F F LE-03MW Electricity Energy Meter Instruction Manual

June 8, 2024
F F

F F LE-03MW Electricity Energy Meter Instruction Manual
F F LE-03MW Electricity Energy Meter

Manual and programming instructions

Full technical documentation of the device for download from the website: www.le.fif.com.pl

Functions

  • 3-phase, 2-way energy meter;
  • direct measurement up to 80 A;
  • energy measurement in 4 tariff zones;
  • built-in real time clock with battery backup to switch tariff zones;
  • registration of total and divided into consumption tariffs:
    • total active and reactive energy;
    • active and reactive energy divided into individual quadrants;
  • 8 time schedules dividing the day into tariff zones;
  • it can settle energy according to schedules specific for business days and weekends;
  • it can divide year into 8 time intervals; in each interval the energy (for weekdays) can be settled according to a different schedule;
  • indication of network parameters (voltages, currents, active power, reactive power, apparent power, power factor, frequency);
  • calculation of power demand for individual tariffs;
  • an additional, resettable energy consumption meter;
  • compliance with MID;
  • RS-485 port, Modbus RTU protocol;
  • optical communication port compliant with EN62056 (IEC1107) standard;
  • 2× SO pulse outputs with a programmable number of pulses per kWh / kvarh.
  • multifunction LCD display.

Measured values

Consumed and supplied| |
---|---|---
active energy| AE+/AE-| [kWh]
Inductive and capacitive| |
reactive energy| RE+/RE-| [kvarh]
Phase voltages| U1, U2, U3| [V]
Phase currents| 11,12,13| [A]
Frequency| F| [Hz]
Consumed and supplied| |
active power| P| [W]
Inductive and capacitive| |
reactive power| Q| [var]
Apparent power| S| [VA]
Power factor| cost()|

Meter number

The meter is marked with individual serial number allowing its unambiguous identification.
The marking is laser engraved and cannot be removed.
Meter Instructions

Sealing
The meter has sealable input and output terminal covers to prevent any attempts to bypass the meter

Wiring diagram

Wiring diagram

20, 21 – RS-485 output
23, 24 – pulse output

Technical data

  • reference voltage: 3×230/400 V
  • minimum current/base current: 0.25/5 A
  • maximum current: 80 A
  • minimum detection current: 0.04 A
  • voltage measuring current
  • L-N 100÷289 V AC
  • L-L 173÷500 V AC
  • rated frequency: 50 Hz
  • measurement accuracy: B class
  • instalation: 3-phase, 4-wire
  • overloading: 30×lmax/10 ms
  • insulation: 4 kV/1 min.; 6 kV/1 μs
  • own meter consumption measured values : <10 VA; <2 W
  • indication range of the meter pulse outputs : 8 digits
  • number of pulse outputs: 2
  • type of pulse outputs: OC (open collector)
  • maximum voltage: 30 V DC
  • maximum current: 27 mA
  • pulse constant for output 1: 1; 10; 100; 1000 pulse/kWh
  • pulse constant for output 2: 1000 pulse/kvar
  • communication port: RS-485
  • communication protocol: Modbus RTU
  • transmission speed: 1200, 2400, 4800, 9600 bps
  • parity: EVEN
  • parity bits: 1
  • reading indication: 2×LED
  • working temperature: -25÷55°C
  • terminal: 25 mm² screw terminals
  • dimensions: 76×100×65 mm (4,5 modules DIN)
  • mounting: on the TH-35 mm rail
  • protection level:  IP51
  • insulation protection class: class II
  • housing: UI94 V-0 self-extinguishing material

Service program
On the fif.com.pl website (on the subpage of the LE-03MW meter) a program is available for PCs with Windows that allows checking the readings of the meter and making all its settings.

CE declaration

A copy of the CE declaration is available for download from the website: www.fif.com.pl from the product subpage.

Conformity
Directive: MID 2014/32/EC, 0120/SGS0306
Norm: EN50470-1/3

Purpose
LE-03MW is an electronic, compliant with the MID Directive, 2-way electricity meter for three-phase electricity, designed for measurement in a direct system.
The built-in real-time clock allows energy consumption to be measured with different tariff zones.
The device is equipped with communication interfaces: RS-485 with Modbus RTU protocol and optical port compliant with EN62056 (IEC1107) standard for remote reading and configuration of the meter


Do not dispose of this device in the trash along with other waste!
According to the Law on Waste, electro coming from households free of charge and can give any amount to up to that end point of collection, as well as to store the occasion of the purchase of new equipment (in accordance with the principle of old-for-new, regardless of brand). Electro thrown in the trash or abandoned in nature, pose a threat to the environment and human health.

WARRANTY

The F&F products are covered by a warranty of the 24 months from the date of purchase. Effective only with proof of purchase.
Contact your dealer or directly with us.
More information how to make a compliant can be found on the website:
www.fif.com.pl/reklamacje

Support

F &F Filipowski sp. j.
Konstantynowska 79/81 95-200 Pabianice
tel/fax (+48 42) 215 23 83; 227 09 71 POLAND
http://www.fif.com.pl
e-mail: biuro@fif.com.pl