DIGITALas D-FORCE 02D Automatic Swing Door Operator Instruction Manual

June 3, 2024
DIGITALas

D-FORCE 02D Automatic Swing Door Operator

AUTOMATIC SWING DOOR OPERATOR
Please read the manual carefully before use this unit

Installation of automatic door should be entrusted to the appointed distributer or professional installation personnel, or it may be dangerous. Installation must be performed by professional installation personnel according to local law.
This manual must be kept well for maintenance.

Content
1 Introduction of product 2 Technical parameters 3 Swing door operator 4 Components 5 Installation step
5.1 Installation demonstration 5.2 Installation of bottom plate 5.3 Installation of pull bar 5.4 Installation of pull bar for glass door 5.5 Installation of push bar 5.6 Installation of Glass clamp for push bar 5.7Mechanism installation 6 Wire diagram 7 Data setting 8 Function of remote 9 LED instructions

1 2 3 4 5-17 5-6 7-8 9-11 12 13 14-16 17 18-22 23 24 25

1.Introduction of product
Application: suitable for wooden door,metal door,frame door open to one direction(both single or double open,special Glass clamp is request for glass door installation Speed/opening time/open degree/ close force adjustable Door width PP Door weight NJV Open degree:60-110 adjustable Installation: open to inside /open to outside (pull/push bar) Voltage: AC100V-240V, Output 24 DC Open device wireless push button/remote control 2000000 service life test, super reliable

2 1 3
12

10
9
P R E S S
8 11

AB

C

D

7

4 5
6

1 Swing door mechanism 2 Microwave sensor 3 E-lock 4 Access control 5 Touchless sensor 6 Footkick sensor 7 Remote control 8 Keypad Integration Access Control 9 Push button 10 Touchless sensor 11 Wireless push button 12 Top Scan

1. ]NOMNYVKKJJIHX[YNRKYYSUZUXRUTMYKXOIKROLKlow noise. /TSGOTGTJYRGKSUJK9KW[KTIK]ORRTUZINGTMKHKIG[YKULKTIU[TZKXGTUHYZGIRK 3*U[HRKMKGXHU^JKYOMTNOMNYVKKJXGZOUNOMNYZXKTgZNIGT]UXQ]OZNQMYJUUXwork with E-lock
]ORRSUXKYGLK 4 6[YNGTJMUL[TIZOUT 5 .:NKURZGMKULZNKIUTZXURRKXOY’)<<]NOINOYGVVROIGHRK]UXRJ]OJK
:NKXGZKJVU]KXULZNKSUZUXOY=

1

2.Technical Parameters

Power AC 100V-240V Active open time 3-7s/90° Hold open time 0-20s Temperature -20- +55 Protection classIP21 Product weight 5.5kg Product size 4758198mm Max open angle 110° mm = Door width kg = Door weight
kg

170

Limited range

150

130

Suitable range

110

90

70

50

60 70 80 90 100 110 120

cm

2

3.Swing door operator

475

81 39.5 7.5

230

230

20

500

98

98

143 81

Pull bar 3

316 Push bar

81 120

4.Components

Side Cover

Controller

Motor

Side cover with power switch

100-240V power input Pull bar

Note: Select one from the pull bar or push bar.

Base Pull bar Cover Push bar Door operator

4

5.Installation step
5.1 Installation demonstration
Installation of Pull bar type suit for door open to inside mechanism is inside
Opening direction
5

5.Installation step
5.1 Installation demonstration
Installation of Push bar type suit for door open to inside mechanism is inside
Opening direction
6

5.Installation step

5.2 Installation of bottom plate

Installation of pull bar type

power liner

sensor liner

41 125

120

125 41

452

28 52

As the picture showing, fix the bottom plate on the frame with eight countersunk head screw.

Operator at right position.

power liner

sensor liner

41 125

120

125 41

452

28 52

As the picture showing, fix the bottom plate on the frame with eight countersunk head screw

Operator at left position.

7

5.Installation step

5.2 Installation of bottom plate Installation of push bar type

power liner

The distance between the bottomULthe mounting plate and the door hole is 6mm

41 125

120

125 41

452
As the picture showing, fix the bottom plate on the frame with eight countersunk head screw

sensor line

Frame

Operator at right position.

Bottom plate

52 52

power liner

sensor line

41 125

120

125 41

The distance between the bottomULthe mounting plate and the door hole is 6mm

452
As the picture showing, fix the bottom plate on the frame with eight countersunk head screw.

Operator at left position.

Frame Bottom plate

8

5.Installation step
5.3 /TYZGRRGZOUTULV[RRHGX

98
0-30 Open direction

Wall *UUXRKGL

5VKTZNKJUUXZUqYROJKZNKV[RRM[OJKXURRKX into track.
2.Fix the Pull bar plate as shown. 3.Move the plate ensure the wheel at the middle VUYOZOUTULZXGIQGYYN]UT .URJZNKVRGZKVUYZOUTLO^ZNKLOXYZYIXK]TKGX )KTZKXULZNKYNGLZ )RUYKZNKJUUXXKVKGZYZKVLO^GTUZNKXYIXK] at another side. 6.Manually move the door to ensure pull bar work YSUUZNR_GJP[YZSKTZOYXKW[KYZKJOLGT_XKYOYZGTIK
during the operating. 7.Fix the last screw.

122 37 52
81

9

5.Installation step
5.3 Installation of pull bar guider(Right position) Installation of pull bar guider

30

230

230

20

120

Fix the pull bar on door leaf with 3 pcs self-tapping screw

Adjust the opening angle by position stopper.

position stopper

10

5.Installation step
5.3 Installation of pull bar guider( Left position) Installation of pull bar guider

120 20

230

230

Fix the pull bar on door leaf with 3 pcs self-tapping screw

30

position stopper

Adjust the opening angle by position stopper

11

81 25

5.Installation step
5.4 /TYZGRRGZOUTULV[RRHGXLUXMRGYYJUUX

500

130

TipEnsure 25mm space for glass top to door frame bottom( Glass door installation)
98

12

93.5 15 52

5.Installation step
5.5 /TYZGRRGZOUTULV[YNHGX 98

Wall *UUXRKGL

5.5.1/TYZGRRGZOUTULV[YNHGXLUXMRGYYJUUX

‘JP[YZZNKV[YNHGXRKTMNZH_Z]UYIXK] GIIUXJOTMZUZNKJUUXLXGSKYJKVZN2
13

Automatic door right installation

5.Installation step
/TYZGRRGZOUTUL-RGYYIRGSVLUXV[Yh bar
4UZK SGQKY[XKZNKXKOYGSSMGVHKZ]KKTZNKZUVULZNKMRGYYGTJZNK HUZZUSULZNKJUUX]NKT[YOTMZNKV[YNGXSULZNKMRGYYJUUX
14

5.Installation step
/TYZGRRGZOUTUL-RGYYIRGSVLUXV[Yh bar

18

50

450

:OV :NKMRGYYIRGSVULZNKV[YNGXSYNGRRHKLGYZKTKJUTZNKJUUX]OTM]OZNVR[MYIXK]Y 3GYYNU]TOTZNKLOM[XK
15

5.Installation step
/TYZGRRGZOUTUL-RGYYIRGSVLUXV[Yh bar

,O^ZNKMRGYYIRGSVGTJYVGIKX]OZNYIXK]3ZOMNZR_UTMRGYYJUUX/TYZGRRZNKLO^VRGZKUL V[YNHGX]OZNYIXK]3UTMRGYYIRGSV

Mechanism

98

93.5 15 52

Push bar

Open direction

Wall
-RGYYIRGSV *UUXRKGL

16

5.Installation step
5.7 Mechanism installation
Hang the mechanism on the fixed base cover with screws. Assemble and disassemble of the mechanism up cover
cover
17

6.Wire diagram

1.UPS+ 2.UPS3. E-lock+
4.OPEN B 5.OPEN A 6.GND 7.+12V 8.+24V

9.+24V 10.+12V 11.GND 12.Anti-collision closing 13.Anti-collision opening
14. Interlock input 15.COM 16.Interlock output
17.Synchronous input 18.GND 19.Synchronous output

Motor

DIP

1. UP-Lock automatically,DOWN-Lock by signal 2. UP-Push and goDOWN-Push no go 3. UP-Right opening DOWN-Left opening 4. UP-Master driveDOWN-Slave drive 5. Signal shielding

L1 .Remote setting indicator L2 .Master drive indicator L3 .Slave drive indicator

Close buffer distance

Close speed

MIN

MAX

Buffer speed

– Learn –

Test
Open buffer distance

Open

speed

L 3

Opening N 2

time

1

1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19

FUSE

Inter lock
14.Innter-lock signal IN 16. Inter-lock signal OUT)
Synchronous

Door A

Door B

17.Synchronous IN GND
19. Synchronous(OUT)

Door A

Door B

AttentionController will alarm while synchronous line not connect or wrong connect buzzer will not bipred and green led will flash 3 times within 4 second
In single modebridge connect terminal 17 and 19

17.Synchronous IN 19. Synchronous OUT

24G Microwave sensor

14.Innter-lock signal IN 16. Innter-lock signal OUT)
17.Synchronous(IN) GND
19. Synchronous(OUT)

Red Black
Yellow Green

8. 24V 6. GND 4. OPEN-B 6. GND
18

6.Wire diagram
UPS

AK04

NC COM
NO GND +12V D-IN OPEN ALARM
D1 D0

Footkick sensor

POWER: AC12-28V/DC12-36V DISTANCE: 0.4M

R RED

E

R

19

AC12-28V

RED

DC12-36V

2. UPS1. UPS+
7. +12V 6. GND 5.OPEN-A 6.GND
8. 24V 6. GND 4. OPEN-B 6. GND

R

E

6.Wire diagram
Photocell

+24V 9 +12V 10 GND 11 Anti-collision closing 12 Anti-collision opening 13
4UZK 6NUZUIKRRNGKZU[YKZNK4)YOMTGR

A)<*)<
COM NO

NEAR TWO GROUPS

FAR ONE GROUP

(GROUP A) RECEIVER TRANSMITTER

(GROUP B) RECEIVER TRANSMITTER

E

R

R

E

)UTTKIZOUTUL+RUIQ
(RGIQ]OXK –
Electric bolt lock Red wire +
(RGIQ]OXK –
Magnetic lock Red wire +

UPS- 2 E-lock+ 3
UPS- 2 E-lock+ 3
20

6.Wire diagram
Access keypad

Connect

Pink Pink Green White Grey Yellow Brown Red Black Blue Purple Orange

8 +24V 7 +12V 6 GND 5 Open A 4 Open B

21

}
} }
}
}
} }
}

6.Wire diagram

:569IGT5VKTGTJ)RUYK

)UTTKIZOUTUL:UVYIGT5VKTUVZK^5’-+*-+:

Power d<‘)) 9GLK:KYZU[ZV[Z C relay
6[RYKOTKXYOUT)RUYKYOJK
9GLK:KYZU[ZV[Z C relay
9ZUVV[RYK5VKTYOJK Output test
5VZOIGRIU[VRKX <URZGMK d<
)

(+) (-) COM NC NO COM NC NO (+) (-)

1. White 2. Brown 3. Green 4. Yellow 5. Grey 6. Pink 7. Blue 8.Red 9. Black 10. Purple

9 +24V

10 +12V

11 GND

12

Anti-collision closing

13

Anti-collision opening

)UTTKIZOUTUL:UVYIGT)RUYK

Power d<‘)) 9GLK:KYZU[ZV[Z C relay
6[RYKOTKXYOUT)RUYKYOJK
9GLK:KYZU[ZV[Z C relay
9ZUVV[RYK5VKTYOJK Output test
5VZOIGRIU[VRKX <URZGMK d<
)

(+) (-) COM NC NO COM NC NO (+) (-)

1. White 2. Brown 3. Green 4. Yellow 5. Grey 6. Pink 7. Blue 8.Red 9. Black 10. Purple

9 +24V

10 +12V

11 GND

12

Anti-collision closing

13

Anti-collision opening

22

7. Data setting

1.UPS+ 2.UPS3. E-lock+
4.OPEN B 5.OPEN A 6.GND 7.+12V 8.+24V

9.+24V 10.+12V 11.GND 12.Anti-collision closing 13.Anti-collision opening
14. Interlock input 15.COM 16.Interlock output
17.Synchronous input 18.GND 19.Synchronous output

Motor

DIP

1. UP-Lock automatically,DOWN-Lock by signal 2. UP-Push and goDOWN-Push no go 3. UP-Right opening DOWN-Left opening 4. UP-Master driveDOWN-Slave drive 5. Signal shielding

L1 .Remote setting indicator L2 .Master drive indicator L3 .Slave drive indicator

Close buffer distance

Close speed

MIN

MAX

Buffer speed

– Learn –

Test
Open buffer distance

Open

speed

L 3

Opening N 2

time

1

1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19

FUSE

Close buffer distance: Distance increase clockwise Open buffer distanceDistance increase clockwise Open speedOpen speed increase clockwise Close speedClose speed increase clockwise Buffer speed Buffer speed increase clockwise Open hold timeHold time increase clockwisec0-20s adjustable
DIP switchThe selection of dip only make sense after restart system
1.E-LOCK:UP-Lock automatically Down-Lock by signal 2.Push and go UP: Active Down: Disable 3.L/R switchUP-right open Down-left opencPower onin the default mode door move to the close direction is correctPlease change the position of Dip switch if door in open direction 4.Master and slave UP-Master drive Down- Slave drive 5,Signal shielding
Button on the controller Test: Test button Press to active one open-close round LearnRemote setting button
LED Indicator
L1: Indicator of remote settingcBlue L2:Master drive indicatorLed flash 1 time in 4secondcRed L3:Slave drive indicatorLed flash 1time in 4 secondcGreen

23

8.Function of remote

AB

FC04: A Always open B Automatic C:Open one time D Full lock

C

D

Add the remote Keep press the learning button on controllerL1 Blue Led is on relese learn button and press A on remote Blue led flash 3 times remote is added
Delet remote Keep press the learning button 9 secondL1 turn from blue to flash all the remote is deletcattention while the process of deletlearning button should keep press
Wireless push button Added and deleted wireless push button is same as remote. Please check the DIP switch if it`s same as the image showncduring setting process

Notes
1. Receiver has been built-in only need remote to approve the always open automatic open one time full lock function and also fit with wireless push button PB04 to open the door When controller is full lock PB04 still can active the door 2. Exit only function:Connect outside sensor or button to terminal”Open-B”, connect inside sensor or button to terminal “Open-A”.Then press “full lock” button on remote 3.In double open mode connect Synchronous line refer to the manual .power on ,make sure the setting is same If open and close speed is not same,please adjust open /close speed, open/close buffer speed,open hold time. 4.When double open, the transmitter should learn both operators together.
5.In double open mode accessories should connect to both controller parallel connection

24

9.LED instructions

Normal working Learning mode

Double open

Master drive
Red Led flash every 4seconds Meanwhile Green led off

Slave drive
Green Led flash every 4seconds Meanwhile Red led off

Red Led on 2secondsOff 2seconds within 4 secondsMeanwhile Green
Led off

Green Led on 2secondsOff 2 seconds within 4 secondsMeanwhile Red led off

Set both operator as main Buzzer not bip Red and green led flash 2times within 4seconds drive or slave drive

Not connect synchronous line or wrong connect

Buzzer not bipRed and green led flash 3times within 4seconds

Single open
Normal working Red and green LED alternately brighten,Red led light up while green
off 1secondthen Green led light up while red off 1seconds
Leanring mode Red and green LED alternately brighten,Red led light up while green
off 2secondthen Green led light up while red off 2seconds

Overcurrent protection Buzzer bip each 1 secondRed led and green led flash 5 times together within 4seconds Motor problem Buzzer bip each 2 secondsRed led and green led flash 4 times together within 4seconds

25

Read User Manual Online (PDF format)

Loading......

Download This Manual (PDF format)

Download this manual  >>

Related Manuals