INSTALLATION

  1. Operate the fan in the speed used for heat or cooling.
  2. Record the supply static pressure.TEC-Air-Flow-Method-Pressure-Matching with-D-FIG2
  3. Remove the filter and install duct blaster. Ensure there is no bypass around duct blaster.
  4. Turn on the system and (if necessary) the Duct Blaster to match previous measured supply static. Record the flow through a two-channel manometer once pressure is matched.