,
connect the indoor unit’s refrigerant piping to the connective piping that
will join the indoor and outdoor units. Refer to the Refrigerant Piping
Connection section of this manual for detailed instructions.
NOTE ON PIPING ANGLE Refrigerant piping can exit the indoor unit from four
different angles:Left-hand side,Right-hand side, Left rear, Right rear.
Step 5:Connect drain hose
By default, the drain hose is attached to the lefthand side of unit (when
you’re facing the back of the unit). However, it can also be attached to the
right-hand side. To ensure proper drainage, attach the drain hose on the same
side that your refrigerant piping exits the unit. Attach drain hose extension
(purchased separately) to the end of drain hose.
Wrap the connection point firmly with Teflon tape to ensure a good seal and to
prevent leaks.
For the portion of the drain hose that will remain indoors, wrap it with foam
pipe insulation to prevent condensation. Remove the air filter and pour a
small amount of water into the drain pan to make sure that water flows from
the unit smoothly.
NOTE ON DRAIN HOSE PLACEMENT
Make sure to arrange the drain hose according to the follo.wing figures.
CORRECT
Make sure there are no kinks or dent in drain hose to ensure proper drainage.
NOT CORRECT
Kinks in the drain hose will create water traps.
Indoor Unit Installation
CAUTION
Be extremely careful not to dent or damage the piping while bending them away
from the unit. Any dents in the piping will affect the unit’s performance.
NOT CORRECT
Kinks in the drain hose will create water traps.
NOT CORRECT Do not place the end of the drain hose in water or in containers that collect water. This will prevent proper drainage.
PLUG THE UNUSED DRAIN HOLE
To prevent unwanted leaks you must plug the unused drain hole with the rubber plug provided.
Page 24
BEFORE PERFORMING ANY
ELECTRICAL WORK, READ THESE
REGULATIONS
1. All wiring must comply with local and national electrical codes,
regulations and must be installed by a licensed electrician.
2. All electrical connections must be made according to the Electrical
Connection Diagram located on the panels of the indoor and outdoor units.
3. If there is a serious safety issue with the power supply, stop work
immediately. Explain your reasoning to the client, and refuse to install the
unit until the safety issue is properly resolved.
4. Power voltage should be within 90-110% of rated voltage. Insufficient
power supply can cause malfunction, electrical shock, or fire.
5. If connecting power to fixed wiring, install a surge protector and main
power switch with a capacity of 1.5 times the maximum current of the unit.
6. If connecting power to fixed wiring, a switch or circuit breaker that
disconnects all poles and has a contact separation of at least 1/8in (3mm)
must be incorporated in the fixed wiring. The qualified technician must use an
approved circuit breaker or switch.
7. Only connect the unit to an individual branch
circuit outlet. Do not connect another
appliance to that outlet.
8. Make sure to properly ground the air conditioner.
9. Every wire must be firmly connected. Loose
wiring can cause the terminal to overheat,
resulting in product malfunction and possible fire.
10.Do not let wires touch or rest against refrigerant
tubing, the compressor, or any moving parts
within the unit.
11. If the unit has an auxiliary electric heater, it must
be installed at least 1 meter (40in) away from
any combustible materials.
12.To avoid getting an electric shock, never touch
the electrical components soon after the power
supply has been turned off. After turning off
the power, always wait 10 minutes or more
before you touch the electrical components.
WARNING
BEFORE PERFORMING ANY ELECTRICAL OR WIRING WORK, TURN OFF THE MAIN POWER TO THE SYSTEM.
Step 6: Connect signal cable
The signal cable enables communication between the indoor and outdoor units.
You must first choose the right cable size before preparing it for connection.
Cable Types · Indoor Power Cable (if applicable):
H05VV-F or H05V2V2-F · Outdoor Power Cable: H07RN-F · Signal Cable: H07RN-F
Minimum Cross-Sectional Area of Power and Signal Cables (For reference)
Rated Current of Appliance (A)
3 and 6 > 6 and 10 > 10 and 16 > 16 and 25 > 25 and 32 > 32 and 40
Nominal Cross-Sectional Area (mm²)
0.75 1 1.5 2.5 4 6
CHOOSE THE RIGHT CABLE SIZE
The size of the power supply cable, signal cable, fuse, and switch needed is
determined by the maximum current of the unit. The maximum current is
indicated on the nameplate located on the side panel of the unit. Refer to
this nameplate to choose the right cable, fuse, or switch.
Indoor Unit Installation
Page 25
1. Open front panel of the indoor unit. 2. Using a screwdriver, open the wire
box cover
on the right side of the unit. This will reveal the terminal block.
Terminal block Wire cover
Screw Cable clamp
WARNING
ALL WIRING MUST BE PERFORMED STRICTLY IN ACCORDANCE WITH THE WIRING DIAGRAM
LOCATED ON THE BACK OF THE INDOOR UNIT ‘S FRONT PANEL .
3. Unscrew the cable clamp below the terminal block and place it to the side.
4. Facing the back of the unit, remove the plastic panel on the bottom left-
hand side.
5. Feed the signal wire through this slot, from the back of the unit to the
front.
6. Facing the front of the unit, connect the wire according to the indoor
unit’s wiring diagram, connect the u-lug and firmly screw each wire to its
corresponding terminal.
CAUTION
DO NOT MIX UP LIVE AND NULL WIRES This is dangerous, and can cause the air
conditioning unit to malfunction. 7. After checking to make sure every
connection is secure, use the cable clamp to fasten the signal cable to the
unit. Screw the cable clamp down tightly. 8. Replace the wire cover on the
front of the unit, and the plastic panel on the back.
NOTE ABOUT WIRING
THE WIRING CONNECTION PROCESS MAY DIFFER SLIGHTLY BETWEEN UNITS AND REGIONS.
Step 7: Wrappiping and cables Before passing the piping, drain hose, and the
signal cable through the wall hole, you must bundle them together to save
space, protect them, and insulate them?.
1. Bundle the drain hose, refrigerant pipes, and signal cable as shown below:
Indoor Unit
Space behind unit
Refrigerant piping Insulation tape
Signal wire Drain hose
DRAIN HOSE MUST BE ON BOTTOM Make sure that the drain hose is at the bottom of
the bundle. Putting the drain hose at the top of the bundle can cause the
drain pan to overflow, which can lead to fire or water damage.
DO NOT INTERTWINE SIGNAL CABLE WITH OTHER WIRES While bundling these items
together, do not intertwine or cross the signal cable with any other wiring.
2. Using adhesive vinyl tape, attach the drain
hose to the underside of the refrigerant pipes. 3. Using insulation tape, wrap
the signal wire,
refrigerant pipes, and drain hose tightly together. Double-check that all
items are bundled.
DO NOT WRAP ENDS OF PIPING When wrapping the bundle, keep the ends of the
piping unwrapped. You need to access them to test for leaks at the end of the
installation process (refer to Electrical Checks and Leak Checks section of
this manual).
Indoor Unit Installation
Page 26
Step 8: Mount indoor unit
If you installed new connective piping to the outdoor unit,do the following:
1. If you have already passed the refrigerant piping through the hole in the
wall, proceed to Step 4.
2. Otherwise, double-check that the ends of the refrigerant pipes are sealed
to prevent dirt or foreign materials from entering the pipes.
3. Slowly pass the wrapped bundle of refrigerant pipes, drain hose, and
signal wire through the hole in the wall.
4. Hook the top of the indoor unit on the upper hook of the mounting plate.
5. Check that unit is hooked firmly on mounting by applying slight pressure
to the left and right-hand sides of the unit. The unit should not jiggle or
shift.
6. Using even pressure, push down on the bottom half of the unit. Keep
pushing down until the unit snaps onto the hooks along the bottom of the
mounting plate.
7. Again, check that the unit is firmly mounted by applying slight pressure
to the left and the right-hand sides of the unit.
If refrigerant piping is already embedded in the wall, do the following:
1. Hook the top of the indoor unit on the upper hook of the mounting plate.
2. Use a bracket or wedge to prop up the unit, giving you enough room to
connect the refrigerant piping, signal cable, and drain hose.
3. Connect drain hose and refrigerant piping (refer to Refrigerant Piping
Connection section of this manual for instructions).
4. Keep pipe connection point exposed to perform the leak test (refer to
Electrical Checks and Leak Checks section of this manual).
5. After the leak test, wrap the connection point with insulation tape.
6. Remove the bracket or wedge that is propping up the unit.
7. Using even pressure, push down on the bottom half of the unit. Keep
pushing down until the unit snaps onto the hooks along the bottom of the
mounting plate.
UNIT IS ADJUSTABLE
Keep in mind that the hooks on the mounting plate are smaller than the holes
on the back of the unit. If you find that you don’t have ample room to connect
embedded pipes to the indoor unit, the unit can be adjusted left or right by
about 30-50mm (1.25-1.95in), depending on the model.
30-50mm (1.2-1.95in)
30-50mm (1.2-1.95in)
Move to left or right
Indoor Unit Installation
Page 27
Installation
Outdoor Unit Installation
Outdoor Unit Installation
Install the unit by following local codes and regulations , there may be differ slightly between different regions.
60cm (24in) above
30ocnmle(1f2t in) 200cimn f(7ro9nint)
3f0rocmm (b1a2cikn)wall 60ocnmri(g2h4tin)
Installation Instructions Outdoor unit
Step 1: Select installation location Before installing the outdoor unit, you
must choose an appropriate location. The following are standards that will
help you choose an appropriate location for the unit.
Proper installation locations meet the following standards:
Meets all spatial requirements shown in Installation Space Requirements above.
Good air circulation and ventilation
Firm and solid–the location can support the unit and will not vibrate
Noise from the unit will not disturb others
Protected from prolonged periods of direct sunlight or rain
Where snowfall is anticipated, raise the unit above the base pad to prevent
ice buildup and coil damage. Mount the unit high enough to be above the
average accumulated area snowfall. The minimum height must be 18 inches
DO NOT install unit in the following locations:
Near an obstacle that will block air inlets and outlets Near a public street,
crowded areas, or where noise from the unit will disturb others Near animals
or plants that will be harmed by hot air discharge Near any source of
combustible gas In a location that is exposed to large amounts of dust In a
location exposed to a excessive amounts of salty air
SPECIAL CONSIDERATIONS FOR EXTREME WEATHER
If the unit is exposed to heavy wind:
Install unit so that air outlet fan is at a 90° angle to the direction of the
wind. If needed, build a barrier in front of the unit to protect it from
extremely heavy winds. See Figures below.
Strong wind
Strong wind
Wind Baffle
Strong wind
If the unit is frequently exposed to heavy rain or snow:
Build a shelter above the unit to protect it from the rain or snow. Be careful
not to obstruct air flow around the unit.
If the unit is frequently exposed to salty air (seaside):
Use outdoor unit that is specially designed to resist corrosion.
Page 28
Step 2: Install drain joint(Heat pump unit only)
Before bolting the outdoor unit in place, you must install the drain joint at
the bottom of the unit. Note that there are two different types of drain
joints depending on the type of outdoor unit.
If the drain joint comes with a rubber seal (see Fig. A ), do the following:
1. Fit the rubber seal on the end of the drain joint that will connect to the
outdoor unit.
2. Insert the drain joint into the hole in the base pan of the unit.
3. Rotate the drain joint 90° until it clicks in place facing the front of
the unit.
4. Connect a drain hose extension (not included) to the drain joint to
redirect water from the unit during heating mode.
If the drain joint doesn’t come with a rubber seal (see Fig. B ), do the
following:
1. Insert the drain joint into the hole in the base pan of the unit. The
drain joint will click in place.
2. Connect a drain hose extension (not included) to the drain joint to
redirect water from the unit during heating mode.
D B
Step 3: Anchor outdoor unit The outdoor unit can be anchored to the ground or
to a wall-mounted bracket with bolt(M10). Prepare the installation base of the
unit according to the dimensions below.
UNIT MOUNTING DIMENSIONS The following is a list of different outdoor unit
sizes and the distance between their mounting feet. Prepare the installation
base of the unit according to the dimensions below.
A
Air inlet
Air inlet
Air outlet
Base pan hole of outdoor unit
Seal
Seal
Drain joint
(A)
(B)
IN COLD CLIMATES
In cold climates, make sure that the drain hose is as vertical as possible to
ensure swift water drainage. If water drains too slowly, it can freeze in the
hose and flood the unit.
H W
Outdoor Unit Installation
Page 29
681x434x285 (26.8″x17.1″x11.2″) 770x555x300 (30.3″x21.8″x11.8″) 946x810x410 (37.2″x31.9″x16.1″)
460 (18.1″) 487 (19.2″) 673 (26.5″)
292 (11.5″) 298 (11.7″) 403 (15.9”)
AR09 AR12&AR18 AR24
If you will install the unit on the ground or on a concrete mounting platform,
do the following: 1. Mark the positions for four expansion bolts
based on dimensions chart. 2. Pre-drill holes for expansion bolts. 3. Place a
nut on the end of each expansion bolt. 4. Hammer expansion bolts into the pre-
drilled
holes. 5. Remove the nuts from expansion bolts, and
place outdoor unit on bolts.
6. Put washer on each expansion bolt, then replace the nuts.
7. Using a wrench, tighten each nut until snug.
WARNING
WHEN DRILLING INTO CONCRETE, EYE PROTECTION IS RECOMMENDED AT ALL TIMES.
If you will install the unit on a wall-mounted bracket , do the following:
CAUTION
Make sure that the wall is made of solid brick, concrete, or of similarly
strong material. The wall must be able to support at least four times the
weight of the unit.
1.Mark the position of bracket holes based on dimensions chart.
2. Pre-drill the holes for the expansion bolts. 3. Place a washer and nut on
the end of each
expansion bolt. 4. Thread expansion bolts through holes in
mounting brackets, put mounting brackets in position, and hammer expansion
bolts into the wall. 5. Check that the mounting brackets are level. 6.
Carefully lift unit and place its mounting feet on brackets. 7. Bolt the unit
firmly to the brackets. 8. If allowed, install the unit with rubber gaskets to
reduce vibrations and noise.
Outdoor Unit Installation
Page 30
Step 4: Connect signal and power cables The outside unit’s terminal block is
protected by an electrical wiring cover on the side of the unit. A
comprehensive wiring diagram is printed on the inside of the wiring cover.
WARNING
BEFORE PERFORMING ANY ELECTRICAL OR WIRING WORK, TURN OFF THE MAIN POWER TO
THE SYSTEM.
1. Prepare the cable for connection: USE THE RIGHT CABLE · Indoor Power Cable
(if applicable): H05VV-F
or H05V2V2-F · Outdoor Power Cable: H07RN-F · Signal Cable: H07RN-F
CHOOSE THE RIGHT CABLE SIZE The size of the power supply cable, signal cable,
fuse, and switch needed is determined by the maximum current of the unit. The
maximum current is indicated on the nameplate located on the side panel of the
unit. Refer to this nameplate to choose the right cable, fuse, or switch. a.
Using wire strippers, strip the rubber
jacket from both ends of cable to reveal about 40mm (1.57in) of the wires
inside. b. Strip the insulation from the ends of the wires. c. Using a wire
crimper, crimp u-lugs on the ends of the wires.
PAY ATTENTION TO LIVE WIRE While crimping wires, make sure you clearly
distinguish the Live (“L”) Wire from other wires.
WARNING
ALL WIRING WORK MUST BE PERFORMED STRICTLY IN ACCORDANCE WITH THE WIRING
DIAGRAM LOCATED INSIDE OF WIRE COVER OF THE OUTDOOR UNIT .
2. Unscrew the electrical wiring cover and remove it. 3. Unscrew the cable
clamp below the terminal
block and place it to the side. 4. Connect the wire according to the wiring
diagram, and firmly screw the u-lug of each wire to its corresponding
terminal. 5. After checking to make sure every connection is secure, loop the
wires around to prevent rain water from flowing into the terminal. 6. Using
the cable clamp, fasten the cable to the unit. Screw the cable clamp down
tightly. 7. Insulate unused wires with PVC electrical tape. Arrange them so
that they do not touch any electrical or metal parts. 8. Replace the wire
cover on the side of the unit, and screw it in place.
Cover
Screw
In North America
1. Remove the wire cover from the unit by loosening the 3 screws.
2. Dismount caps on the conduit panel. 3. Temperarily mount the conduit
tubes(not
included) on the conduit panel. 4. Properly connect both the power supply and
low voltage lines to the corresponding terminals on the terminal block. 5.
Ground the unit in accordance with local codes. 6. Be sure to size each wire
allowing several inches longer than the required length for wiring. 7. Use
lock nuts to secure the conduit tubes.
Terminal block Over 1.57in.(40mm)
Connecting cable
G
Power supply cord
Conduit panel
Wire Cover
Please select the appropriate through-hole according to the diameter of the
wire.
Outdoor Unit Installation
Page 31
Refrigerant Piping Connection
When connecting refrigerant piping, do not let substances or gases other than
the specified refrigerant enter the unit. The presence of other gases or
substances will lower the unit’s capacity, and can cause abnormally high
pressure in the refrigeration cycle. This can cause explosion and injury.
Note on Pipe Length
The length of refrigerant piping will affect the performance and energy
efficiency of the unit. Nominal efficiency is tested on units with a pipe
length of 5 meters (16.5ft) A minimum pipe run of 3 metres is required to
minimise vibration & excessive noise.
Refer to the table below for specifications on the maximum length and drop
height of piping. Maximum Length and Drop Height of Refrigerant Piping per
Unit Model
Model
R410A,R32 Inverter Split Air Conditioner
Capacity (BTU/h) < 15,000
15,000 and < 24,000 24,000 and < 36,000
Max. Length (m) 25 (82ft) 30 (98.5ft) 50 (164ft)
Max. Drop Height (m) 10 (33ft) 20 (66ft) 25 (82ft)
Connection Instructions Refrigerant Piping
Step 1: Cut pipes
When preparing refrigerant pipes, take extra care to cut and flare them
properly. This will ensure efficient operation and minimize the need for
future maintenance.
1. Measure the distance between the indoor and outdoor units.
2. Using a pipe cutter, cut the pipe a little longer than the measured
distance.
3. Make sure that the pipe is cut at a perfect 90° angle.
90°
Oblique Rough Warped
DO NOT DEFORM PIPE WHILE CUTTING
Be extra careful not to damage, dent, or deform the pipe while cutting. This
will drastically reduce the heating efficiency of the unit.
Refrigerant piping Connection
Page 32
Step 2: Remove burrs Burrs can affect the air-tight seal of refrigerant piping
connection. They must be completely removed.
1. Hold the pipe at a downward angle to prevent burrs from falling into the
pipe.
2. Using a reamer or deburring tool, remove all burrs from the cut section of
the pipe.
Pipe Reamer
Point down
PIPING EXTENSION BEYOND FLARE FORM
Outer Diameter of Pipe (mm)
Ø 6.35 (Ø 0.25″) Ø 9.52 (Ø 0.375″) Ø12.7 ( Ø 0.5″) Ø 15.9 (Ø 0.63″) Ø 19.05 (Ø
0.75″)
A (mm)
Min.
MMaaxx..
0.7 (0.0275″) 1.3 (0.05″)
1.0 (0.04″) 1.6 (0.063″)
1.0 (0.04″) 1.8 (0.07″)
2.0 (0.078″) 2.2 (0.086″)
2.0 (0.078″) 2.4 (0.094″)
Flare form
A
Step 3: Flare pipe ends Proper flaring is essential to achieve an airtight
seal. 1. After removing burrs from cut pipe, seal
the ends with PVC tape to prevent foreign materials from entering the pipe. 2.
Sheath the pipe with insulating material. 3. Place flare nuts on both ends of
pipe. Make sure they are facing in the right direction, because you can’t put
them on or change their direction after flaring.
Flare nut
Copper pipe
Pipe
6. Place flaring tool onto the form. 7. Turn the handle of the flaring tool
clockwise
until the pipe is fully flared. 8. Remove the flaring tool and flare form,
then
inspect the end of the pipe for cracks and even flaring.
Step 4: Connect pipes
When connecting refrigerant pipes, be careful not to use excessive torque or
to deform the piping in any way. You should first connect the low-pressure
pipe, then the high-pressure pipe.
MINIMUM BEND RADIUS
When bending connective refrigerant piping, the minimum bending radius is
10cm.
4. Remove PVC tape from ends of pipe when ready to perform flaring work.
5. Clamp flare form on the end of the pipe. The end of the pipe must extend
beyond the edge of the flare form in accordance with the dimensions shown in
the table below.
Radius 10cm (4in)
Instructions for Connecting Piping to Indoor Unit
1. Align the center of the two pipes that you will connect.
Indoor unit tubing
Flare nut Pipe
Refrigerant piping Connection
Page 33
2. Tighten the flare nut as tightly as possible by hand.
3. Using a spanner, grip the nut on the unit tubing.
4. While firmly gripping the nut on the unit tubing, use a torque wrench to
tighten the flare nut according to the torque values in the Torque
Requirements table below. Loosen the flaring nut slightly, then tighten again.
Outer Diameter of Pipe (mm)
Ø 6.35 (Ø 0.25″)
Ø 9.52 (Ø 0.375″) Ø 12.7 (Ø 0.5″)
Ø 15.9 (Ø 0.63″) Ø 19.05 (Ø 0.75″)
TORQUE REQUIREMENTS
Tightening Torque (N·m) 18~20(180~200kgf.cm)
32~39(320~390kgf.cm)
49~59(490~590kgf.cm)
Flare dimension(B) (mm) 8.4~8.7 (0.33~0.34″)
13.2~13.5 (0.52~0.53″)
16.2~16.5 (0.64~0.65″)
57~71(570~710kgf.cm) 19.2~19.7 (0.76~0.78″) 67~101(670~1010kgf.cm) 23.2~23.7 (0.91~0.93″)
Flare shape
90 °± 4 45 °±2
B
R0.4~0. 8
DO NOT USE EXCESSIVE TORQUE
Excessive force can break the nut or damage the refrigerant piping. You must
not exceed torque requirements shown in the table above.
Instructions for Connecting Piping to Outdoor Unit
1. Unscrew the cover from the packed valve on the side of the outdoor unit.
2. Remove protective caps from ends of valves.
3. Align flared pipe end with each valve, and tighten the flare nut as
tightly as possible by hand.
4. Using a spanner, grip the body of the valve. Do not grip the nut that
seals the service valve.
6. Loosen the flaring nut slightly, then tighten again.
7. Repeat Steps 3 to 6 for the remaining pipe.
USE SPANNER TO GRIP MAIN BODY OF VALVE
Torque from tightening the flare nut can snap off other parts of valve.
Refrigerant piping Connection
Valve cover
5. While firmly gripping the body of the valve, use a torque wrench to
tighten the flare nut according to the correct torque values.
Page 34
Air Evacuation
Preparations and Precautions
8. If there is a change in system pressure, refer to Gas Leak Check section for information
Air and foreign matter in the refrigerant circuit can
on how to check for leaks. If there is no
cause abnormal rises in pressure, which can damage change in system pressure, unscrew the cap
the air conditioner, reduce its efficiency, and cause 9. from the packed valve (high pressure valve).
injury. Use a vacuum pump and manifold gauge to evacuate the refrigerant
circuit, removing any non-condensable gas and moisture from the system.
Evacuation should be performed upon initial
Insert hexagonal wrench into the packed valve (high pressure valve) and open the valve by turning the wrench in a 1/4 counterclockwise turn. Listen for gas to exit the system, then close the valve after 5 seconds.
installation and when unit is relocated.
10. Watch the Pressure Gauge for one minute
BEFORE PERFORMING EVACUATION
Check to make sure the connective pipes between the indoor and outdoor units
are connected properly .
to make sure that there is no change in pressure. The Pressure Gauge should
read slightly higher than atmospheric pressure.
11. Remove the charge hose from the service port.
Check to make sure all wiring is connected
Flare nut
properly.
Evacuation Instructions
1. Connect the charge hose of the manifold gauge to service port on the
outdoor unit’s low pressure valve.
2. Connect another charge hose from the manifold gauge to the vacuum pump.
3. Open the Low Pressure side of the manifold
gauge. Keep the High Pressure side closed. 4. Turn on the vacuum pump to
evacuate the
system. 5. Run the vacuum for at least 15 minutes, or
until the Compound Meter reads -76cmHG (-10 5Pa).
Manifold Gauge
Compound gauge
Pressure gauge
-76cmHg
Low pressure valve Pressure hose /
Charge hose
High pressure valve
Charge hose Vacuum pump
Cap
valve body valve stem
12. Using hexagonal wrench, fully open both the high pressure and low
pressure valves.
13. Tighten valve caps on all three valves (service port, high pressure, low
pressure) by hand. You may tighten it further using a torque wrench if needed.
OPEN VALVE STEMS GENTLY
When opening valve stems, turn the hexagonal wrench until it hits against the
stopper. Do not try to force the valve to open further.
Low pressure valve
6. Close the Low Pressure side of the manifold gauge, and turn off the vacuum
pump.
7. Wait for 5 minutes, then check that there has been no change in system
pressure.
Air Evacuation
Page 35
Note on Adding Refrigerant
Some systems require additional charging depending on pipe lengths. The
refrigerant should be charged from the service port on the outdoor unit’s low
pressure valve. The additional refrigerant to be charged can be calculated
using the following formula:
ADDITIONAL REFRIGERANT PER PIPE LENGTH
Connective Pipe Air Purging
Length (m)
Method
< Standard pipe length Vacuum Pump
Additional Refrigerant
N/A
Standard pipe length
Vacuum Pump
Liquid Side: Ø 6.35 (ø 0.25″)
Liquid Side: Ø 9.52 (ø 0.375″)
R32:
R32:
(Pipe length standard length) x 12g/m (Pipe length standard length) x 24g/m
(Pipe length standard length) x 0.13oZ/ft (Pipe length standard length) x 0.26oZ/ft
CAUTION DO NOT mix refrigerant types.
Precautions on adding the R-32 refrigerant
In addition to the conventional charging procedure, the following requirements
shall be kept. · Make sure that contamination by other refrigerants
does not occur for charging. · To minimize the amount of refrigerant, keep the
hoses and lines as short as possible. · The cylinders shall be kept upright. ·
Make sure that the refrigeration system is earthed
before charging. · Label the system after charging, if necessary. · Extreme
care is required not to overcharge the
system. · Before recharging, the pressure shall be checked
with nitrogen blowing. · After charging, check for leakage before
commissioning. · Be sure to check for leakage before leaving the work
area.
Air Evacuation
Electrical and Gas Leak Checks
Before Test Run
Only perform test run after you have completed the following steps: ·
Electrical Safety Checks Confirm that
the unit’s electrical system is safe and operating properly · Gas Leak Checks
Check all flare nut connections and confirm that the system is not leaking ·
Confirm that gas and liquid (high and low pressure) valves are fully open
Electrical Safety Checks
After installation, confirm that all electrical wiring is installed in
accordance with local and national regulations, and according to the
Installation Manual.
BEFORE TEST RUN
Check Grounding Work
Measure grounding resistance by visual detection and with grounding resistance
tester. Grounding resistance must be less than 0.1.
Note: This may not be required for some locations in the US.
DURING TEST RUN
Check for Electrical Leakage
During the Test Run, use an electroprobe and multimeter to perform a
comprehensive electrical leakage test.
If electrical leakage is detected, turn off the unit immediately and call a
licensed electrician to find and resolve the cause of the leakage.
Note: This may not be required for some locations in the US.
WARNING RISK OF ELECTRIC SHOCK
ALL WIRING MUST COMPLY WITH LOCAL AND NATIONAL ELECTRICAL CODES, AND MUST BE
INSTALLED BY A LICENSED ELECTRICIAN.
Gas Leak Checks
There are two different methods to check for gas leaks.
Soap and Water Method
Using a soft brush, apply soapy water or liquid detergent to all pipe
connection points on the indoor unit and outdoor unit. The presence of bubbles
indicates a leak.
Leak Detector Method
If using leak detector, refer to the device’s operation manual for proper
usage instructions.
AFTER PERFORMING GAS LEAK CHECKS After confirming that the all pipe connection
points DO NOT leak, replace the valve cover on the outside unit.
Check-point of indoor unit
Check-point of outdoor unit
D
B
C
A
A: Low pressure stop valve B: High pressure stop valve C& D: Indoor unit flare nuts
Electrical and Gas Leak Checks
Test Run
Test Run Instructions
You should perform the Test Run for at least 30 minutes. 1. Connect power to
the unit.
2. Press the ON/OFF button on the remote controller to turn it on.
3. Press the MODE button to scroll through the following functions, one at a
time:
· COOL Select lowest possible temperature · HEAT Select highest possible
temperature
4. Let each function run for 5 minutes, and perform the following checks:
List of Checks to Perform No electrical leakage
PASS/FAIL
Unit is properly grounded
All electrical terminals properly covered
Indoor and outdoor units are solidly installed
All pipe connection points do not leak
Outdoor Indoor
(2):
(2):
Water drains properly from drain hose
All piping is properly insulated
Unit performs COOL function properly
Unit performs HEAT function properly
Indoor unit louvers rotate properly
Indoor unit responds to remote controller
DOUBLE-CHECK PIPE CONNECTIONS During operation, the pressure of the
refrigerant circuit will increase. This may reveal leaks that were not present
during your initial leak check. Take time during the Test Run to double-check
that all refrigerant pipe connection points do not have leaks. Refer to Gas
Leak Check section for instructions. 5. After the Test Run is successfully
completed,
and you confirm that all checks points in List of Checks to Perform have
PASSED, do the following: a. Using remote control, return unit to
normal operating temperature. b. Using insulation tape, wrap the indoor
refrigerant pipe connections that you left uncovered during the indoor unit
installation process.
IF AMBIENT TEMPERATURE IS BELOW 17°C (62°F) You can’t use the remote
controller to turn on the COOL function when the ambient temperature is below
17°C. In this instance, you can use the MANUAL CONTROL button to test the COOL
function. 1. Lift the front panel of the indoor unit, and
raise it until it clicks in place. 2. The MANUAL CONTROL button is located
on the right-hand side of the unit. Press it 2 times to select the COOL
function. 3. Perform Test Run as normal.
Manual control button
Test Run
In using R-32
General information
· Do not use means to accelerate the defrost operation or to clean, other than
those recommended by Samsung.
· Do not pierce or burn.
· Be aware that refrigerants may not contain an odour.
· For the product that uses the R-32 refrigerant, be cautious not to generate
a spark by keeping the following requirements: Do not remove the fuses with
power on. Do not disconnect the power plug from the wall outlet with power
on. It is recommended to locate the outlet in a high position. Place the
cords so that they are not tangled.
CAUTION
· Keep the piping length at a minimum to minimize the additional refrigerant
charge due to piping extension.
· When connecting the pipes, make sure that surrounding objects do not
interfere with or contact them to prevent refrigerant leakage due to physical
damage.
· Make sure that the spaces where the refrigerant pipes are installed comply
with national gas regulations.
· Be sure to perform works such as additional refrigerant charging and pipe
welding under the conditions of good ventilation.
· Be sure to perform welding and piping works for mechanical connections under
the conditions that the refrigerant does not circulate.
· When reconnecting the pipes, make sure to perform flared-jointing newly to
prevent refrigerant leakage.
· When working on the refrigerant pipes and the flexible refrigerant
connectors, be careful that they are not damaged physically by surrounding
objects.
Installation of the product
· The outdoor unit shall be installed in an open space that is always
ventilated.
· The local gas regulations shall be observed.
· To handle, purge, and dispose the refrigerant, or break into the refrigerant
circuit, the worker should have a certificate from an industry-accredited
authority.
· Do not install the indoor unit in the following areas: Area filled with
minerals, splashed oil, or steam. It will deteriorate plastic parts, causing
failure or leakage.
Area that is close to heat sources.
Area that produces substances such as sulfuric gas, chlorine gas, acid, and
alkali. It may cause corrosion of the pipings and brazed joints.
Area that can cause leakage of combustible gas and suspension of carbon
fibers, flammable dust, or volatile flammables.
Area where refrigerant leaks and settles.
Area where animals may urinate on the product. Ammonia may be generated.
· Do not use the indoor unit for preservation of food items, plants,
equipment, and art works. This may cause deterioration of their quality.
· Do not install the indoor unit if it has any drainage problem.
· Because your air conditioner contains R-32 refrigerant, make sure that it is
installed, operated, and stored it in a room whose floor area is larger than
the minimum required floor area specified in the following table:
Wall-mounted type
m (kg)
A (m2)
1.842 1.843
1.9 2.0 2.2 2.4 2.6 2.8 3.0
No requirement 4.45 4.58 4.83 5.31 5.79 6.39 7.41 8.51
· m : Total refrigerant charge in the system
· A : Minimum required floor area
· IMPORTANT: it’s mandatory to consider either the table above or taking into
consideration the local law regarding the minimum living space of the
premises.
· Minimum installation height of indoor unit is 0.6 m for floor mounted, 1.8 m for wall, 2.2 m for ceiling.
Installation of the outdoor unit
· While in installation or relocation of the product, do not mix the
refrigerant with other gases including air or unspecified refrigerant. Failure
to do so may cause pressure increase to result in rupture or injury.
· Do not cut or burn the refrigerant container or pipings.
· Use clean parts such as manifold gauge, vacuum pump, and charging hose for
the refrigerant.
· Installation must be carried out by qualified personnel for handling the
refrigerant. Additionally, reference the regulations and laws.
· Be careful not to let foreign substances (lubricating oil, refrigerant,
water, etc.) enter the pipings. The application of oil or refrigerant
deteriorates the pipings to result in drain leakage. For storage, securely
seal their openings.
· When mechanical ventilation is required, ventilation openings shall be kept
clear of obstruction.
· For disposal of the product, follow the local laws and regulations.
· Do not work in a confined place.
· The work area shall be blocked.
· The refrigerant pipings shall be installed in the position where there are
no substances that may result in corrosion.
· The following checks shall be performed for installation: The charging
amount depends on the room size. The ventilation devices and outlets are
operating normally and are not obstructed. Markings and signs on the
equipment shall be visible and legible.
· Upon leakage of the refrigerant, ventilate the room. When the leaked
refrigerant is exposed to flame, it may cause generation of toxic gases.
· Make sure that the work area is safe from flammable substances.
· To purge air in the refrigerant, be sure to use a vacuum pump.
· Note that the refrigerant has no odour.
· The units are not explosion proof so they must be installed with no risk of
explosion.
· This product contains fluorinated gases that contribute to global greenhouse
effect. Accordingly, do not vent gases into the atmosphere.
· Because the working pressure for R-32 is 1.6 times higher than that for
R-22, use exclusive pipings and tools specified. In case of replacing an R-22
model with an R-32 model, be sure to replace the conventional pipings and
flare nuts with exclusive ones.
· The models that use the refrigerant R-32 have a different thread diameter
for the charging port to prevent charging failure. Therefore, check its
diameter (1/2 inch) in advance.
· Servicing shall be performed as recommended by the manufacturer. In case
other skilled persons are joined for servicing, it shall be carried out under
supervision of the person who is competent in handling flammable refrigerants.
· For servicing the units containing flammable refrigerants, safety checks are
required to minimise the risk of ignition.
· Servicing shall be performed following the controlled procedure to minimize
the risk of flammable refrigerant or gases.
· Do not install where there is a risk of combustible gas leakage.
· Do not place heat sources.
· Be cautious not to generate a spark as follows: Do not remove the fuses
with power on.
Do not disconnect the power plug from the wall outlet with power on.
It is recommended to locate the outlet in a high position. Place the cords
so that they are not tangled.
· If the indoor unit is not R-32 compatible, an error signal appears and the
unit will not operate.
· After installation, check for leakage. Toxic gas may be generated and if it
comes into contact with an ignition source such as fan heater, stove, and
cooker. cylinders, make sure that only the refrigerant recovery cylinders are
used.
Preparation of fire extinguisher
· If a hot work is to be done, an appropriate fire extinguishing equipment
should have been available.
· A dry powder or CO2 fire extinguisher shall be equipped near the charging
area.
Ignition sources free
· Make sure to store the units in a place without continuously operating
ignition sources (for example, open flames, an operating gas appliance or an
operating electric heater).
· The service engineers shall not use any ignition sources with the risk of
fire or explosion.
· Potential ignition sources shall be kept away from the work area where the
flammable refrigerant can possibly be released to the surrounding.
· The work area should be checked to ensure that there are no flammable
hazards or ignition risks. The “No Smoking” sign shall be attached.
· Under no circumstances shall potential sources of ignition be used while in
detection of leakage.
· Make sure that the seals or sealing materials have not degraded.
· Safe parts are the ones with which the worker can work in a flammable
atmosphere. Other parts may result in ignition due to leakage.
· Replace components only with parts specified by Samsung. Other parts may
result in the ignition of refrigerant in the atmosphere from a leak.
Area ventilation
· Make sure that the work area is well ventilated before performing a hot
work.
· Ventilation shall be made even during the work. · The ventilation should
safely disperse any
released gases and preferably expel them into the atmosphere.
· Ventilation shall be made even during the work.
Leakage detection methods
· The leakage detector shall be calibrated in a refrigerant-free area.
· Make sure that the detector is not a potential source of ignition.
· The leakage detector shall be set to the LFL (lower flammability limit).
· The use of detergents containing chlorine shall be avoided for cleaning
because the chlorine may react with the refrigerant and corrode the pipings.
· If leakage is suspected, naked flames shall be removed.
· If a leakage is found while in brazing, the entire refrigerant shall be
recovered from the product or isolated (e.g. using shut-off valves). It shall
not be directly released to the environment. Oxygen free nitrogen (OFN) shall
be used for purging the system before and during the brazing process.
· The work area shall be checked with an appropriate refrigerant detector
before and during work.
· Ensure that the leakage detector is appropriate for use with flammable
refrigerants.
Labelling
· The parts shall be labelled to ensure that they have been decommissioned and
emptied of refrigerant.
· The labels shall be dated. · Make sure that the labels are affixed on the
system
to notify it contains flammable refrigerant.
Recovery
· When removing refrigerant from the system for servicing or decommissioning,
it is recommended to remove the entire refrigerant.
· When transferring refrigerant into cylinders, make sure that only the
refrigerant recovery cylinders are used.
· All cylinders used for the recovered refrigerant shall be labelled.
· Cylinders shall be equipped with pressure relief valves and shut-off valves
in a proper order.
· Empty recovery cylinders shall be evacuated and cooled before recovery.
· The recovery system shall operate normally according to the specified
instructions and shall be suitable for refrigerant recovery.
· In addition, the calibration scales shall operate normally.
· Hoses shall be equipped with leak-free disconnect couplings.
· Before starting the recovery, check for the status of the recovery system
and sealing state. Consult with the manufacturer if suspected.
· The recovered refrigerant shall be returned to the supplier in the correct
recovery cylinders with the Waste Transfer Note attached.
· Do not mix refrigerants in the recovery units or cylinders.
· If compressors or compressor oils are to be removed, make sure that they
have been evacuated to the acceptable level to ensure that flammable
refrigerant does not remain in the lubricant.
· The evacuation process shall be performed before sending the compressor to
the suppliers.
· Only the electrical heating to the compressor body is allowed to accelerate
the process.
· Oil shall be drained safely from the system. · For installation with
handling the refrigerant
(R-32), use dedicated tools and piping materials. Because the pressure of the
refrigerant, R-32 is approximately 1.6 times higher than that of R-22, failure
to use the dedicated tools and piping materials may cause rupture or injury.
Furthermore, it may cause serious accidents such as water leakage, electric
shock, or fire. · Never install a motor-driven equipment to prevent ignition.
41
Maintenance Procedures
Performing the gas leak tests for repair
In case of repair of the refrigerant circuit, the following procedure must be
kept to consider flammability.
1 Remove the refrigerant.
2 Purge the refrigerant circuit with inert gas.
3 Perform evacuation.
4 Purge the circuit again with inert gas.
5 Open the circuit.
6 Perform repair work.
7 Charge the system with refrigerant.
8 Flush the system with nitrogen blowing for safety.
9 Repeat the previous steps several times until no refrigerant is within the
system.
CAUTION
· Compressed air or oxygen shall not be used. · Flush the system with nitrogen
blowing, fill the
refrigerant until the working pressure is reached, ventilate to atmosphere,
and then pull down to a vacuum state. · For the final nitrogen blowing charge,
the system shall be ventilated down to atmospheric pressure. · The procedure
is absolutely vital in case of brazing on the pipings. · Make sure that the
outlet of the vacuum pump is not closed to any ignition sources and there is
ventilation available. · Do not apply any permanent inductive or capacitance
loads to the circuit without ensuring that this will not exceed the
permissible voltage and current permitted for the air condiitoner.
· Before starting the process, power supply must be available.
1 Be familiar with the equipment details.
2 Isolate the system electrically.
3 Before starting the process, make sure that: · Any mechanical equipment is
available for
handling refrigerant cylinders. · All PPE (personal protective equipment) is
available for servicing. · The recovery process shall be supervised by a
competent person. · The recovery equipment and cylinders comply
with the standards. 4 Lower the refrigeration system, if possible.
5 If vacuuming is not possible, make a manifold so that refrigerant can be
easily removed from the parts of the system.
6 Make sure that the cylinders are placed on the scales before recovery.
7 Run the recovery system in accordance with the manufacturer’s instructions.
8 Do not overcharge the cylinders. (No more than 80 %)
9 Be sure to keep the cylinder within the maximum working pressure, even
temporarily.
10 After charging, make sure that the cylinders and the equipment are promptly
removed from the site and all isolation valves are closed.
11 Recovered refrigerant shall not be charged into other refrigeration system
unless it is cleaned and checked.
Decommissioning
The following requirements must be fulfilled before and while taking the
decommissioning procedure:
· Before decommissioning, the worker shall be familiar with the product
details.
· The entire refrigerant shall be recovered safely. · Before starting the
process, oil and refrigerant
samples shall be taken just in case analysis is required for reuse.
42
Operation of buttons
6
1
7
2
8
3
9
4
10
5 11
RG57B/BGE
3
Operation of buttons
6
7
6
1
7
2
8
3
9
4
10
5 11
8
RG57B/BGE
9
4
QUESTIONS OR COMMENTS?
COUNTRY
MALAYSIA
CALL
1800-88-9999 (OTH) +603-7713 7420 (Overseas contact)
OR VISIT US ONLINE AT
www.samsung.com/my/support
This appliance is filled with R-32.
References
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>