BLUERIDGE BC1P Series Painted Cased Evaporator Coil Instruction Manual

June 3, 2024
BLUERIDGE

Series Painted Cased Evaporator Coil
Instruction Manual

Painted Cased Evaporator Coil

This manual must be left with the homeowner for future reference.
**** This is a safety alert symbol and should never be ignored. When you see this symbol on labels or in manuals, be alert to the potential for personal injury or death.

**IMPORTANT
The Clean Air Act of 1990 bans the intentional venting of refrigerant (CFCs, HCFCs and HFCs) as of July 1, 1992. Approved methods of recovery, recycling or reclaiming   ust be followed. Fines and/or incarceration may be levied for noncompliance.
WARNING Improper installation, adjustment, alteration, service or maintenance can cause personal injury, loss of life, or damage to property. Installation and service must be performed by a licensed professional installer (or equivalent) or a service agency.
CAUTION
** As with any mechanical equipment, contact with sharp sheet metal edges can result in personal injury. Take care while handling this equipment and wear gloves and protective clothing.

(P) 507792-01B  (P) 0674398-00

Model Number Identification

BLUERIDGE BC1P Series Painted Cased Evaporator Coil -
Fig1

NOTE: Special procedures are required for cleaning the aluminum coil in this unit. See Page 8 in this instruction for information.
General
The BC4X and BC1P upflow evaporator coils are available cased only. The BC1P coil includes a factory-installed HFC-410A fixed orifice (RFC) metering device that must be replaced if the system match with the coil requires a fieldinstalled check/expansion valve. The BC4X coil includes an externally equalized factory-installed HFC-410A check/ expansion valve. The coil drain pan has a maximum service temperature of 500°F.
The drain pan must be at least 2″ away from a standard gas-fired furnace heat exchanger and at least 4″-6” away from any drum-type or oil-fired furnace heat exchanger, depending on furnace model. Closer spacing may damage the drain pan and cause a leak. Refer to the Product Specification for the proper use of these coils with specific furnaces, air handlers, condensers and line sets.
These instructions are intended as a general guide and do not supersede local or national codes in any way. Authorities who have jurisdiction should be consulted before installation.
Shipping and Packing List
Package 1 of 1 contains:
BC1P
1 – Evaporator coil
BC4X
1 – Evaporator coil
Check the components for shipping damage; if found, immediately contact the last carrier.

Releasing Air Charge

CAUTION
The coil is shipped from the factory pressurized with dry air. Pierce a hole in the rubber plug that seals the vapor line to relieve the pressure before removing the plugs.
NOTE: If there is no pressure released when the vapor  ine rubber plug is pierced, check the coil for leaks before continuing with the installation.
The BC1P & BC4X coils are shipped with a 10 psi dry air holding charge. Puncture the suction line rubber plug to release the charge. Remove the rubber plug. Ensure that  the coil is void of pressure.
Installation
Air Leakage
All indoor cabinets MUST be taped after installation to seal against any air leaks. System performance and efficiency will be reduced if air leakage exists.
**WARNING
** Risk of explosion or fire.
Can cause injury or death.
Recover all refrigerant to relieve pressure before opening the system.
Install the furnace or air handler and condensing unit according to the installation instructions provided with the unit.
Position the cased coil on top of the furnace or air handler cabinet and secure it using field-provided screws. NOTE: If the coil is to be installed on an oil furnace, it may  be  ecessary to install a field-installed transition between the furnace and the coil to prevent airflow restriction and possible damage to the coil drain pan. See the oil furnace installation instructions for details.
NOTE: The coil cabinet has six screw clearance holes  which should be aligned with the furnace engagement holes. Secure the coil cabinet o the furnace or air handlerusing six field-provided #8 X 1″ screws.

Refrigerant Line Connections
Line Sizes
The refrigerant line sets should be sized according to the recommendations given in the condensing unit installation instructions. Use Table 1 to determine correct braze  connection sizes. A field-provided adapter may be required to match line set connections.

Model Number Suction Liquid

-24
-30
-36| 3/4 Inch| 3/8 Inch
-48
-49
-60| 7/8 Inch

Table 1. Refrigerant Line Connections
Replacement Parts

If replacement parts are necessary, order kit 69J46. The
kit includes:

  • 10 – Brass nuts for liquid line assemblies
  • 20 – Teflon rings
  • 10 – Liquid line orifice housings
  • 10 Liquid line assemblies

BLUERIDGE BC1P Series Painted Cased Evaporator Coil -
Fig3

Brazing Guidelines
Use a silver alloy brazing rod (5 or 6 percent silver alloy for copper-to- copper connections or 45 percent silver alloy for copper-to-brass or copper- to-steel connections). Before making brazed connections, place a field- provided heat shield, such as a wet rag, against the unit cabinet and around the piping stubs, expansion valve and sensing  bulb. The heat shield must be in place to prevent heat damage during brazing. See Figure 2.

BLUERIDGE BC1P Series Painted Cased Evaporator Coil -
Fig2 Figure 2. Braze Refrigerant Lines

Suction Line Connection
Use the following procedure to connect the suction line to the indoor coil:

  1.  Remove rubber plug from the stubbed connection.
  2. Position the properly sized refrigerant piping and make the brazed connection following the brazing guidelines.
  3. Do not remove the water-saturated rags from the cabinet and piping until the piping has cooled completely.

BC1P Suction Line Equalizer Fitting
Remove the copper flare seat bonnet if present from the male equalizer line fitting (Figure 3).

BLUERIDGE BC1P Series Painted Cased Evaporator Coil -
Fig4

IMPORTANT
When removing the flare nut, ensure that the copper flare seal bonnet is removed as illustrated in Figure 3.
Figure 3. BC1P Suction Line Male Equalizer Line Fitting Modifications
BC1P Liquid Line Connection
NOTE: BC1P coils are shipped with a factory-installed HFC-410A fixed orifice (RFC) metering device. Some system matches with this coil require use of a check/ expansion valve.
NOTE: If the system match requires an HFC-410A check/expansion valve on the liquid line connection, the fixed orifice device must be removed BEFORE a check/ expansion valve is installed. BC4X coils include a factory-installed HFC-410A check/expansion valve.
BC1P Fixed Orifice Removal (if necessary)

  1. Remove the coil access and plumbing panels.
  2. Remove any shipping clamps that secure the liquid line and distributor assembly.
  3. Using two wrenches, disconnect the liquid line stub from the orifice housing. Take care not to twist or damage the distributor tubes during this process.
  4. Remove and discard the existing orifice, valve stem assembly (if present) and Teflon ring as illustrated in Figure 4.
  5. Retain brass nut to be used later with the liquid line assembly.

BLUERIDGE BC1P Series Painted Cased Evaporator Coil -
Fig45

BC1P Expansion Valve / Liquid Line Installation Some system matches for the BC1P coils require a check/  expansion valve. The expansion valve must be installed external to the indoor coil   abinet. Refer to the instructions provided with the expansion valve kit for proper installation  of the valve and sensing bulb.  See the BC1P Product Specifications for approved expansion valve match-ups and application information.

  1. After the expansion valve, equalizer line and sensing  bulb have been installed per the kit instructions, braze the properly sized refrigerant piping into place. Carefully follow  razing guidelines and use wet rags toprevent heat damage.
  2. Do not remove the water-saturated rags from the cabinet and piping until the piping has cooled completely.

NOTE: To prevent any possibility of water damage, properly insulate all parts of the expansion valve assembly that may sweat due to temperature differences between  the  alve and its surrounding ambient temperatures.
BC4X Liquid Line Connection
BC4X coils include a factory-installed HFC-410A check/ expansion valve metering device.
Connect the properly sized field-provided liquid line to the liquid line stub as shown in Figure 5 using one of the following procedures:

  1.  Position the properly sized refrigerant piping and make the brazed connection following the brazing guidelines.
  2. Do not remove the water-saturated rags from the cabinet and piping until the piping has cooled completely.

OR

  1. Cut the copper liquid line on a vertical or horizontal section. Use a field-provided coupling to join the   properly sized field-provided refrigerant piping and the liquid line  ub on the coil. Follow the brazing guidelines.
  2. Do not remove the water-saturated rags from the cabinet and piping until the piping has cooled, completely.

BLUERIDGE BC1P Series Painted Cased Evaporator Coil -
Fig46

Figure 5. BC4X Liquid Line Connections
Refer to the outdoor unit instruction for leak testing, evacuating and charging procedures. Always leak check entire system before charging.
The following best practices are recommended to ensure better condensate removal:

  • Main and overflow drain lines should NOT be smaller than both drain connections at drain pan.
  • Overflow drain line should run to an area where homeowner will notice drainage.
  • It is recommended that the overflow drain line be vented and a trap installed. Refer to local codes.

Sealing Ducts
WARNING
Ensure that the duct is secured and all joints are properly sealed to the coil cabinet flanges. There must be an airtight seal between the bottom of the furnace and the return  ir  lenum. Use fiberglass sealing strips, caulking, or equivalent sealing method  between the  lenum and the air handler cabinet to ensure a tight seal. Return air must not be  rawn from a  room where the air handler or any gas-fueled appliance (i.e., water heater), or  arbon monoxide- producingdevice (i.e., wood fireplace) is installed.
IMPORTANT
DUCT SYSTEM SIZING – The duct system should be properly sized and installed according to the ASHRAE  Standard Manual D. The supply and return air duct systems  hould be designed for the cfm and static requirements of the job. Consult the blower performance chart in the unit installation instructions to verify that the  blower meets  the application requirements.

Condensate Drain Connections
Main Drain
Connect the main drain and route drain tubing downward drain line or sump. Do not connect drain to a closed waste system. See Figure 7 for typical drain trap configuration.
Overflow Drain
It is recommended that the overflow drain stub be connected to an overflow drain line for all units. If the overflow drain not connected to a drain line, it must be plugged  it the provided cap.
IMPORTANT
After removal of drain pan plug(s), check drain hole(s) to verify that drain opening is fully open and free of any debris. Also check to make sure that no debris has fallen into   he drain pan during installation that may plug up the drain opening.
Condensate Drain Recommendations
The following practices are recommended to ensure better condensate removal:

  • Main and overflow drain lines should NOT be smallernthan both drain connections at drain pan.
  • Overflow drain line should run to an area where homeowner will notice drainage.
  • It is recommended that the overflow drain line be vented and a trap installed. Refer to local codes.

Blower Speed Selection

BLUERIDGE BC1P Series Painted Cased Evaporator Coil -
Fig5 Figure 6. Static Pressure Test

Cabinet Vol: CFM Drop: in. w.g.
Model Width in. Dry
24A 14-1/2 800
24B 17-1/2 800
30A 14-1/2 1000
30B 17-1/2 1000
36B 17-1/2 1200
48B 17-1/2 1400
17-1/2 1600 .30
48C 21 1400
21 1600 .16
49C 21 1600
60C 21 2000

Table 2. Air Volume / Static Pressure Drop Across Coil

BLUERIDGE BC1P Series Painted Cased Evaporator Coil -
Fig7

Figure 7. Typical Main and Overflow Drain Installations
**CAUTION**
Take care when drilling test holes into the furnace flange and the duct. Drill holes away from refrigerant piping. Test holes should be drilled where specified in order to  avoid unit damage.
Proper air volume must be provided over the evaporator coil. Select a blower motor speed tap that will provide 400  ± 50 CFM per 12,000 Btuh of cooling capacity (wet coil).    static pressure reading must be taken to see if the pressure drop falls within the proper range. See Table 2. To ensure accuracy, air must be read from below the coil  and above the coil. See Figure 6 for an example to obtain an accurate reading.

  1. Drill one 5/16” air test hole into the delta plate between the coil slabs
  2. Drill one 5/16” air  est hole into the duct above the top of the coil.
  3. Connect the instrument for static pressure measurement hoses to the air entering side of coil. Insert the hoses so that 1/4” extends inside the duct or end seal. Seal around holes with Permagum®.
  4. Turn on electrical power to the furnace and set the thermostat to initiate a cooling demand.
  5. Table 2 lists air volumes and equivalent static pressure readings for these units. Observe the static pressure reading. If the reading is below the required air volume, increase the blower speed; if the reading is above the required air volume, decrease the blower speed. Refer to the furnace wiring diagram for blower speed settings.
  6. When the required static pressure readings are obtained, remove the test hose lines and insert snap hole plugs into test holes.

Maintenance

NOTE
Failure to follow instructions will cause damage to the unit.
This unit is equipped with an aluminum coil. Aluminum coils may be damaged by exposure to solutions with a pH below 5 or above 9. The aluminum coil should be cleaned   sing potable water at a moderate pressure (less than 50psi). If the coil cannot be cleaned using water alone, it is recommended to use a coil cleaner with a pH in the range of 5   o 9. The coil must be rinsed thoroughly after cleaning. In coastal areas, the coil should be cleaned with potable water several times per year to avoid corrosive buildup (salt).
A trained technician or service agency must perform maintenance and service on equipment. At the beginning of each heating or cooling season, indoor coils should be  cleaned.
Do not use hydrofluoric acid, alkaline, or similar chemicals on coils. These chemicals are not necessary to dissolve salt, and may damage the fin coating. Acid washes are  used  o dissolve oils and greases, which generally are not present on most installations.
Do not use alkaline washes. Alkaline washes are useful
for dissolving oxides such as zinc oxide, aluminum oxide, and iron oxide (rust). However, these three oxides are  more corrosion resistant than base metals, so dissolving or removing them will cause an increase in corrosion.
Cleaning the Coil
The coil should be inspected twice each year and cleaned at least once per year or more, if necessary. Indoor coil  cleaning should be performed by a licensed professional service technician (or equivalent).
CAUTION
A damaged coil fin can affect equipment operation and performance. Do not use flame, high-pressure water,  steam, or volatile cleaners on fins or tubing surfaces. If cleaning  equires the use of acidic or alkaline cleaners, follow the manufacturer’s instructions. Thoroughly flush  cleaner from all equipment components. (Be careful to prevent damage  corrosion of the components connected to the system or areas surrounding the equipment being cleaned.)

  1. Before beginning this or any other maintenance, turn off all power to the indoor unit at the main unit disconnect switch. It is also recommended that you wear personal protective gear: safety glasses and/or a face shield, waterproof clothing and gloves.

  2. Remove the coil from the cabinet or plenum, and take the coil to an appropriate place to clean it.

  3. Vacuum or brush the coil to remove matted and surface debris from the fins. Use vacuum attachments and /or brushes that are non-destructive to fins.

  4. If oil deposits are present, spray the coil with a mild household liquid detergent to soften deposits. Do not leave the detergent on the coil for more than 10 minutes. Flush the coil thoroughly with potable water.
    NOTE: For units in coastal regions, fresh water will dissolve away any salt deposits. (Wash coils with fresh water at least every six months.)

  5. Spray the coil at a vertical angle of 30 to 45 degrees with a constant stream of water at moderate pressure. A pressure washer with a fan nozzle will work best. Do not spray the coil from a horizontal direction.

  6. Direct the spray so that any debris is washed out of the coil and base pan. For most residential units, hot water is not necessary. NOTE: Attempting to back flush from the inside of the coil will require removing parts from the unit, and it may be very difficult to flush the whole coil surface. Attempting to blow water through a coil will slow the water stream and reduce the flushing action of the outer fin surface.

  7. Replace the coil into the cabinet or plenum. Ensure that you have followed the proper procedure for routing and securing the refrigerant tubing.

**IMPORTANT**
Ensure that the distributor lines are not rubbing together or kinked. All tubes must have enough clearance from other metal parts. Use wire ties to secure tubes to prevent  ovement that could cause the refrigerant tubing to fail.

Blue Summit LLC
8201 C National Turnpike
Louisville, KY 40214

Read User Manual Online (PDF format)

Read User Manual Online (PDF format)  >>

Download This Manual (PDF format)

Download this manual  >>

BLUERIDGE User Manuals

Related Manuals