HYTRONIK HIM14 Surface Mount Dual Sense Motion Sensor Instruction Manual

June 3, 2024
HYTRONIK

HYTRONIK -logo SURFACE MOUNT DUAL SENSE MOTION SENSOR HIM14

Technical Specifications

Product type  Dual sense DALI sensor (HF and PIR, daylight harvest)
Operating voltage 120~277VAC  50/60Hz
Switched power Maximum 20pcs devices, maximum 40mA
Power consumption  < 1W
Detection angle 360°
Detection area (Max.)* Installation Height : 6m

Detection Range (Ø) :12m
Detection range| 10% / 50% / 75% / 100%
Hold time|  2s / 30s / 1min / 5min / 10min / 15min / 20min / 30min
Stand-by time|   0s / 10s / 1min / 5min / 10min / 30min / 1h / +∞
Stand-by dimming level| 10% / 20% / 30% / 50%
Daylight threshold|   50 ~ 500Lux, Disable
Warmming up time| 30s
Operating temperature|  -20 °C  ~ +55 ° C
Sensor mode|   PIR, HF, PIR+HF, PIR / HF

Installation

Warnings:

  1. Installation must be carried out by a qualified engineer in accordance with local regulations.
  2. Disconnect supply before installing.
  3. Install to a solid surface – vibrations may cause mis-triggering.
  4. Ensure environmental conditions are suitable for electronic equipment

HYTRONIK HIM14 Surface Mount Dual Sense Motion Sensor-

HYTRONIK HIM14 Surface Mount Dual Sense Motion Sensor-
fig1

Note: the blinds are optional, they may be inserted behind the lens for focussing the detection range.

HYTRONIK HIM14 Surface Mount Dual Sense Motion Sensor-
fig2

Direct junction “J” box mounting
a. Separate control board (A) from facia (B) & junction box (C).
b. Make electrical connections to control board (A). See detailed wiring diagram on next page.
c. Secure control board (A) to junction box.
d. Set-up sensor modes as per sections 3 & 4 of this manual.
e. Clip facial plate (B) to control board (A).

HYTRONIK HIM14 Surface Mount Dual Sense Motion Sensor-
fig3

Surface mount assembly
a. Separate control board (A) from facia (B) & Surface box (C).
b. Securely mount surface box (C) to a flat and solid surface.
c. Make electrical connections to control board (A). See detailed wiring diagram on next page.
d. Set-up sensor modes as per sections 3 & 4 of this manual.
e. Secure control board (A) to surface box (C).
f. Clip facial plate (B) to control board (A).

HYTRONIK HIM14 Surface Mount Dual Sense Motion Sensor-
fig4

Rotary Switch Settings

A rotary switch is built inside the sensor for  scene selection / fast programming. Total 16 channels available:

HYTRONIK -icon1

Channel| Detection
range| Hold
time| Stand-by
time| Stand-by
dimming level| Daylight
threshold
---|---|---|---|---|---
0| 100%| 5s| 10s| 10%| Disable
1| 100%| 1min| 5min| 10%| 50Lux
2| 100%| 5min| 10min| 10%| 50Lux
3| 100%| 5min| +∞| 10%| 75Lux
4| 100%| 5min| +∞| 10%| 100Lux
5| 100%| 5min| +∞| 30%| 200Lux
6| 100%| 10min| 30min| 10%| 50Lux
7| 100%| 10min| +∞| 10%| 75Lux
8| 100%| 10min| +∞| 10%| 100Lux
9| 100%| 10min| +∞| 30%| 200Lux
A| 100%| 20min| 1h| 10%| 100Lux
B| 100%| 20min| +∞| 30%| 200Lux
C| 100%| 30min| +∞| 10%| 100Lux
D| 100%| 30min| +∞| 30%| 200Lux
E| 100%| 30min| +∞| 50%| 400Lux
F| 100%| 5s| 10s| 10%| 100Lux

Note: settings can also be changed by remote control HRC-11. The last action controls.

Sensor Mode Selection

Sensor mode can be easily selected by choosing the correct combination of the DIP switches (see table below):

HF+PIR: Light is on when both HF and PIR sensors are activated.
HF/PIR: Light is on when HF or PIR sensors are activated.

Functions

5.1 Daylight Harvest (Daylight Regulating)
The built-in daylight sensor can measure ambient natural light, and calculate how much electrical light is needed to reach the target lux level. The demand is given to the LED driver by DALI signal, so as to deliver the needed amount of electric light. The target lux level can be adjusted by remote control or long press on the push switch.

HYTRONIK HIM14 Surface Mount Dual Sense Motion Sensor-
fig6

5.2 Lux Off Function
The light dims to minimum level even switches off completelly if ambient daylight is sufficient (natural light level exceeds target lux level), no matter it is during hold-time or stand-by time, with or without motion.
Note: if the stand-by time is preset at “+∞”, the light never turns off even when natural light is sufficient.

5.3 Manual Override (Push Function)
With the help of push-switch, this sensor maybe over-ridden by the end-users to switch on/off the lights manually, or adjust the target lux level. This makes the product more user-friendly and offers more options to fit for extra- ordinary demands.

  • Short push (<1s): on/off function;
    ON → OFF: the light turns off immediately and cannot be lighten for a certain time (equals to hold time preset) even movement is detected. After this period, the sensor goes back to auto sensor mode.
    OFF → ON: the light turns on and goes to auto sensor mode.
  • Long push (>1s): adjust the target lux level by turning the light up or down. Both the adjustment by remote control and push switch can overwrite each other, the last
    adjustment remains in memory.
    5.4 Semi-auto Function (Absence Detection)
    The motion sensor is employed, but only activated on the manual press of the push switch. With presence, the light remains on and can interact with ambient natural light, then dims down in absence, eventually switching off automatically after the stand-by time has expired.
    Note: end-user can choose either function 5.3 or 5.4 for application. Default function is 5.3.
    5.5 Synchronization Function
    By connecting the “SYNC” terminals in parallel (see wiring diagram), no matter which sensor detects motion, all HIM14 in the group will turn on the lights when surrounding natural light is below the daylight threshold. The sensor module is shared and the detection area could be widely enlarged in this way.

Wiring Diagram

HYTRONIK HIM14 Surface Mount Dual Sense Motion Sensor-
fig7

Note: if neither function 5.3 nor 5.4 is desired, simply leave the “push” terminal disconnected.

Detection Pattern

HYTRONIK HIM14 Surface Mount Dual Sense Motion Sensor-
fig8

Description of the Button Functions (remote control HRC-11)

HYTRONIK HIM14 Surface Mount Dual Sense Motion Sensor-
fig9

Permanent ON/OFF [button(1)] Press button 1 to select permanent ON or permanent OFF mode.

  • Press button 2/4 to resume automatic operation.
    The mode will change to AUTO Mode after power failure.
    RESET [ button 2]
    Press button 2, all settings go back to the rotary switch settings.
    Sensor mode return to DIP switch settings.
    Shift [ button3]
    Press button3 , the LED on the top left corner flashes for indication.
    All values / settings in RED are in valid for 20 seconds.
    Auto Mode [ button 4]
    Press button 4to initiate automatic mode. The sensor starts working and all settings remain as before the light was switched ON/OFF.
    Semi-auto Mode [ button 3 &4 ]
    1. Press button 3 Shift (the red LED flashes for indication),
    2. press button4 to initiate semi-auto mode. The fixture is manually on by push-switch and automatically off in semi-auto mode.
    Power output [ button 5 ]
    Press button5 , the light output shifts between 80% and 100%.
    Note: the function of “Sensor off” and “Twilight” are disabled.
    Brightness +/- [ button6 ]
    Press button 6 to adjust light brightness to reset the target lux level.
    Scene prog. [ zone7 ] (One-key-commissioning)

    1. Press button “Start” to program.
    2. Select the buttons in 8 “Detection range”,9/ 10 “Daylight threshold”, 11 “Hold time”, 12 “Stand-by time”, 13 “Stand-by dimming level” to set all parameters.
    3.  Press button “Memory” to save all the settings programmed in the remote control.
    4. Press button “Apply” to set the settings to each sensor unit(s).
      For example, to pre-set detection range 100%, daylight threshold Disable, hold time 5min, stand-by time +∞, stand-by dimming level 30%, steps should be:
      Press button 7 Start, button 8 100%, 10 Disable, 3 Shift, 11 5min,  12 Shift, +∞ , 30%, Memory. By pointing to the sensor unit(s)and pressing Apply, all settings are passed on the sensor(s).

Detection range [ zone 8 ]
Press buttons in zone to set HF detection range at 100% / 75% / 8 50% / 10%.
Daylight threshold [ zone9 ] Press buttons in zone 9 to set the daylight sensor at 50Lux / 100Lux / 300Lux / 500Lux or Disable as threshold / target Lux level.
Note: 2Lux / 10Lux are disabled.
To set daylight sensor at 100Lux / 300 Lux / 500Lux, press button 3 Shift at first.
Ambient daylight threshold [ button 10] 1. Press button3 Shift, the red LED flashes for indication.
2. Press button10 , the ambient lux level is sampled and set as daylight threshold / target Lux level.
Hold time [ zone 11 ]
Press buttons in zone 11 to set the hold time at 2s / 30s / 1min / 5min / 10min / 15min / 20min / 30min.
Note: 1.To set hold-time at 30s / 5min / 15min / 30min, press button 3 Shift at first.
2. 2s is for test purpose only, stand-by time and daylight sensor settings are disabled in this mode.

  • To exit from Test mode, press 2 button or any button in zone 11 .
    Stand-by time [ zone 12 ]
    Press buttons in zone 12 to set the stand-by time at 0s / 10s / 1min / 5min / 10min / 30min / 1h / +∞.
    Note: “0s” means on/off control; “+∞” means bi-level control, 100% on when motion detected, and remains at the stand-by dimming level when no presence after hold-time.
    Stand-by dimming level [ zone 13 ]
    Press buttons in zone 13 to set the stand-by dimming level at 10% / 20% / 30% / 50%.
    Daylight harvest auto-configuration function
    1. Press button “Shift”, the red LED is on for indication.
    2. Select a time period and the sensor will do light level measurement and determine/save the lowest light level (commission line) with 100% light on, so as to set the target lux level automatically.
    Note: 1. Make sure the light level measurement covers the night time.
    2. The fixture will go into sensor mode after the measurement,
    all sensor settings remain unchanged
    Dual tech & RF mode [ zone 14 ]
    1. Press buttons in zone 14 to select sensor technology.
    HF+PIR: Light is on when both HF and PIR sensors are activated.
    HF/PIR: Light is on when HF or PIR sensors are activated.
    2. Learn / Erase, Transmit, RX100% and RX STBY% are disabled.

HYTRONIK -logoHytronik Industrial Ltd. | www.hytronik.com
3rd Floor, block C, complex building, 155#, Bai’gang road south,
Bai’gang village, Xiao Jin Kou town, Huicheng district, Huizhou 516023
Tel: 86-752-2772020 Fax: 86-752-2777877
HIM14-20190104-A1

Read User Manual Online (PDF format)

Read User Manual Online (PDF format)  >>

Download This Manual (PDF format)

Download this manual  >>

HYTRONIK User Manuals

Related Manuals