Warmup DS-2C Outdoor Snow Melting Controller Instruction Manual
- June 3, 2024
- Warmup
Table of Contents
DS-2C Outdoor Snow Melting Controller
Instruction Manual
DS-2C Outdoor Snow Melting Controller
CAUTION: Read all instructions carefully before installation.
Save this Installation Manual for future reference.
Warmup DS-2C
RAIN/SNOW SENSOR CONTROLLER INSTALLATION MANUAL
General Safety Instructions
- THIS UNIT SHOULD BE INSTALLED, OPENED, AND REPAIRED BY QUALIFIED PERSONNEL ONLY!
- To avoid shock hazard do not open the front cover with power connected to the DS-2C or any controlled equipment.
- To avoid fire hazard replace fuse F1 with a 1/2 Amp 250 VAC 2AG fast acting fuse ONLY.
Selecting a Mounting Location for the DS-2C
The interleaved grid on the top of the DS-2C is the precipitation sensor or
“moisture grid.” The rubber “boot” protruding from the bottom of the enclosure
is the temperature sensor. For reliable rain and snow detection the unit must
be mounted in a location that exposes the moisture grid to a clear view of the
sky. The unit should not be mounted directly under eaves or overhangs. It
should not be mounted so close to the ground that it may become buried in
snow. For proper temperature detection the DS-2C must be mounted outdoors,
away from furnace vents, dryer vents, and other sources of heat. Note that,
when powered, the DS-2C moisture grid will always remain hot. This is normal.
This allows the grid to continuously melt snow and evaporate both rain and
snow from the grid. The DS-2C can be mounted by screwing the base conduit hub
onto an appropriate size free-standing conduit or by using the mounting holes
in each corner of the enclosure.
DO NOT DRILL HOLES THROUGH THE ENCLOSURE FOR MOUNTING! NE FONT PAS LES
TROUS DE FORET PAR LA BOÎTE POUR LE SUPPORT!
This can allow water into the enclosure causing a potential shock hazard. It
is recommended that a weatherproof junction box be mounted below the DS-2C for
termination of the power and load pigtails to the building wiring.
Always Use Care When Replacing the Front Cover
Be sure the front cover gasket is not pinched or rolled. Do not overtighten
the front cover screws.
Voltage Selection, Power & Load Connection
The DS-2C requires a 100-120VAC or 200-240VAC power source. Typically the DS-
2C is provided without the voltage selectionjumpers installed. Determine your
inputvoltage and install the voltage select jumpers as shown. Power
consumption for the DS-2C is a maximum of 15 Watts, 50-60 Hz. The controlled
load is switched by the
load relay through the “Load” connection points. The load relay is rated for
30 Amps\240 VAC. Note that it is a “dry contact” closure. Some wiring
suggestions are provided under “Typical Load Wiring” in this manual. However,
always consult local electrical codes for the wire color and size required for
both power and load connections. Applying Power with Incorrect
Jumper Settings May Damage the Unit
Setting the Configuration Switches
The following table outlines the operating modes for the DS-2C and explains
the functions of the adjustments. Trigger temp (TT) is adjustable from
34°F-44°F (1°C-7°C) using the “Temp Adjust” control. When ambient air
temperature (AT) is below this trigger point precipitation is assumed to be
snow. When above this temperature, precipitation is assumed to be rain. The
SNOW switch will cause the sensor to activate when snow is detected. The RAIN
switch will cause the sensor to activate when rain is detected. If RAIN and
SNOW are both set “OFF” the unit will operate as a low temperature thermostat.
The DEL configuration switch activates the “Delay Off” drying cycle timer on
the DS-2C. The timer allows the DS-2C to dry the heated surface through
evaporation once precipitation has stopped. The drying cycle reduces the
chance of moisture left behind refreezing into ice. This timer is restarted by
each precipitation detection. Therefore, the DS-2C will continue to operate as
long as precipitation is detected, then for the Delay Off period once precip
has stopped. All “sensor” modes (DEL off) provide a minimum 2 minute closure
to reduce cycling of an external controller. When in “controller” mode (DEL
on) the Delay Off time can be adjusted from 30-90 minutes using the “Delay
Adjust” control. Note the “Manual On” function at the low end of the Delay
Adjust control. The relay will close when this area is entered and open when
exited. Only use the “Manual On” function for testing. Never leave the Delay
Adjust control near the “Manual On” area during normal operation.
The Low Temperature Cutoff (LTC) option is
typically used on snow melting systems with limited output capacity. If
selected, the sensor will not trigger if precipitation is initially detected
when the outdoor temperature is below 15°F (-9.5°C.) However, if the deicing
system has been activated, precipitation continues, and the ambient
temperature drops below 15°F (-9.5°C), LTC will be ignored. This assures that
water on the surface from melting snow will not immediately refreeze into ice
as a result of deactivating the deicing system. Reference the following table
for suggested configuration switch settings.
Power Must Be Cycled For Configuration Switch Changes to Take Effect
Recommended Switch Settings by Function
Function | Trigger | Delay | LTC | DEL | RAIN | SNOW |
---|---|---|---|---|---|---|
Snow sensor Mc) LTC | TT>AT | 2 Min | OFF | OFF | OFF | ON |
Snow sensor wITC | TT>AT>15 ‘F | 2 Min | ON | OFF | OFF | ON |
Snow controller Mc) LTC | TT>AT | 30-90 Min | OFF | ON | OFF | ON |
Snow controller wITC | TT>AT>15°F | 30-90 Min | ON | ON | OFF | ON |
Precipitation sensor | Not Used | 2 Min | X | OFF | ON | ON |
Precipitation controller | Not Used | 30-90 Min | X | ON | ON | ON |
Rain sensor | AT>TT | 2 Min | X | OFF | ON | OFF |
Rain controller | AT>TT | 30-90 Min | X | ON | ON | OFF |
LT thermostat Mc) LTC | TT>AT | 2 Min | OFF | X | OFF | OFF |
LT thermostat wITC | TT>AT>15°F | 2 Min | ON | X | OFF | OFF |
Fine Adjustment for Efficient Operation
The DS-2C is shipped with the TEMP and DEL adjustments in the center position,
representing 39°F (3.9°C) and 30 minutes of Delay-Off time respectively.
Depending on local conditions the user may find that fine adjustment of the
controls may provide more satisfactory operation. If the sensor does not
trigger during very wet snows the trigger temperature may need to be adjusted
higher. Conversely, if the user notices false triggers during cold rains that
do not freeze, the trigger temperature may need to be lowered. The Delay-Off
time can also be adjusted to provide clean melt-off without excessive running
time. Fine adjustment can both save operating expense and provide more
reliable operation. However, to keep reliability high, always make adjustments
in small increments.
Always Use Care When Replacing The Front Cover
Be sure the front cover gasket is not pinched or rolled. Do not overtighten
the front cover screws.
Manual Override Switch Operation
An override switch mounted on the side is provided for testing and special
operational requirements. Placing the switch in the “Automatic” position will
allow the sensor to operate normally, activating the controlled equipment as
needed. Placing the switch in “Manual On” will close the load relay,
activating the controlled equipment. The “Standby/Reset” position prohibits
triggering of the unit, clears any active delay timer, and opens the load
relay. In order to reduce excessive runtime for the heater the “Manual On”
mode will remain in effect for a maximum of 40 hours, then return to
“Automatic” mode even if the switch is still in the “Manual On” position. You
may put the DS-2C back into “Manual On” mode by switching to “Automatic”, then
back to “Manual On”. This will restart the 40 hour timer.
If the override switch is placed in “Manual On” for less than 2 seconds, then
switched back to “Automatic” the controller will execute one delay off cycle.
This can be used to clear a frost or hail buildup without the danger of
leaving the system in a continuous “Manual On” condition. “Standby/Reset” can
still be used to clear this delay off cycle.
Typical Load Wiring
The two load leads of the DS-2C do not supply power directly to your load. The relay inside the DS-2C, like a switch or thermostat, is used to switch a voltage of your choice. While not as convenient as directly supplying power for the load this allows you to operate the DS-2C from one voltage while controlling a load of a different voltage without adding an external relay or contactor. For example, the DS- 2C can be powered from 120VAC but can directly control a 24VAC signal for a boiler system or 240VAC for heating wire. The following diagrams show some possible wiring schemes for connecting the DS-2C to your load. Your load may be a direct connection to a heater, a contactor coil, or a control voltage. For clarity the safety GROUND leads are not shown.
120VAC In, 120VAC Load, Shared Feed (Strap DS-2C for 120VAC
Power) 240VAC In, 240VAC Load, Shared Feed (Strap DS-
2C for 240VAC Power) 120VAC In, 240VAC Load, Separate Feed (Strap DS-
2C for 120VAC Power) 240VAC In, Dry Contact for Boiler/Circulation
Pump (Strap DS-2C for 240VAC Power)
These are just some of the possible wiring schemes that can be used to connect
the DS-2C to your load for control. The DS-2C should always be strapped for
the voltage that is connected to Line/L1 and Neu/L2. Remember, these are only
suggestions. You should always check with a qualified electrician to insure
conformance with local electrical codes!
LIMITED WARRANTY
The DS-2C is warranted against defects in workmanship and materials for two
years from date of sale. This warranty does not apply to damage resulting from
accident, misuse, or alteration nor where connected voltage is more than 5%
above the configured operating voltage, nor to equipment improperly installed
or wired or maintained in violation of this Owner’s Manual. No other written
or oral warranty applies. No employee, agent, dealer or other person is
authorized to give any warranties on behalf of WARMUP.
The customer shall be responsible for all costs incurred in the removal or
reinstallation and shipping of the product for repairs. Within the limitations
of this warranty, inoperative units should be returned, freight prepaid to
WARMUP and we will repair or replace, at our option, at no charge to you with
return freight paid by WARMUP. It is agreed that such repair or replacement is
the exclusive remedy available from WARMUP and that WARMUP IS NOT RESPONSIBLE
FOR DAMAGES OF ANY KIND, INCLUDING INCIDENTAL AND CONSEQUENTIAL DAMAGE. Some
states do not allow the exclusion or limitation of incidental or consequential
damages so the above exclusion may not apply to you. The warranty gives you
specific legal rights, and you may also have other rights which vary from
state to state.
US: 1-888-927-6333
CANADA: 1-888-592-7687
warmup.com or
warmup.ca
References
- WARMUP Inc — Heated Floors | Official Canadian Website
- WARMUP Inc — Radiant Floor Heating Company | Official US Website
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>