Sol-Ark 8K-2P-N Outdoor Hybrid Inverter Owner’s Manual
- June 13, 2024
- Sol-Ark
Table of Contents
- 8K-2P-N Outdoor Hybrid Inverter
- Upon Receiving Shipment
- Wire Gauge Guide (copper)
- Wiring Diagrams
- Physical Installation
- Wi-Fi / Internet Connection
- GUI Screens
- Programming Guide
- Install Tips
- Batteries
- Troubleshooting Guide
- Install Verification Checklist
- Sol-Ark 8K Limited Warranty
- References
- Read User Manual Online (PDF format)
- Download This Manual (PDF format)
OUTDOOR SOL-ARK 8K-2P
INSTALL GUIDE & OWNER’S MANUAL
8K-2P-N Outdoor Hybrid Inverter
Disclaimer
UNLESS SPECIFICALLY AGREED TO IN WRITING, SOL-ARK:
(a) MAKES NO WARRANTY REGARDING THE ACCURACY, SUFFICIENCY, OR SUITABILITY OF
ANY TECHNICAL OR OTHER INFORMATION PROVIDED IN ITS MANUALS OR OTHER
DOCUMENTATION.
(b) ASSUMES NO RESPONSIBILITY OR LIABILITY FOR LOSS OR DAMAGE, WHETHER DIRECT,
INDIRECT, CONSEQUENTIAL, OR INCIDENTAL, WHICH MIGHT ARISE OUT OF THE USE OF
SUCH INFORMATION. THE USE OF ANY SUCH INFORMATION WILL BE ENTIRELY AT THE
USER’S RISK.
Sol-Ark cannot be responsible for system failure, damages, or injury resulting
from improper installation of their products.
The information included in this manual is subject to change without notice.
This version is for OUTDOOR MODELS ONLY; previous hardware versions of the
Sol-Ark 8K are not compatible with the wire diagrams and instructions
contained herein.
Warning Symbols
****| This symbol indicates information that, if ignored, could result in
minor injury or damage to the equipment.
---|---
| This symbol indicates information that, if ignored, could result in serious
injury, damage to the equipment, or death.
| This symbol indicates information that is important but not hazard-related.
Warnings
Read this entire document before installing or using the Sol-Ark 8K
inverter. Failure to follow any of the instructions or warnings in this
document can result in electrical shock, serious injury, or death.
Damage to the 8K inverter is also possible, potentially rendering it
inoperable.
High Life Risk Due to Fire or Electrocution – ONLY qualified persons
should install the Sol-Ark 8K inverter.
The system must have Ground connections and Neutral connections. Ground
MUST be bonded to Neutral ONLY ONCE in the circuit.
Solar PV+/PV- are UNGROUNDED. Note, you may ground PV Racking/Mounts,
but doing so directly to the Sol-Ark will likely result in damage in the case
of a direct lightning strike to the PV array.
DO NOT connect the grid to the Load Output Breaker.
DO NOT reverse the polarity of batteries. Damage WILL occur.
DO NOT exceed more than 500Voc on any MPPT on the Sol-Ark.
DO NOT use impact drivers to tighten any fasteners on the Sol-Ark.
MUST use Strain Reliefs ON ALL wires entering/exiting the Sol-Ark 8K
user area.
MUST use conduit (or double insulated wire) for AC Wires
entering/exiting Sol-Ark 8K user area.
ALL terminals/breakers including battery, MPPT, and AC breaker inputs
should only have one conductor connecting to them.
Upon Receiving Shipment
Inspect Shipment
A. Compare the package condition to the condition of the package in the photo
we sent you before it left our facility.
You must note any damage due to shipping with delivery driver before accepting
the package otherwise the shipping company will deny any claim.
B. If damaged, contact us immediately at
972-575-8875 Ext. 3
Component Guide
A. Limiter Sensors included: 5/8″ CT sensors x2 (Included)
B. Limiter Sensors if purchased: 15/16″ CT sensors x2 (Sold Separately)
C. Limiter Sensors if purchased: 2″ CT sensors x2 (Sold Separately)
D. Battery Temperature Sensor: for voltage adjustment
E. Battery Cable Toroid x2
F. CAT 5 cable for parallel communications
G. WIFI Dongle: For software updates and remote monitoring (use M4x10 screws
to hold in)
H. French Cleat: For wall mounting the Sol-Ark 8K
8K-2P-N
UL Model: “Sol-Ark-8K-48-ST”
Solar Input Power 11,000W
Max Allowed PV Power| 5,500W + 5,500W =11,000W
Max PV Power Delivered to Battery & AC Outputs| 8,000W
Max DC Voltage (Voc)| 500V @ 18A, 450V @20A
MPPT Voltage Range| 150-425V
Starting Voltage| 12W
Number of MPPT| 2
Max Solar Strings Per MPPT| 2
Max DC Current per MPPT (Self Lim-king)| 20A
Max AC Coupled Input (Micro/String Inverters)| 9,600W
AC Output Power 8kW On-Grid & Off-Grid
Connections| 120/240/208V Split Phase
Continuous AC Power to Grid (On-Grid)| 8,000W 33.3A-L (240V)
Continuous AC Power to Load (Off- Grid)| 8,000W 33.3A-L (240V)
Surge AC Power 10sec
Surge AC Power 100ms| 16,000VA L-L (240V)
25,000VA L-L(240V)
Fault Current 100ms| 104A L-L (240V)
Parallel Stacking| No
Frequency| 60/50Hz
Continuous AC Power with Grid or Generator| 15,120W 63A L-L (240V)
7,560W 63A L-N (120V)
CEC Efficiency| 96.5% (Peak 97.5%)
Idle Consumption Typical—No Load| 60W
Sell Back Power Modes| Limited to Household/Fully Grid-Tied
Design (DC to AC)| Transformerless DC
Response Time (Grid-Tied to Off-Grid)| 4ms
Power Factor| +/- 0.9 – 1.0
Battery (optional) Output Power 8,000W
Type| Lead-Acid or Li-Ion
Nominal DC Input| 48V
Capacity| 50 — 9900Ah
Voltage Range| 43.0 — 63.0V
Continuous Battery Charging Output| 185A
Charging Curve| 3-Stage w/ Equalization
Grid to Batt Charging Efficiency| 96.%
External Temperature Sensor| Included
Current Shunt for Accurate % SOC| Integrated
External Gen Start Based on Voltage or %SOC| Integrated
Communication to Lithium Battery| CanBus & RS485
General
Dimensions (H x W x D)| 30.0″ x 18.3″ x
10.0″
Weight| 78 lbs
Enclosure| NEMA 3R
Ambient Temperature| -25-55°C, >45°C Derating
Installation Style| Wall-Mounted
Wi-Fi & LAN Communication| Included
Standard Warranty (verified by HALT Testing)| 5 Years (10 yr ext)
Contact Sales@sol-ark.com for 10 year extension
Protections & Certifications
Electronics Certified Safety by SGS Labs to NEC & UL Specs – NEC 690.4B & NEC
705.4/6| Yes
Grid Sell Back — UL1741-2010/2018, IEE- E1547a-2003/2014, FCC 15 Class B,
UL1741SA, CA Rule 21, HECO Rule 14H| Yes
PV DC Disconnect Switch — NEC 240.15| Integrated
Ground Fault Detection — NEC 690.5| Integrated
PV Rapid Shutdown Control — NEC 690.12| Integrated
PV Arc Fault Detection — NEC 690.11| Integrated
PV Input Lightning Protection| Integrated
PV String Input Reverse Polarity Protection| Integrated
AC Output Breakers – 63A| Integrated
250A Battery Breaker / Disconnect| Integrated
Surge Protection| DC Type II / AC Type II
Temperature Derating
DC: 90C-100C Shutdown @ 100C
AC: 75C-82C Shutdown @ 82C
Sol-Ark 8K Torque Values Application Note
Load Breaker | 26.5 IN Lbs | 3 NM |
---|---|---|
Grid Breaker | 26.5 IN Lbs | 3 NM |
Gen Breaker | 26.5 IN Lbs | 3 NM |
Neutral / Ground Busbars | 26.5 IN Lbs | 3 NM |
Cover Screws | 26.5 IN Lbs | 3 NM |
Battery Connection | 90.0 IN Lbs | 10 NM |
**** Do Not Use Impact Drivers to Tighten Any Fasteners on the Sol-Ark.
Wire Gauge Guide (copper)
PV input: 10AWG
All AC Inputs/Outputs: 6-4AWG
All Sensors: 20-24AWG
CT Sensors: 10′ Wire Included
Batt Temp Sensor: 6′ Wire Included
RJ45 Cable: 7′ Included (Extendable up to 20′)
All Sensor Inputs
0’ – 100’: 24 AWG
100’ – 400’: 23 AWG CAT 6
Extensions for Limiter Sensors must be twisted pair
(Shielded CAT6 Recommended)
Wiring Diagrams
These Single Line Diagrams (SLDs) are examples of common use-cases for Sol-Ark
inverters.
Sol-Ark does not provide custom diagrams; however, you may contact support
@sol-ark.com for any questions about an
existing SLD.
CT Sensors are optional, but necessary to enable Peak Shaving. See pg. 16 and pg.34 for additional info.
|
---|---
Physical Installation
Inverter Components
A. LCD Touch Screen
B. Power Button
C. PV DC Disconnect Switch
D. 250A Battery Breaker
E. Battery Terminals (+/-)| F. Sensor Pin-Out Board
G. Comms/Paralleling Ports
H. AC Breakers (Grid 63A/Gen 50A/Load 63A)
I. Neutral/Ground Bus Bar
J. MPPT Charge Controllers
---|---
Deciding Backup Circuits
A. We recommend subpanels and require them if you have Arc-Fault / GFI
breakers
B. Ensure you keep the inverter within its amperage limits
- ON-Grid = 63A Continuous (pass-through)
- OFF-Grid = 33.3A Conutuous | 67A Peak (10s) | 104A Peak (100ms)
C. Verify each load circuit by measuring typical and max Amps with a clip-on
Amp meter. Amps x 120V = Watts
D. Install a subpanel for backup loads if you have Arc-Fault / GFI breakers,
NOT a multi-circuit transfer switch
Single System Installs
A. Install Double Pole 60A breaker in Main Panel for Grid In/Out
B. Best practice to install at the opposite end of the bus bar from the main
breaker, which is usually at the bottom of the breaker panel (see figure
above)
Mounting the Sol-Ark
A. Keeping in mind Sol-Ark’s dimensions, find a suitable location for the
system (s)
B. NEMA 3R rating for Outdoor installations
** C. PROTECT the LCD screen from excessive UV exposure
D. System weight = 78lbs (35kg). Securely attach to the wall. Affix a mounting
board to studs using 6-8 screws
E. Using 2-3 screws + washers (choose screw length and surface type) to mount
the French Cleat to the board/wall
F. Mount Sol-Ark on the installed French Cleat / Ensure Sol-Ark is level and
sits properly
G. Add two screws for the bottom mount
Integrating Batteries (Sol-Ark POWERED “OFF”)**
A. Connect batteries to Sol-Ark as shown in Fig. B below
B. Install included toroids (Part e. on pg. 4) on battery input cables as
shown in Fig. A to the rightC. Ensure the built-in battery disconnect is OFF
while connecting batteries, or arcing may occur
**** Sol-Ark 8K is a 48V system. Do NOT wire the battery bank to any other
nominal voltage.
When using 12V batteries do not exceed FOUR (4) batteries in series.
When using other battery chemistries, stay within the voltage range: MIN 43V-
MAX 63V
E.M.P Systems Only
Suppressor installation
-
If your system was purchased with Lightning / EMP Hardening, the vast majority of protection is in the Sol-Ark.
However, you also have EMP suppressors that get installed on the power cords of appliances that are connected to the transfer switch. Although not critical, it is recommended they be installed as close as possible to the appliance. -
You also have EMP suppressors that get installed on both solar panel wires with a zip tie. Closer to the panel is better.
If you purchased the panels from us, we already installed >150kV/m protection inside the solar panels.
Connecting Solar Panels
A. Sol-Ark has DUAL MPPTs for two separate PV input pairs
B. MAX PV input = 11kW (± 5%) / system | 5.5kW / MPPT | MAX 500VOC PV | MAX
ISC /MPPT 25A (limiting to 20A)
Damage will occur if PV VOC > 550V
C. Parallel strings per MPPT must be the same Voltage
i. PV1 A/B must be the same voltage if using both strings
ii. Panels on the same MPPT CAN face different directions
D. Ground the panel MOUNTS/FRAMES to any ground in the Home via 12AWG wire
E. IF using Y-Connectors: Running two strings in parallel, totaling 20A (self-
limiting)
F. Connect the solar panel strings as indicated by the following diagram:
Each string can use separate wires
String minimum is usually 5 panels or 175V
Integrating a Generator
Generators < 10kW (GEN Breaker)— See Diagram 1-2
A. ONLY supports 240V / 208V generators | 50A breaker
B. Connect the generator output to the “GEN” input breaker in the SolArk 12K
user area
C. THD of less than 15% preferred but not required
Standby Generators > 10kW (GRID Breaker)— See Diagram 1 (OFF-GRID)
A. Supports 220V / 240V / 208V generators | Depends on “Grid Type” selection |
63A breaker
B. Off-Grid / Whole-home Generator on ATS installations require selecting “GEN
Connected to Grid Input”
Home Screen → Gear Icon → Grid Setup → Sell Control → GEN Connected to Grid
Input
C. Off-Grid = turn “Grid Sell” off | Only need CT’s (on Gen lines) if using
Grid Peak Shaving (see below)
Increase Gen/Sol-Ark efficiency
- Select “Limited to Load”
- Select “General Standard”
- Increase Grid frequency range: 55-65H
Weekly Gen Exercise
If the Sol-Ark is up to date with MCU version xx73 or newer, and your
generator has two-wire start compatibility, you will experience weekly
generator tests.
These tests occur at 8AM (local time) every Monday by default.
The test takes approximately 20 minutes to complete. During that time, the
generator will auto-start and auto-stop.
The generator will not provide power during this test. The generator may
charge the batteries if the batteries reach designated generator start point,
however.
Grid Peak Shaving Mode (For Gen Connected to Grid Breaker)
A. Prevents the Sol-Ark from overloading generators
B. Must place the CT sensors so that they measure L1 and L2 of the generator’s
output, pointing arrows on the CT’s towards the generator
C. Sol-Ark contributes power above the “Power” value threshold to prevent
overloading the generator
D. This mode will auto-adjust the Grid Charge Amperage to avoid overloads
Gen Start V or % (Grid Start if Gen on Grid Breaker)
Value batts need to reach BEFORE automatically starting a generator connected
to the GEN breaker to charge the battery bank.
**** Sol-Ark will NOT charge batteries from a generator until the batteries
reach this value.
Gen Start A (Grid Start if Gen on Grid Breaker)
This is how many amps (DC) you can pull specifically from the Generator to
charge the batts. To ensure you do not overload a small Generator, you will
want to adjust the GEN or GRID Start A value. Multiply value by # of Sol-Arks
for actual current value into batteries.
Suppose PV production = 0W | Disabled TOU | Enabled Grid/Gen Charge: the
batteries will be charged to “full” using the Grid or a Generator (if
available) until the battery bank accepts only 5% of its rated capacity in
Amperes. This value correlates to roughly 90-93% full for most batteries and
is the generator’s default “OFF” signal. If producing PV, the system will use
PV to charge the batteries to 100% full instead.
Integrating Sensors and Accessory Placement
Sensor Pin Out (Located in Sol-Ark user
(1,2) Batt Temp: Battery Temperature Sensor has no polarity and is needed for
voltage correction when using lead acid batteries.
(+3, -4) CT1 & (+5,-6) CT2: Current transformers used for limited to home mode
and peak shaving
(7,8) Gen Start Relay: Two wire start for generators, simple open or closed
relay
(9,10) Gen On Relay: Not currently used
(B 11, B 12) Emergency Stop: Short these pins to initiate emergency stop. This
will shutdown AC output from the inverter and initiate rapid shutdown of the
PV.
(+13, -14) Optional 12V input signal for RSD
(+15, -16) 12V power supply for RSD transmitters: such as TIGO and Midnite
Rated for a maximum of 1.2W (100mA @12V)
Battery Temperature Sensor
- Place between batteries with tape (See Fig. C).
- This sensor has no polarity and helps perform voltage charging adjustmentsand capacity calculations.
Note: Lithium Batteries do NOT require a Temperature sensor.
Limiter Sensors (CT Sensors)
- Install sensors on incoming electrical service wires on L1 and L2 (see Diagrams Section)
- Limited To Home Mode (meter zero) and Peak Shaving Modes require CT sensors
- CT winding default ratio is 2000:1; however, this ratio is programmable
- To ensure the sensors will fit, please check the wire size before ordering
GEN Start Signal (Two-Wire)
- The signal comes from a normally open relay that closes when the Gen Start state is active
CANbus & RS485
- To connect batteries to the Sol-Ark 8K via RJ45, you need to splice the end connecting to the Sol-Ark 8K
- Use the middle two conductors
- RS485 is SunSpec draft 4 (will not work with draft 3)
Wi-Fi Antenna (Dongle)
Remote monitoring and software updates require an internet connection through
the Wi-Fi dongle
Emergency Stop Signal & PV Rapid Shutdown Signal
Pins 11 and 12 use a normally open & latching switch to connect the two
emergency stop pins that cut off the RSD power supply when triggered, thus
stopping the inverter AC output.
Pins 15 and 16 provide the 12V / 100mA signal power lost when the Sol-Ark
shuts down using the front button.
Emergency Stop Diagram (Only available on select hardware versions | Shown
with TIGO TS4)
Rapid Shutdown: TIGO TS4-A-O | TIGO TS4-A-F | TIGO TS4-O | TIGO TS4-O-DUO
| APsmart RSD S-PLC / RSD-D
- The Built-in 12V power supply in the user area of the Sol-Ark (Pins 15 and 16) is rated for 100mA (1.2W)
- Transmitter fits inside the user area of the Sol-Ark 8K but can cause interference (sometimes requires placing it outside of the user area)
- TIGO Optimizers are compatible with the Sol-Ark 8K (Do not use the built in 12V Power supply in the Sol-Ark user area to Power the Tigo Optimizer TX transmitter)
Misc. Hardware Recommendations
Disconnect / Transfer Switches: 200A Non-Fused Transfer Switch Model #TC10324R
(GE) | 200A Fused Transfer Switch Model #DG224NRK (Eaton)
PV Fuses: 15A PV MC4 in-line fuse holder (ZOOKOTO or DPJ)
Electrical Panel: Any appropriately rated panel for your loads (Check local
hardware stores for recommendations)
Powering-Up and Testing the Sol-Ark 8K
Check the voltage on each PV input circuit
A. Should be no higher than 500Voc Temp. corrected
B. DO NOT connect PV+ OR PV- to GND
C. Verify polarity (backward polarity shows 0V)
Turn ON with one of three sources of power:
- PV
- Grid
- ON/OFF Battery
Check Grid Input Voltage
A. Measure L1 to Neutral and L2 to Neutral. Ensure 120Vac
B. Measure L1 and L2Ensure 240Vac
C. Check Neutral and Ground are ~0V AC
D. Verify L1 voltage on AC in/out is 0Vac with the main L1 connection in the
panel Same for L2
Power Cycle Sequence
- Turn on the Built-In battery disconnect
- Make sure that Sol-Ark 8K is properly connected to the batteries, panels, grid, etc. (see system wiring diagram).
- Turn on grid power breakers.
- Press the power button on the front of the unit.
- Make sure Solar panel inputs are not connected to Ground, then Turn on DC disconnect switch.
- Turn on load breakers.
- Reverse the steps to turn off
Check Battery Voltage
A. Turn on the battery switch (if using a Lithium battery)
B. Turn on the built-in battery disconnect in the user area
C. The voltage should be 45Vdc-60Vdc
Provide Power to Sol-Ark
A. Turn on Grid Breaker and Load Breaker
B. Turn PV disconnect switch to the “ON” position
C. Press the ON/OFF Button on the front, and the blue light should turn on
Indicator LED’s
DC
A. Green = DC Solar Panels are producing
B. Off = Solar Panels are not producing
AC
A. Green = Grid (or Gen or AC Coupled) is Connected
B. Off = grid is not Connected
Normal
A. Green = Sol-Ark 8K is working properly
B. Off = Sol-Ark 8K is not working properly
Alarm
A. Red = Alarm, check the alarms menu
B. Off = No alarms
Wi-Fi / Internet Connection
Remote Monitoring Setup
Ethernet Dongle
A. Open the dongle enclosure and thread the ethernet cable through the hole
and plug into the RJ45 port
B. Reassemble the dongle housing and plug dongle into Sol-Ark and secure with
screws
If all is well, you will see solid red and green lights
C. Register the dongle via the app or www.mysol-ark.com
Wi-Fi (Via Cell Phone or computer)
A. Plug Wi-Fi dongle into Sol-Ark
B. Using your device look for an “EAP” network containing the last 5 digits of
the dongle S/N
C. Password: 12345678
D. Follow the instructions in the upcoming pages
You can access PowerView on a computer with the following link: http://www
.mysol-ark.com**
Download PV Pro App**
iPhone: (Will only show up as PV Pro)
https://apps.apple.com/lk/app/powerview-pro/id1247121391
Android
https://play.google.com/store/apps/details?id=com.elinter.
app.powerview&hl=en_US&gl=US
Attention Installers
If you plan to add an install to your installer account for monitoring
multiple installs, you must first make the plant under the customer’s account.
Once created, the customer can share the plant, with Manager permissions, to
the installer via the app (“…”under My Plants) or webpage (press the “…” next
to the plant name in Power View).
PV Pro App Tutorial Video
https://www.youtube.com/watch?v=3zp1-V3z-
iY&list=PLlRPtB4nbqt9MIVfNuSX3lMioz88V6Onq&index=3| PV Pro Website
Tutorial Video https://www.youtube.com/watch?v=3zp1-V3z-
iY&list=PLlRPtB4nbqt9MIVfNuSX3lMioz88V6Onq&index=3
---|---
Create an Account and Sign In
Add a Plant
Connect the System to the Internet
It takes about 60sec for the lights to turn on after setup Red LED: Connected to Sol-Ark and has power Green LED: Connected to Internet and Server Flashing Green LED: Connected to router but not server (usually a VPN or firewall issue)
Start Monitoring The Data
IP Address Setup Instructions (PC or Smart Phone)
Please Note that this method only achieves internet connectivity. For
registration and account management please use the app and/or www.mysol-
ark.com
Connect to the Dongle Network
A. Settings → Wi-Fi → Select the Network with EAP- ##### (The last 5 digits of
your SN number)
Password: 12345678
Disclaimer: The Wi-Fi dongle does not have internet; You still need to be connected to the dongle for this process.
Login to Web Portal using ANY Search Browser
A. Open Google or Safari → type in the search bar: 10.10.10.1
B. Scroll Down to “Wi-Fi Connection”
C. Press “Scan” to search local networks
Select Your HOME Network
A. Find the home network
B. Enter personal Wi-Fi Password
C. DO NOT SELECT DONGLE NETWORK
D. Select “Connect”
Disclaimer
Connecting the dongle via the IP address only connects the dongle to the
internet
YOU MUST STILL CREATE AN ACCOUNT VIA THE POWER VIEW APP
Save Your Information
If Successful you should see a Red and Green light on the Dongle showing a
successful connection.
Red LED: Connected to Sol-Ark and has power.
Green LED: Connected to Internet and Server
Flashing Green LED: Connected to router but not server (usually a VPN or
firewall issue)
GUI Screens
Main Menus
Basic Setup
Battery Setup
Grid Setup
Programming Guide
Sol-Ark Menus
Main Screens (Touchscreen)
Detailed Volts View
-
Top row = Total power for column
-
Middle Row = Line 1/PV1 voltage, Amps, and Watts
(note: PV Voltage not to exceed 500V) -
Bottom Row = Line 2/PV2 voltage, Amps, and Watts
(note: PV Voltage not to exceed 500V) -
Batt Temperature will show -20°C if the temperature sensor is not connected. Batt SOC % = % batteries are charged
-
DC Temp = Temperature of DC conversion electronics
- Batt → AC
- PV → Batt
- AC → Batt
-
AC Temp = Temperature of AC conversion electronics
- Batt → AC
- PV → AC
-
Grid Column
- If selling to the Grid, Grid Watts = negative
- If buying from the Grid, Grid Watts = positive
- HM = power detected by the external current sensors on the entire home L1 & L2
- LD = power detected using internal sensors on AC grid in/out breaker
Note: Reversed Grid Watt values may indicate incorrectly installed
current sensors (reversed polarity). See Page 34.
PV Graphical View
A. Displays power production over time for the PV array
B. Use up/down buttons to navigate between days
C. Month view, Year view, and Total view
Grid Graphical View
A. Displays power drawn from and sold to the grid over time
B. Bars above the line indicate power bought from the grid
C. Bars below the line indicate power sold back to the grid
This view can help determine when the peak power is used in the Home and for
Time of Use programing
System Setup Menu
A. ID = LCD serial #. Support uses the Wi-Fi serial #.
B. COMM = LCD software version
C. MCU = Inverter software version
Basic Setup
Display
A. Brightness adjustment
B. Auto dim (must be enabled for the warranty to cover LCD screen)
C. Enable/disable BEEP
Time
A. Set date and time for the system
B. Set up to 3 seasons for Time of Use to follow
Gen Peak Shaving (Gen Limit Power)
Set the threshold at which the Sol-Ark will contribute to the generator to
prevent large loads overloading the generator.
Load Limit Power
Set the total AC Output of the Sol-Ark, excess power will be curtailed. The
default value is always the Maximum output of the inverter.
Grid Peak Shaving
Set the Sol-Ark’s threshold to begin contributing power to keep the power
drawn from the grid below the threshold.
CT Ratio
Set the CT ratio; Default value is 2000/1. DO NOT change this value unless you
speak with support, use of 3rd party CT sensors require our permission to not
void warranty.
UPS Time
Set the delay to Sol-Ark’s UPS transfer time; When set to 0ms, the UPS
transfer time will be 4ms.
Parallel (connecting multiple systems)
This tab does not apply to the Sol-Ark 8K, as it is a single-system solution.
System Alarms
A. Lists all recorded System alarms in chronological order
Battery Setup
Batt
Batt Capacity: enter the size of the battery bank connected to the
system. Series = add Voltage | Parallel = add Amp-Hours
Max A Charge: set the max charge rate for the batteries (This also sets
PV → Battery charge rate)
Suggest 20%-30% of battery capacity for lead-acid
Max A discharge: set max discharge for battery bank (In off-grid mode,
the battery bank will discharge 120% of this value for 10 seconds before the
inverter shuts down to prevent battery damage)
TEMPCO: Temperature coefficient used in conjunction with the batt temp
sensor to adjust optimal voltages for leadacid batteries
Use Batt V Charged: displays battery charge in terms of voltage
Use Batt % Charged: Battery voltage can be misleading for determining the
% Charged. So, we use algorithms measuring power in and out to measure a true
value for % Charged. It compensates for aging batteries also.
Charge
Float V: Set value appropriate for the batteries connected to the system
Absorption V: Set value suitable for the batteries connected to the
system
- Absorption will stop at 2% of the capacity of the battery bank and drop to float
- Ex: 400Ah battery would be 8A
Equalization V: Set value appropriate for the batteries in use.
Days: the period between equalization cycles
Hours: period taken to equalize batteries
Note if Hours = 0 system will not equalize the batteries
Gen Charge: uses the gen input of the system to charge the battery bank
from an attached generator.
Start V: voltage at which system will AutoStart a connected generator to
charge the battery bank
Start percentage: Percent S.O.C at which system will AutoStart a
corresponding generator to charge the battery bank
A: Charge rate from the attached Generator in Amps (DC)
Size this value according to the generator size
Grid Charge: uses Grid input to charge batteries from grid or generator
Gen Exercise Cycle (Day & Time): Set a weekly Gen exercise schedule. (Day
of the week/Time/Duration Length) Gen must have two-wire start connected to
Sol-Ark. To disable the exercise, set the duration length to 0 min.
Discharge
Shutdown V: battery voltage at which the inverter will shut down (battery
symbol on the home screen will turn red)
Low Batt: Low battery voltage (battery symbol on the home screen will
turn yellow)
Restart: battery voltage at which AC output will resume
Batt Resistance: used in % SOC batt calculations
Batt Charge Efficiency: used in % SOC batt calculations
Batt Empty V: sets reserve capacity and improves % SOC calculations. It
is not Batt_I adjusted
(Recommendations: 45V for AGMs, 48V for Lithium Iron Phosphate)
Smart Load (Gen Breaker)
A. This mode utilizes the Gen input connection as an output that only receives
power when the battery exceeds a userprogrammable threshold.
B. Enable “Use gen input as load output” to power high power loads such as a
water heater, irrigation pump, AC unit, pool pump, etc.
Smart Load OFF Batt
Battery voltage at which the Gen Load will stop receiving power
Smart Load ON Batt
Battery voltage at which the Gen Load will start receiving power
Using Gen load for a water heater, we recommend that only one leg (120V) be
connected to the bottom element. This significantly reduces the power
consumption of the water heater while retaining core functionality (it will
heat water, only slower).
Gen Load is limited to 50A at 240V (Do not exceed!)
Solar Watts is for on Grid
A. The system waits to turn on smart load until enough PV power is produced
(when on grid)
AC Coupling Settings (” For AC Coupled Input”)
A. To use the Gen input breaker as an AC coupled input, check the “For AC
Coupled Input” box (this feature will also work with “Grid-Tied” Inverters)
B. The meaning of Smart Load OFF Batt and Smart Load ON Batt change in this
mode
Smart Load OFF Batt: The SOC at which the AC coupled inverter(s) are shut
down when in off-grid mode 90% recommended
Smart Load ON Batt: The SOC at which the AC coupled inverter(s) are
turned on when in off-grid mode 60%-80% recommended
When On-Grid, the AC-coupled inverter will always be on, and the will sell any
extra power back to the grid.
AC Coupled PV Arrays will not work WITHOUT grid sell enabled (while grid is
available).
To use the LOAD breaker for AC coupling grid tied inverter(s)
i. You must select “For Micro Inverter Input”
ii. The Gen Breaker is not used (even though the GEN breaker is not physically
being used for this mode, AC coupling on the LOAD breaker prevents the use of
the GEN breaker)
iii. Wire as show in the preceding example diagram labeled “Load side AC
coupling example”
**** Some load-side AC coupling installs will require a line side tap instead
of the 50A breaker shown in the example diagram
Grid Setup
Limiter
Grid Sell: maximum watts sold to grid
Limited To Home : Limits power produced by the system to match the demand
of the Home
Limited To Load: Limits power produced by the system to match the demand
of connected loads
Time Of Use: Control battery behavior w/ grid available
Time: When the System will sell batt/PV power to the Grid or Home
Power(W): Max watts called from the battery only at each time
Batt: The battery voltage or % at which the system will limit selling to
the Grid or Home from the battery. The system will drain the battery until
reaching that percent/voltage.
Charge: Enables grid/gen charging up to the voltage or percentage
specified on the line during a selected period. PV will always charge 100%. If
using a generator, select the charge box for the times that may need the
generator, and the Gen will charge the battery to the voltage of percentage
specified in the “Batt” column.
Sell: The sell check box allows the battery to be discharged for grid
sell-back for that time slot
Note: If you need the batteries to never charge from the grid, uncheck
the “Grid Charge” box under the charge tab of the battery menu.
Sell Control
General Standard: uses Protect Parameters in table
UL 1741 & IEEE1547: Enables sell compliant functionality
UL1741SA: Enables wider Freq, Voltage, and Power Factor
GEN connect to Grid Input: Enable if Generator connects to the AC Grid
breaker
Zero Export Power: Power drawn from the grid at all times
Grid Input
Grid Frequency: Select the Grid Frequency connection
Grid Type:
- 220V Single Phase (Call us before using)
- 120/240V Split Phase (North America)
- 120/208V 3 Phase
Protect Parameters: (when Settings when the system will connect/disconnect from the grid. UL 1741 & IEEE1547 do not use these parameters.
We recommend widening the frequency range when connecting a generator to the
grid breaker (55-65Hz)
If 120/208V, the L1 and L2 are phase specific. So, you may have to swap Grid
L1 L2 for 208V applications.
Inverter power cycle is required each time the input/output voltage is changed
Selecting Power Mode
Sol-Ark 8K will simultaneously use various power sources available to meet
loads demand. The following power modes allow the user to determine the power
sources available to the Sol-Ark 8K.
Limited Load / Self Consumption
A. Sol-Ark will only power loads connected to it.
B. It will not produce more power than the connected loads require.
C. This mode will neither sell back to the Home nor Grid.
Limited To Home (Zero-Metering)
Main Menu → System Settings → Grid Setup → Limiter → Limited to Home
A. Pushes power to the whole Home without selling back any excess to the grid
(no net metering agreement required)
B. This mode requires the use of the limiter sensors
C. Power source priority is the same as Grid Sell Back
Grid Sell
Main Menu → System Settings → Grid Setup → Limiter → Grid Sell
A. This mode allows Sol-Ark 8K to sell back any excess power produced by the
solar panels to the grid.
Power source priority:
- Solar Panels
- Grid
- Generator (Manual)
- Batteries (until reaching programmable % discharge)
Simultaneously select Grid Sell and Limited to Home
Load (light bulb) icon on the home screen now includes both the load breaker
power and the home’s consumption.
Time Of Use (using batteries during peak power times)
Main Menu → System Settings → Grid Setup → Limiter → Time Of Use
A. Use the batteries to reduce power consumption from the grid during a user
programable peak pricing time.
Power source priority:
- Solar Panels
- Batteries (programmable % discharge)
- Grid (control when Grid charges)
- Generator
FreqVolt (UL 1741SA must be enabled in “Sell Control” tab)
Puerto Rico Grid Compliance Settings:
Kauai Grid Compliance Settings:
HECO Grid Compliance Settings for O’ahu, Maui, Hawai’i:
HECO Grid Compliance Settings for Lana’I and Moloka’i:
PowFac
Power Factor is programmable from 0.8 – 1.0
Limiter Sensor Automatic Setup
Requires Batteries, AC coupled panels must be off while detecting, and does
NOT work for 208V installs.
If you do not have batteries or are in 208V mode: verify CT sensor placement
manually.
A. Install limiter sensors as previously described (shown in all diagrams as
well). Battery and grid connections also required before starting auto-setup.
B. Navigate to the “Advanced” Tab of the Basic Setup screen (follow the
directions below to get there)
A. Touch the gear icon → Touch the Basic Setup button → Select the Advanced
tab (see Fig. C)
C. Select “Auto detect Home Limit Sensors” and press “OK”
D. Wait for the Sol-Ark to finish its learning process (Sol-Ark will alternate
sell back between legs and magnitude automatically determining the correct
settings for the sensors)
E. Verify sensors were correctly configured (see Fig. D) if they are not
correct, repeat the learn function
Verifying proper sensor direction:
- Any loads in the home will show a positive HM (+) value in Watts
- Turning on solar panels and enabling Grid Sell should show a negative HM (-) in Watts if you are producing more power than the loads are consuming
- If you turn on limited power to Home mode, then HM: ~0 Watts to zero the meter (system matches the loads to within 99%)
If you installed limiter sensors (CTs) for Limited To Home selling mode, verifying the proper sensor placement and direction is critical. Remove one sensor from the main L1 connection, and the power should drop to 0W.
Install Tips
Off-Grid Install Tips
Sol-Ark 8K will automatically operate in Off-Grid Mode without the grid (under
the same power priority as TOU).
A. Limiter Sensors are not required for completely Off-Grid installs unless
using Grid Peak Shaving with a Gen connected to Grid input breaker.
B. The Grid input breaker on the Sol-Ark should be used as the Generator input
(4-30kW generators) so that you maintain Smart Load output capability when
off-grid. Smart Load will allow you to run high-power non-essential appliances
(hot water, dehumidifier, heat pump, irrigation pump) on solar power instead
of batteries. Therefore, you will use Grid Charge (default) in the Battery
Setup/Charge menu.
C. When off-grid, there is no need for a transfer switch: connect the load
output of the Sol-Ark to the whole home.
D. Do not use Grid Sell or Limited To Home Modes Off-Grid. Only Limited power
to load (default).
E. The Auto Generator start functions as a 2-wire switch (closes the circuit
when needing charging)
i. Auto Gen-start will be triggered when the battery voltage or percent
reaches the level programmed in the battery setup menu. Then, the generator
will continue to charge the batteries until they are about 95% full (this
percentage is not programmable) before turning the generator off.
ii. When using the Sol-Ark to control a generator, an exercise function will
turn on the generator once a week on Monday mornings at 8 AM by default
F. We recommend changing the “Grid Reconnect Time” under the Sell control tab
of the grid setup menu to 30 seconds; otherwise, the Sol-Ark will not charge
from the generator until it has been on for at least 5 minutes per the default
value of 300 seconds.
G. Under setup for Grid/Sell Control, select General Standard and “GEN connect
to Grid Input.” Then go to Grid input to widen the input frequency range to
55-65Hz to work with any frequency generator.
H. If you would like to use a wind turbine in conjunction with the Sol-Ark 8K,
the turbine must have a 48V charge controller with a dump load to prevent
overcharging the batteries. Connect the charge controller on the turbine to
the battery bank the Sol-Ark is using, and the turbine will help charge the
batteries.
I. Don’t forget to set the Battery capacity and reasonable charge rates.
Grid-Tie / No Battery Install Tips
A. Under Battery setup, select no Battery & disable Activate Battery (or
system will beep).
B. Note: a whole system power cycle is required when changing the battery to
no battery settings.
C. Under Grid Setup, select Grid Sell.
D. Touch Battery Icon to see the Detailed Volts View to verify your inputs &
outputs.
Batteries
Battery Charging Information
4-Stage Charging
The MPPT has a 4-stage battery charging algorithm for rapid, efficient, and
safe battery charging. The figure below shows the stage sequence.
Bulk Charge Stage
In the Bulk Charge stage, the battery is not at a 100% state of charge and has
not yet reached the Absorption voltage setpoint. The controller will deliver
100% of available solar power to recharge the battery.
Absorption Stage
When the battery has reached the absorption
voltage setpoint, we use constant-voltage
regulation to maintain battery voltage at the absorption setpoint, preventing
heating and excessive battery gassing. The battery is allowed to come to a
full state of charge at the absorption voltage setpoint. Absorption lasts
until batteries charge at 2% of the programmed Ah size.
Float Stage
After the Absorption stage charges the battery fully, the MPPT reduces the
battery voltage to the float voltage setpoint. If batts have 100% charge,
there can be no more chemical reactions, and all the charging current turns
into heat and gassing. The float stage provides a meager rate of maintenance
charging while reducing the heating and gassing of a fully charged battery.
The purpose of float is to protect the battery from long-term overcharge.
Battery Charging Setpoint Examples (48V)
Default
Battery Type| Absorption Stage| Float Stage| Equalize Stage
(every 30 days 3hr)
---|---|---|---
AGM / PCC| 14.4v (57.6v)| 115v (53.6v)| 14.4v (57.6v)
Gel| 14.1v (56.4v)| 13.5v (54.0v)|
Wet| 14.7v (59.0v)| 13.7v (55.0V)| 14.7v (59.0v)
Lithium| 14.1v (54.6v)| 13.2v (54.3v)| 14.1v (54.6v)
Calculating Battery Bank’s Amp-Hours (PCC 230)
Battery Count| Voltage / Battery| Amp Hours /Battery| Total
Amp Hours @48V| Max Charge/Discharge Amp
---|---|---|---|---
4| 12V| 230Ah| 230Ah| 100A
8| 12V| 230Ah| 460Ah| 185A
12| 12V| 230Ah| 690Ah| 185A
16| 12V| 230Ah| 920Ah| 185A
- Batteries in series: ADD VOLTAGES
- Batteries in parallel: ADD AMP-HOURS
Sol-Ark PCC-230 Battery
Batt Capacity: 230Ah x #Parallel_Batteries
(1 parallel = 4 Batt in series, 2 = 8 Batt, 3 = 12 Batt, 4 =16 Batt)
Max A Charge: 100A x #Parallel_Batteries
Max A Discharge: 100A x #Parallel_Batteries
Max A Grid Charge: 50A x #Parallel_Batteries
TEMPCO: -5mV/C/Cell
Float V: 53.6V
Absorption V: 57.6V
Equalization V: 57.6V
Equalization Days: 30
Equalization Duration: 3 Hours
Recommended Shutdown V / Percentage: 47.0V & 20%
Recommended Low Batt V / Percentage: 47.5V & 35%
Recommended Restart V / Percentage: 52.0V & 50%
Battery Resistance: 35mOhms (8 Batt) or 25mOhms (16 Batt)
Battery Charge Efficiency: 99%
Battery Empty Voltage: 45V
Time | Watts | SOC | GridCharge |
---|---|---|---|
1:00AM | 1500*Par_Batts | 70% | |
5:00AM | 1500*Par_Batts | 70% | |
9:00AM | 1500*Par_Batts | 70% | |
1:00PM | 1500*Par_Batts | 100% | |
4:00PM | 1500*Par_Batts | 70% | |
9:00PM | 1500*Par_Batts | 70% |
These settings will charge the batteries off solar only.
Discharge the batteries down to a maximum of 70% full.
Limited To Home mode will not sell to the grid from the batteries (only the
home will use battery power). The 100% time slot is to ensure that the
batteries are properly cycled each day.
Generation 2 Fortress Battery-eVault18.5
Batt Capacity: 360Ah x #Parallel_Batteries
Max A Charge: 150A (100A for life) x #Parallel_Batteries
Max A Discharge: 160A x #Parallel_Batteries
Max A Grid Charge: 100A x #Parallel_Batteries
TEMPCO: 0mV/C/Cell
BMS Lithium Batt: 04
Float V: 54.2V
Absorption V: 54.4V
Equalization V: 55.5V
Equalization Days: 30
Equalization Duration: 1 Hours (tops off battery)
Recommended Shutdown V / Percentage: 51.3V & 20%
Recommended Low Batt V / Percentage: 51.7V & 30%
Recommended Restart V / Percentage: 51.9V & 40%
Battery Resistance: 5mOhms
Battery Charge Efficiency: 99%
Battery Empty Voltage: 46V
Time | Watts | SOC | GridCharge |
---|---|---|---|
1:00AM | 6000*Par_Batts | 40% | |
5:00AM | 6000*Par_Batts | 40% | |
9:00AM | 6000*Par_Batts | 40% | |
1:00PM | 6000*Par_Batts | 40% | |
5:00PM | 6000*Par_Batts | 40% | |
9:00PM | 6000*Par_Batts | 40% |
These settings will charge the batteries off solar only.
Discharge the batteries down to a maximum of 40% full.
Limited To Home mode will not sell to the grid from the batteries (only the
home will use battery power).
Simpliphi Power: PHI 3.8 Battery 48V
Batt Capacity: 75Ah x # Batt
Max A Charge: 37.5A x # Batt (20A for better lifespan)
Max A Discharge: 37.5A x # Batt (34A for better lifespan)
Max A Grid Charge: 20A x # Batt
TEMPCO: 0mV/C/Cell
BMS Lithium Batt: Not Selected
Float V: 55.6V
Absorption V: 56V
Equalization V: 56V
Equalization Days: 30
Equalization Duration: 2 Hours (tops off battery)
Recommended Shutdown V / Percentage: 50.2V & 20%
Recommended Low Batt V / Percentage: 50.6V & 30%
Recommended Restart V / Percentage: 51.0V & 40%
Battery Resistance: 24mOhms ÷ (battery Count)
Battery Charge Efficiency: 99%
Battery Empty Voltage: 46V
Time | Watts | SOC | GridCharge |
---|---|---|---|
1:00AM | 1000*Batts | 40% | |
5:00AM | 1000*Batts | 40% | |
9:00AM | 1000*Batts | 40% | |
1:00PM | 1000*Batts | 40% | |
5:00PM | 1000*Batts | 40% | |
9:00PM | 1000*Batts | 40% |
These settings will charge the batteries off solar only.
Discharge the batteries down to a maximum of 40% full.
Limited To Home mode will not sell to the grid from the batteries (only the
home will use battery power).
Blue Ion 2.0 Battery
Batt Capacity: 40Ah x #Parallel_Batteries
(4 Parallel = 160Ah, 6 = 240Ah, 8 = 320Ah)
Max A Charge: 160A w/ 4 Batteries, 185A w/ 6+
Max A Discharge: 160A w/ 4 Batteries, 185A w/ 6+
Max A Grid Charge: 160A w/ 4 Batteries, 185A w/ 6+
TEMPCO: 0mV/C/Cell
BMS Lithium Batt: 03 (eGauge) / 00 (Namaka Box)
Float V: 55.2V
Absorption V: 55.2V
Equalization V: 55.2V
Equalization Days: 30
Equalization Duration: 1 Hours (tops off battery)
Recommended Shutdown V / Percentage: 47.0V & 20%
Recommended Low Batt V / Percentage: 49.0V & 30%
Recommended Restart V / Percentage: 52.0V & 40%
Battery Resistance: 5mOhms
Battery Charge Efficiency: 99%
Battery Empty Voltage: 46V
Time | Watts | SOC | GridCharge |
---|---|---|---|
1:00AM | 8000*Par_Batts | 40% | |
5:00AM | 8000*Par_Batts | 40% | |
9:00AM | 8000*Par_Batts | 40% | |
1:00PM | 8000*Par_Batts | 40% | |
4:00PM | 8000*Par_Batts | 40% | |
9:00PM | 8000*Par_Batts | 40% |
These settings will charge the batteries off solar only.
Discharge the batteries down to a maximum of 40% full.
Limited To Home mode will not sell to the grid from the batteries (only the
home will use battery power). The 100% time slot is to ensure that the
batteries are properly cycled each day.
Dyness B4850 Battery Module
Batt Capacity: 50Ah x #Parallel_Batteries
Max A Charge: 50A (25A for life) x #Parallel_Batteries
Max A Discharge: 50A x #Parallel_Batteries
Max A Grid Charge: 50A x #Parallel_Batteries
TEMPCO: 0mV/C/Cell
BMS Lithium Batt: 01
Float V: 53.8V
Absorption V: 54.0V
Equalization V: 54.0V
Equalization Days: 30
Equalization Duration: 1 Hours (tops off battery)
Recommended Shutdown V / Percentage: 47V & 20%
Recommended Low Batt V / Percentage: 48V & 30%
Recommended Restart V / Percentage: 49V & 40%
Battery Resistance: 5mOhms
Battery Charge Efficiency: 99%
Battery Empty Voltage: 46V
Time | Watts | SOC | GridCharge |
---|---|---|---|
1:00AM | 2400*Par_Batts | 40% | |
5:00AM | 2400*Par_Batts | 40% | |
9:00AM | 2400*Par_Batts | 40% | |
1:00PM | 2400*Par_Batts | 40% | |
5:00PM | 2400*Par_Batts | 40% | |
9:00PM | 2400*Par_Batts | 40% |
These settings will charge the batteries off solar only.
Discharge the batteries down to a maximum of 40% full.
Limited To Home mode will not sell to the grid from the batteries (only the
home will use battery power).
MODBUS/RJ45 Application Note
BMS Lithium Batt Modes (Subject to Change):
00: CANBus Battery mode – Inverter also acts a ModBus slave with slave ID set
by “ModBus SN Setting” (Pg. 29)
01: Storz ModBus Protocol
02: Pylontech ModBus Protocol
03: Old Blue Ion + eGauge / Polarium ModBus Protocol
04: Fortress Power ModBus Protocol
05: Kilovault HAB ModBus Protocol
06: Battery or Battery Controller is ModBus master and writes battery data to
inverter’s BMS registers (not currently in use).
Find our full list of currently supported battery communications www.sol-
ark.com/battery-partners
Our Battery Communications Integration Guide can also be found here www
.sol-ark.com/support
Use the information below at your own risk; the warranty will not cover any
damage caused by the improper use of the communications protocols. Read-Only
Modbus Map available upon request at support@sol-ark.com
Combined RS-485 and CANBus
Pin 1 or 8 is RS-485 B- (Data -)
Pin 2 or 7 is RS-485 A+ (Data +)
Pin 4 CAN High
Pin 5 CAN Low
Pin 6 is GND
Baud 9600
8bits data
One stop bit, no parity
Does not require termination
Incorporating 3rd Party ModBus Devices:
If your device utilizes BMS Lithium Batt 00, you need to set the inverter
Modbus SN to 01. The default ModBus SN is 00.
Troubleshooting Guide
LCD is not powering on
- Check all connections- at least one of the following power sources is required: PV/Grid/Battery
- Try pressing the power button, touchscreen, or navigation buttons
Panels are connected, but DC Light is not on
- PV voltage must be 150V-425V | It’s night
Panels are not producing
- Check for proper wiring on all solar panel connections
- Turn PV disconnect “ON”
- Check that the PV input voltage is not greater than 425V
- If the system says PV = 0V, check the PV polarity
Panels are not producing much power
- PV Wire Strip Length: 5/8″. Your batteries are charged; you can test Grid Sell to verify.
The system does not keep batteries charged
- Check the charge setting in the Charge Menu
Auto Gen-Start is not working
- Check to make sure your generator is compatible with Auto Start
- Make sure that the Auto Gen Start wire is adequately connected to the Sol-Ark 8K and the generator
Normal LED isn’t on
- Sol-Ark 8K is in pass-through-only mode, with only a Grid connection.
- Sol-Ark 8K is not working correctly (Call us)
The alarm light is on
- Check the system alarms menu to identify the alarm
Grid HM value is negative when it should be positive (only applies in limited home mode)
- Limiter Sensors are backward, L1/L2 sensors are swapped, or incorrectly wired L1/L2 sensors. Try Auto Learn.
AC Overload Fault or Bus Unbalance Fault
- Check Transfer Switch/Subpanel wiring
- Check for large loads that consume more than the inverter rating (EX: AC units over 3 tons)
The system connects to the grid and quickly disconnects
- With a DMM, verify your Neutral wire connection (should be 0 Vac referenced to GND)
- Check your Freq is set to 60Hz, and the 8K measures 120V on L1 / L2 vs. N.
- If overloading: verify 120/240V grid input and load output wires are not swapped.
- If 120/208V, the L1 and L2 are phase-specific. So, you may have to swap Grid L1 / L2 for 208V applications.
DC Overload Fault
- Check PV voltage
- Make sure you have not wired more than two (2) solar strings in parallel
System is beeping
- Check the system alarms menu to see which alarm has been triggered. Most alarms will self-reset.
- There is no battery connected. If not using a battery, select no battery and disable activate batt in Batt menu.
- Turn off the center button, remove AC Grid and PV Power for the 30s (screen is dead), and then power up to fully reset the system.
Battery cable sparks when connected
- Put the built-in battery breaker in the off position before connecting or disconnecting the batteries.
The battery symbol on the home screen is red
- The battery is under-Voltage or over-Voltage
The battery symbol on the home screen is yellow
- The battery is low, or the charge/discharge current is close to the programmed limit (which is ok)
The grid symbol on the home screen is yellow
- Grid parameters are out of specified range, or the grid is down
System has restarted
- It happens if the system is overloaded, the battery voltage is greater than 63V, or the Software update
Batteries were connected backward
- The battery breaker will trip. It can cause damage!
Why is the LCD screen still on when the power button is off?
- If PV or Grid power, LCD stays on, but the inverter and loads are off.
The Batt % meter is not reaching 100%
- The system needs to go through a small discharge/charge cycle first to calibrate the battery
The generator setup is reading 0Hz
- Select “General Standard” instead of UL1741. Then widen the frequency range to 55Hz-65Hz.
Color Touchscreen is Frozen
- Press and hold the escape button [←] for 7-10 seconds
Troubleshooting Phasing Issues
If the Sol-Ark screen shows Grid Phase Wrong there is a phasing issue with
your wiring and it may cause overload faults (F18, F26, F34) even with the
Load breaker off and WILL CAUSE DAMAGE if left unchecked.
Single Sol-Ark: To locate the improperly wired phases, measure L1 to L1 (Top
Screws) between the Grid and Load breaker; you should see 0V AC. Repeat for L2
to L2 between the Grid and Load breaker. Attempt to correct the wiring until
you are only reading 0V AC between L1 to L1 & L2 to L2.
Make sure to correct both the Grid and Load wiring; they both need to be
correct.
If the error persists, you will need to check your AC wiring beyond the
inverter and may also need to verify that the phases are properly labeled
coming from your meter.
Sol-Ark 8K Error Codes
Fault | Instruction | Common Cause/Remedy |
---|---|---|
Fl | DC Inversed Failure | If you have parallel systems and turn one system off, |
you with get this notification. Not a fault.
F8| GFDI_Relay_Failure| Current Leakage from inverter AC output to Ground,
check Ground and neutral are connected at the main panel
F13| Grid_Mode_change| It can happen when not using batteries or if Grid Input
settings are changed. This is a notification, NOT a fault. If you switch from
No Batt to Battery mode, Power the System down completely to restart.
F15| AC_OverCurr_Failure| It is usually caused by Loads too large for the
inverter. If off-grid, the battery discharge amps are programmed too low.
Overloads can result in F15, F18, F20, or F26.
F16| GFCI_Failure| Ground fault. Check PV+ or PV- wiring (which must be
ungrounded). Exposed PV conductors + rain can also
cause. Check that the neutral line and Ground are not double-bonded (common
with portable generators).
F18| Tz_Ac_OverCurr_Fault| Overloaded the Load Output: reduce loads. Wiring
Short on the AC Side can also cause this error. Overloads can result in F15,
F18, F20, or F26.
F20| Tz_Dc_OverCurr_Fault| It is typically caused by DC current from the
battery that is too large (ex: 4 Ton AC Unit). Overloads can result in F15,
F18, F20, or F26.
F22| Tz_EmergStop_Fault| Initiated Emergency Stop; see sensor pinout table.
F23| Tz_GFCI_OC_Fault| PV Ground fault. Check PV+ or PV- wiring (which must be
ungrounded or damage can occur). Typically caused by pinched PV wire grounding
the PV+ or PV-. Grounded PV wire can cause F20, F23, or F26.
F24| DC_Insulation_Fault| An exposed PV conductor combined with moisture is
faulting (can cause F16, F24, F26).
F25| AC_Active_Batt_Fault| No battery connection to the Inverter and Activate
Battery is enabled. Disable Activate Battery in settings while no battery is
connected.
F26| BusUnbalance_Fault| Too much load on one leg (L1 or L2) Vs. the other leg
or DC loads on the AC output when off-grid. Grounded PV wire can cause F20,
F23, or F26.
F29| Parallel_CANBus_Fault| Usually, a communication error for parallel
systems, check cables and MODBUS addresses
F30| AC_MainContactor_Fault| Contact Sol-Ark.com
F31| Soft_Start_Failed| Soft Start of large motor failed
F34| AC Overload Fault| AC Overload or load shorted. Reduce heavy loads.
F35| AC_NoUtility_Fault| Grid connection lost
F37| DCLLC_Soft_Over_Cur| Software DC overcurrent
F39
F40| DCLLC_Over_Current| Hardware DC overcurrent
Batt_Over_Current| Batteries exceeded their current discharge limit
F41| Parallel_System_Stop| If one system faults in parallel, this normal fault
will register on the other units as they disconnect from grid
F45| AC_UV_OverVolt_Fault| Grid under voltage causes a disconnect. This will
self-reset when grid stabilizes.
F45| AC_UV_OverVolt_Fault| Cannot communicate with other parallel systems.
Check Master = 1, Slaves are 2-9, ethernet cables are connected.
F47| AC_OverFreq_Fault| Grid over Frequency (common in power outages) causes a
disconnect. Will self-reset when grid stabilizes.
F48| AC_UnderFreq_Fault| Grid under Frequency (common in power outages) causes
a disconnect. Will self-reset when grid stabilizes.
F55| DC_VoltHigh_Fault| PV may be higher than 500V. Battery voltage should not
be above 59V or 63V (depending on the model).
F56| DC_VoltLow_Fault| Batteries are overly-discharged, inverter is off grid
and exceeded programmed batt discharge current by 20%, or Lithium BMS has shut
down. If battery settings are incorrect, this can also happen.
F58| BMS communication fault| Sol-Ark is programmed to BMS Lithium Battery
Mode but cannot communicate with a BMS
F60| Gen_Volt_or_Fre_Fault| Generator Voltage or Frequency went outside the
allowable range
F61| Button_Manual_OFF| The parallel Slave system turned off without turning
off Master
F63| ARC_Fault| It can be a lousy PV connector/connection. And sometimes a
false alarm due to powerful lightning storms.
F64| Heatsink_HighTemp_Fault| Check the built-in fans are running; ambient
temp may be too high
Install Verification Checklist
For the installer to complete AFTER the system is operational. The purpose is to protect the installer, homeowner, and inverter.
-
The 8K installed in a location where the LCD is protected from direct sunlight and has 6″ clearance left and right for cooling Y/N
-
Are all the battery lugs tightened? Y/N
-
8K should connect to the grid, 8K 63A load/Grid breakers ON, batteries connected, PV input on, and ON button on. With the inverter running, the Backup load’s panel and Grid-connected:
A. Did any breakers trip? Y/N
B. Did the inverter overload? Y/N -
If you have problems, please take pictures of these and email them to support@Sol-Ark.com
A. Battery icon screen, showing detailed voltages (the screen shown below)
B. Sol-Ark 8K with batteries and user wiring area -
Load and solar test
A. Press the battery icon for the detailed voltages screen.
B. Is the batt temp sensor working? Y/N
C. Turn on many loads for the Backup circuits. Are solar panels producing enough power to match the load (provided there is enough sun)? Y/N
D. Program Full Grid Sell Mode. If there are enough panels and sun or light loads in the entire house, the Grid HM measurements will be negative on both L1/L2. Are they negative (solar selling back to the grid)? Y/N
E. Program limited power to home mode. The Grid HM sensors will be near zero or slightly positive. Are they both nzero and canceling out the whole home power? Y/N
F. You have verified the limit sensors are correctly installed. An auto-learn function corrects any mistakes in CT limiter wiring (provided you have batteries and in 120/240V). Program in the correct Grid mode the customer will use. -
Did you program the correct Ah for the battery bank and max Amps charge/discharge? Y/N
-
Did you program the correct battery charge voltages for your battery type? Y/N
-
Turn off the AC breaker so 8K is operating in an off-grid mode for several minutes. Are appliances still powered? Y/N
-
Turn off the PV input, running only on batteries for several minutes. Are appliances still powered? Y/N
-
Turn on the PV input and AC Grid inputs. Y/N
-
Did you set up the Wi-Fi plug to the customer’s internet? Y/N
-
Absolutely important for software updates. Did you help the customer register system on Monitoring App? Y/N
-
Does the customer have a standby generator or a small portable Generator? Y/N
A. Did you turn off UL1741/IEEE1547 (use General Standard) and reprogram grid freq. range to 55-65Hz? Y/N
B. Did you enable Gen charging and adequately set the charge current if using a small gas generator on Gen inputs? Y/N -
If EMP protected, did you install EMP Suppressors on essential appliance cords? Y/N
Installer Name ____
Customer Name ____
Installer Signature ____
Date ____
Customer Signature ____
Date ____
Sol-Ark 8K Limited Warranty
5-Year Limited Warranty for SOL-ARK (Portable Solar LLC) Products. Sol-Ark
provides a Five-year (5) limited Warranty (“Warranty”) against defects in
materials and workmanship for its Sol-Ark products (“Product”). The term of
this warranty begins on the Product(s) initial purchase date or the date of
receipt of the Product(s) by the end user, whichever is later. This must be
indicated on your installer’s invoice and bill of sale. This warranty applies
to the original Sol-Ark Product purchaser and is transferable only if the
Product remains installed in the original use location. Please call Sol-Ark to
let us know if you are selling your Home and give us name and contact of the
new owner.
The warranty does not apply to any Product or Product part that has been
modified or damaged by the following:
- Installation or Removal (examples: wrong voltage batteries, connecting batteries backwards, damage due to water/rain to electronics, preventable damage to solar wires.)
- Alteration or Disassembly
- Normal Wear and Tear
- Accident or Abuse
- Unauthorized Firmware updates/software updates or alterations to the software code
- Corrosion
- Lightning: unless using EMP hardened system, then Portable Solar will repair product
- Repair or service provided by an unauthorized repair facility
- Operation or installation contrary to manufacturer product instructions
- Fire, Floods or Acts of Nature
- Shipping or Transportation
- Incidental or consequential damage caused by other components of the power system
- Any product whose serial number has been altered, defaced or removed
- Any other event not foreseeable by Portable Solar, LLC
Contact Us: 1-972-575-8875
For Info/Purchasing: sales@sol-ark.com | ext.1
For Tech Support/Warranty
Claim: support@sol-ark.com | ext.2
For Administrative Help: ext.3
Sol-Ark (Portable Solar LLC) liability for any defective Product, or any
Product part, shall be limited to the repair or replacement of the Product, at
Portable Solar LLC discretion. Sol-Ark does not warrant or guarantee
workmanship performed by any person or firm installing its Products. This
warranty does not cover the costs of installation, removal, shipping (except
as described below), or reinstallation of Products or parts of Products. LCD
screen and fans are covered for 5 years from date of purchase.
THIS LIMITED WARRANTY IS THE EXCLUSIVE WARRANTY APPLICABLE TO SOL-ARK
(PORTABLE SOLAR LLC) PRODUCTS. SOL-ARK EXPRESSLY DISCLAIMS ANY OTHER EXPRESS
OR IMPLIED WARRANTIES OF ITS PRODUCTS. SOL-ARK ALSO EXPRESSLY LIMITS ITS
LIABILITY IN THE EVENT OF A PRODUCT DEFECT TO REPAIR OR REPLACEMENT IN
ACCORDANCE WITH THE TERMS OF THIS LIMITED WARRANTY AND EXCLUDES ALL LIABILITY
FOR INCIDENTAL OR CONSEQUENTIAL DAMAGES, INCLUDING WITHOUT LIMITATION ANY
LIABILITY FOR PRODUCTS NOT BEING AVAILABLE FOR USE OR LOST REVENUES OR
PROFITS, EVEN IF IT IS MADE AWARE OF SUCH POTENTIAL DAMAGES.
Return Policy – No returns will be accepted without prior authorization and
must include the Return Material Authorization (RMA) number. Please call and
talk to one of our engineers to obtain this number at
972-575-8875.
Return Material Authorization (RMA) A request for an RMA number requires all
of the following information: 1. Product model and serial number; 2. Proof-of-
purchase in the form of a copy of the original Product purchase invoice or
receipt confirming the Product model number and serial number; 3. Description
of the problem; 4. Validation of problem by Technical Support, and 5.
Shipping address for the repaired or replacement equipment. Upon receiving
this information, the Sol-Ark representative can issue an RMA number.
Any product that is returned must be brand new, in excellent condition and
packaged in the original manufacturer’s carton with all corresponding hardware
and documentation. Returns must be shipped with prepaid freight and insured
via the carrier of your choice to arrive back at Portable Solar within 30 days
of your initial delivery or pick-up. Shipping charges will not be refunded.
All returns are subject to a 35% restocking fee. No returns will be accepted
beyond 30 days of original delivery. The value and cost of replacing any items
missing (e.g. parts, manuals, etc.) will be deducted from the refund. If you
have any questions regarding our return policy, please email us at sales
@sol-ark.com or call us at the number above
during regular (M-F) business hours.
Sol-Ark 8K Install Operational Verification Checklist Questionnaire must be
filled out, signed, and dated to secure full warranty coverage.
Contact Us:
PHONE: 1-972-575-8875 x2
EMAIL:SUPPORT@SOL-ARK.COM
WEBSITE:WWW.SOL-ARK.COM
References
- powerview
- powerview
- Solar Battery Partners | Energy Storage Systems | Sol-Ark®
- Sol-Ark® Customer & Installer Resources | Sol-Ark®
- Register Your Sol-Ark -Sol-Ark
- Register Your Sol-Ark® Hybrid Inverter | Sol-Ark®