Blueridge BMKH18LM21 Multizone Mini Split Installation Guide

July 3, 2024
BLUERIDGE

BMKH18LM21 Multizone Mini Split

“`html

Product Information

Specifications

  • Product Name: INVERTER ONE-TWO/ONE-THREE/ONE-FOUR/ONE-FIVE
    SPLIT-TYPE AIR CONDITIONER

  • Installation Types: Outdoor unit, Standard wall mount, Ceiling
    Cassette, Low wall air handler, Wall/Ceiling, Concealed duct air
    handler

Product Usage Instructions

Safety Precautions

Read the safety precautions carefully before operating or
installing the air conditioning unit. Failure to follow
instructions may result in serious damage or injury.

Unit Parts And Major Functions

Refer to the Owner’s Manual for detailed information on the
parts and major functions of the air conditioning unit.

Manual Operations And Maintenance

Follow the instructions in the manual for operating and
maintaining the air conditioning unit to ensure optimal
performance.

Troubleshooting

Consult the troubleshooting section in the manual for guidance
in case of any issues with the air conditioning unit.

Installation Instructions

Refer to the Installation Manual for step-by-step guidance on
installing the air conditioning unit based on the specific
installation type.

FAQ

Q: What should I do if the air conditioning unit is not cooling

properly?

A: Check the troubleshooting section in the manual for possible
solutions. Ensure proper maintenance and cleaning of the unit’s
filters and coils.

“`

Multi-zone Installation Manual Table of Contents:
Outdoor unit installation page 2 Standard wall mount installation page 47 Ceiling Cassette installation page 89 Low wall air handler installation 107 Wall/Ceiling (also referred to as floor/ceiling) installation page 134 Concealed duct air handler installation page 150

INVERTER ONE-TWO/ONE-THREE/ONE-FOUR/ONE-FIVE SPLIT-TYPE AIR CONDITIONER
Owner’s Manual & Installation Manual
IMPORTANT NOTE: Read this manual carefully before installing or operating your new air conditioning unit. Make sure to save this manual for future reference. Please check the applicable models, technical data, F-GAS(if any) and manufacturer information from the “Owner’s Manual – Product Fiche ” in the packaging of the outdoor unit. (European Union products only)

Table of Contents
Safety Precautions ………………………………………………………………04
Owner’s Manual
Unit Parts And Major Functions ……………………………………………08
1. Unit Parts ………………………………………………………………………………………………………………………………………………………..08 2. Operating temperature ………………………………………………………………………………………………………………………………..10 3. Features ………………………………………………………………………………………………………………………………………………………….11
Manual Operations And Maintenance……………………………………13 Troubleshooting ………………………………………………………………….14

Installation Manual
Accessories ……………………………………………………………………………17
Installation Summary ……………………………………………………………….18
Installation Diagram…………………………………………………………………19
Specifications………………………………………………………………………….20
Outdoor Unit Installation ………………………………………………………….21
1. Select installation location ………………………………………………………………………………………………………………………………….21 2. Install drain joint …………………………………………………………………………………………………………………………………………………..22 3. Anchor outdoor unit …………………………………………………………………………………………………………………………………………….22
Refrigerant Piping Connection …………………………………………………24
1. Cut pipe ………………………………………………………………………………………………………………………………………………………………….24 2. Remove burrs ………………………………………………………………………………………………………………………………………………………24 3. Flare pipe ends ……………………………………………………………………………………………………………………………………………………..24 4. Connect pipes ……………………………………………………………………………………………………………………………………………………….25
Wiring …………………………………………………………………………………….27
1. Outdoor Uint Wiring ……………………………………………………………………………………………………………………………………………..29 2. Wiring Figure …………………………………………………………………………………………………………………………………………………………30
Air Evacuation ………………………………………………………………………..37
1. Note On Adding Refrigerant ……………………………………………………………………………………………………………………………….38 2. Safety And Leakage Check ………………………………………………………………………………………………………………………………….40
Test Run………………………………………………………………………………….41
Function of Automatic Wiring/Piping Correction………………………..42

Safety InPtPrroreedccuaacuutittoiiononnss

Safety Precautions

Read Safety Precautions Before Operation and Installation
Incorrect installation due to ignoring instructions can cause serious damage or injury. The seriousness of potential damage or injuries is classified as either a WARNING or CAUTION.

WARNING
This symbol indicates the possibility of personnel injury or loss of life.

CAUTION
This symbol indicates the possibility of property damage or serious consequences.

WARNING
This appliance can be used by children aged from 8 years and above and persons with reduced physical, sensory or mental capabilities or lack of experience and knowledge if they have been given supervision or instruction concerning use of the appliance in a safe way and understand the hazards involved. Children shall not play with the appliance. Cleaning and user maintenance shall not be made by children without supervision
This appliance is not intended for use by persons(including children) with reduced physical, sensory or mental capabilities, or lack of experience and knowledge, unless they have been given supervision or instruction concerning use of the appliance by a person responsible for their safety. Children should be supervised to ensure that they do not play with the appliance.

WARNINGS FOR PRODUCT USE
· If an abnormal situation arises (like a burning smell), immediately turn off the unit and disconnect the power. Call your dealer for instructions to avoid electric shock, fire or injury.
· Do not insert fingers, rods or other objects into the air inlet or outlet. This may cause injury, since the fan may be rotating at high speeds.
· Do not use flammable sprays such as hair spray, lacquer or paint near the unit. This may cause fire or combustion.
· Do not operate the air conditioner in places near or around combustible gases. Emitted gas may collect around the unit and cause explosion.
· Do not operate your air conditioner in a wet room such as a bathroom or laundry room. Too much exposure to water can cause electrical components to short circuit.
· Do not expose your body directly to cool air for a prolonged period of time.
· Do not allow children to play with the air conditioner. Children must be supervised around the unit at all times.
· If the air conditioner is used together with burners or other heating devices, thoroughly ventilate
the room to avoid oxygen deficiency. · In certain functional environments, such as kitchens, server rooms, etc., the use of specially
designed air-conditioning units is highly recommended.

CLEANING AND MAINTENANCE WARNINGS
· Turn off the device and disconnect the power before cleaning. Failure to do so can cause electrical shock.
· Do not clean the air conditioner with excessive amounts of water.

Safety Precautions

CLEANING AND MAINTENANCE WARNINGS
· Do not clean the air conditioner with combustible cleaning agents. Combustible cleaning agents can cause fire or deformation.
CAUTION
· Turn off the air conditioner and disconnect the power if you are not going to use it for a long time. · Turn off and unplug the unit during storms. · Make sure that water condensation can drain unhindered from the unit. · Do not operate the air conditioner with wet hands. This may cause electric shock. · Do not use device for any other purpose than its intended use. · Do not climb onto or place objects on top of the outdoor unit. · Do not allow the air conditioner to operate for long periods of time with doors or windows open,
or if the humidity is very high.

ELECTRICAL WARNINGS
· Only use the specified power cord. If the power cord is damaged, it must be replaced by the manufacturer, its service agent or similarly qualified persons in order to avoid a hazard.
· Keep power plug clean. Remove any dust or grime that accumulates on or around the plug. Dirty plugs can cause fire or electric shock.
· Do not pull power cord to unplug unit. Hold the plug firmly and pull it from the outlet. Pulling directly on the cord can damage it, which can lead to fire or electric shock.
· Do not modify the length of the power supply cord or use an extension cord to power the unit. · Do not share the electrical outlet with other appliances. Improper or insufficient power supply
can cause fire or electrical shock. · The product must be properly grounded at the time of installation, or electrical shock may occur. · For all electrical work, follow all local and national wiring standards, regulations, and the
Installation Manual. Connect cables tightly, and clamp them securely to prevent external forces from damaging the terminal. Improper electrical connections can overheat and cause fire, and may also cause shock. All electrical connections must be made according to the Electrical Connection Diagram located on the panels of the indoor and outdoor units. · All wiring must be properly arranged to ensure that the control board cover can close properly. If the control board cover is not closed properly, it can lead to corrosion and cause the connection points on the terminal to heat up, catch fire, or cause electrical shock. · If connecting power to fixed wiring, an all-pole disconnection device which has at least 3mm clearances in all poles, and have a leakage current that may exceed 10mA, the residual current device(RCD) having a rated residual operating current not exceeding 30mA, and disconnection must be incorporated in the fixed wiring in accordance with the wiring rules.
TAKE NOTE OF FUSE SPECIFICATIONS
The air conditioner’s circuit board (PCB) is designed with a fuse to provide overcurrent protection. The specifications of the fuse are printed on the circuit board ,such as : T20A/250VAC(for <24000Btu/h unit), T30A/250VAC(for

24000Btu/h unit) NOTE: For the units with R32 or R290 refrigerant , only the blast-proof ceramic fuse can be used.

WARNINGS FOR PRODUCT INSTALLATION
1. Installation must be performed by an authorized dealer or specialist. Defective installation can cause water leakage, electrical shock, or fire.

Safety Precautions

WARNINGS FOR PRODUCT INSTALLATION
2. Installation must be performed according to the installation instructions. Improper installation can cause water leakage, electrical shock, or fire. In North America,installation must be performed in accordance with the requirement of NEC and CEC by authorized personnel only.)
3. Contact an authorized service technician for repair or maintenance of this unit. This appliance shall be installed in accordance with national wiring regulations.
4. Only use the included accessories, parts, and specified parts for installation. Using non-standard parts can cause water leakage, electrical shock, fire, and can cause the unit to fail.
5. Install the unit in a firm location that can support the unit’s weight. If the chosen location cannot support the unit’s weight, or the installation is not done properly, the unit may drop and cause serious injury and damage.
6. Install drainage piping according to the instructions in this manual. Improper drainage may cause water damage to your home and property.
7. For units that have an auxiliary electric heater, do not install the unit within 1 meter (3 feet) of any combustible materials.
8. Do not install the unit in a location that may be exposed to combustible gas leaks. If combustible gas accumulates around the unit, it may cause fire.
9. Do not turn on the power until all work has been completed. 10. When moving or relocating the air conditioner, consult experienced service technicians for
disconnection and reinstallation of the unit. 11. How to install the appliance to its support, please read the information for details in “indoor unit
installation” and “outdoor unit installation” sections .
Note about Fluorinated Gasses(Not applicable to the unit using R290 Refrigerant)
1. This air-conditioning unit contains fluorinated greenhouse gasses. For specific information on the type of gas and the amount, please refer to the relevant label on the unit itself or the “Owner’s Manual – Product Fiche ” in the packaging of the outdoor unit. (European Union products only).
2. Installation, service, maintenance and repair of this unit must be performed by a certified technician.
3. Product uninstallation and recycling must be performed by a certified technician. 4. For equipment that contains fluorinated greenhouse gases in quantities of 5 tonnes of CO2
equivalent or more, but of less than 50 tonnes of CO2 equivalent, If the system has a leakdetection system installed, it must be checked for leaks at least every 24 months. 5. When the unit is checked for leaks, proper record- keeping of all checks is strongly recommended.
WARNING for Using R32 Refrigerant
When flammable refrigerant are employed, appliance shall be stored in a well -ventilated area where the room size corresponds to the room area as specifiec for operation. For R32 frigerant models: Appliance shall be installed, operated and stored in a room with a floor area larger than X m² . Appliance shall not be installed in an unvertilated space, if that space is smaller than X m² . (Please see the following form).

Safety Precautions

Amount of refrigerant Installation height Minimum room Amount of refrigerant Installation height Minimum room

to be charged (kg)

(m)

area (m²)

to be charged (kg)

(m)

area (m²)

1.0

0.6 /1.8 /2.2

9 /1 /1

1.95

0.6 /1.8 /2.2

33 /4 /2.5

1.05

0.6 /1.8 /2.2

9.5 /1.5 /1

2.0

0.6 /1.8 /2.2

34.5 /4 /3

1.1

0.6 /1.8 /2.2

10.5 /1.5 /1

2.05

0.6 /1.8 /2.2

36 /4 /3

1.15

0.6 /1.8 /2.2

11.5 /1.5 /1

2.1

0.6 /1.8 /2.2

38 /4.5 /3

1.2

0.6 /1.8 /2.2

12.5 /1.5 /1

2.15

0.6 /1.8 /2.2

40 /4.5 /3

1.25

0.6 /1.8 /2.2

13.5 /1.5 /1

2.2

0.6 /1.8 /2.2

41.5 /5 /3.5

1.3

0.6 /1.8 /2.2

14.5 /2 /1.5

2.25

0.6 /1.8 /2.2

43.5 /5 /3.5

1.35

0.6 /1.8 /2.2

16 /2 /1.5

2.3

0.6 /1.8 /2.2

45.5/5 /3.5

1.4

0.6 /1.8 /2.2

17/2 /1.5

2.35

0.6 /1.8 /2.2

47.5/5.5 /4

1.45

0.6 /1.8 /2.2

18 /2 /1.5

2.4

0.6 /1.8 /2.2

49.5 /5.5 /4

1.5

0.6 /1.8 /2.2

19.5 /2.5 /1.5

2.45

0.6 /1.8 /2.2

51.5 /6 /4

1.55

0.6 /1.8 /2.2

21 /2.5 /2

2.5

0.6 /1.8 /2.2

54 /6 /4

1.6

0.6 /1.8 /2.2

22 /2.5 /2

2.55

0.6 /1.8 /2.2

56 /6.5 /4.5

1.65

0.6 /1.8 /2.2

23.5 /3 /2

2.6

0.6 /1.8 /2.2

58 /6.5 /4.5

1.7

0.6 /1.8 /2.2

25 /3 /2

2.65

0.6 /1.8 /2.2

60.5/7 /4.5

1.75

0.6 /1.8 /2.2

26.5 /3 /2

2.7

0.6 /1.8 /2.2

63 /7 /5

1.8

0.6 /1.8 /2.2

28 /3.5 /2.5

2.75

0.6 /1.8 /2.2

65 /7.5 /5

1.85

0.6 /1.8 /2.2

29.5 /3.5 /2.5

2.8

0.6 /1.8 /2.2

67.5 /7.5 /5

1.9

0.6 /1.8 /2.2

31/3.5 /2.5

2.85

0.6 /1.8 /2.2

70 /8 /5.5

Reusable mechanical connectors and flared joints are not allowed indoors. (EN Standard Requirements). Mechanical connectors used indoors shall have a rate of not more than 3g/year at 25% of the maximum allowable pressure. When mechanical connectors are reused indoors, sealing parts shall be renewed. When flared joints are reused indoors, the flare part shall be re-fabricated. (UL Standard Requirements) When mechanical connectors are reused indoors, sealing parts shall be renewed. When flared joints are reused indoors, the flare part shall be re-fabricated. (IEC Standard Requirements) Mechanical connectors used indoors shall comply with ISO 14903.

European Disposal Guidelines
This marking shown on the product or its literature, indicates that waste electrical and eletrical equipment should not be mixed with general household waste.

Co rrect D isp o sal o f Th is Pro d u ct (W ast e Elect rical & Elect ro n ic Eq u ip men t )

This appliance contains refrigerant and other potentially hazardous materials. When disposing of this appliance, the law requires special collection and treatment. Do not dispose of this product as household waste or unsorted municipal waste. When disposing of this appliance, you have the following options:
· Dispose of the appliance at designated municipal electronic waste collection facility. · When buying a new appliance, the retailer will take back the old appliance free of charge. · The manufacturer will take back the old appliance free of charge. · Sell the appliance to certified scrap metal dealers.
Special notice
Disposing of this appliance in the forest or other natural surroundings endangers your health and is bad for the environment. Hazardous substances may leak into the ground water and enter the food chain.

Unit Parts And Major Functions

Unit Parts And Major Functions

Unit Parts (A) Wall-mounted type

(B) Duct / Ceiling type
4

Indoor unit 1. Panel frame 2. Rear air intake grille 3. Front panel 4. Air purifying filter & Air filter(behind) 5. Horizontal louver 6. LCD display window 7. Vertical louver 8. Manual control button(behind) 9. Remote controller holder
Outdoor unit 10. Drain hose, refrigerant connecting pipe 11. Connective cable 12. Stop valve 13. Fan hood

Indoor unit 1. Air outlet 2. Air inlet 3. Air filter 4. Electric control cabinet 5. Wire controller
Outdoor unit 6. Drain hose, refrigerant connecting pipe 7. Connective cable 8. Stop valve 9. Fan hood

Unit Parts And Major Functions

(C) Floor and standing type(console)

(D) Compact four-way cassette type

Indoor unit 1. Air flow louver (at air outlet) 2. Air inlet (containing air filter) 3. Remote controller 4. Installation part 5. Display panel
Outdoor unit 6. Drain hose, refrigerant connecting pipe 7. Connective cable 8. Stop valve 9. Fan hood

Indoor unit 1. Drain pump(drain water from indoor unit) 2. Drain hose 3. Air outlet 4. Air inlet 5. Air-in grill 6. Display panel 7. Remote controller
Outdoor unit 8. refrigerant connecting pipe 9. Connective cable 10. Stop valve 11. Fan hood

Unit Parts And Major Functions

NOTE: For multi-split type air conditioners, one outdoor unit can be matched to different types of indoor units. All of the pictures in this manual are for demonstration purposes only. Your air conditioner may be slightly different, if similar in shape. The following pages introduce several kinds of indoor units that can be matched with the outdoor units.

Operating Conditions

Operating temperature
When your air conditioner is used outside of the following temperature ranges, certain safety protection features may activate and cause the unit to disable.

COOL mode

Room Temperature

17°C – 32°C (62°F – 90°F)

HEAT mode
0°C – 30°C (32°F – 86°F)

DRY mode
10°C – 32°C (50°F – 90°F)

0°C – 50°C (32°F – 122°F)

Outdoor Temperature

-15°C – 50°C (5°F – 122°F)
(For models with low temp. cooling systems.)

-15°C – 24°C (5°F – 75°F)

0°C – 50°C (32°F – 122°F)

FOR OUTDOOR UNITS WITH AUXILIARY ELECTRIC HEATER
When outside temperature is below 0°C (32°F ), we strongly recommend keeping the unit plugged in at all time to ensure smooth ongoing performance.

0°C – 52°C (32°F – 126°F)
(For special tropical models)

0°C – 52°C (32°F – 126°F)
(For special tropical models)

NOTE: Room relative humidity less than 80%. If the air conditioner operates in excess of this figure, the surface of the air conditioner may attract condensation. Please sets the vertical air flow louver to its maximum angle (vertically to the floor), and set HIGH fan mode.
To further optimize the performance of your unit, do the following: · Keep doors and windows closed. · Limit energy usage by using TIMER ON and TIMER OFF functions. · Do not block air inlets or outlets. · Regularly inspect and clean air filters.

Unit Parts And Major Functions

Features

Protection of the air conditioner

White mist emerging from the indoor unit

Compressor protection · The compressor cannot restart for 3 minutes
after it stops.
Anti-cold air (Cooling and heating models
only) · The unit is designed not to blow cold air on
HEAT mode, when the indoor heat exchanger is in one of the following three situations and the set temperature has not been reached.

· A white mist may be generated due to a large temperature difference between air inlet and air outlet on COOL mode in places with high relative humidity.
· A white mist may be generated due to moisture created in the defrosting process when the air conditioner restarts in HEAT mode operation after defrosting.

A) When heating has just started.

Noise coming from the air conditioner

B) During defrosting. C) Low temperature heating. · The indoor or outdoor fan stop running when defrosting (Cooling and heating models only).
Defrosting (Cooling and heating models only) · Frost may be generated on the outdoor unit
during a heat cycle when outdoor temperature is low and humidity is high resulting in lower heating efficiency in the air conditioner. · Under these conditions, the air conditioner will stop heating operations and start defrosting

· ·

You may hear a low hissing sound when the compressor is running or has just stopped running. This sound is the sound of the refrigerant flowing or coming to a stop. You may also hear a low “squeaking” sound when the compressor is running or has just stopped running. This is caused by tempera heat expansion and cold contraction of the plastic parts in the unit when the temperature is changing.

automatically.

· A noise may be heard due to the louver

· The time to defrost may vary from 4 to 10

restoring itself to its original position when

minutes, depending the outdoor temperature

power is first turned on.

and the amount of frost buildup on the outdoor unit.

Dust blowing out from the indoor unit. This is happens when the air conditioner has not

Auto-Restart (some models) In case of power failure, the system will immediately stop. When power returns, the Operation light on the indoor unit will flash. To restart the unit, press the ON/OFF button on the remote control. If the system has an auto restart

been used for a long time or during its first use.
Smell emitting from the indoor unit. This is caused by the indoor unit giving off smells permeated from building materials, furniture,or smoke.

function, the unit will restart using the same

settings.

Unit Parts And Major Functions

The air conditioner turns to FAN ONLY mode from COOL or HEAT (for cooling and heating models only) mode.
When the indoor temperature reaches the set temperature setting, the compressor will stop automatically, and the air conditioner turns to FAN only mode. The compressor will start again when the indoor temperature rises on COOL mode or falls on HEAT mode to the set point.
Droplets of water may form on the surface of the indoor unit when cooling occurs in relatively high humidity (defined as higher than 80%). Adjust the horizontal louver to the maximum air outlet position and select HIGH fan speed.

Heating mode (For cooling and heating
models only)
The air conditioner draws in heat from the outdoor unit and releases it via the indoor unit during heating. When the outdoor temperature falls, heat drawn in by the air conditioner decreases accordingly. At the same time, heat loading of the air conditioner increases due to larger difference between indoor and outdoor temperature. If a comfortable temperature cannot be achieved with the air conditioner alone, it is recommended that you use a supplementary heating device.
Lightning or a car wireless telephone operating nearby may cause the unit to malfunction. Disconnect the unit from its power source and then re-connect the unit with the power source again. Push the ON/OFF button on the remote controller to restart operations.

Energy Saving Tips
· DO NOT set the unit to excessive temperature levels. · While cooling, close the curtains to avoid direct sunlight. · Doors and windows should be kept closed to keep cool or warm air in the room. · DO NOT place objects near the air inlet and outlet of the unit. This will reduce the efficiency of the unit. · Set a timer and use the built-in SLEEP/ECONOMY mode if applicable. · If you don’t plan to use the unit for a long time, remove the batteries from the remote control. · Clean the air filter every two weeks. A dirty filter can reduce cooling or heating efficiency. · Adjust louvers properly and avoid direct airflow.

Closing curtains during heating also helps keep the heat in

Doors and windows should be kept closed

Manual Operations And Maintenance

Manual Operations And Maintenance

Operation mode selection

Optimal operation

While two or more indoor units are simultaneously operating, make sure the modes do not conflict with each other. The heat mode claims precedence over all other modes. If the unit intially started to operate in HEAT mode, the other units can operate in HEAT mode only. For example: If the unit intially started operates under COOL (or FAN) mode, the other units can operate under any mode except HEAT. If one of the unit selects HEAT mode, the other operating units will stop operation and diplay “–” (for units with display window only) or the auto and operation indication light will flash rapidly, the defrost indication light will turn off, and the timer indication light will remain on (for units without a display window). Alternatively, the defrost and alarm indication light (if applicable) wil light up, or the operation indication light will flash rapidly, and the timer indication light will turn off ( for the floor and standing type).

To achieve optimal performance, please note the following:
· Adjust the direction of the air flow so that it is notblowing directly on people.
· Adjust the temperature to achieve the highest possible level of comfort. Do not adjust the unit to excessive temperature levels.
· Close doors and windows in COOL mode or HEAT mode.
· Use the TIMER ON button on the remote controller to select a time you want to start your air conditioner.
· Do not place any object near the air inlet or air outlet, as the efficiency of the air conditioner may be reduced and the air conditioner may stop running.
· Clean the air filter periodically, otherwise cooling or heating per formance may be reduced.
· Do not operate unit with horizontal louvre in closed position.

Maintenance
If you plan to leave the unit idle for a long time, perform the following tasks: 1. Clean the indoor unit and air filter. 2. Select FAN ONLY mode and let the indoor fan
run for a time to dry the inside of the unit. 3. Disconnect the power supply and remove the
battery from the remote control. 4. Check components of the outdoor unit
periodically. Contact a local dealer or a customer service centre if the unit requires servicing.
NOTE: Before you clean the air conditioner, be sure to switch off the unit and disconnect the power supply plug.

Suggestion: For units that feature an electric heater, when the outside ambient temperature is below 0°C (32°F), it is strongly recommended that you to keep the machine plugged in so as to guarantee smooth operation.
When the air conditioner is to be used again:
· Use a dry cloth to wipe off the dust accumulated on the rear air intake grille in order to avoid the dust being dispersed from the indoor unit.
· Check that the wiring is not broken off or disconnected.
· Check that the air filter is installed. · Check if the air outlet or inlet is blocked after
the air conditioner has not been used for a long time.

Troubleshooting

Troubleshooting

SAFETY PRECAUTIONS
If any of the following conditions occurs, turn off your unit immediately! · The power cord is damaged or abnormally warm · You smell a burning odor · The unit emits loud or abnormal sounds · A power fuse blows or the circuit breaker frequently trips · Water or other objects fall into or out of the unit DO NOT ATTEMPT TO FIX THESE YOURSELF! CONTACT AN AUTHORIZED SERVICE PROVIDER IMMEDIATELY!

Common Issues The following problems are not a malfunction and in most situations will not require repairs.

Problem
Unit does not turn on when pressing ON/ OFF button

Possible Causes
The unit has a 3-minute protection feature that prevents the unit from overloading. The unit cannot be restarted within three minutes of being turned off.
Cooling and Heating Models: If the Operation light and PRE-DEF (Pre-heating/ Defrost) indicators are lit up, the outdoor temperature is too cold and the unit’s anti-cold wind is activated in order to defrost the unit.
In Cooling-only Models: If the “Fan Only” indicator is lit up, the outdoor temperature is too cold and the unit’s anti-freeze protection is activated in order to defrost the unit.

The unit changes from COOL mode to FAN mode

The unit changes its setting to prevent frost from forming on the unit. Once the temperature increases, the unit will start operating again.
The set temperature has been reached, at which point the unit turns off the compressor. The unit will resume operating when the temperature fluctuates again.

The indoor unit emits white mist

In humid regions, a large temperature difference between the room’s air and the conditioned air can cause white mist.

Both the indoor and outdoor units emit white mist

When the unit restarts in HEAT mode after defrosting, white mist may be emitted due to moisture generated from the defrosting process.

Troubleshooting

Problem
The indoor unit makes noises

Possible Causes
A squeaking sound is heard when the system is OFF or in COOL mode. The noise is also heard when the drain pump (optional) is in operation.
A squeaking sound may occur after running the unit in HEAT mode due to expansion and contraction of the unit’s plastic parts.

Both the indoor unit and outdoor unit make noises

A low hissing sound may occur during operation. This is normal and is caused by refrigerant gas flowing through both the indoor and outdoor units.
A low hissing sound may be heard when the system starts, has just stopped running or is defrosting. This noise is normal and is caused by the refrigerant gas stopping or changing direction.

The outdoor unit makes noises

The unit will make different sounds based on its current operating mode.

Dust is emitted from The unit may accumulate dust during extended periods of non-use, which

either the indoor or will be emitted when the unit is turned on. This can be mitigated by covering

outdoor unit

the unit during long periods of inactivity.

The unit emits a bad odor

The unit may absorb odors from the environment (such as furniture, cooking, cigarettes, etc.) which will be emitted during operations.
The unit’s filters have become moldy and should be cleaned.

The fan of the outdoor unit does not operate

During operation, the fan speed is controlled to optimize product operation.

Troubleshooting

Troubleshooting Tips

When troubles occur, please check the following points before contacting a repair company.

Problem The unit is not working
Poor cooling performance
The unit starts and stops frequently
Poor heating performance

Possible Causes Power failure The power switch is off The fuse is burned out
Remote control batteries are dead The unit’s 3-minute protection has been activated Temperature setting may be higher than the ambient room temperature The heat exchanger on the indoor or outdoor unit is dirty
The air filter is dirty
The air inlet or outlet of either unit is blocked
Doors and windows are open
Excessive heat is generated by sunlight Low refrigerant due to leak or long- term use
There’s too much or too little refrigerant in the system There is air, incompressible gas or foreign material in the refrigeration system.
System circuit is blocked
The compressor is broken The voltage is too high or too low
The outdoor temperature is lower than 7°C (44.5°F) Cold air is entering through doors and windows Low refrigerant due to leak or long-term use

Solution Wait for the power to be restored Turn on the power Replace the fuse
Replace the remote control batteries
Wait three minutes after restarting the unit
Lower the temperature setting
Clean the affected heat exchanger
Remove the filter and clean it according to instructions Turn the unit off, remove the obstruction and turn it back on Make sure that all doors and windows are closed while operating the unit Close windows and curtains during periods of high heat or bright sunshine Check for leaks, re-seal if necessary and top off refrigerant Check for leaks and recharge the system with refrigerant Evacuate and recharge the system with refrigerant
Determine which circuit is blocked and replace the malfunctioning piece of equipment Replace the compressor Install a manostat to regulate the voltage
Check for leaks and recharge the system with refrigerant Make sure that all doors and windows are closed during use Check for leaks, re-seal if necessary and top off refrigerant

Accessories

Accessories

The air conditioning system comes with the following accessories. Use all of the installation parts and accessories to install the air conditioner. Improper installation may result in water leakage, electrical shock and fire, or cause the equipment to fail. The items are not included with the air conditioner must be purchased separately.

Name of Accessories Q`ty(pc)

Manual

2~4

Installation plate

(some models)

1

Plastic expansion

5-8 (depending

sheath (some models) on models)

5-8

Self-Tapping Screw A (depending

(some models)

on models)

Transfer connector (packed with the indoor or outdoor unit, depending on models) NOTE: Pipe size may

Optional part (one piece/ one indoor unit)

differ from appliance Optional to appliance. To meet part

different pipe size (1-5 pieces

requirements,

for outdoor

sometimes the pipe unit,

connections need a depending

transfer connector on models)

installed on the

outdoor unit .

Shape

Name of Accessories
Drain joint (some models)

Q`ty(pc) 1

Seal ring (some models)

1

Magnetic ring (Hitch it on the connective cable between indoor unit and outdoor unit after installation.) (some models)

Varies by model

Cord protection rubber

ring(If the cord clamp

cannot fasten on a

small cord, use the

cord protection rubber

ring [supplied with

accessories] to wrap

1

around the cord. Then

fix it in place with the

cord clamp.)

(some models)

Shape

Optional accessories
· There are two types of remote controls: wired and wireless. Select a remote controller based on customer preferences and requirements and install in an appropriate place. Refer to catalogues and technical literature for guidance on selecting a suitable remote controller.

Name
Connecting pipe assembly

Shape
Liquid side Gas side

6.35( 1/4i n) 9.52( 3/8in) 9.52( 3/8in) 12.7( 1/2in) 16( 5/8in)

Quantity(PC)
Parts you must purc hase separately. Consult the dealer about the proper pipe size of the unit you purchased.

Installation Summary

INSTALLATION ORDER

1

2

3 L(L1) N (L2)

Install the outdoor unit

Connect the refrigerant pipes

Connect the wires

5

4

MC

MC

Perform a test run

Evacuate the refrigeration system

Installation Summary

Installation Diagram

Installation Diagram

4

3

Remote controller holder
5

Safety Precautions
CAUTION
· To prevent wall damage, use a stud finder to locate studs.
· A minimum pipe run of 3 metres is required to minimise vibration & excessive noise.
· Two of the A, B, and C air circulation pathways must be free from obstructions at all times.
· This illustration is for demonstration purposes only.
· The actual shape of your air condtioner may be slightly different.
· Copper lines must be independently insulated.
NOTE: The installation must be performed in accordance with the requirement of local and national standards. The installation may be slightly different in different areas.

2 Air-break Switch

Mounting screw ST3.9×25-C-H

1
Installation plate Clip anchor
Air-break Switch

2 5 4 3

1
Drainage Pipe

Mounting screw ST3.9×25-C-H

Outdoor Unit Power Cable

More than

The maximum amount of the connection cables is 5. This section is for reference only.

(1)

Installation plate
Clip anchor

Refrigerant pipe
Remote controller holder
More than
(2)

Installation Diagram

Outdoor Unit

Specifications

Number of units that can be used together Compressor stop/start frequency
Power source voltage

Connected units
Stop time voltage fluctuation voltage drop during start interval unbalance

1-5 units
3 min or more within ±10% of rated voltage within ±15% of rated voltage within ±3% of rated voltage

Max. length for all rooms Max. length for one indoor unit Max. height different between indoor and outdoor unit Max. height different between indoor units

1 drive 2 40131 25/82 15/49 10/33

1 drive 3 60/197 30/98 15/49 10/33

Unit: m/ft. 1 drive 4 1 drive 5 80/262 80/262 35/115 35/115 15/49 15/49 10/33 10/33

NOTE: For the units adopt quick connectors, no more than two pipes can be connected, and the Max. length for each pipe is 7.5 meters.

When installing multiple indoor units with a single outdoor unit, ensure that the length of the refrigerant pipe and the drop height between the indoor and outdoor units meet the requirements illustrated in the following diagram:

Outdoor unit

Indoor unit Max.Height difference

Indoor unit 15m(49ft)

Specifications

10m(32.8ft) 15m(49ft) Indoor unit

Outdoor Unit Installation

Install the unit by following local codes and regulations , there may be differ slightly between different regions.

60cm (24in) above

30ocmn le(1ft2in) 200cmin (f7ro9nint)

3fr0ocmmb(1a2ciknw) all 60ocnmrig(2h4tin)

Installation Instructions ­ Outdoor unit
Step 1: Select installation location Before installing the outdoor unit, you must choose an appropriate location. The following are standards that will help you choose an appropriate location for the unit.
Proper installation locations meet the following standards:
Meets all spatial requirements shown in Installation Space Requirements above.
Good air circulation and ventilation
Firm and solid–the location can support the unit and will not vibrate
Noise from the unit will not disturb others
Protected from prolonged periods of direct sunlight or rain
Where snowfall is anticipated, take appropriate measures to prevent ice buildup and coil damage.

DO NOT install unit in the following locations: Near an obstacle that will block air inlets and outlets Near a public street, crowded areas, or where noise from the unit will disturb others Near animals or plants that will be harmed by hot air discharge Near any source of combustible gas In a location that is exposed to large amounts of dust In a location exposed to a excessive amounts of salty air
SPECIAL CONSIDERATIONS FOR EXTREME WEATHER
If the unit is exposed to heavy wind: Install unit so that air outlet fan is at a 90° angle to the direction of the wind. If needed, build a barrier in front of the unit to protect it from extremely heavy winds. See Figures below.

Strong wind

Strong wind

Wind Baffle

Strong wind
If the unit is frequently exposed to heavy rain or snow: Build a shelter above the unit to protect it from the rain or snow. Be careful not to obstruct air flow around the unit. If the unit is frequently exposed to salty air (seaside): Use outdoor unit that is specially designed to resist corrosion.

Outdoor Unit Installation

Step 2: Install drain joint (Heat pump unit only)
Before bolting the outdoor unit in place, you must install the drain joint at the bottom of the unit. Note that there are two different types of drain joints depending on the type of outdoor unit.
If the drain joint comes with a rubber seal (see Fig. A ), do the following:
1. Fit the rubber seal on the end of the drain joint that will connect to the outdoor unit.
2. Insert the drain joint into the hole in the base pan of the unit.
3. Rotate the drain joint 90° until it clicks in place facing the front of the unit.
4. Connect a drain hose extension (not included) to the drain joint to redirect water from the unit during heating mode.
If the drain joint doesn’t come with a rubber seal (see Fig. B ), do the following: 1. Insert the drain joint into the hole in the base
pan of the unit. The drain joint will click in place. 2. Connect a drain hose extension (not included) to the drain joint to redirect water from the unit during heating mode.

Step 3: Anchor outdoor unit The outdoor unit can be anchored to the ground or to a wall-mounted bracket with bolt(M10). Prepare the installation base of the unit according to the dimensions below.
UNIT MOUNTING DIMENSIONS The following is a list of different outdoor unit sizes and the distance between their mounting feet. Prepare the installation base of the unit according to the dimensions below. Outdoor Unit Types and Specifications
Split Type Outdoor Unit
H
W W

Outdoor Unit Installation

Base pan hole of outdoor unit Seal
Seal

Drain joint

(A)

(B)

D

IN COLD CLIMATES In cold climates, make sure that the drain hose is as vertical as possible to ensure swift water drainage. If water drains too slowly, it can freeze in the hose and flood the unit.

H
A B

Outdoor Unit Dimensions W x H x D
760x590x285 (29.9×23.2×11.2) 810x558x310 (31.9x22x12.2) 845x700x320 (33.27×27.5×12.6) 900x860x315 (35.4×33.85×12.4) 945x810x395 (37.2×31.9×15.55) 990x965x345 (38.98x38x13.58) 938x1369x392 (36.93×53.9×15.43) 900x1170x350 (35.4x46x13.8) 800x554x333 (31.5×21.8×13.1) 845x702x363 (33.27×27.6×14.3) 946x810x420 (37.2×31.9×16.53) 946x810x410 (37.2×31.9×16.14) 952x1333x410 (37.5×52.5×16.14) 952x1333x415 (37.5×52.5×16.14) 890x673x342 (35.0″x 26.5″x 13.5″)

(unit: mm/inch)

Mounting Dimensions

Distance A Distance B

530 (20.85) 290 (11.4)

549 (21.6) 325 (12.8)

560 (22)

335 (13.2)

590 (23.2) 333 (13.1)

640 (25.2) 624 (24.58)

405 (15.95) 366 (14.4)

634 (24.96) 404 (15.9)

590 (23.2) 514 (20.24) 540 (21.26) 673 (26.5) 673 (26.5) 634 (24.96) 634 (24.96) 663 (26.1″)

378 (14.88) 340 (13.39) 350 (13.8) 403 (15.87) 403 (15.87) 404 (15.9) 404 (15.9) 354 (13.9″)

Rows of series installation
The relations between H, A and L are as follows.

L

A

L 1/2H 25 cm / 9.8″ or more L H
1/2H < L H 30 cm / 11.8″ or more

L H

Can not be installed

Notes On Drilling Hole In Wall
You must drill a hole in the wall for the refrigerant piping, and the signal cable that will connect the indoor and outdoor units.
1. Determine the location of the wall hole based on the location of the outdoor unit.
2. Using a 65-mm (2.5″) core drill, drill a hole in the wall.
NOTE: When drilling the wall hole, make sure to avoid wires, plumbing, and other sensitive components.
3. Place the protective wall cuff in the hole. This protects the edges of the hole and helps seal it when you finish the installation process.

When Select a 24K Indoor Unit

The 24K indoor unit can only be connected with an A system. If there are two 24K indoor units, they can be connected with A and B systems.

Connective pipe size of an A and B system

Indoor Unit capacity (Btu/h) 7K/9K/12K 12K/18K 24K

(unit: inch)

Liquid Gas

1/4

3/8

1/4

1/2

3/8

5/8

o2r5mcomre/ 9.8″

o2r5mcmore/ 9.8″

H

L A

300 cm / 118″ or more

150 ocrmm/o5r9e”

60

cm or

m/ 2o3r.e6″

Outdoor Unit Installation

Refrigerant Piping Connection

NOTE: For quick-connect models, please refer to the internal machine manual for the installation method of the connecting pipe. The external machine manual does not repeat the instructions.
When connecting refrigerant piping, do not let substances or gases other than the specified refrigerant enter the unit. The presence of other gases or substances will lower the unit’s capacity, and can cause abnormally high pressure in the refrigeration cycle. This can cause explosion and injury.
Connection Instructions ­ Refrigerant Piping
CAUTION
· The branching pipe must be installed horizontally. An angle of more than 10° may cause malfunction.
· DO NOT install the connecting pipe until both indoor and outdoor units have been installed.
· Insulate both the gas and liquid piping to prevent water leakage.
Step 1: Cut pipes
When preparing refrigerant pipes, take extra care to cut and flare them properly. This will ensure efficient operation and minimize the need for future maintenance. 1. Measure the distance between the indoor 2. and outdoor units.
Using a pipe cutter, cut the pipe a little longer than the measured distance.
3. Make sure that the pipe is cut at a perfect 90° angle.

DO NOT DEFORM PIPE WHILE CUTTING
Be extra careful not to damage, dent, or deform the pipe while cutting. This will drastically reduce the heating efficiency of the unit.
Step 2: Remove burrs. Burrs can affect the air-tight seal of refrigerant piping connection. They must be completely removed. 1. Hold the pipe at a downward angle to
prevent burrs from falling into the pipe. 2. Using a reamer or deburring tool, remove
all burrs from the cut section of the pipe.
Pipe Reamer
Point down
Step 3: Flare pipe ends Proper flaring is essential to achieve an airtight seal. 1. After removing burrs from cut pipe, seal
the ends with PVC tape to prevent foreign materials from entering the pipe. 2. Sheath the pipe with insulating material. 3. Place flare nuts on both ends of pipe. Make sure they are facing in the right direction, because you can’t put them on or change their direction after flaring.
Flare nut

90°

Oblique Rough Warped

Copper pipe

Refrigerant Piping Connection

4. Remove PVC tape from ends of pipe when ready to perform flaring work.
5. Clamp flare form on the end of the pipe. The end of the pipe must extend beyond the flare form.
Flare form

Pipe

6. Place flaring tool onto the form.
7. Turn the handle of the flaring tool clockwise until the pipe is fully flared. Flare the pipe in accordance with the dimensions .

PIPING EXTENSION BEYOND FLARE FORM

Pipe gauge
Ø 6.4 Ø 9.5 Ø 12.7 Ø 15.9 Ø 19.1 Ø 22

Tightening torque
18-20 N.m (183-204 kgf.cm)
25-26 N.m (255-265 kgf.cm)
35-36 N.m (357-367 kgf.cm)
45-47 N.m (459-480 kgf.cm)
65-67 N.m (663-683 kgf.cm)
75-85N.m (765-867 kgf.cm)

Flare dimension (A) (Unit: mm/Inch)

Min.

Max .

8.4/0.33 8.7/0.34

13.2/0.52 13.5/0.53

16.2/0.64 16.5/0.65

19.2/0.76 19.7/0.78

23.2/0.91 23.7/0.93

26.4/1.04 26.9/1.06

Flare shape
90 °± 4 45 °±2
A R0.4~0.8

8. Remove the flaring tool and flare form, then inspect the end of the pipe for cracks and even flaring.

Step 4: Connect pipes
Connect the copper pipes to the indoor unit first, then connect it to the outdoor unit. You should first connect the low-pressure pipe, then the high- pressure pipe.

Indoor unit tubing

Flare nut

Pipe

3. Tighten the flare nut as tightly as possible by hand.
4. Using a spanner, grip the nut on the unit tubing.
5. While firmly gripping the nut, use a torque wrench to tighten the flare nut according to the torque values in above table.
NOTE: Use both a spanner and a torque wrench when connecting or disconnecting pipes to/from the unit.

CAUTION
· Ensure to wrap insulation around the piping. Direct contact with the bare piping may result in burns or frostbite.
· Make sure the pipe is properly connected. Over tightening may damage the bell mouth and under tightening may lead to leakage.

1. When connecting the flare nuts, apply a thin coat of refrigeration oil to the flared ends of the pipes.
2. Align the center of the two pipes that you will connect.

Refrigerant Piping Connection

NOTE ON MINIMUM BEND RADIUS Carefully bend the tubing in the middle according to the diagram below. DO NOT bend the tubing more than 90° or more than 3 times.
Bend the pipe with thumb
min-radius 10cm (3.9″)
6. After connecting the copper pipes to the indoor unit, wrap the power cable, signal cable and the piping together with binding tape.
NOTE: DO NOT intertwine signal cable with other wires. While bundling these items together, do not intertwine or cross the signal cable with any other wiring.

7. Thread this pipeline through the wall and connect it to the outdoor unit.
8. Insulate all the piping, including the valves of the outdoor unit.
9. Open the stop valves of the outdoor unit to start the flow of the refrigerant between the indoor and outdoor unit.
CAUTION
Check to make sure there is no refrigerant leak after completing the installation work. If there is a refrigerant leak, ventilate the area immediately and evacuate the system (refer to the Air Evacuation section of this manual).

Refrigerant Piping Connection

Wiring

BEFORE PERFORMING ANY
ELECTRICAL WORK, READ
THESE REGULATIONS
1. All wiring must comply with local and national electrical codes, regulations and must be installed by a licensed electrician.
2. All electrical connections must be made according to the Electrical Connection Diagram located on the panels of the indoor and outdoor units.
3. If there is a serious safety issue with the power supply, stop work immediately. Explain your reasoning to the client, and refuse to install the unit until the safety issue is properly resolved.
4. Power voltage should be within 90-110% of rated voltage. Insufficient power supply can cause malfunction, electrical shock, or fire.
5. If connecting power to fixed wiring, a surgeprotector and main power switch should be installed.
6. If connecting power to fixed wiring, a switch or circuit breaker that disconnects all poles and has a contact separation of at least 1/8in (3mm) must be incorporated in the fixed wiring. The qualified technician must use an approved circuit breaker or switch.
7. Only connect the unit to an individual branch circuit outlet. Do not connect another appliance to that outlet.
8. Make sure to properly ground the air conditioner. 9. Every wire must be firmly connected. Loose
wiring can cause the terminal to overheat, resulting in product malfunction and possible fire. 10.Do not let wires touch or rest against refrigerant tubing, the compressor, or any moving parts within the unit. 11.If the unit has an auxiliary electric heater, it must be installed at least 1 meter (40in) away from any combustible materials. 12.To avoid getting an electric shock, never touch the electrical components soon after the power supply has been turned off. After turning off the power, always wait 10 minutes or more before you touch the electrical components.

13. Make sure that you do not cross your
electrical wiring with your signal wiring. This may cause distortion and interference.
14. The unit must be connected to the
main outlet. Normally, the power supply must have a impedance of 32 ohms.
15. No other equipment should be
connected to the same power circuit.
16. Connect the outdoor wires before
connecting the indoor wires.

WARNING
BEFORE PERFORMING ANY ELECTRICAL OR WIRING WORK, TURN OFF THE MAIN POWER TO THE SYSTEM.

NOTE ON AIR SWITCH
When the maximum current of the air conditioner is more than 16A, an air switch or leakage protection switch with protective device shall be used (purchased seperately) . When the maximum current of the air conditioner is less than 16A, the power cord of air conditioner shall be equipped with plug (purchased seperately).
The North American market is wired
according to NEC and CEC requirements.

Air switch

(A)

(purchased seperately)

Outdoor unit power wires Indoor & Outdoor connective wires
(purchased seperately)

Outdoor unit

Indoor unit

Wiring

(B) Indoor unit power wires

Air switch (purchased seperately)

1. Prepare the cable for connection
a. You must first choose the right cable size. Be sure to use H07RN-F cables.

Outdoor unit
Indoor & Outdoor connective wires (purchased seperately) (C) Air switch (purchased seperately) Indoor unit power wires
Outdoor unit power wires

Indoor unit
Air switch (purchased seperately)

Outdoor unit

Indoor unit

Indoor & Outdoor connective wires (purchased seperately) (D) (Only for the North American)
Air switch (purchased seperately)
Outdoor unit power wires
Outdoor unit Air switch
(purchased seperately)

Indoor & Outdoor connective wires (purchased seperately)
Indoor unit

NOTE: The cographs are for explanation purpose only. Your machine may be slightly different. The actual shape shall prevail.
Outdoor Unit Wiring

NOTE: In North America, choose the cable type according to the local electrical codes and regulations.

Minimum Cross-Sectional Area of Power and Signal Cables (For reference)

Rated Current of Appliance (A)

3 and 6 > 6 and 10 > 10 and 16 > 16 and 25 > 25 and 32 > 32 and 40

Nominal Cross-Sectional Area (mm²)
0.75 1 1.5 2.5 4 6

CHOOSE THE RIGHT CABLE SIZE
The size of the power supply cable, signal cable, fuse, and switch needed is determined by the maximum current of the unit. The maximum current is indicated on the nameplate located on the side panel of the unit. Refer to this nameplate to choose the right cable, fuse, or switch. NOTE: In North America, please choose the right cable size according to the Minimum Circuit Ampacity indicated on the nameplate of the unit.
b. Using wire strippers, strip the rubber jacketfrom both ends of the signal cable to reveal approximately 15cm (5.9″) of wire.
c. Strip the insulation from the ends.
d. Using a wire crimper, crimp u-lugs on the ends.
NOTE: When connecting the wires, strictly follow the wiring diagram found inside the electrical box cover.

WARNING
Before performing any electrical or wiring work, turn off the main power to the system.

Wiring

2. Remove the electric cover of the outdoor unit. If there is no cover on the outdoor unit, take off the bolts from the maintenance board and remove the protection board.
Cover
Screw
3. Connect the u-lugs to the terminals Match the wire colors/labels with the labels on the terminal block, and firmly screw the u-lug of each wire to its corresponding terminal.
4. Clamp down the cable with designated cable clamp. 5. Insulate unused wires with electrical tape. Keep them away from any electrical or metal parts. 6. Reinstall the cover of the electric control box.
Harmonic declaration “The equipment M4OB-36HFN8-Q complies with IEC 61000-3-12 provided that the shortcircuit power Ssc is greater than or equal to 4787737.5 at the interface point between the user’s supply and the public system. It is the responsibility of the installer or user of the equipment to ensure, by consultation with the distribution network operator if necessary, that the equipment is con-nected only to a supply with a short-circuit power Ssc greater than or equal to 4787737.5.” “The equipment M5OD-42HFN8-Q complies with IEC 61000-3-12 provided that the shortcircuit power Ssc is greater than or equal to 3190042.5 at the interface point between the user’s supply and the public system. It is the responsibility of the installer or user of the equipment to ensure, by consultation with the distribution network operator if necessary, that the equipment is con-nected only to a supply with a short- circuit power Ssc greater than or equal to 3190042.5.”
Wiring Figure
CAUTION
Connect the connective cables to the terminals, as identified, with their matching numbers on the terminal block of the indoor and outdoor units. For example, Terminal L1(A) of the outdoor unit must connect with terminal L1/1 on the indoor unit. The outdoor unit can match different types of indoor unit, the numbers on the terminal block of the indoor unit may be slightly different. Please pay special attention while connecting the wire.

Wiring
OPTIONAL

or

or

NOTE: For quick-connector models, please refer to <<Owner’s Manual & Installation Manual >> packed with the indoor unit.
NOTE:Refer to the following figures if end-users wish to perform their own wiring. Run the main power cord through the lower line-outlet of the cord clamp. —- This symbol indicates field wiring.
One-two models:

OPTIONAL OPTIONAL
OPTIONAL OPTIONAL OPTIONAL
OPTIONAL OPTIONAL OPTIONAL
OPTIONAL OPTIONAL OPTIONAL
OPTIONAL

OPTIONAL
OPTIONAL
OPTIONAL OPTIONAL
OPTIONAL
OPTIONAL OPTIONAL OPTIONAL
OPTIONAL OPTIONAL OPTIONAL
OPTIONAL

Model A

Model B

Model C

Model D

W L N L(1)

L(A) N(A) S(A) L(B) N(B) S(B)

W L N L(1)

L(A) N(A) S(A) L(B) N(B) S(B)

Model E

Model F

108&3 SUPPLY
🙁
Model G

108&3 SUPPLY
🙁
Model H

NOTE:Use the magnetic ring ( not supplied, optional part) to hitch the connective cable of indoorand outdoor units after installation.One magnetic ring is used for one cable

LN

– ”
/ ”
4 ”

– #
/ #
4 #

S(2) S(A) N(A) L(A) N S(1) S(B) N(B) L(B) L

S(2) S(A) N(A) L(A) N S(1) S(B) N(B) L(B) L

S(2) S(A) N(A) L(A) N S(1) S(B) N(B) L(B) L

108&3
SUPPLY

TO A 🙁

TO B 🙁

Model I

POWER SUPPLY

or 1(L) 2(N) 3(S)

or 1(L) 2(N) 3(S)

TO B

TO A

Model J

TO B

POWER SUPPLY

TO A

Model K

W TO B

POWER W

SUPPL Y

TO A

Model L

OPTIONAL OPTIONAL OPTIONAL OPTIONAL OPTIONAL OPTIONAL OPTIONAL OPTIONAL OPTIONAL OPTIONAL OPTIONAL
OPTIONAL
Wiring

OPTIONAL OPTIONAL
OPTIONAL OPTIONAL
OPTIONAL OPTIONAL
OPTIONAL
OPTIONAL OPTIONAL

W L N L(1)

L(A) N(A) S(A) L(B) N(B) S(B)

W L N L(1)

L(A) N(A) S(A) L(B) N(B) S(B)

108&3 SUPPLY

TO A

Model M

108&3 SUPPLY

TO A

Model N

Model O

OPTIONAL OPTIONAL
OPTIONAL OPTIONAL OPTIONAL
OPTIONAL OPTIONAL OPTIONAL
OPTIONAL

OPTIONAL
OPTIONAL
OPTIONAL
OPTIONAL
OPTIONAL
OPTIONAL

Model P

Model Q

Model R

L1 L2

1(A) 2(A) 3(A) 1(B) 2(B) 3(B)

L1 L2

L1(A)L2(A)S(A) L1(B) L2(B)S(B)

POWER SUPPLY

1 2 3
TO A

1 2 3

Model S

POWER SUPPLY

1 2 3
TO A

1 2 3

Model T

L N

– ”
/ ”
4 ”

– #
/ #
4 #

L N

– ”
/ ”
4 ”
– #
/ #
4 #

OPTIONAL OPTIONAL

OPTIONAL
OPTIONAL
OPTIONAL

or or

To indoor unit A

To indoor unit B

Model U

POWER SUPPLY

or

or

or

or

To indoor To indoor

unit A

unit B

Model V

POWER SUPPLY

or

or

or

or

To indoor To indoor

unit A

unit B

Model W

OPTIONAL
OPTIONAL OPTIONAL
OPTIONAL

Wiring

One-three models:

OPTIONAL OPTIONAL OPTIONAL
OPTIONAL OPTIONAL OPTIONAL OPTIONAL
OPTIONAL
OPTIONAL OPTIONAL OPTIONAL
OPTIONAL

Model A

Model B

Model C

OPTIONAL OPTIONAL OPTIONAL
OPTIONAL
OPTIONAL OPTIONAL OPTIONAL
OPTIONAL
OPTIONAL OPTIONAL OPTIONAL
OPTIONAL

Model D

– ”
/ ”
4 ”

– #
/ #
4 #

– $
/ $
4 $

LN

Model E Model H

Model F Model I

OPTIONAL OPTIONAL OPTIONAL
OPTIONAL
OPTIONAL OPTIONAL OPTIONAL
OPTIONAL
OPTIONAL OPTIONAL OPTIONAL
OPTIONAL

108&3 SUPPLY

TO A 🙁

TO B 🙁

TO C 🙁

Model G

– $
/ $
4 $

1(L) or 2(N) 3(S)

or

or

OPTIONAL OPTIONAL OPTIONAL

1(L) 2(N) 3(S)

1(L) 2(N) 3(S)

or

or

or

OPTIONAL

Wiring

To indoor To indoor

unit A

unit B

To indoor unit C

Model J

One-four models:

OPTIONAL OPTIONAL OPTIONAL OPTIONAL
OPTIONAL
OPTIONAL OPTIONAL OPTIONAL OPTIONAL
OPTIONAL

OPTIONAL OPTIONAL OPTIONAL OPTIONAL
OPTIONAL
OPTIONAL OPTIONAL OPTIONAL OPTIONAL
OPTIONAL

OPTIONAL OPTIONAL
OPTIONAL OPTIONAL
OPTIONAL OPTIONAL
OPTIONAL OPTIONAL OPTIONAL
OPTIONAL

Model A

Model B

or

1(L) 2(N) 3(S)

or

1(L) 2(N) 3(S)

1(L) 2(N) 3(S)

1(L) 2(N) 3(S)

Model C

Model D

LN

– ”
/ ”
4 ”

– #
/ #
4 #

– $
/ $
4 $

– %
/ %
4 %

Model E



$
$
$
%
%
%

L1 L2

108&3 SUPPLY

TO A 🙁

TO B 🙁

Model F

L1 L2

– ”
– ”
4 ”
– #
– #
4 #

TO A 🙁

TO B 🙁

– $
– $
4 $
– %
– %
4 %

50″ 50#

50$ 50%

POWER SUPPLY

Model G

POWER SUPPLY

50″ 50#

50$ 50%

Model H

Wiring
OPTIONAL OPTIONAL OPTIONAL
OPTIONAL OPTIONAL
OPTIONAL OPTIONAL OPTIONAL OPTIONAL
OPTIONAL

OPTIONAL
OPTIONAL OPTIONAL
OPTIONAL OPTIONAL
OPTIONAL
OPTIONAL
OPTIONAL OPTIONAL
OPTIONAL

OPTIONAL
OPTIONAL OPTIONAL OPTIONAL
OPTIONAL
OPTIONAL OPTIONAL OPTIONAL OPTIONAL
OPTIONAL



$
$
$
%
%
%

L1 L2

L1 L2

– ”
– ”
4 ”
– #
– #
4 #

– $
– $
4 $
– %
– %
4 %

50″ 50#

50$ 50%

POWER SUPPLY

Model I

POWER SUPPLY

50″ 50#

50$ 50%

Model J

Mode K
L(C) N(C) S(C) L(D) N(D) S(D)

Model L

or or
To indoor unit A

or or

To indoor unit B

To indoor unit C

To indoor unit D

Model M

OPTIONAL
OPTIONAL OPTIONAL OPTIONAL
OPTIONAL

Wiring

One-five models:

OPTIONAL OPTIONAL OPTIONAL OPTIONAL OPTIONAL OPTIONAL
OPTIONAL OPTIONAL OPTIONAL
OPTIONAL OPTIONAL OPTIONAL

1(L) or 2(N) 3(S)

1(L) 2(N) 3(S)

1(L) or 2(N) 3(S)

1(L) 2(N) 3(S)

1(L) 2(N) 3(S)

Model B

Model A

OPTIONAL OPTIONAL OPTIONAL
OPTIONAL OPTIONAL
OPTIONAL
OPTIONAL OPTIONAL OPTIONAL
OPTIONAL OPTIONAL
OPTIONAL

Model C

Model D



$
$
$
%
%
%
&
&
&

– ”
/ ”
4 ”
– #
/ #
4 #

– $
/ $
4 $
– %
/ %
4 %
– &
/ &
4 &

L1 L2

LN

OPTIONAL
OPTIONAL
OPTIONAL
OPTIONAL OPTIONAL
OPTIONAL OPTIONAL
OPTIONAL
OPTIONAL
OPTIONAL OPTIONAL
OPTIONAL

50″ 50#

50$ 50% 50&

50″ 50#

50$ 50% 50&

POWER SUPPLY

Model E

Model F

POWER SUPPLY

Wiring
OPTIONAL OPTIONAL OPTIONAL
OPTIONAL OPTIONAL
OPTIONAL
OPTIONAL OPTIONAL OPTIONAL
OPTIONAL OPTIONAL
OPTIONAL

Model G

Model H



$
$
$
%
%
%
&
&
&

L1 L2

– ”
– ”
4 ”
– #
– #
4 #

– $
– $
4 $
– %
– %
4 %
– &
– &
4 &

L1 L2

OPTIONAL
OPTIONAL
OPTIONAL
OPTIONAL OPTIONAL
OPTIONAL OPTIONAL
OPTIONAL
OPTIONAL
OPTIONAL OPTIONAL
OPTIONAL

50″ 50#

50$ 50% 50&

POWER SUPPLY

– ”
– ”
4 ”
– #
– #
4 #

Model I
– $
– $
4 $
– %
– %
4 %
– &
– &
4 &

L1 L2

50″ 50#

50$ 50% 50&

POWER SUPPLY

Model J

OPTIONAL
OPTIONAL
OPTIONAL
OPTIONAL OPTIONAL
OPTIONAL

50″ 50#

50$ 50% 50&

POWER SUPPLY

Model K

CAUTION
After confirmation of the above conditions, follow these guidelines when performing wiring: · Always have an individual power circuit specifically for the air conditioner. Always follow
the circuit diagram posted on the inside of the control cover. · Screws fastening the wiring in the casing of electrical fittings may come loose during
transporation. Because loose screws may cause wire burn-ou, check that the screws are tightly fastened. · Check the specifications for the power source. · Confirm that electrical capacity is sufficient. · Confirm that starting voltage is maintained at more than 90 percent of the rated voltage marked on the name plate. · Confirm that the cable thickness is as specified in the power source specifications. · Always install an earth leakage circuit breaker in wet or moist areas. · The following can be caused by a drop in voltage: vibration of a magnetic switch, damaging the contact point, broken fuses, and disturbance of normal functioning. · Disconnection from a power supply must be incorporated into the fixed wiring. It must have an air gap contact separation of at least 3mm in each active (phase) conductors. · Before accessing terminals, all supply circuits must be disconnected.
NOTE: To satisfy the EMC compulsory regulations, which is required by the international standard CISPR 14-1:2005/A2:2011 in specific countries or districts ,please make sure you apply the correct magnetic rings on your equipment according to the wiring diagram that adhere to the your equipment . Please contact your distributor or installer to get further information and purchase magnetic rings (The supplier of magnetic ring is TDKcmodel ZCAT3035-1330or similar) .

Wiring

Air Evacuation

Preparations and Precautions
Air and foreign matter in the refrigerant circuit can cause abnormal rises in pressure, which can damage the air conditioner, reduce its efficiency, and cause injury. Use a vacuum pump and manifold gauge to evacuate the refrigerant circuit, removing any non-condensable gas and moisture from the system.
Evacuation should be performed upon initial installation and when unit is relocated.

NOTE: If there is no change in system pressure, unscrew the cap from the packed valve (high pressure valve). If there is a change in system pressure, there may be a gas leak.
8. Insert hexagonal wrench into the packed valve (high pressure valve) and open the valve by turning the wrench 1/4 counterclockwise. Listen for gas to exit the system, then close the valve after 5 seconds.

BEFORE PERFORMING EVACUATION Check to make sure the connective pipes
between the indoor and outdoor units are connected properly . Check to make sure all wiring is connected
Evacuation Instructions Before using a manifold gauge and a vacuum pump, read their operation manuals to make sure you know how to use them properly.
Manifold Gauge Compound gauge Pressure gauge
-76cmHg

Flare nut
Cap Valve body
Valve stem
9. Watch the Pressure Gauge for one minute to make sure that there is no change in pressure. It should read slightly higher than the atmospheric pressure.
10. Remove the charge hose from the service port. 11. Using hexagonal wrench, fully open both the
high pressure and low pressure valves.

Low pressure valve Charge hose

High pressure valve Charge hose
Vacuum pump

OPEN VALVE STEMS GENTLY
When opening valve stems, turn the hexagonal wrench until it hits against the stopper. DO NOT try to force the valve to open further.

Low pressure valve

12. Tighten valve caps by hand, then tighten it using the proper tool.

1. Connect the manifold gauge’s charge hose to the service port on the outdoor unit’s low pressure valve.
2. Connect the manifold gauge’s charge hose from the to the vacuum pump.
3. Open the Low Pressure side of the manifold

13. If the outdoor unit uses all vacuum valves, and the vacuum position is at the main valve, the system is not connected with the indoor unit. The valve must be tightened with a screw nut. Check for gas leaks before operation to prevent leakage.

gauge. Keep the High Pressure side closed.

4. Turn on the vacuum pump to evacuate the system.

5. Run the vacuum for at least 15 minutes, or until

the Compound Meter reads -76cmHG (-1x105Pa).

6. Close the manifold gauge’s Low Pressure valve

and turn off the vacuum pump.

7. Wait for 5 minutes, then check that there has

been no change in system pressure.

Air Evacuation

Note On Adding Refrigerant

CAUTION
· Refrigerant charging must be performed after wiring, vacuuming, and the leak testing. · DO NOT exceed the maximum allowable quantity of refrigerant or overcharge the system.
Doing so can damage the unit or impact it’s functioning. · Charging with unsuitable substances may cause explosions or accidents. Ensure that the
appropriate refrigerant is used. · Refrigerant containers must be opened slowly. Always use protective gear when charging the
system. · DO NOT mix refrigerants types. · For the R290 or R32 refrigerant model, make sure the condtions within the area have been
made safe by control of flammable material when the refrigerant added into air conditioner.
N=2(one-twin models), N=3(one-three models), N=4(one-four models), N=5(one- five models). Depending on the length of connective piping or the pressure of the evacuated system, you made need to add refrigerant. Refer to table below for refrigerant amounts to be added:
ADDITIONAL REFRIGERANT PER PIPE LENGTH

Connective Pipe Length(m)

Air Purging Method

Additional Refrigerant

Pre-charge pipe length (ft/m) (pre-charge pipe length xN )

Vacuum Pump

N/A

More than (pre-charge pipe lengthxN) ft/m

Liquid Side: Ø 6.35 (Ø 1/4″)

Liquid Side: Ø 9.52 (Ø 3/8″)

R32

R32

(Total pipe length – pre-charge pipe lengthxN) x12g/m (Total pipe length – pre-charge pipe lengthxN) x24g/m

(Total pipe length – pre-charge pipe lengthxN) x0.13oZ/ft (Total pipe length – pre-charge pipe lengthxN) x0.26oZ/ft Vacuum Pump

Liquid Side: Ø 6.35 (Ø 1/4″)

Liquid Side: Ø 9.52 (Ø 3/8″)

R410A

R410A

(Total pipe length – pre-charge pipe lengthxN) x15g/m (Total pipe length – pre-charge pipe lengthxN) x30g/m

(Total pipe length – pre-charge pipe lengthxN) x0.16oZ/ft (Total pipe length – pre-charge pipe lengthxN) x0.32oZ/ft

NOTE: The standard pipe length is 7.5m.

Air Evacuation

Only for Australia models : · DO NOT mix refrigerants types. N=2(one-twin models),N=3(one-three models),N=4(one-four models),N=5(one-five models). Some systems require additional charging depending on pipe lengths. The standard pipe length is 10m. The additional refrigerant to be charged can be calculated using the following formula:

ADDITIONAL REFRIGERANT PER PIPE LENGTH

Connective Pipe Length(m)

Air Purging Method

Additional Refrigerant(R410A)

Less than Standard pipe length x N

Vacuum Pump

N/A

More than

Vacuum Pump

Liquid Side: Ø 6.35 (Ø 1/4″)

Liquid Side: Ø 9.52 (Ø 3/8″)

Standard pipe length x N

(Total pipe length – pre-charge pipe lengthxN) x15g/m (Total pipe length – pre-charge pipe lengthxN) x30g/m

Make sure to remove the additional refrigerant charge according to the rated volume (5m refrigerant piping) when doing market or government verification test.

Air Evacuation

Safety And Leakage Check

Electrical safety check
Perform the electrical safety check after completing installation. Cover the following areas: 1. Insulated resistance
The insulated resistance must be more than 2M. 2. Grounding work After finishing grounding work, measure the grounding resistance by visual detection and using the grounding resistance tester. Make sure the grounding resistance is less than 4. 3. Electrical leakage check (performing during test while unit is on) During a test operation after completed installation, the use the electroprobe and multimeter to perform an electrical leakage check. Turn off the unit immediately if leakage happens. Try and evaluate different solutions until the unit operates properly.

Gas leak check 1. Soap water method:
Apply a soap-water solution or a liquid neutral detergent on the indoor unit connection or outdoor unit connections with a soft brush to check for leakage of the connecting points of the piping. If bubbles emerge, the pipes are experiencing leakage. 2. Leak detector Use the leak detector to check for leakage.
NOTE: The illustration is for example purposes only. The actual order of A, B, C, D, and E on the machine may be slightly different from the unit you purchased but the general shape will remain the same.
Indoor unit check point

Outdoor unit check point

A, B,C,D are points for one-four type. A, B,C,D, and E are points for the one- five type.

Air Evacuation

Page 40

Test Run

Before Test Run
A test run must be performed after the entire system has been completely installed. Confirm the following points before performing the test:
a) The indoor and outdoor units are properly installed.
b) Piping and wiring are properly connected. c) No obstacles near the inlet and outlet of the
unit that might cause poor performance or product malfunction. d) The refrigeration system does not leak.
e) Drainage system is unimpeded and draining to a safe location.
f) The heating insulation is properly installed.
g) The grounding wires are properly connected.
h) Length of the piping and additional refrigerant stow capacity have been recorded.
i) The power voltage is the correct voltage for the air conditioner.

f. Check to see that the drainage system is unimpeded and draining smoothly.
g. Ensure there is no vibration or abnormal noise during operation.
5. For the Outdoor Unit
a. Check to see if the refrigeration system is leaking.
b. Make sure there is no vibration or abnormal noise during operation.
c. Ensure the wind, noise, and water generated by the unit do not disturb your neighbors or pose a safety hazard.
NOTE: If the unit malfunctions or does not operate according to your expectations, please refer to the Troubleshooting section of the Owner’s Manual before calling customer service.

CAUTION
Failure to perform the test run may result in unit damage, property damage or personal injury.
Test Run Instructions
1. Open both the liquid and gas stop valves. 2. Turn on the main power switch and allow the
unit to warm up. 3. Set the air conditioner to COOL mode. 4. For the Indoor Unit
a. Ensure the remote control and its buttons work properly.
b. Ensure the louvers move properly and can be changed using the remote control.
c. Double check to see if the room temperature is being registered correctly.
d. Ensure the indicators on the remote control and the display panel on the indoor unit work properly.
e. Ensure the manual buttons on the indoor unit works properly.

Test Run

Page 41

Function of Automatic Wiring/Piping Correction
Automatic Wiring/Piping Correction Function More recent models now feature automatic correction of wiring/piping errors. Press the “check switch” on the outdoor unit PCB board for 5 seconds until the LED displays “CE”, indicatomg that this function is working, Approximately 5-10 minutes after the switch is pressed, the “CE” disappears, meaning that the wiring/piping error is corrected and all wiring/piping is properly connected.
Check switch
LED display

Correct Terminal B block A
Liquid/ B Gas pipe A Outdoor unit Incorrect wiring Terminal B block A
Liquid/ B Gas pipe A Outdoor unit Incorrect wiring Terminal B block A
Liquid/ B Gas pipe A Outdoor unit

Indoor unit B Indoor unit A
Indoor unit B Indoor unit A
Indoor unit B Indoor unit A

How To Activate This Function
1. Check that outside temperature is above 5¥. (This function does not work when outside temperature is not above 5¥)
2. Check that the stop valves of the liquid pipe and gas pipe are open. 3. Turn on the breaker and wait at least 2 minutes. 4. Press the check switch on the outdoor PCB board unit LED display “C E”.

Page 42

Function of Automatic Wiring/ Piping Correction

The design and specifications are subject to change without prior notice for product improvement. Consult with the sales agency or manufacturer for details. Any updates to the manual will be uploaded to the service website, please check for the latest version.
QS003UI-YTD 16122300000557
20210915

SPLIT-TYPE ROOM AIR CONDITIONER
Owner’s Manual & Installation Manual
IMPORTANT NOTE: Read this manual and SAFETY MANUAL(if any) carefully before installing or operating your new air conditioning unit. Make sure to save this manual for future reference. Please check the applicable models, technical data, F-GAS(if any) and manufacturer information from the “Owner’s Manual – Product Fiche ” in the packaging of the outdoor unit (European Union products only) or in the packaging of the indoor unit (model dependent)

Table of Contents
Safety Precautions ……………………………………………………………………………………03
Owner’s Manual
Unit Specifications and Features…………………………………………………………………..07
1. Indoor unit display………………………………………………………………………………………………………………………………..07 2. Operating temperature………………………………………………………………………………………………………………………….08 3. Other features …………………………………………………………………………………………………………………………………….09 4. Setting angle of airflow…………………………………………………………………………………………………………………………10 5. Manual operation (without Remote)………………………………………………………………………………………………………..10
Care and Maintenance……………………………………………………………………………..11 Troubleshooting……………………………………………………………………………………….13
Installation Manual
Accessories………………………………………………………………………………………………..16 Installation Summary – Indoor Unit ……………………………………………………………17 Unit Parts…………………………………………………………………………………………………..18 Indoor Unit Installation……………………………………………………………………………..19
1. Select installation location………………………………………………………………………………………………………………………..19 2. Attach mounting plate to wall…………………………………………………………………………………………………………………..19 3. Drill wall hole for connective piping……………………………………………………………………………………………………………20 4. Prepare refrigerant piping…………………………………………………………………………………………………………………………21 5. Connect drain hose…………………………………………………………………………………………………………………………………21 6. Connect signal and power cables………………………………………………………………………………………………………………22 7. Wrap piping and cables……………………………………………………………………………………………………………………………23 8. Mount indoor unit………………………………………………………………………………………………………………………………….24
Outdoor Unit Installation…………………………………………………………………………………..25
1. Select installation location………………………………………………………………………………………………………………………….25 2. Install drain joint………………………………………………………………………………………………………………………………………26 3. Anchor outdoor unit…………………………………………………………………………………………………………………………………26 4. Connect signal and power cables………………………………………………………………………………………………………………..28
Refrigerant Piping Connection……………………………………………………………………29
A. Note on Pipe Length………………………………………………………………………………………………………………………………..29 B. Connection Instructions ­Refrigerant Piping…………………………………………………………………………………………………29
1. Cut pipe……………………………………………………………………………………………………………………………………………29 2. Remove burrs…………………………………………………………………………………………………………………………………….30 3. Flare pipe ends…………………………………………………………………………………………………………………………………..30 4. Connect pipes……………………………………………………………………………………………………………………………………30
Air Evacuation……………………………………………………………………………..32
1. Evacuation Instructions……………………………………………………………………………………………………………32 2. Note on Adding Refrigerant……………………………………………………………………………………………………..33
Electrical and Gas Leak Checks………………………………………………………34
Test Run…………………………………………………………………………………………………….35 Packing and unpacking the unit …………………………………………………………………36

Safety Precautions

Safety Precautions

Read Safety Precautions Before Operation and Installation
Incorrect installation due to ignoring instructions can cause serious damage or injury. The seriousness of potential damage or injuries is classified as either a WARNING or CAUTION.

WARNING
This symbol indicates the possibility of personnel injury or loss of life.

CAUTION
This symbol indicates the possibility of property damage or serious consequences.

WARNING
This appliance can be used by children aged from 8 years and above and persons with reduced physical, sensory or mental capabilities or lack of experience and knowledge if they have been given supervision or instruction concerning use of the appliance in a safe way and understand the hazards involved. Children shall not play with the appliance. Cleaning and user maintenance shall not be made by children without supervision European Union countries
.
This appliance is not intended for use by persons(including children) with reduced physical, sensory or mental capabilities, or lack of experience and knowledge, unless they have been given supervision or instruction concerning use of the appliance by a person responsible for their safety. Children should be supervised to ensure that they do not play with the appliance.

WARNINGS FOR PRODUCT USE · If an abnormal situation arises (like a burning smell), immediately turn off the unit and disconnect
the power. Call your dealer for instructions to avoid electric shock, fire or injury. · Do not insert fingers, rods or other objects into the air inlet or outlet. This may cause injury, since
the fan may be rotating at high speeds. · Do not use flammable sprays such as hair spray, lacquer or paint near the unit. This may cause
fire or combustion. · Do not operate the air conditioner in places near or around combustible gases. Emitted gas may
collect around the unit and cause explosion. · Do not operate your air conditioner in a wet room such as a bathroom or laundry room. Too
much exposure to water can cause electrical components to short circuit. · Do not expose your body directly to cool air for a prolonged period of time.
· Do not allow children to play with the air conditioner. Children must be supervised around the unit at all times.
· If the air conditioner is used together with burners or other heating devices, thoroughly ventilate
the room to avoid oxygen deficiency. · In certain functional environments, such as kitchens, server rooms, etc., the use of specially
designed air-conditioning units is highly recommended.
CLEANING AND MAINTENANCE WARNINGS
· Turn off the device and disconnect the power before cleaning. Failure to do so can cause electrical shock.
· Do not clean the air conditioner with excessive amounts of water.
· Do not clean the air conditioner with combustible cleaning agents. Combustible cleaning agents can cause fire or deformation.

Page 3

Safety Precautions

CAUTION
· Turn off the air conditioner and disconnect the power if you are not going to use it for a long time. · Turn off and unplug the unit during storms. · Make sure that water condensation can drain unhindered from the unit. · Do not operate the air conditioner with wet hands. This may cause electric shock. · Do not use device for any other purpose than its intended use. · Do not climb onto or place objects on top of the outdoor unit. · Do not allow the air conditioner to operate for long periods of time with doors or windows open,
or if the humidity is very high.
ELECTRICAL WARNINGS · Only use the specified power cord. If the power cord is damaged, it must be replaced by the
manufacturer, its service agent or similarly qualified persons in order to avoid a hazard. · Keep power plug clean. Remove any dust or grime that accumulates on or around the plug. Dirty
plugs can cause fire or electric shock. · Do not pull power cord to unplug unit. Hold the plug firmly and pull it from the outlet. Pulling
directly on the cord can damage it, which can lead to fire or electric shock. · Do not modify the length of the power supply cord or use an extension cord to power the unit. · Do not share the electrical outlet with other appliances. Improper or insufficient power supply
can cause fire or electrical shock. · The product must be properly grounded at the time of installation, or electrical shock may occur. · For all electrical work, follow all local and national wiring standards, regulations, and the
Installation Manual. Connect cables tightly, and clamp them securely to prevent external forces from damaging the terminal. Improper electrical connections can overheat and cause fire, and may also cause shock. All electrical connections must be made according to the Electrical Connection Diagram located on the panels of the indoor and outdoor units. · All wiring must be properly arranged to ensure that the control board cover can close properly. If the control board cover is not closed properly, it can lead to corrosion and cause the connection points on the terminal to heat up, catch fire, or cause electrical shock. · If connecting power to fixed wiring, an all-pole disconnection device which has at least 3mm clearances in all poles, and have a leakage current that may exceed 10mA, the residual current device(RCD) having a rated residual operating current not exceeding 30mA, and disconnection must be incorporated in the fixed wiring in accordance with the wiring rules.
TAKE NOTE OF FUSE SPECIFICATIONS
The air conditioner’s circuit board (PCB) is designed with a fuse to provide overcurrent protection. The specifications of the fuse are printed on the circuit board ,such as : T3.15AL/250VAC, T5AL/250VAC, T3.15A/250VAC, T5A/250VAC, T20A/250VAC, T30A/250VAC,etc. NOTE: For the units using R32 or R290 refrigerant , only the blast-proof ceramic fuse can be used.
UV-C lamp(Applicable to the unit contains an UV-C lamp only)
This appliance contains a UV-C lamp. Read the maintenance instructions before opening the appliance. 1. Do not operate UV-C lamps outside of the appliance. 2. Appliances that are obviously damaged must not be operated. 3. Unintended use of the appliance or damage to the housing may result in the escape of dangerous UV-C
radiation. UV-C radiation may, even in small doses, cause harm to the eyes and skin.
Page 4

Safety Precautions

4. Before opening doors and access panels bearing the ULTRAVIOLET RADIATION hazard symbol for the conducting USER MAINTENANCE, it is recommended to disconnect the power.
5. The UV-C lamp can not be cleaned, repaired and replaced. 6. UV-C BARRIERS bearing the ULTRAVIOLET RADIATION hazard symbol should not be removed.
WARNING This appliance contains an UV emitter. Do not stare at the light source.
WARNINGS FOR PRODUCT INSTALLATION
1. Installation must be performed by an authorized dealer or specialist. Defective installation can cause water leakage, electrical shock, or fire.
2. Installation must be performed according to the installation instructions. Improper installation can cause water leakage, electrical shock, or fire. In North America,installation must be performed in accordance with the requirement of NEC and CEC by authorized personnel only.)
3. Contact an authorized service technician for repair or maintenance of this unit. This appliance shall be installed in accordance with national wiring regulations.
4. Only use the included accessories, parts, and specified parts for installation. Using non-standard parts can cause water leakage, electrical shock, fire, and can cause the unit to fail.
5. Install the unit in a firm location that can support the unit’s weight. If the chosen location cannot support the unit’s weight, or the installation is not done properly, the unit may drop and cause serious injury and damage.
6. Install drainage piping according to the instructions in this manual. Improper drainage may cause water damage to your home and property.
7. For units that have an auxiliary electric heater, do not install the unit within 1 meter (3 feet) of any combustible materials.
8. Do not install the unit in a location that may be exposed to combustible gas leaks. If combustible gas accumulates around the unit, it may cause fire.
9. Do not turn on the power until all work has been completed. 10.When moving or relocating the air conditioner, consult experienced service technicians for
disconnection and reinstallation of the unit. 11.How to install the appliance to its support, please read the information for details in “indoor unit
installation” and “outdoor unit installation” sections .
Note about Fluorinated Gasses(Not applicable to the unit using R290 Refrigerant)
1. This air-conditioning unit contains fluorinated greenhouse gasses. For specific information on the type of gas and the amount, please refer to the relevant label on the unit itself or the “Owner’s Manual – Product Fiche ” in the packaging of the outdoor unit. (European Union products only).
2. Installation, service, maintenance and repair of this unit must be performed by a certified technician.
3. Product uninstallation and recycling must be performed by a certified technician. 4. For equipment that contains fluorinated greenhouse gases in quantities of 5 tonnes of CO2
equivalent or more, but of less than 50 tonnes of CO2 equivalent, If the system has a leakdetection system installed, it must be checked for leaks at least every 24 months. 5. When the unit is checked for leaks, proper record- keeping of all checks is strongly recommended.
Page 5

Safety Precautions

WARNING for Using R32/R290 Refrigerant
When flammable refrigerant are employed, appliance shall be stored in a well -ventilated area where the room size corresponds to the room area as specifiec for operation. For R32 frigerant models: Appliance shall be installed, operated and stored in a room with a floor area larger than 4m 2. For R290 refrigerant models, appliance shall be installed, operated and stored in a room with a floor area larger than: <=9000Btu/h units: 13m2 >9000Btu/h and <=12000Btu/h units: 17m2 >12000Btu/h and <=18000Btu/h units: 26m2 >18000Btu/h and <=24000Btu/h units: 35m2 Reusable mechanical connectors and flared joints are not allowed indoors. (EN Standard Requirements). Mechanical connectors used indoors shall have a rate of not more than 3g/year at 25% of the maximum allowable pressure. When mechanical connectors are reused indoors, sealing parts shall be renewed. When flared joints are reused indoors, the flare part shall be re-fabricated. (UL Standard Requirements) When mechanical connectors are reused indoors, sealing parts shall be renewed. When flared joints are reused indoors, the flare part shall be re-fabricated. (IEC Standard Requirements) Mechanical connectors used indoors shall comply with ISO 14903.
European Disposal Guidelines
This marking shown on the product or its literature, indicates that waste electrical and eletrical equipment should not be mixed with general household waste.
Correct Disposal of This Product
(Waste Electrical & Electronic Equipment)
This appliance contains refrigerant and other potentially hazardous materials. When disposing of this appliance, the law requires special collection and treatment. Do not dispose of this product as household waste or unsorted municipal waste. When disposing of this appliance, you have the following options:
· Dispose of the appliance at designated municipal electronic waste collection facility. · When buying a new appliance, the retailer will take back the old appliance free of charge. · The manufacturer will take back the old appliance free of charge. · Sell the appliance to certified scrap metal dealers.
Special notice Disposing of this appliance in the forest or other natural surroundings endangers your health and is bad for the environment. Hazardous substances may leak into the ground water and enter the food chain.
Page 6

Unit Specifications and Features

Unit Specifications and Features

Indoor unit display
NOTE: Different models have different front panels and display windows. Not all the display codes describing below are available for the air conditioner you purchased. Please check the indoor display window of the unit you purchased.
Illustrations in this manual are for explanatory purposes. The actual shape of your indoor unit may be slightly different. The actual shape shall prevail.
Front Panel Power Cable (Some Units )

Louver

Remote Control Remote Control Holder (Some Units)

Functional Filter (On Back of Main Filter – Some Units)

Display window

fresh defrost run timer

(A)

(B)

” fresh ” when Fresh and UV-C lamp(if any)feature is activated(some units)

“defrost” when defrost feature is activated.

” run ” when the unit is on.

” timer ” when TIMER is set. ” ” when Wireless Control feature is activated(some units)

Display Code Meanings

” ” Displays temperature, operation feature and error codes:

” ” for 3 seconds when: · TIMER ON is set (if the unit is OFF, ” ” remains on when TIMER ON is set ) · FRESH, UV-C lamp, SWING, TURBO, ECO,or SILENCE feature is turned on

” ” for 3 seconds when: · TIMER OFF is set · FRESH, UV-C lamp, SWING, TURBO, ECO,or SILENCE feature is turned off

” ” when defrosting

” ” when 8 C heating feature is turned on(some units)

” when Active Clean feature is turned on(For Inverter split type)

when unit is self-cleaning(For Fixed-speed type)

Page 7

Unit Specifications and Features

Operating temperature
When your air conditioner is used outside of the following temperature ranges, certain safety protection features may activate and cause the unit to disable.

Inverter Split Type

COOL mode

Room Temperature

16°C – 32°C (60°F – 90°F)

HEAT mode
0°C – 30°C (32°F – 86°F)

DRY mode
10°C – 32°C (50°F – 90°F)

0°C – 50°C (32°F – 122°F)

Outdoor Temperature

-15°C – 50°C (5°F – 122°F)
(For models with low temp. cooling systems.)

-15°C – 24°C (5°F – 75°F)

0°C – 50°C (32°F – 122°F)

FOR OUTDOOR UNITS WITH AUXILIARY ELECTRIC HEATER
When outside temperature is below 0°C (32°F ), we strongly recommend keeping the unit plugged in at all time to ensure smooth ongoing performance.

0°C – 52°C (32°F – 126°F)
(For special tropical models)

0°C – 52°C (32°F – 126°F)
(For special tropical models)

Fixed-speed Type

COOL mode

Room Temperature

16°C-32°C (60°F-90°F)

18°C-43°C (64°F-109°F)

Outdoor Temperature

-7°C-43°C (19°F-109°F) (For models with low-temp cooling systems)

18°C-52°C (64°F-126°F)

(For special tropical models)

HEAT mode 0°C-30°C (32°F-86°F)
-7°C-24°C (19°F-75°F)

DRY mode
10°C-32°C (50°F-90°F) 11°C-43°C (52°F-109°F) 18°C-43°C (64°F-109°F) 18°C-52°C (64°F-126°F) (For special tropical models)

NOTE: Room relative humidity less than 80%. If the air conditioner operates in excess of this figure, the surface of the air conditioner may attract condensation. Please sets the vertical air flow louver to its maximum angle (vertically to the floor), and set HIGH fan mode.

To further optimize the performance of your unit, do the following: · Keep doors and windows closed. · Limit energy usage by using TIMER ON and TIMER OFF functions. · Do not block air inlets or outlets. · Regularly inspect and clean air filters.

Page 8

Unit Specifications and Features

A guide on using the infrared remote is not included in this literature package. Not all the functions are available for the air conditioner, please check the indoor display and remote control of the unit you purchased.
Other Features

· Breeze Away (some units) This feature avoids direct air flow blowing on the body and make you feel indulging in silky coolness.
· Refrigerant Leakage Detection (some units)

· Auto-Restart(some units) If the unit loses power, it will automatically
restart with the prior settings once power has
been restored.

The indoor unit will automatically display “EL0C”or flash LEDS (model dependent )
when it detects refrigerant leakage.

· Anti-mildew (some units) When turning off the unit from COOL, AUTO (COOL), or DRY modes, the air conditioner will continue operate at very low power to dry up

· Sleep Operation The SLEEP function is used to decrease energy use while you sleep (and don’t need the same temperature settings to

condensed water and prevent mildew growth.

stay comfortable). This function can only

· Wireless Control (some units) Wireless control allows you to control your air conditioner using your mobile phone and a wireless connection. For the USB device access, replacement, maintenance operations must be carried out by professional staff.
· Louver Angle Memory(some units) When turning on your unit, the louver will automatically resume its former angle.
· Active Clean function(some units) — The Active Clean Technology washes away
dust when it adheres to the heat exchanger by automatically freezing and then rapidly thawing the frost. A “pi-pi” sound will be heard.

be activated via remote control. And the Sleep function is not available in FAN or DRY mode.
Press the SLEEP button when you are ready to go to sleep. When in COOL mode, the unit will increase the temperature by 1°C (2°F) after 1 hour, and will increase an additional 1°C (2°F) after another hour. When in HEAT mode, the unit will decrease the temperature by 1°C (2°F) after 1 hour, and will decrease an additional 1°C (2°F) after another hour.
The sleep feature will stop after 8 hours and the system will keep running with final situation.

The Active clean operation is used to produce

SLEEP Operation

more condensed water to improve the cleaning effect, and the cold air will blow out. After cleaning, the internal wind wheel then keeps

Set temperature

Cool mode(+1 C/2 F) per hour for the first two hours

1hr

1hr

Keep running

operating with hot air to blow-dry the evaporator, thus keeping the inside clean.

Heat mode( -1 C/2 F) per hour for the first two hours

— When this function is turned on, the indoor

unit display window appears “CL ” , after 20

to 130 minutes, the unit will turn off automatically and cancel Active Clean function.

Saving energy during sleep

— For some units, the system will start hightemperature cleaning process, and the

NOTE:

temperature of air outlet is very high. Please keep away from it. And this would lead to the rising of the room temperature .

For multi-split air condtioners, the following functions are not available: Active clean function, Silence feature, Breeze

away function, Refrigerant leakage detection

function and Eco feature.

Page 9

· Setting Angle of Air Flow

Unit Specifications and Features

Setting vertical angle of air flow
While the unit is on, use the SWING/ DIRECT button on remote control to set the direction (vertical angle) of airflow. Please refer to the Remote Control Manual for details.
NOTE ON LOUVER ANGLES
When using COOL or DRY mode, do not set louver at too vertical an angle for long periods of time. This can cause water to condense on the louver blade, which will drop on your floor or furnishings. When using COOL or HEAT mode, setting the louver at too small an angle can reduce the performance of the unit due to restricted air flow. NOTE: According to the relative standards requirement
please sets the vertical air flow louver to its maximum angle under heating capacity test
Setting horizontal angle of air flow
The horizontal angle of the airflow must be set manually. Grip the deflector rod (See Fig.B) and manually adjust it to your preferred direction. For some units, the horizontal angle of the airflow can be set by remote control. please refer to the Remote Control Manual.
Manual Operation(without remote)

Range

NOTE: Do not move louver by hand. This will

cause the louver to become out of sync. If this

occurs, turn off the unit and unplug it for a few

seconds, then restart the unit. This will reset the

louver.

Fig. A

CAUTION
Do not put your fingers in or near the blower and suction side of the unit. The high-speed fan inside the unit may cause injury.

Deflector rod

CAUTION
The manual button is intended for testing purposes and emergency operation only. Please do not use this function unless the remote control is lost and it is absolutely necessary. To restore regular operation, use the remote control to activate the unit. Unit must be turned off before manual operation.
To operate your unit manually:
1. Open the front panel of the indoor unit.
2. Locate the MANUAL CONTROL button on the right-hand side of the unit.
3. Press the MANUAL CONTROL button one time to activate FORCED AUTO mode.
4. Press the MANUAL CONTROL button again to activate FORCED COOLING mode.
5. Press the MANUAL CONTROL button a third time to turn the unit off.
6. Close the front panel.

Fig. B
Manual control button

Page 10

Care and Maintenance

Care and Maintenance

Cleaning Your Indoor Unit
BEFORE CLEANING OR MAINTENANCE
ALWAYS TURN OFF YOUR AIR CONDITIONER SYSTEM AND DISCONNECT ITS POWER SUPPLY BEFORE CLEANING OR MAINTENANCE.
CAUTION
Only use a soft, dry cloth to wipe the unit clean. If the unit is especially dirty, you can use a cloth soaked in warm water to wipe it clean.
· Do not use chemicals or chemically treated cloths to clean the unit
· Do not use benzene, paint thinner, polishing powder or other solvents to clean the unit. They can cause the plastic surface to crack or deform.
· Do not use water hotter than 40°C (104°F) to clean the front panel. This can cause the panel to deform or become discolored.

6. Rinse the filter with fresh water, then shake off excess water.
7. Dry it in a cool, dry place, and refrain from exposing it to direct sunlight.
8. When dry, re-clip the air freshening filter to the larger filter, then slide it back into the indoor unit.
9. Close the front panel of the indoor unit.
Filter Tab

Cleaning Your Air Filter

A clogged air conditioner can reduce the cooling efficiency of your unit, and can also be bad for your health. Make sure to clean the filter once every two weeks.
1. Lift the front panel of the indoor unit.
2. First press the tab on the end of filter to loosen the buckle, lift it up, then pull it towards yourself.
3. Now pull the filter out. 4. If your filter has a small air freshening filter,
unclip it from the larger filter. Clean this air freshening filter with a hand-held vacuum.
5. Clean the large air filter with warm, soapy water. Be sure to use a mild detergent.

Remove air freshening Gilter from back of larger filter (some units)
CAUTION Do not touch air freshening (Plasma) filter for at least 10 minutes after turning off the unit.

Page 11

Care and Maintenance

CAUTION
· Before changing the filter or cleaning, turn off the unit and disconnect its power supply.
· When removing filter, do not touch metal parts in the unit. The sharp metal edges can cut you.
· Do not use water to clean the inside of the indoor unit. This can destroy insulation and cause electrical shock.
· Do not expose filter to direct sunlight when drying. This can shrink the filter.
Air Filter Reminders (Optional)
Air Filter Cleaning Reminder
After 240 hours of use, the display window on the indoor unit will flash “CL.” This is a reminder to clean your filter. After 15 seconds, the unit will revert to its previous display.
To reset the reminder, press the LED button on your remote control 4 times, or press the MANUAL CONTROL button 3 times. If you don’t reset the reminder, the “CL” indicator will flash again when you restart the unit.
Air Filter Replacement Reminder
After 2,880 hours of use, the display window on the indoor unit will flash “nF.” This is a reminder to replace your filter. After 15 seconds, the unit will revert to its previous display.
To reset the reminder, press the LED button on your remote control 4 times, or press the MANUAL CONTROL button 3 times. If you don’t reset the reminder, the “nF” indicator will flash again when you restart the unit.

Maintenance ­ Long Periods of Non-Use
If you plan not to use your air conditioner for an extended period of time, do the following:

Clean all filters

Turn on FAN function until unit dries out completely

Turn off the unit and disconnect the power

Remove batteries from remote control

Maintenance ­ Pre-Season Inspection
After long periods of non-use, or before periods of frequent use, do the following:

Check for damaged wires

Clean all filters

CAUTION
· Any maintenance and cleaning of outdoor unit should be performed by an authorized dealer or a licensed service provider.
· Any unit repairs should be performed by an authorized dealer or a licensed service provider.

Check for leaks

Replace batteries

Make sure nothing is blocking all air inlets and outlets

Page 12

Troubleshooting

Troubleshooting

SAFETY PRECAUTIONS
If ANY of the following conditions occurs, turn off your unit immediately! · The power cord is damaged or abnormally warm · You smell a burning odor · The unit emits loud or abnormal sounds · A power fuse blows or the circuit breaker frequently trips · Water or other objects fall into or out of the unit
DO NOT ATTEMPT TO FIX THESE YOURSELF! CONTACT AN AUTHORIZED SERVICE PROVIDER IMMEDIATELY!

Common Issues

The following problems are not a malfunction and in most situations will not require repairs.

Issue Unit does not turn on when pressing ON/OFF button The unit changes from COOL/HEAT mode to FAN mode
The indoor unit emits white mist

Possible Causes
The Unit has a 3-minute protection feature that prevents the unit from overloading. The unit cannot be restarted within three minutes of being turned off.
The unit may change its setting to prevent frost from forming on the unit. Once the temperature increases, the unit will start operating in the previously selected mode again.
The set temperature has been reached, at which point the unit turns off the compressor. The unit will continue operating when the temperature fluctuates again.
In humid regions, a large temperature difference between the room’s air and the conditioned air can cause white mist.

Both the indoor and outdoor units emit white mist

When the unit restarts in HEAT mode after defrosting, white mist may be emitted due to moisture generated from the defrosting process.

The indoor unit makes noises

A rushing air sound may occur when the louver resets its position.
A squeaking sound may occur after running the unit in HEAT mode due to expansion and contraction of the unit’s plastic parts.

Both the indoor unit and outdoor unit make noises

Low hissing sound during operation: This is normal and is caused by refrigerant gas flowing through both indoor and outdoor units.
Low hissing sound when the system starts, has just stopped running, or is defrosting: This noise is normal and is caused by the refrigerant gas stopping or changing direction.
Squeaking sound: Normal expansion and contraction of plastic and metal parts caused by temperature changes during operation can cause squeaking noises.

Page 13

Troubleshooting

Issue
The outdoor unit makes noises
Dust is emitted from either the indoor or outdoor unit

Possible Causes
The unit will make different sounds based on its current operating mode.
The unit may accumulate dust during extended periods of non-use, which will be emitted when the unit is turned on. This can be mitigated by covering the unit during long periods of inactivity.

The unit emits a bad odor

The unit may absorb odors from the environment (such as furniture, cooking, cigarettes, etc.) which will be emitted during operations.
The unit’s filters have become moldy and should be cleaned.

The fan of the outdoor unit does not operate During operation, the fan speed is controlled to optimize product operation.

Operation is erratic, unpredictable, or unit is unresponsive

Interference from cell phone towers and remote boosters may cause the unit to malfunction.
In this case, try the following: · Disconnect the power, then reconnect. · Press ON/OFF button on remote control to restart operation.

NOTE: If problem persists, contact a local dealer or your nearest customer service center. Provide them with a detailed description of the unit malfunction as well as your model number.

Troubleshooting

When troubles occur, please check the following points before contacting a repair company.

Problem

Possible Causes

Solution

Temperature setting may be higher than ambient room temperature

Lower the temperature setting

Poor Cooling Performance

The heat exchanger on the indoor Clean the affected heat exchanger or outdoor unit is dirty

The air filter is dirty
The air inlet or outlet of either unit is blocked Doors and windows are open
Excessive heat is generated by sunlight

Remove the filter and clean it according to instructions
Turn the unit off, remove the obstruction and turn it back on
Make sure that all doors and windows are closed while operating the unit
Close windows and curtains during periods of high heat or bright sunshine

Too many sources of heat in the room (people, computers, electronics, etc.)
Low refrigerant due to leak or long-term use
SILENCE function is activated (optional function)

Reduce amount of heat sources
Check for leaks, re-seal if necessary and top off refrigerant SILENCE function can lower product performance by reducing operating frequency. Turn off SILENCE function.

Page 14

Troubleshooting

Problem
The unit is not working
The unit starts and stops frequently
Poor heating performance
Indicator lamps continue flashing Error code appears and begins with the letters as the following in the window display of indoor unit: · E(x), P(x), F(x) · EH(xx), EL(xx), EC(xx) · PH(xx), PL(xx), PC(xx)

Possible Causes Power failure

Solution Wait for the power to be restored

The power is turned off

Turn on the power

The fuse is burned out

Replace the fuse

Remote control batteries are dead Replace batteries

The Unit’s 3-minute protection has been activated
Timer is activated

Wait three minutes after restarting the unit
Turn timer off

There’s too much or too little refrigerant in the system

Check for leaks and recharge the system with refrigerant.

Incompressible gas or moisture Evacuate and recharge the system

has entered the system.

with refrigerant

The compressor is broken

Replace the compressor

The voltage is too high or too low

Install a manostat to regulate the voltage

The outdoor temperature is extremely low

Use auxiliary heating device

Cold air is entering through doors and windows
Low refrigerant due to leak or long-term use

Make sure that all doors and windows are closed during use
Check for leaks, re-seal if necessary and top off refrigerant

The unit may stop operation or continue to run safely. If the indicator lamps continue to flash or error codes appear, wait for about 10 minutes. The problem may resolve itself. If not, disconnect the power, then connect it again. Turn the unit on. If the problem persists, disconnect the power and contact your nearest customer service center.

NOTE: If your problem persists after performing the checks and diagnostics above, turn off your unit immediately and contact an authorized service center.

Page 15

Accessories

The air conditioning system comes with the following accessories. Use all of the installation parts and accessories to install the air conditioner. Improper installation may result in water leakage, electrical shock and fire, or cause the equipment to fail. The items are not included with the air conditioner must be purchased separately.

Name of Accessories Q`ty(pc)

Shape

Name of Accessories Q`ty(pc)

Shape

Manual

2~3

Remote controller

1

Drain joint

(for cooling &

1

heating models)

Seal

(for cooling &

1

heating models)

Mounting plate

1

Anchor
Mounting plate fixing screw

5~8 (depending on models)
5~8 (depending on models)

Battery

2

Remote controller

holder(optional)

1

Fixing screw for

remote controller

2

holder(optional)

Small Filter (Need to be installed on the back of main air filter by the authorized technician while installing the machine)

1~2 (depending on models)

Name
Connecting pipe assembly
Magnetic ring and belt (if supplied ,please refer to the wiring diagram to install it on the connective cable. )

Shape
Liquid side Gas side

6.35( 1/4i n) 9.52( 3/8in) 9.52( 3/8in) 12.7( 1/2in) 16( 5/8in)
19( 3/4in)

1 2 3

Quantity(PC)
Parts you must purc hase separately. Consult the dealer about the proper pipe size of the unit you purchased.

Pass the belt through the hole of the Magnetic ring to fix it on the cable

Varies by model

Accessories

Page 16

Installation Summary – Indoor Unit

1

15cm (5.9in)

2

3

12cm (4.75in)
2.3m (90.55in)

12cm (4.75in)

Select Installation Location
44

Determine Wall Hole Position

5

6

Attach Mounting Plate

Installation Summary -Indoor Unit

Drill Wall Hole
7

Connect Piping
8

Connect Wiring (not applicable for some locations in North America )

Prepare Drain Hose

Wrap Piping and Cable (not applicable for some locations in North America )

9

8 STEP

Mount Indoor Unit
Page 17

Unit Parts
NOTE: The installation must be performed in accordance with the requirement of local and national standards. The installation may be slightly different in different areas.

1
2 4
5

3 2

4 6

5 7

8

9

10

1 Air-break switch 3
6 7 8

Unit Parts

11

11

c1
1 Wall Mounting Plate 2 Front Panel 3 Power Cable (Some Units) 4 Louver

c2

5

Functional Filter (On Back of Main Filter – Some Units)

6 Drainage Pipe

7 Signal Cable 8 Refrigerant Piping

9 Remote Controller
10 Remote controller Holder (Some Units)
11 Outdoor Unit Power Cable (Some Units)

NOTE ON ILLUSTRATIONS
Illustrations in this manual are for explanatory purposes. The actual shape of your indoor unit may be slightly different. The actual shape shall prevail.

Page 18

Indoor Unit Installation

Installation Instructions ­ Indoor unit
PRIOR TO INSTALLATION
Before installing the indoor unit, refer to the label on the product box to make sure that the model number of the indoor unit matches the model number of the outdoor unit.
Step 1: Select installation location Before installing the indoor unit, you must choose an appropriate location. The following are standards that will help you choose an appropriate location for the unit.
Proper installation locations meet the following standards:
Good air circulation Convenient drainage Noise from the unit will not disturb other
people Firm and solid–the location will not vibrate Strong enough to support the weight of the
unit A location at least one meter from all other
electrical devices (e.g., TV, radio, computer)
DO NOT install unit in the following locations:
Near any source of heat, steam, or combustible gas
Near flammable items such as curtains or clothing
Near any obstacle that might block air circulation
Near the doorway
In a location subject to direct sunlight

NOTE ABOUT WALL HOLE:
If there is no fixed refrigerant piping:
While choosing a location, be aware that you should leave ample room for a wall hole (see Drill wall hole for connective piping step) for the signal cable and refrigerant piping that connect the indoor and outdoor units. The default position for all piping is the right side of the indoor unit (while facing the unit). However, the unit can accommodate piping to both the left and right.
Refer to the following diagram to ensure proper distance from walls and ceiling:
15cm (5.9in) or more

12cm (4.75in) or more

12cm (4.75in) or more

2.3m (90.55in) or more
Step 2: Attach mounting plate to wall The mounting plate is the device on which you will mount the indoor unit.
Remove the screw that attaches the mounting plate to the back of the indoor unit.

Screw
Secure the mounting plate to the wall with the screws provided. Make sure that mounting plate is flat against the wall.
NOTE FOR CONCRETE OR BRICK WALLS: If the wall is made of brick, concrete, or similar material, drill 5mm-diameter (0.2in-diameter) holes in the wall and insert the sleeve anchors provided. Then secure the mounting plate to the wall by tightening the screws directly into the clip anchors.

Indoor Unit Installation

Page 19

Step 3: Drill wall hole for connective piping
1. Determine the location of the wall hole based on the position of the mounting plate. Refer to Mounting Plate Dimensions.
2. Using a 65mm (2.5in) or 90mm(3.54in) (depending on models )core drill, drill a hole in the wall. Make sure that the hole is drilled at a slight downward angle, so that the outdoor end of the hole is lower than the indoor end by about 5mm to 7mm (0.2-0.275in). This will ensure proper water drainage.
3. Place the protective wall cuff in the hole. This protects the edges of the hole and will help seal it when you finish the installation process.

CAUTION
When drilling the wall hole, make sure to avoid wires, plumbing, and other sensitive components.

Wall

Indoor

Outdoor

49mm (1.95in) 37mm
(1.45in)

101mm(4.0in)

348.4mm(13.7in) 179mm(7.1in) 136mm(5.4in)
Indoor unit outline

292mm(11.5in) 49mm(1.95in)

Left rear wall hole 65mm (2.5in)

729mm(28.7in)

Right rear wall hole 65mm (2.5in)

Model A
230mm(9.1in) 190mm(7.5in)

403mm(15.9in) 231mm(9.1in)
121mm(4.8in)

36mm (1.4in)

53mm (2.1in)

295mm(11.6in) 47mm(1.8in)

Left rear wall hole 65mm (2.5in)

805mm(31.7in) Model B

Right rear wall hole 65mm (2.5in)

244mm(9.6in) 190mm(7.5in)

418mm(16.5in) 246mm(9.7in)
121mm(4.8in)

53mm (2.1in) 36mm
(1.4in)

295mm(11.6in) 47mm(1.8in)

Left rear wall hole 65mm (2.5in)

835mm(32.9in) Model C

Right rear wall hole 65mm (2.5in)

165mm(6.5in)
106mm(4.2in)

527mm(20.7in) 247mm(9.7in)

37mm (2.1in)

321mm(12.6in) 48mm(1.9in)
29mm(1.1in)

5-7mm (0.2-0.275in)

Indoor Unit Installation

139mm (5.5in)

48mm (1.9in)

MOUNTING PLATE DIMENSIONS Different models have different mounting plates. For the different customization requirements, the shape of the mounting plate and the dimensions of the indoor unit may be slightly different. See Type A and Type B for example:
Correct orientation of Mounting Plate

Left rear wall hole 65mm (2.5in)

971mm(38.2in) Model D

Right rear wall hole 65mm (2.5in)

199mm(7.8in)
129mm(5.1in)

603mm(23.7in) 322mm(12.7in)

55mm (2.2in)

337mm(13.3in) 54mm (2.1in)

173mm (6.8in)

54mm (2.1in)

Left rear wall hole 90mm (3.54in)

1082mm(42.6in) Model E

643.6mm (25.3in)

389mm (15.3in)

257mm (10.1in)

172mm (6.8in)

332mm (13.05in)

Right rear wall hole 90mm (3.54in)

362mm (14.25in)

Indoor unit outline

Type A

Type B

Left rear wall hole 90mm (3.54in)

52mm (2.05in)
1259mm (49.55in)
Model F

52mm (2.05in)
Right rear wall hole 90mm (3.54in)

NOTE: When the gas side connective pipe is
16mm(5/8in) or more, the wall hole should
be 90mm(3.54in).

Page 20

Step 4: Prepare refrigerant piping The refrigerant piping is inside an insulating sleeve attached to the back of the unit. You must prepare the piping before passing it through the hole in the wall. 1. Based on the position of the wall hole relative
to the mounting plate, choose the side from which the piping will exit the unit. 2. If the wall hole is behind the unit, keep the knock-out panel in place. If the wall hole is to the side of the indoor unit, remove the plastic knock-out panel from that side of the unit. This will create a slot through which your piping can exit the unit. Use needle nose pliers if the plastic panel is too difficult to remove by hand.
Knock-out Panel
3. If existing connective piping is already embedded in the wall, proceed directly to the Connect Drain Hose step. If there is no embedded piping, connect the indoor unit’s refrigerant piping to the connective piping that will join the indoor and outdoor units. Refer to the Refrigerant Piping Connection section of this manual for detailed instructions.
NOTE ON PIPING ANGLE Refrigerant piping can exit the indoor unit from four different angles:Left-hand side,Right-hand side, Left rear, Right rear.

Step 5:Connect drain hose
By default, the drain hose is attached to the lefthand side of unit (when you’re facing the back of the unit). However, it can also be attached to the right-hand side. To ensure proper drainage, attach the drain hose on the same side that your refrigerant piping exits the unit. Attach drain hose extension (purchased separately) to the end of drain hose.
Wrap the connection point firmly with Teflon tape to ensure a good seal and to prevent leaks.
For the portion of the drain hose that will remain indoors, wrap it with foam pipe insulation to prevent condensation. Remove the air filter and pour a small amount of water into the drain pan to make sure that water flows from the unit smoothly.
NOTE ON DRAIN HOSE PLACEMENT
Make sure to arrange the drain hose according to the follo.wing figures.

CORRECT
Make sure there are no kinks or dent in drain hose to ensure proper drainage.

NOT CORRECT
Kinks in the drain hose will create water traps.

Indoor Unit Installation

CAUTION
Be extremely careful not to dent or damage the piping while bending them away from the unit. Any dents in the piping will affect the unit’s performance.

NOT CORRECT
Kinks in the drain hose will create water traps.

NOT CORRECT Do not place the end of the drain hose in water or in containers that collect water. This will prevent proper drainage.

PLUG THE UNUSED DRAIN HOLE

To prevent unwanted leaks you must plug the unused drain hole with the rubber plug provided.

Page 21

BEFORE PERFORMING ANY

WARNING

ELECTRICAL WORK, READ THESE BEFORE PERFORMING ANY ELECTRICAL

REGULATIONS

OR WIRING WORK, TURN OFF THE

1. All wiring must comply with local and national MAIN POWER TO THE SYSTEM.

electrical codes, regulations and must be

Step 6: Connect signal and power cables

installed by a licensed electrician. 2. All electrical connections must be made
according to the Electrical Connection Diagram located on the panels of the indoor and outdoor units. 3. If there is a serious safety issue with the power supply, stop work immediately. Explain your reasoning to the client, and refuse to install the unit until the safety issue is properly resolved.

The signal cable enables communication between the indoor and outdoor units. You must first choose the right cable size before preparing it for connection. Cable Types
· Indoor Power Cable (if applicable):
H05VV-F or H05V2V2-F
· Outdoor Power Cable: H07RN-F or H05RN-F

4. Power voltage should be within 90-110% of · Signal Cable: H07RN-F

rated voltage. Insufficient power supply can

NOTE: In North America, choose the cable type

cause malfunction, electrical shock, or fire. 5. If connecting power to fixed wiring, a surge
protector and main power switch should be installed.

according to the local electrical codes and regulations.
Minimum Cross-Sectional Area of

6. If connecting power to fixed wiring, a switch

Power and Signal Cables (For reference)

or circuit breaker that disconnects all poles and has a contact separation of at least 1/8in (3mm) must be incorporated in the fixed wiring. The qualified technician must use an approved

(Not applicable for North America)

Rated Current of Nominal Cross-Sectional

Appliance (A)

Area (mm²)

circuit breaker or switch.

3 and 6

0.75

7. Only connect the unit to an individual branch

6 and 10

1

circuit outlet. Do not connect another appliance

10 and 16

1.5

to that outlet. 8. Make sure to properly ground the air conditioner. 9. Every wire must be firmly connected. Loose
wiring can cause the terminal to overheat,

16 and 25 > 25 and 32 > 32 and 40

2.5 4 6

resulting in product malfunction and possible fire. 10. Do not let wires touch or rest against refrigerant
tubing, the compressor, or any moving parts within the unit. 11. If the unit has an auxiliary electric heater, it must be installed at least 1 meter (40in) away from any combustible materials. 12. To avoid getting an electric shock, never touch

CHOOSE THE RIGHT CABLE SIZE
The size of the power supply cable, signal cable, fuse, and switch needed is determined by the maximum current of the unit. The maximum current is indicated on the nameplate located on the side panel of the unit. NOTE: In North America, please choose the right cable size according to the Minimum Circuit

the electrical components soon after the power Ampacity indicated on the nameplate of the unit.

supply has been turned off. After turning off

the power, always wait 10 minutes or more before you touch the electrical components.

WARNING ALL WIRING MUST BE PERFORMED

STRICTLY IN ACCORDANCE WITH THE

WIRING DIAGRAM LOCATED ON THE

BACK OF THE INDOOR UNIT’S FRONT

PANEL .

Indoor Unit Installation

Page 22

1. Open front panel of the indoor unit. 2. Using a screwdriver, open the wire box cover
on the right side of the unit. This will reveal the terminal block.
Front view Terminal block
Wire cover
Screw Cable clamp
Back view (For some units only)
Knock-out panel
NOTE: For the units with conduit tube to connect the cable, remove the big plastic konck-out panel to create a slot through which the conduit tube can be installed. For the units with five-core cable, remove the middle small plactic knock-out panel to create a slot through which the cable can exit. Use needle nose pliers if the plastic panel is too difficult to remove by hand.
3. Unscrew the cable clamp below the terminal block and place it to the side.
4. Facing the back of the unit, remove the plastic panel on the bottom left- hand side.
5. Feed the signal wire through this slot, from the back of the unit to the front.
6. Facing the front of the unit, connect the wire according to the indoor unit’s wiring diagram, connect the u-lug and firmly screw each wire to its corresponding terminal.
CAUTION
DO NOT MIX UP LIVE AND NULL WIRES This is dangerous, and can cause the air conditioning unit to malfunction.
7. After checking to make sure every connection is secure, use the cable clamp to fasten the signal cable to the unit. Screw the cable clamp down tightly.
8. Replace the wire cover on the front of the unit, and the plastic panel on the back.

NOTE ABOUT WIRING
THE WIRING CONNECTION PROCESS MAY DIFFER SLIGHTLY BETWEEN UNITS AND REGIONS.
Step 7: Wrappiping and cables Before passing the piping, drain hose, and the signal cable through the wall hole, you must bundle them together to save space, protect them, and insulate them(Not applicable in North America). 1. Bundle the drain hose, refrigerant pipes, and
signal cable as shown below:
Indoor Unit
Space behind unit
Refrigerant piping Insulation tape
Signal wire Drain hose
DRAIN HOSE MUST BE ON BOTTOM Make sure that the drain hose is at the bottom of the bundle. Putting the drain hose at the top of the bundle can cause the drain pan to overflow, which can lead to fire or water damage.
DO NOT INTERTWINE SIGNAL CABLE WITH OTHER WIRES While bundling these items together, do not intertwine or cross the signal cable with any other wiring. 2. Using adhesive vinyl tape, attach the drain
hose to the underside of the refrigerant pipes. 3. Using insulation tape, wrap the signal wire,
refrigerant pipes, and drain hose tightly together. Double-check that all items are bundled.
DO NOT WRAP ENDS OF PIPING When wrapping the bundle, keep the ends of the piping unwrapped. You need to access them to test for leaks at the end of the installation process (refer to Electrical Checks and Leak Checks section of this manual).
Page 23

Indoor Unit Installation

Step 8: Mount indoor unit
If you installed new connective piping to the outdoor unit,do the following:
1. If you have already passed the refrigerant piping through the hole in the wall, proceed to Step 4.
2. Otherwise, double-check that the ends of the refrigerant pipes are sealed to prevent dirt or foreign materials from entering the pipes.
3. Slowly pass the wrapped bundle of refrigerant pipes, drain hose, and signal wire through the hole in the wall.
4. Hook the top of the indoor unit on the upper hook of the mounting plate.
5. Check that unit is hooked firmly on mounting by applying slight pressure to the left and right-hand sides of the unit. The unit should not jiggle or shift.
6. Using even pressure, push down on the bottom half of the unit. Keep pushing down until the unit snaps onto the hooks along the bottom of the mounting plate.
7. Again, check that the unit is firmly mounted by applying slight pressure to the left and the right-hand sides of the unit.
If refrigerant piping is already embedded in the wall, do the following:
1. Hook the top of the indoor unit on the upper hook of the mounting plate.
2. Use a bracket or wedge to prop up the unit, giving you enough room to connect the refrigerant piping, signal cable, and drain hose.

3. Connect drain hose and refrigerant piping (refer to Refrigerant Piping Connection section of this manual for instructions).
4. Keep pipe connection point exposed to perform the leak test (refer to Electrical Checks and Leak Checks section of this manual).
5. After the leak test, wrap the connection point with insulation tape.
6. Remove the bracket or wedge that is propping up the unit.
7. Using even pressure, push down on the bottom half of the unit. Keep pushing down until the unit snaps onto the hooks along the bottom of the mounting plate.

UNIT IS ADJUSTABLE
Keep in mind that the hooks on the mounting plate are smaller than the holes on the back of the unit. If you find that you don’t have ample room to connect embedded pipes to the indoor unit, the unit can be adjusted left or right by about 30-50mm (1.18-1.96in), depending on the model.

30-50mm (1.18-1.96in)

30-50mm (1.18-1.96in)

Move to left or right

Indoor Unit Installation

Page 24

Installation

Outdoor Unit Installation

Install the unit by following local codes and regulations , there may be differ slightly between different regions.

60cm (24in) above

30ocnmle(1f2t in) 200cimn f(7ro9nint)

3f0rocmm (b1a2cikn)wall 60ocnmri(g2h4tin)

Installation Instructions ­ Outdoor unit
Step 1: Select installation location Before installing the outdoor unit, you must choose an appropriate location. The following are standards that will help you choose an appropriate location for the unit.
Proper installation locations meet the following standards:
Meets all spatial requirements shown in Installation Space Requirements above.
Good air circulation and ventilation
Firm and solid–the location can support the unit and will not vibrate
Noise from the unit will not disturb others
Protected from prolonged periods of direct sunlight or rain
Where snowfall is anticipated, take appropriate measures to prevent ice buildup and coil damage.

DO NOT install unit in the following locations:
Near an obstacle that will block air inlets and outlets Near a public street, crowded areas, or where noise from the unit will disturb others Near animals or plants that will be harmed by hot air discharge Near

References

Read User Manual Online (PDF format)

Read User Manual Online (PDF format)  >>

Download This Manual (PDF format)

Download this manual  >>

BLUERIDGE User Manuals

Related Manuals