C-TEC CFP704-4 CFP Standard 4 Zone Conventional Fire Alarm Panel User Manual
- October 30, 2023
- C-TEC
Table of Contents
CFP Standard 4 Zone Conventional Fire Alarm Panel
Part No. CFP704-4
User Manual
Overview
Certified to EN54 parts 2, 4 and 13, C-TEC’s CFP 4 zone conventional fire alarm panel offers an array of user and installer-friendly features at a very competitive price. Supplied in an attractive flush or surface mountable plastic enclosure, it includes two detector zones, four conventional sounder circuits, class change and alert inputs, on-board fire and fault relays and combined keypad/keyswitch entry. A wide range of engineering functions are also provided including selectable zone delays, coincidence and non-latching zone facilities. Comprehensive test and fault finding facilities are also provided. Optional repeaters and relay expansion boards also available.
More Information
- Third-party certified to EN54 parts 2 and 4 by the Loss Prevention Certification Board (LPCB) and EN54 part 13 certified by Kiwa Telefication.
- Intuitive user-friendly interface with colour-coded buttons and combined keypad/keyswitch entry.
- Manufactured by C-TEC in the UK.
- Four detector zone circuits.
- Four conventional sounder circuits.
- Integral 1.5A EN54-4/A2 compliant switch mode PSU.
- Wide range of engineering functions including zone test, coincidence, zone delay and non-latching zones.
- Two on-board relays (Fire and Fault).
- Two open-collector outputs (Remote and Reset).
- ‘Class change’ and alert inputs.
- Installer-friendly design.
- Attractive flush or surface mountable plastic lid and enclosure – no bezel required.
- Low 25mA quiescent current.
- Multiple indicators.
- System expansion connections provided for up to eight two-wire repeaters (one CFP761 network card required per system), optional CFP relay boards and optional EN54-13 compliant sounder circuit boards.
- Space for two x 12V 3.3Ah VRLA batteries.
- Fully compatible with C-TEC’s ActiV fire detectors, sounders and visual alarm devices.
Technical Specifications
Approvals/certifications| Certifed to EN54 Parts 2 & 4 by the LPCB., Certified
to EN54-13 by Kiwa Telefication.
---|---
Mains supply| 230V 50/60Hz.
Mains rated current| 350mA maximum.
Internal power supply| 19V-28.5V (27V nominal). Ripple 7V maximum (battery
fault).
Total output current limited to| 1.5A @ 230Vac (ImaxA eq 146mA).
Quiescent current| 25mA (mains failed, internal sounder active, PSU & gen
fault LED lit)
Max battery size and type| 2 x 12V 3.2Ah VRLA connected in series. Min.
battery size 1.2Ah.
No. of detector zone circuits| 4 (Max. length per circuit is 500m).
Call point resistor value| 470 to 680Ω.
Max. devices per detector zone| 25 detectors (or 32 detectors/manual call
points combined).
No. of conventional sounder circuits| 4 (Max. length per circuit is 500m).
EOL resistor value| 6800Ω 5% Tol. 0/25W (blue, grey, red, gold).
Alarm voltage| 27V max, 20V min (final battery voltage)
Max. sounder output current| 4 x 200mA (800mA total).
Auxiliary relays| Two: (1) Aux. Fire; (2) Fault. Volt free single pole
changeover. Max. switch current 1A; Max. switch voltage 30Vdc.
Open collector outputs| Two: (1) Reset (Active during reset cycle); (2) Remote
(Active during any unsilenced fire condition
provided all relevant delays have expired). Max. sink current 30mA, Max. open
circuit voltag
Other outputs| 24V Aux. Power (Protected by a resettable fuse. 100mA min. hold
current. Resets when fault removed).
Auxiliary inputs| Two: (1) ‘Class Change’ (constant sounders); (2) Alert
(pulsed sounders). Connect to 0V to trigger, Max.
input voltage 27V (non-latching)
Engineer (AL3) functions| Program coincidence (double knock); Invoke One Man
Walk Test; Program delays; Set up zones for nonlatching operation; Program
sounders to resound (or not resound) when a new zone enters al
Expansion connections| Yes – for optional network driver cards (one required
per repeater system), relay output cards and
EN54-13 sounder circuit interface boards.
Product dimensions (mm)| 380 W x 235 H x D 96mm (hole required for flush
mounting = 367 W x 220 H x 75 D mm. No bezel required).
Construction & finish| Plastic lid and base; RAL7035 textured
IP Rating| IP30.
Weight| 1.75kg (without batteries)
Operating conditions/temperature| -5ºC to +40ºC. Max relative humidity: 95%.