STAHL 210731 miniCLIX Plug Connector Coupling Owner’s Manual
- June 3, 2024
- STAHL
Table of Contents
STAHL 210731 miniCLIX Plug Connector Coupling
Introduction
- Simple installation and maintenance in Zone 1, safe and fast disconnection under load
- 6+1- pole, rated voltage up to 400 V AC, rated current up to 16 A
- Suitable for harsh industry environments, IP66/ IP68, for Zones 1 and 2
WebCode 8591B
R. STAHL Series 8591/ 2 7- pole, explosion-protected miniCLIX plug
connectors disconnect non-intrinsically safe circuits up to 400 V/ 16 A and
are used as a hot swap plug connection for signal and data cables. They are
available in various versions and materials: Device plugs, flange sockets,
plugs/ couplers made of polyamide, nickel-plated brass, or stainless steel.
The cable can be connected using a crimp or spring clamp terminal.
Preinstalled cables for device plugs and flange sockets enable fast and safe
installation in the end devices.
Technical Data
Explosion Protection
Application range (zones)| 1
2
IECEx gas certificate| IECEx BKI 07.0001X
IECEx gas explosion protection| Ex db eb IIC T6 Gb
ATEX gas certificate| PTB 07 ATEX 1028 X
ATEX gas explosion protection| E II 2 G Ex db eb IIC T6 Gb
Certificates| ATEX (PTB), IECEx (BKI)
Electrical Data
Rated operational voltage AC| 230 – 250 V
Switching capacity| IEC/EN 60947
AC-1: 400 V / 16 A
DC-1: 400 V / 1 A
DC-3: 60 V / 0.5 A
Frequency Hz (for AC)| 50
60
Ambient Conditions
Ambient temperature| -55 °C … +40 °C
Note| – 20 … + 40 °C plastic version
– 20 … + 75 °C plastic version Ith max. 1 A
– 55 … + 40 °C metal version
– 55 … + 75 °C metal version Ith max. 1 A
Mechanical Data
Degree of protection (IP)| IP66
Degree of protection note| IP68 (2 m water column, 1 hour) according to IEC/EN
60529
(with protective caps closed and secured as well as properly fitted and secured compo-
nents)
Mechanical Data
Mechanical Data
Enclosure material| Nickel-plated brass
Clamping range| 7 … 11 mm
Recommended colour ring coding| Red
Coding (clock hour position)| 6
Detailed number of poles| 6 P + PE
Weight| 0.1 kg
Weight| 0.22 lb
Mounting / Installation
Connection type| 1.5 mm² crimp
Components
Locking device present| No
Protective cap available| No
Dimensional Drawings
(All Dimensions in mm [inches]) – Subject to Alterations
Coupler (plastic, metal)
Accessories
Art. No. | ||
---|---|---|
**** | 165671 | |
**** | for coupler, flange socket: brass, nickel-plated |
Anti-twist protection
****| for flange socket, device plug|
154587
---|---|---
Crimping tool
**| for all crimp connection versions up to 4 mm²|
109116
---|---|---
for all crimp connection versions up to 4 mm²|
109116
Strain relief
Art. No.**
****| Ø 7 … 11 mm, with gasket/washer + PE connection| 154585
We reserve the right to make alterations to the technical data, dimensions, weights, designs and products available without notice. The illustrations cannot be considered binding.
R. STAHL Schaltgeräte GmbH | Am Bahnhof 30 | 74638 WALDENBURG. Tel. +49 7942 943 1700 | +49 7942 943 1777 | Email: sales.de@r-stahl.com | r-stahl.com.
References
- R. STAHL | Explosion Hazard Systems | Industrial Explosion Protection
- You will find a little bit of Stahl chemistry everywhere | Stahl | Stahl