Sol-Ark 5K, 8K, 12K, 15K Pytes Instructions

June 3, 2024
Sol-Ark

Sol-Ark-logo

Sol-Ark 5K, 8K, 12K, 15K Pytes

Sol-Ark-5K-8K-12K-15K-Pytes-product-image

Connect the cables

Connect the power cables between inverter and battery or the Busbars as mentioned.

Figure 2.1 Sol-Ark Battery Connector

As for the cable gauge that connects the busbar to the inverter, 4/0 gauge power cable is commended for Sol-Ark 15K model and 3/0 gauge power cable is commended for 8K/12K model.
A standard ethernet cable can be used for the communication since Sol-Ark inverter pin assignment is the same as Pytes E-BOX battery.

Figure 2.2 Sol-Ark Standard ethernet cable

Set the DIP Switch of every master battery as Figure 2.3 shown.

Figure 2.3 Sol-Ark inverter DIP Switch Setting

Plug in the battery end into the CAN port of the Pytes E-BOX battery and plug in the inverter end into Sol-Ark Battery CANBus Port as shown in the Figure 2.4.

Figure 2.4 Sol-Ark inverter comm cable connection

Program the inverter
Press the gear icon on the top right of the screen and then press battery set up menu.

Figure 2.5 Sol-Ark Batt Setup

Set the battery parameters
  • Batt Capacity: 100Ah per unit
  • Max A Charge/Discharge: 185A is the max amps that Sol-Ark 8K/12K mode supports and the corresponding number is 275A for 15K mode. Fill in the max amps or (50Aunit numbers) which is lower. (For example, there are three Pytes E-BOX batteries and one 12K Sol-Ark inverter in a system. The max amps of 12K is 185A and three batteries can support 150A(503). So the number should fill in is 150A.)
  • Select “Use Batt% Charged”.
  • Enable “BMS Lithium Batt” and set its value to “00”.
  • Turn on “Activate Battery”.
    Note that enabling BMS Lithium Batt 00 will adjust some values and make other values adjustable (like the temperature coefficient above). Just ignore those values – the BMS is in control.

Figure 2.6 Batt Setup

Sol-Ark-5K-8K-12K-15K-Pytes-06

Program the Charge tab in Batt Setup
See the right picture in Figure 2.6.

  • Start%: 15%
  • A: Same as the Max A Charge in Batt Seting
  • Float V: 55.6V
  • Absorption V: 56V
  • Equalization V: 56V

Program the Discharge tab in Batt Setup

  • Shutdown: 10%
  • Low Batt: 20%
  • Batt Empty: 47.5V

Figure 2.7 Batt Discharge Setup

Please refer to the Sol-Ark inverter manual for more setting such as Grid Setup, PV Setting, Time-of-Use, etc.

Confirm Inverter-Battery Communication

Figure 2.8 communication confirm

References

Read User Manual Online (PDF format)

Loading......

Download This Manual (PDF format)

Download this manual  >>

Sol-Ark User Manuals

Related Manuals