TEC Air Flow Method Pressure Matching with Duct Blaster Instruction Manual
- June 3, 2024
- TEC
Table of Contents
TEC Air Flow Method Pressure Matching with Duct Blaster
INSTALLATION
- Operate the fan in the speed used for heat or cooling.
- Record the supply static pressure.
- Remove the filter and install duct blaster. Ensure there is no bypass around duct blaster.
- Turn on the system and (if necessary) the Duct Blaster to match previous measured supply static. Record the flow through a two-channel manometer once pressure is matched.
Read User Manual Online (PDF format)