Technical Specifications
- Product type High bay microwave DALI sensor (Tri-level control)
- Operating voltage 120~277VAC 50/60Hz
- Rated load Maximum 20pcs devices, maximum 40mA
- Power consumption < 1W
- Detection angle 360o
- **Detection area (Max.)*** Detection range 10% / 50% / 75% / 100%
- Hold time 2s / 30s / 1min / 5min / 10min / 15min / 20min / 30min
- Stand-by time 0s / 10s / 1min / 5min / 10min / 30min / 1h / +
- Stand-by dimming level 10% / 20% / 30% / 50%
- Daylight threshold 2~ 500Lux, Disable
- Warmming up time 20s
- Operating temperature -20o C ~ +50oC
- IP rating IP42
Installation
Warnings
- Installation must be carried out by a qualified engineer in accordance with local regulations.
- Disconnect supply before installing.
- Install to a solid surface – vibrations may cause mis-triggering.
- Ensure environmental conditions are suitable for electronic equipment
Note: We recommend the mounting distance between sensor to sensor should be more than 2m to prevent sensors from false-triggering.
Direct junction “J” box mounting
- a. Separate control board (A) from facia (B) & junction box (C).
- b. Make electrical connections to control board (A). See detailed wiring diagram on next page.
- c. Secure control board (A) to junction box.
- d. Set-up sensor modes as per sections 3 & 4 of this manual.
- e. Clip facial plate (B) to control board (A).
Surface mount assembly
- a. Separate control board (A) from facia (B) & Surface box (C).
- b. Securely mount surface box (C) to a flat and solid surface.
- c. Make electrical connections to control board (A). See detailed wiring diagram on next page.
- d. Set-up sensor modes as per sections 3 & 4 of this manual.
- e. Secure control board (A) to surface box (C).
- f. Clip facial plate (B) to control board (A).
Rotary Switch Settings
A rotary switch is built inside the sensor for scene selection / fast programming. Total 16 channels available:
Note: settings can also be changed by remote control HRC-11. The last action controls.
Functions
Tri-level Control (Corridor Function)
Hytronik builds this function inside the motion sensor to achieve tri-level
control, for some areas require a light change notice before switch-off.
It offers 3 levels of light: 100%–>dimmed light–>off; and 2 periods of
selectable waiting time: motion hold-time and stand-by time; Selectable
daylight threshold and detection area.
4.2 Lux Off Function
The built-in daylight sensor can read ambient natural light and switch off the
fixture automatically whenever artificial light is not required (natural light
lux level exceeds daylight threshold).
Note: if the stand-by time is preset at “+∞”, the fixture never switches off
even when natural light is sufficient.
Synchronization Function
By connecting the “SYNC” terminals in parallel (see wiring diagram), no matter which sensor detects motion, all HMW15 in the group will turn on the lights when surrounding natural light is below the daylight threshold. The sensor module is shared and the detection area could be widely enlarged in this way.
Manual Override
With the help of push-switch, this sensor maybe over-ridden by the end-users to switch on/off the lights manually, or adjust the light brightness during motion hold-time. This makes the product more user-friendly and offers more options to fit for extra-ordinary demands.
- Short push (<1s): on/off function;
ON → OFF: the light turns off immediately and cannot be lighten for a certain time (equals to hold time preset) even there is movement is detected. After this period, the sensor goes back to auto sensor mode.
OFF → ON: the light turns on 100% and goes to auto sensor mode, even when ambient
Lux level exceeds the daylight threshold. - Long push (>1s): adjust the maximum brightness (between 10% and 100%) during hold-time. Both the settings on remote control and push switch can overwrite each other, the last adjustment remains in memory.
Semi-auto Function (Absence Detection)
The motion sensor is employed, but only activated on the manual press of the
push switch, The light remains on during presence and dims down in absence,
eventually switching off automatically after the stand-by time has expired.
Note: in this mode, the push terminal used for the ‘manual on’ switch
input.
End-user can choose either function 4.4 or 4.5 for application. Default
function is 4.4.
Wiring Diagram
Detection Pattern
Description of the Button Functions (remote control HRC-11)
Permanent ON/OFF [buttonO1
Press button 1 to select permanent ON or permanent OFF mode.
Press button 2/4 to resume automatic operation.
The mode will change to AUTO Mode after power failure.
RESET [ button 2
Press button 2, all settings go back to the rotary switch settings.
Shift [ button 3
Press button 3, the LED on the top left corner is on for indication.
All values/ settings in RED are in valid for 20 seconds.
Auto Mode [ button 4
Press button 4 inítiate automatic mode. The sensor starts working and all settings remain as before the light was switched ON/OFF.
Semi-auto Mode [ button 3 &4]
- Press button 3 Shift (the red LED is on for indication),
- press button 4 initiate semi-auto mode. The fixture is manually on by push-switch and automatically off in semi-auto mode.
Power output [ button 5
Press button 5, the light output shifts between 80% and 100%.
Note: the function of “Sensor off” and “Twilight” are disabled.
Brightness+/-[ button 6
Press button 6 to adjust the light brightness between 10%- 100%.
Scene prog. [ zone 7] (One-key-commissioning)
- Press button “Start’ to program.
- Select the buttons in 8 “Detection range”, 9/10 Daylight threshold”, OHold time”, “Stand-by time”, “Stand-by dimming level” to0 Sel all parameters.
- Press button “Memory” to save all the settings programmed in the remote control.
- Press button “Apply” to set the settings to each sensor unitfs).
For example, to pre-set detection range 100%, daylight threshold Disable, hold time 5min, stand-by time +o, stand-by dimming level 30%, steps should be:
Press button Start 7, button 8 100%, 10 Disable, 3 Shift, 11 5min, 3 Shift,+12 , 13 30%,7 Memory. By pointing to the sensor unit(s) and pressing 7 Apply, all settings are passed on the sensor(s).
Detection range [ zone 8 ]
Press buttons 8 in zone to set detection range at 100% / 75% / 50% / 10%.
Daylight threshold [ zone 9 ]
Press buttons in zone 9 to set the daylight sensor at 2Lux / 10Lux 50Lux /
100Lux / 300Lux / 500Lux or Disable.
Note: To set daylight sensor at 100Lux / 300 Lux / 500Lux, press button
3Shift at first.
Ambient daylight threshold [ button 10
- Press button 3 Shift, the red LED is on for indication.
- Press button 10, the ambient lux level is sampled and set as the new daylight threshold.
Hold time [ zone 11 ]
Press buttons in zone 11 to set the hold time at 2s / 30s / 1min / 5min /
10min / 15min / 20min / 30min.
- Note: To set hold-time at 30s / 5min / 15min / 30min, press button 3 Shift at first.
- 2s is for test purpose only, stand-by period and daylight sensor settings are disabled in this mode.
To exit from Test mode, press button 2 or any button in zone 11
Stand-by time [ zone 12 ].
Press buttons in zone 12 to set the stand-by period at 0s / 10s / 1min / 5min
/ 10min / 30min / 1h / +.
Note: “0s” means on/off control; “+” means bi-level control, 100% on when
motion detected, and remains at the stand-by dimming level when no presence
after hold-time.
Stand-by dimming level [ zone 13 ]
Press buttons in zone to set the stand-by dimming level at 10% / 20% / 30% /
50%.
Note: the function of 24h /12h /4h /30s are disabled.
Dual tech & RF mode [ zone 14 ]
All buttons in zone 14 are disabled.