CAENels F1K5-DISS Magnet Power Supply Systems User Manual
- June 3, 2024
- CAENels
Table of Contents
F1K5-DISS
4-Quadrant Operation Crate for
FAST-PS-1K5 Digital Bipolar
Power Supply Series
User’s Manual
All Rights Reserved
© CAEN ELS s.r.l.
Rev. 1.1 – November 2022
F1K5-DISS Magnet Power Supply Systems
This manual covers the following optional units:
- F1K5D4100015 – F1K5-DISS-100-15 – 4-Quadrant Operation Crate for FAST-PS-1K5 ±100 A @ ±15 V
- F1K5D4050030 – F1K5-DISS-50-30 – 4-Quadrant Operation Crate for FAST-PS-1K5 ±50 A @ ±30 V
For technical assistance please refer to the following contact:
CAEN ELS S.R.L.
SS14 km 163,5 in Area Science Park – loc. Basovizza 34149 – Trieste (TS) –
Italy
(Building Q1)
Phone: +39 040 375 6610
Fax: +39 040 375 6611
Document Revisions
Revision | Date | Comment |
---|---|---|
0.1 | September 30th, 2020 | Preliminary |
1.0 | January 11th, 2021 | First Release |
1.1 | November 22nd, 2022 | Added UKCA compliance logo |
Safety information
The following table shows the general environmental requirements for a correct operation of instruments referred in this User’s Manual:
Environmental Conditions | Requirements |
---|---|
Environment | Indore use |
Operating Temperature | 0°C to 45°C |
Operating Humidity | 20% to 80% RH (non-condensing) |
Altitude | Up to 2000 m |
Pollution degree | 2 |
Overvoltage Category | II |
Storage Temperature | -10°C to 60°C |
Storage Humidity | 5% to 90% RH (non-condensing) |
The following symbols are used within this manual or are reported in the box and along this manual:
- Caution: Risk of Electrical Shock
- Caution : Documentation must be consulted in all cases where this symbol is marked
- **** Indicates ground terminal
- **** Protective Ground Conductor Terminal
- Caution: Hot Surface
- WARNING The WARNING sign denotes a hazard. An attention to a procedure is called. Not following the procedure correctly could result in personal injury. A WARNING sign should not be skipped and all indicated conditions must be fully understood and met.
- CAUTION The CAUTION sign denotes a hazard. An attention to a procedure is called. Not following procedure correctly could result in damage to the equipment. Do not proceed beyond a CAUTION sign until all indicated conditions are fully understood and met.
CAEN ELS s.r.l. will repair or replace any product within the guarantee period
if the Guarantor declares that the product is defective due to workmanship or
materials
and has not been caused by mishandling, negligence on behalf of the User,
accident or any abnormal conditions or operations.
Please read carefully the manual before operating any part of the instrument
WARNING
Do NOT open the BOX TOP COVER
CAEN ELS S.r.l. declines all responsibility for damages or injuries caused by
an improper use of the Modules due to negligence on behalf of the User. It is
strongly recommended to read thoroughly this User’s Manual before any kind of
operation.
CAEN ELS S.r.l. reserves the right to change partially or entirely the
contents of this Manual at any time and without giving any notice.
Disposal of the Product
The product must never be dumped in the Municipal Waste. Please check your
local regulations for disposal of electronics products.
WARNING
- Do not use this product in any manner not specified by the manufacturer. The protective features of this product may be impaired if it is used in a manner not specified in this manual.
- Do not use the device if it is damaged. Before you use the device, inspect the instrument for possible cracks or breaks before each use.
- Do not operate the device around explosives gas, vapor or dust.
- Always use the device with the cables provided.
- Turn off the device before establishing any connection.
- Do not operate the device with the cover removed or loosened.
- Do not install substitute parts or perform any unauthorized modification to the product.
- Return the product to the manufacturer for service and repair to ensure that safety features are maintained
Introduction
This chapter describes the general characteristics and main features of the
F1K5DISS power dissipation unit.
1.1 F1K5-DISS Overview
The FAST-PS-1K5 by CAEN ELS is an independent current- or voltage-
controlled digital bipolar power supply module. Standalone, the FAST-PS-1K5 is
a bipolar power converter able to work in the positive current/positive
voltage and negative current/negative voltage quadrants only continuously.
The F1K5-DISS unit adds current/voltage sinking capabilities to the system so
that a FAST-PS-1K5 together with a F1K5-DISS becomes a full 4-quadrant system
capable not only sourcing but also sinking up to 1.500 W.
There are two commercially available models for the F1K5-DISS unit that can be
matched to specific models of the FAST-PS-1K5 power unit:
Model Name | Current | Voltage | Compatible with |
---|---|---|---|
FAST4R100015 | ±100 A | ±15 V | FAST-PS-1K5 100-15 |
FAST4R050030 | ±50 A | ±30 V | FAST-PS-1K5 50-30 |
Table 1: F1K5-DISS models
The F1K5-DISS module is compact and fits in a single 19-inch 1U standard
crate. The whole system together with a FAST-PS-1K5 fits in a 19” – 3U slot.
Installation
This chapter contains the main instructions for initial inspection and
preparation for use.
2.1 Preparation for Use
In order to put the system into operation, the power supply must be connected
to an appropriate AC source. The AC source voltage should be within the power
supply specification. Do not apply power before reading this manual. Table 2
Error! Reference source not found.lists the basic setup procedure. Follow the
instructions in the given sequence to prepare the power supply for use.
Step | Checklist | Description |
---|---|---|
1 | Initial inspection | Physical inspection of power supply |
2 | Mounting | Installing the power supply, ensuring proper ventilation |
3 | F1K5-DISS Connections | Connect the dissipation unit to main power converter |
4 | FAST-PS-1K5 Connections | Connect the power supply to the AC source |
5 | First switch-on | Switch-on checkout procedure |
6 | FAST-PS-1K5 Configuration | Configure full current sink capability |
Table 2: Installation checklist
2.2 Initial Inspection
Prior to shipment, this F1K5-DISS unit was inspected and found free of
mechanical or electrical defects. Upon unpacking of the power supply, inspect
for any damage which may have occurred in transit.
The inspection should confirm that there is no exterior damage to the power
supply such as broken switches or connectors and that all panels and display
are not scratched or cracked. Keep all packing material until the inspection
has been completed. If damage is detected, compile the RMA form available to
the CAEN ELS web site.
2.3 Mounting
The FAST-PS-1K5 & F1K5-DISS system can be used either as a desktop unit or as
a rack-mount device since the unit form factor is designed to be installed in
a standard
3U 19-inch cabinet.
CAUTION
This system is fan cooled, the air intake is at the front panel and the
exhaust is at the rear panel. Upon installation allow cooling air to reach the
front panel ventilation inlets. Allow minimum 10 cm of unrestricted air space
at the front and 20 cm on the rear of the unit.
Rack Mounting
The FAST-PS-1K5 & F1K5-DISS system is designed to fit in a standard 19”
equipment rack.
CAUTION
Use a support bar to provide adequate support for the power supply.
Desktop Use
The FAST-PS-1K5 & F1K5-DISS system can be used as desktop unit but every
precaution must be used to avoid touching the output connectors because of the
high energy source.
WARNING
User shall protect output contacts by placing the FAST-PS1K5 & F1K5-DISS
system inside a closed rack or by restricting the access to the back side.
2.2.3 Thermal Management
F1K5-DISS converts electrical into thermal energy, considerable amount of
heat is generated. This fact must be taken into consideration when installing
the system. Fans cool the dissipation element by drawing air from front side
and exhausting it out the back, therefore minimum 10 cm of unrestricted air
space at the front and 20 cm on the back of the unit must be provided.
If specific application requires high power dissipation for long periods (>
800 W; > 10 min) it is recommended to install FAST-PS-1K5 and F1K5-DISS with
1U of clearance in between to mitigate heating problems and using blanking
panels to prevent mixing hot and cold air. Proper equipment rack ventilation
shall be provided to reduce ambient temperature not exceed 45 °C on the front
of the units.
WARNING
Do not touch the hot surfaces. The temperature of the back and top-right
surfaces may be high when the unit is operating at high power.
2.4 F1K5-DISS connection
WARNING
Turn off the AC input power before making or changing any rear panel
connection. Ensure that all connections are securely tightened before applying
power. There is a potential shock hazard when using a power supply with a
rated output greater than 60 V
2.4.1 Power Connection
It is recommended to use original cables that are contained with the unit.
If custom longer connection is required keep wire size of main power
connection at 16 mm 2 (AWG 6) and not longer than 1m. Strip wires insulation
back 15 mm and push them straight into the power plug and screw them tightly.
Be sure that they fit well and make a good contact.
Connect main power cable to DISSIPATIVE UNIT connector on FAST-PS-1K5 and to
FAST-PS-1K5 connector on dissipation unit. Secure cable assembly with
connectors screws on both ends.
2.4.2 Status Cable Connection
Connect the supplied coaxial cable to STATUS BNC connector on F1K5-DISS side
and AUX2 BNC connector on FAST-PS-1K5 side.
2.5 FAST-PS-1K5 Connections
For installation and connection instructions refer to FAST-PS-1K5 User’s
Manual, chapter 2.
2.6 FAST-PS-1K5 Configuration
FAST-PS-1K5 in standalone configuration has 100 W of negative power. Even
if dissipation unit is connected to main power converter 100 W limit is still
active and system will go in fault if this limit is exceeded. To achieve full
current sinking capability when using dissipative unit this option must be
enabled in FAST-PS-1K5 configuration. Power converters purchased together with
F1K5-DISS dissipation unit have this option already enabled by default.
To enable (or disable) full current sinking capability use FAST-PS-1K5’s web
server interface. Under CONFIG tab select INTERNAL MEMORY. Set Value of ID 54
(Dissipative enabled on AUX2 at start-up) to “1”. For more information on
configuration refer to Remote Control Manual.
Whenever changing this parameter FAST-PS-1K5 must be power-cycled for new
value to be valid.
2.7 Front Panel LED Indicator
The F1K5-DISS has front panel LED indicator as shown in the Figure 3.
The front panel indicator and its behaviour is outlined in the following table:
Color | Action | Meaning |
---|---|---|
GREEN | Blinking, LONG interval | Ready, not sinking any current |
GREEN | Blinking, SHORT interval | Active, sinking current, below 1.000 W |
ORANGE | Blinking, SHORT interval | Active, sinking current, above 1.000 W |
Color | Action | Meaning |
--- | --- | --- |
ORANGE | Blinking, LONG interval | Ready, not sinking any current, high |
temperature
RED| Solid| Error condition
RED, GREEN, ORANGE, OFF| Blinking in circular fashion| Firmware Update mode
Table 3 – Front-panel LED behaviour
Status LED in green indicates the module is connected properly and fully
operational. Solid red at power-on means that wrong FAST-PS-1K5 was detected.
LED will flash orange to indicate warnings; the module is sinking current when
flashing interval is short, warning may be for the following reasons: high
power, high temperature or fan malfunction. When interval is long the module
is not active, warning indicates fan malfunction or high temperature of the
module caused by just finished power dissipation. Solid red is reserved for
major errors: thermal overload, too high input current, too high input power
or hardware failure. In all this cases dissipation unit reports error to FAST-
PS-1K5 which then disables its output and activates crowbar function to
prevent potential or further damage.
When in firmware update mode LED will be changing colours. FAST-PS-1K5 will
automatically disable its output.
Firmware Update
If a firmware update is necessary, this can be done using Firmware-Update.exe
utility. It requires the C run-time libraries (CRT), if not already installed
you can do it by running “vcredist_x86.exe” which can be found in the same
directory ad firmware update utility on supplied USB Flash drive.
3.1 Firmware Update Procedure
Save the file to your computer and note the directory where the file is saved.
A firmware update is a file with a “.hex” extension. Preferably save it in the
same directory of Firmware-Update.exe utility.
To perform the update F1K5-DISS must be connected to FAST-PS-1K5 which must be
switched on with its output disabled. Never try to update if FAST-PS-1K5
output is not disabled.
Connect the computer’s USB port to the F1K5-DISS’s USB-B port with a USB
cable.
Using Windows Device Manager identify COM port number – locate Ports (COM &
LPT) in the list, expand it and check for USB Serial Port. Open Command Prompt
(CMD) and change directory to folder where Firmware-Update.exe resides. Launch
update utility with following parameters:
- a
firmware update filename with path – mandatory - p COM
e.g. COM9 – mandatory - b
baud rate – optional
Firmware update takes ~30 seconds with default baud rate. After successful completion front panel status led turns blinking green and the module is ready to use.
Technical Specifications
The main technical specifications for the F1K5-DISS units are hereafter listed in Table 4:
Technical Specifications | F1K5D4100015 | F1K5D4050030 |
---|---|---|
Continuos Maximum Power Dissipation | 1500 W | 1500 W |
Maximum Case Temperature (Input air = 45 °C) | 110 °C | 110 °C |
Maximum Air Exaust Tmperature (input air = 45 °C) | 80 °C | 80 °C |
Fault Temperature (RED LED) | 100 °C | 100 °C |
Maximum Input Voltage | 30 V | 50 V |
Maximum Input Current | 60 A | 40 A |
Status “Error” Voltage | 1.5 V | |
Status “Warning” Voltage | 3 V | |
Status “OK” Voltage | 5 V | |
Weight | 7 kg | |
Maximum Acoustic Noise (at 1-m distance) | 68 dBA |
Table 4: Technical Specifications
4.2 Mechanical Dimensions
The mechanical dimensions of the F1K5D4100015/F1K5D4050030 units are shown (in
mm) in Figure 4:
All Rights Reserved
© CAEN ELS s.r.l.
Rev. 1.1 – November 2022
This product is & compliant.
CAEN ELS s.r.l.
in AREA Science Park
S.S. 14 km 163,5 – loc. Basovizza – 34149 Trieste (TS)
Italy
Mail:info@caenels.com
Web:www.caenels.com
Registered office: via Vetraia 11 – 55049 Viareggio (LU) – Italy
Documents / Resources
|
CAENels F1K5-DISS Magnet Power Supply
Systems
[pdf] User Manual
F1K5-DISS, Magnet Power Supply Systems, F1K5-DISS Magnet Power Supply Systems,
Power Supply Systems, FAST-PS-1K5
---|---
References
- CAEN ELS - Precision Power Supplies and Electronic Instruments
- CAEN ELS - Precision Power Supplies and Electronic Instruments
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>