TEC Air Flow Method Pressure Matching with Duct Blaster Instruction Manual

June 3, 2024
TEC

TEC Air Flow Method Pressure Matching with Duct Blaster

INSTALLATION

  1. Operate the fan in the speed used for heat or cooling.
  2. Record the supply static pressure.TEC-Air-Flow-Method-Pressure-Matching with-D-FIG2
  3. Remove the filter and install duct blaster. Ensure there is no bypass around duct blaster.
  4. Turn on the system and (if necessary) the Duct Blaster to match previous measured supply static. Record the flow through a two-channel manometer once pressure is matched.

Read User Manual Online (PDF format)

Read User Manual Online (PDF format)  >>

Download This Manual (PDF format)

Download this manual  >>

TEC User Manuals

Related Manuals