Warmup DS-2C Outdoor Snow Melting Controller Instruction Manual

June 3, 2024
Warmup

DS-2C Outdoor Snow Melting Controller
Instruction Manual

Warmup DS-2C Outdoor Snow Melting Controller

DS-2C Outdoor Snow Melting Controller

CAUTION: Read all instructions carefully before installation.
Save this Installation Manual for future reference.
Warmup DS-2C
RAIN/SNOW SENSOR CONTROLLER INSTALLATION MANUAL

General Safety Instructions

  1. THIS UNIT SHOULD BE INSTALLED, OPENED, AND REPAIRED BY QUALIFIED PERSONNEL ONLY!
  2. To avoid shock hazard do not open the front cover with power connected to the DS-2C or any controlled equipment.
  3. To avoid fire hazard replace fuse F1 with a 1/2 Amp 250 VAC 2AG fast acting fuse ONLY.

Selecting a Mounting Location for the DS-2C
The interleaved grid on the top of the DS-2C is the precipitation sensor or “moisture grid.” The rubber “boot” protruding from the bottom of the enclosure is the temperature sensor. For reliable rain and snow detection the unit must be mounted in a location that exposes the moisture grid to a clear view of the sky. The unit should not be mounted directly under eaves or overhangs. It should not be mounted so close to the ground that it may become buried in snow. For proper temperature detection the DS-2C must be mounted outdoors, away from furnace vents, dryer vents, and other sources of heat. Note that, when powered, the DS-2C moisture grid will always remain hot. This is normal. This allows the grid to continuously melt snow and evaporate both rain and snow from the grid. The DS-2C can be mounted by screwing the base conduit hub onto an appropriate size free-standing conduit or by using the mounting holes in each corner of the enclosure.
DO NOT DRILL HOLES THROUGH THE ENCLOSURE FOR MOUNTING! NE FONT PAS LES TROUS DE FORET PAR LA BOÎTE POUR LE SUPPORT!
This can allow water into the enclosure causing a potential shock hazard. It is recommended that a weatherproof junction box be mounted below the DS-2C for termination of the power and load pigtails to the building wiring.
Always Use Care When Replacing the Front Cover
Be sure the front cover gasket is not pinched or rolled. Do not overtighten the front cover screws.Warmup DS-2C Outdoor Snow Melting Controller -
fig

Voltage Selection, Power & Load Connection

The DS-2C requires a 100-120VAC or 200-240VAC power source. Typically the DS- 2C is provided without the voltage selectionjumpers installed. Determine your inputvoltage and install the voltage select jumpers as shown. Power consumption for the DS-2C is a maximum of 15 Watts, 50-60 Hz. The controlled load is switched by the
load relay through the “Load” connection points. The load relay is rated for 30 Amps\240 VAC. Note that it is a “dry contact” closure. Some wiring suggestions are provided under “Typical Load Wiring” in this manual. However, always consult local electrical codes for the wire color and size required for both power and load connections. Warmup DS-2C Outdoor Snow Melting
Controller - fig 1 Applying Power with Incorrect Jumper Settings May Damage the Unit

Setting the Configuration Switches

The following table outlines the operating modes for the DS-2C and explains the functions of the adjustments. Trigger temp (TT) is adjustable from 34°F-44°F (1°C-7°C) using the “Temp Adjust” control. When ambient air temperature (AT) is below this trigger point precipitation is assumed to be snow. When above this temperature, precipitation is assumed to be rain. The SNOW switch will cause the sensor to activate when snow is detected. The RAIN switch will cause the sensor to activate when rain is detected. If RAIN and SNOW are both set “OFF” the unit will operate as a low temperature thermostat. The DEL configuration switch activates the “Delay Off” drying cycle timer on the DS-2C. The timer allows the DS-2C to dry the heated surface through evaporation once precipitation has stopped. The drying cycle reduces the chance of moisture left behind refreezing into ice. This timer is restarted by each precipitation detection. Therefore, the DS-2C will continue to operate as long as precipitation is detected, then for the Delay Off period once precip has stopped. All “sensor” modes (DEL off) provide a minimum 2 minute closure to reduce cycling of an external controller. When in “controller” mode (DEL on) the Delay Off time can be adjusted from 30-90 minutes using the “Delay Adjust” control. Note the “Manual On” function at the low end of the Delay Adjust control. The relay will close when this area is entered and open when exited. Only use the “Manual On” function for testing. Never leave the Delay Adjust control near the “Manual On” area during normal operation.
The Low Temperature Cutoff (LTC) option is typically used on snow melting systems with limited output capacity. If selected, the sensor will not trigger if precipitation is  initially detected when the outdoor temperature is below 15°F (-9.5°C.) However, if the deicing system has been activated, precipitation continues, and the ambient temperature drops below 15°F (-9.5°C), LTC will be ignored. This assures that water on the surface from melting snow will not immediately refreeze into ice as a result of deactivating the deicing system. Reference the following table for suggested configuration switch settings.

Power Must Be Cycled For Configuration Switch Changes to Take Effect
Recommended Switch Settings by Function

Function Trigger Delay LTC DEL RAIN SNOW
Snow sensor Mc) LTC TT>AT 2 Min OFF OFF OFF ON
Snow sensor wITC TT>AT>15 ‘F 2 Min ON OFF OFF ON
Snow controller Mc) LTC TT>AT 30-90 Min OFF ON OFF ON
Snow controller wITC TT>AT>15°F 30-90 Min ON ON OFF ON
Precipitation sensor Not Used 2 Min X OFF ON ON
Precipitation controller Not Used 30-90 Min X ON ON ON
Rain sensor AT>TT 2 Min X OFF ON OFF
Rain controller AT>TT 30-90 Min X ON ON OFF
LT thermostat Mc) LTC TT>AT 2 Min OFF X OFF OFF
LT thermostat wITC TT>AT>15°F 2 Min ON X OFF OFF

Fine Adjustment for Efficient Operation

The DS-2C is shipped with the TEMP and DEL adjustments in the center position, representing 39°F (3.9°C) and 30 minutes of Delay-Off time respectively. Depending on local conditions the user may find that fine adjustment of the controls may provide more satisfactory operation. If the sensor does not trigger during very wet snows the trigger temperature may need to be adjusted higher. Conversely, if the user notices false triggers during cold rains that do not freeze, the trigger temperature may need to be lowered. The Delay-Off time can also be adjusted to provide clean melt-off without excessive running time. Fine adjustment can both save operating expense and provide more reliable operation. However, to keep reliability high, always make adjustments in small increments.
Always Use Care When Replacing The Front Cover
Be sure the front cover gasket is not pinched or rolled. Do not overtighten the front cover screws.

Manual Override Switch Operation

An override switch mounted on the side is provided for testing and special operational requirements. Placing the switch in the “Automatic” position will allow the sensor to operate normally, activating the controlled equipment as needed. Placing the switch in “Manual On” will close the load relay, activating the controlled equipment. The “Standby/Reset” position prohibits triggering of the unit, clears any active delay timer, and opens the load relay. In order to reduce excessive runtime for the heater the “Manual On” mode will remain in effect for a maximum of 40 hours, then return to “Automatic” mode even if the switch is still in the “Manual On” position. You may put the DS-2C back into “Manual On” mode by switching to “Automatic”, then back to “Manual On”. This will restart the 40 hour timer.
If the override switch is placed in “Manual On” for less than 2 seconds, then switched back to “Automatic” the controller will execute one delay off cycle. This can be used to clear a frost or hail buildup without the danger of leaving the system in a continuous “Manual On” condition. “Standby/Reset” can still be used to clear this delay off cycle.

Typical Load Wiring

The two load leads of the DS-2C do not supply power directly to your load. The relay inside the DS-2C, like a switch or thermostat, is used to switch a voltage of your choice. While not as convenient as directly supplying power for the load this allows you to operate the DS-2C from one voltage while controlling a load of a different voltage without adding an external relay or contactor. For example, the DS- 2C can be powered from 120VAC but can directly control a 24VAC signal for a boiler system or 240VAC for heating wire. The following diagrams show some possible wiring schemes for connecting the DS-2C to your load. Your load may be a direct connection to a heater, a contactor coil, or a control voltage. For clarity the safety GROUND leads are not shown.Warmup DS-2C Outdoor Snow Melting Controller - fig
7

120VAC In, 120VAC Load, Shared Feed (Strap DS-2C for 120VAC Power)Warmup DS-2C Outdoor Snow Melting Controller - fig
8 240VAC In, 240VAC Load, Shared Feed (Strap DS- 2C for 240VAC Power)Warmup DS-2C Outdoor Snow Melting Controller - fig
9 120VAC In, 240VAC Load, Separate Feed (Strap DS- 2C for 120VAC Power)Warmup DS-2C Outdoor Snow Melting Controller - fig
10 240VAC In, Dry Contact for Boiler/Circulation Pump (Strap DS-2C for 240VAC Power)
These are just some of the possible wiring schemes that can be used to connect the DS-2C to your load for control. The DS-2C should always be strapped for the voltage that is connected to Line/L1 and Neu/L2. Remember, these are only suggestions. You should always check with a qualified electrician to insure conformance with local electrical codes!

LIMITED WARRANTY

The DS-2C is warranted against defects in workmanship and materials for two years from date of sale. This warranty does not apply to damage resulting from accident, misuse, or alteration nor where connected voltage is more than 5% above the configured operating voltage, nor to equipment improperly installed or wired or maintained in violation of this Owner’s Manual. No other written or oral warranty applies. No employee, agent, dealer or other person is authorized to give any warranties on behalf of WARMUP.
The customer shall be responsible for all costs incurred in the removal or reinstallation and shipping of the product for repairs. Within the limitations of this warranty, inoperative units should be returned, freight prepaid to WARMUP and we will repair or replace, at our option, at no charge to you with return freight paid by WARMUP. It is agreed that such repair or replacement is the exclusive remedy available from WARMUP and that WARMUP IS NOT RESPONSIBLE FOR DAMAGES OF ANY KIND, INCLUDING INCIDENTAL AND CONSEQUENTIAL DAMAGE. Some states do not allow the exclusion or limitation of incidental or consequential damages so the above exclusion may not apply to you. The warranty gives you specific legal rights, and you may also have other rights which vary from state to state.

US: 1-888-927-6333
CANADA: 1-888-592-7687
warmup.com or
warmup.ca

References

Read User Manual Online (PDF format)

Read User Manual Online (PDF format)  >>

Download This Manual (PDF format)

Download this manual  >>

Related Manuals