GIRA RTR 230 V Changer System 55 Pure White User Manual

June 9, 2024
GIRA

RTC 230 V~ with NC contact
Order no.: 2470 00
Operating instructions

Safety instructions

Electrical devices may only be mounted and connected by electrically skilled persons.
Serious injuries, fire or property damage possible. Please read and follow manual fully.
Danger of electric shock. Always disconnect before carrying out work on the device or load. In so doing, take all the circuit breakers into account, which support dangerous voltages to the device and or load.
This manual is an integral part of the product, and must remain with the end customer.

Device components

GIRA RTR 230 V Changer System 55 Pure White - fig

(1) Room temperature controller insert
(2) Cover frame
(3) Central plate
(4) Control knob
(5) Internal temperature sensor
(6) Adjustment rings temperature limit
During renovation work, the temperature sensor (5) must not become dirty or be painted over.

 Intended use

  • Electronic room temperature controller for controlling electrothermal valve drives for 230 V~
  • Control of the room temperature in closed rooms
  • Mounting in appliance box with dimensions according to DIN 49073

Product characteristics

  • Manually setting a comfort temperature
  • Internal temperature sensor
  • Silent switching
  • Controller output working method: pulse width modulation (PWM)
  • Operates with valve type “deenergised closed”
  • Valve protection function (once a week opening and closing of valve)

Operation

Increasing or reducing the room temperature
■ Turn the control knob to the right or left.
In the centre position, the device regulates to approx. 20 °C setpoint temperature. The lowest setpoint temperature is approx. 5 °C and the highest setpoint temperature is  approx. 30 °C (Figure 4).

Information for electrically skilled persons

Selecting a suitable installation location

  • Recommended installation height: 1.50 m on interior walls
  • Do not mount the device near sources of interference, such as ovens, refrigerators, draughts (e.g. next to the door) or direct sunlight. This affects the temperature measurement of the internal temperature sensor.
  • Do not mount the device within shelf walls or behind curtains and similar covers
  • Do not use the device in multiple combinations with heat-generating devices such as dimmers

DANGER!
Mortal danger of electric shock.
Disconnect the device. Cover up live parts.

Connecting and fitting the device

GIRA RTR 230 V Changer System 55 Pure White - fig1

  • Connect electrothermal valve drive (7) to insert (1) according to connection diagram (Figure 2). Observe the conductor cross-sections (Figure 3).
  • Fit device in appliance box; terminals must be at the bottom.
  • Fit cover frame (2), central plate (3) and control knob (4).
  • Switch on mains voltage.

Setting the temperature limits
The room temperature controller has a setting range of 5 … 30 °C. The adjustment rings on the central plate can be used to limit the temperature setting range.
The specified temperature values may deviate from the actual room temperature depending on the installation location.GIRA RTR 230 V Changer System 55 Pure
White - fig3

  • Pull the control knob (4) off the central plate (3) so that the adjustment rings (6) are visible (Figure 4). The temperature values shown in the picture are for orientation purposes.
  • Turn the large blue adjustment ring clockwise to the desired minimum temperature. Each notch corresponds to a change of about 1 °C.
  • Turn the small red adjustment ring anticlockwise to the desired maximum temperature.
  • Replace the control knob, observing the coding of the control knob and rotary axle.

Technical data

Rated voltage AC 230 V ~
Mains frequency 50 / 60 Hz
Standby power max. 0.5 W
Connected load 20 W

Connection: Thermal valve drive ordering no.: 2169 00

Number valve drive 1 … 10
Ambient temperature -5 … +45 °C
Storage/transport temperature -25 … +70 °C
Controller class (EU 811/2013) IV
Contribution to energy efficiency 2%

Data according to EN 60730-1
Type of action| 1.Y
Degree of soiling| 2
Measured surge voltage| 4000 V

Warranty
The warranty is provided in accordance with statutory requirements via the specialist trade.
Please submit or send faulty devices postage paid together with an error description to your responsible salesperson (specialist trade/installation company/electrical specialist trade). They will forward the devices to the Gira Service Center.

Gira
Giersiepen GmbH & Co. KG
Elektro-InstallationsSysteme
Industriegebiet Mermbach
Dahlienstraße
42477 Radevormwald
Postfach 12 20
42461 Radevormwald
Deutschland
Tel +49(0)21 95 – 602-0
Fax +49(0)21 95 – 602-191
www.gira.de