DIGITALas D-FORCE 02D Automatic Swing Door Operator Instruction Manual
- June 3, 2024
- DIGITALas
Table of Contents
D-FORCE 02D Automatic Swing Door Operator
AUTOMATIC SWING DOOR OPERATOR
Please read the manual carefully before use this unit
Installation of automatic door should be entrusted to the appointed
distributer or professional installation personnel, or it may be dangerous.
Installation must be performed by professional installation personnel
according to local law.
This manual must be kept well for maintenance.
Content
1 Introduction of product 2 Technical parameters 3 Swing door operator 4
Components 5 Installation step
5.1 Installation demonstration 5.2 Installation of bottom plate 5.3
Installation of pull bar 5.4 Installation of pull bar for glass door 5.5
Installation of push bar 5.6 Installation of Glass clamp for push bar
5.7Mechanism installation 6 Wire diagram 7 Data setting 8 Function of remote 9
LED instructions
1 2 3 4 5-17 5-6 7-8 9-11 12 13 14-16 17 18-22 23 24 25
1.Introduction of product
Application: suitable for wooden door,metal door,frame door open to one
direction(both single or double open,special Glass clamp is request for glass
door installation Speed/opening time/open degree/ close force adjustable Door
width PP Door weight NJV Open degree:60-110 adjustable Installation: open to
inside /open to outside (pull/push bar) Voltage: AC100V-240V, Output 24 DC
Open device wireless push button/remote control 2000000 service life test,
super reliable
2 1 3
12
10
9
P R E S S
8 11
AB
C
D
7
4 5
6
1 Swing door mechanism 2 Microwave sensor 3 E-lock 4 Access control 5 Touchless sensor 6 Footkick sensor 7 Remote control 8 Keypad Integration Access Control 9 Push button 10 Touchless sensor 11 Wireless push button 12 Top Scan
1. ]NOMNYVKKJJIHX[YNRKYYSUZUXRUTMYKXOIKROLKlow noise.
/TSGOTGTJYRGKSUJK9KW[KTIK]ORRTUZINGTMKHKIG[YKULKTIU[TZKXGTUHYZGIRK
3*U[HRKMKGXHU^JKYOMTNOMNYVKKJXGZOUNOMNYZXKTgZNIGT]UXQ]OZNQMYJUUXwork with
E-lock
]ORRSUXKYGLK 4 6[YNGTJMUL[TIZOUT 5
.:NKURZGMKULZNKIUTZXURRKXOY’)<<]NOINOYGVVROIGHRK]UXRJ]OJK
:NKXGZKJVU]KXULZNKSUZUXOY=
1
2.Technical Parameters
Power AC 100V-240V Active open time 3-7s/90° Hold open time 0-20s Temperature
-20- +55 Protection classIP21 Product weight 5.5kg Product size 4758198mm
Max open angle 110° mm = Door width kg = Door weight
kg
170
Limited range
150
130
Suitable range
110
90
70
50
60 70 80 90 100 110 120
cm
2
3.Swing door operator
475
81 39.5 7.5
230
230
20
500
98
98
143 81
Pull bar 3
316 Push bar
81 120
4.Components
Side Cover
Controller
Motor
Side cover with power switch
100-240V power input Pull bar
Note: Select one from the pull bar or push bar.
Base Pull bar Cover Push bar Door operator
4
5.Installation step
5.1 Installation demonstration
Installation of Pull bar type suit for door open to inside mechanism is inside
Opening direction
5
5.Installation step
5.1 Installation demonstration
Installation of Push bar type suit for door open to inside mechanism is inside
Opening direction
6
5.Installation step
5.2 Installation of bottom plate
Installation of pull bar type
power liner
sensor liner
41 125
120
125 41
452
28 52
As the picture showing, fix the bottom plate on the frame with eight countersunk head screw.
Operator at right position.
power liner
sensor liner
41 125
120
125 41
452
28 52
As the picture showing, fix the bottom plate on the frame with eight countersunk head screw
Operator at left position.
7
5.Installation step
5.2 Installation of bottom plate Installation of push bar type
power liner
The distance between the bottomULthe mounting plate and the door hole is 6mm
41 125
120
125 41
452
As the picture showing, fix the bottom plate on the frame with eight
countersunk head screw
sensor line
Frame
Operator at right position.
Bottom plate
52 52
power liner
sensor line
41 125
120
125 41
The distance between the bottomULthe mounting plate and the door hole is 6mm
452
As the picture showing, fix the bottom plate on the frame with eight
countersunk head screw.
Operator at left position.
Frame Bottom plate
8
5.Installation step
5.3 /TYZGRRGZOUTULV[RRHGX
98
0-30 Open direction
Wall *UUXRKGL
5VKTZNKJUUXZUqYROJKZNKV[RRM[OJKXURRKX into track.
2.Fix the Pull bar plate as shown. 3.Move the plate ensure the wheel at the
middle VUYOZOUTULZXGIQGYYN]UT .URJZNKVRGZKVUYZOUTLO^ZNKLOXYZYIXK]TKGX
)KTZKXULZNKYNGLZ )RUYKZNKJUUXXKVKGZYZKVLO^GTUZNKXYIXK] at another side.
6.Manually move the door to ensure pull bar work
YSUUZNR_GJP[YZSKTZOYXKW[KYZKJOLGT_XKYOYZGTIK
during the operating. 7.Fix the last screw.
122 37 52
81
9
5.Installation step
5.3 Installation of pull bar guider(Right position) Installation of pull bar
guider
30
230
230
20
120
Fix the pull bar on door leaf with 3 pcs self-tapping screw
Adjust the opening angle by position stopper.
position stopper
10
5.Installation step
5.3 Installation of pull bar guider( Left position) Installation of pull bar
guider
120 20
230
230
Fix the pull bar on door leaf with 3 pcs self-tapping screw
30
position stopper
Adjust the opening angle by position stopper
11
81 25
5.Installation step
5.4 /TYZGRRGZOUTULV[RRHGXLUXMRGYYJUUX
500
130
TipEnsure 25mm space for glass top to door frame bottom( Glass door
installation)
98
12
93.5 15 52
5.Installation step
5.5 /TYZGRRGZOUTULV[YNHGX 98
Wall *UUXRKGL
5.5.1/TYZGRRGZOUTULV[YNHGXLUXMRGYYJUUX
‘JP[YZZNKV[YNHGXRKTMNZH_Z]UYIXK] GIIUXJOTMZUZNKJUUXLXGSKYJKVZN2
13
Automatic door right installation
5.Installation step
/TYZGRRGZOUTUL-RGYYIRGSVLUXV[Yh bar
4UZK SGQKY[XKZNKXKOYGSSMGVHKZ]KKTZNKZUVULZNKMRGYYGTJZNK
HUZZUSULZNKJUUX]NKT[YOTMZNKV[YNGXSULZNKMRGYYJUUX
14
5.Installation step
/TYZGRRGZOUTUL-RGYYIRGSVLUXV[Yh bar
18
50
450
:OV :NKMRGYYIRGSVULZNKV[YNGXSYNGRRHKLGYZKTKJUTZNKJUUX]OTM]OZNVR[MYIXK]Y
3GYYNU]TOTZNKLOM[XK
15
5.Installation step
/TYZGRRGZOUTUL-RGYYIRGSVLUXV[Yh bar
,O^ZNKMRGYYIRGSVGTJYVGIKX]OZNYIXK]3ZOMNZR_UTMRGYYJUUX/TYZGRRZNKLO^VRGZKUL V[YNHGX]OZNYIXK]3UTMRGYYIRGSV
Mechanism
98
93.5 15 52
Push bar
Open direction
Wall
-RGYYIRGSV *UUXRKGL
16
5.Installation step
5.7 Mechanism installation
Hang the mechanism on the fixed base cover with screws. Assemble and
disassemble of the mechanism up cover
cover
17
6.Wire diagram
1.UPS+ 2.UPS3. E-lock+
4.OPEN B 5.OPEN A 6.GND 7.+12V 8.+24V
9.+24V 10.+12V 11.GND 12.Anti-collision closing 13.Anti-collision opening
14. Interlock input 15.COM 16.Interlock output
17.Synchronous input 18.GND 19.Synchronous output
Motor
DIP
1. UP-Lock automatically,DOWN-Lock by signal 2. UP-Push and goDOWN-Push no go 3. UP-Right opening DOWN-Left opening 4. UP-Master driveDOWN-Slave drive 5. Signal shielding
L1 .Remote setting indicator L2 .Master drive indicator L3 .Slave drive indicator
Close buffer distance
Close speed
MIN
MAX
Buffer speed
– Learn –
–
Test
Open buffer distance
Open
speed
L 3
Opening N 2
time
1
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19
FUSE
Inter lock
14.Innter-lock signal IN 16. Inter-lock signal OUT)
Synchronous
Door A
Door B
17.Synchronous IN GND
19. Synchronous(OUT)
Door A
Door B
AttentionController will alarm while synchronous line not connect or wrong
connect buzzer will not bipred and green led will flash 3 times within 4
second
In single modebridge connect terminal 17 and 19
17.Synchronous IN 19. Synchronous OUT
24G Microwave sensor
14.Innter-lock signal IN 16. Innter-lock signal OUT)
17.Synchronous(IN) GND
19. Synchronous(OUT)
Red Black
Yellow Green
8. 24V 6. GND 4. OPEN-B 6. GND
18
6.Wire diagram
UPS
AK04
NC COM
NO GND +12V D-IN OPEN ALARM
D1 D0
Footkick sensor
POWER: AC12-28V/DC12-36V DISTANCE: 0.4M
R RED
E
R
19
AC12-28V
RED
DC12-36V
2. UPS1. UPS+
7. +12V 6. GND 5.OPEN-A 6.GND
8. 24V 6. GND 4. OPEN-B 6. GND
R
E
6.Wire diagram
Photocell
+24V 9 +12V 10 GND 11 Anti-collision closing 12 Anti-collision opening 13
4UZK 6NUZUIKRRNGKZU[YKZNK4)YOMTGR
A)<*)<
COM NO
NEAR TWO GROUPS
FAR ONE GROUP
(GROUP A) RECEIVER TRANSMITTER
(GROUP B) RECEIVER TRANSMITTER
E
R
R
E
)UTTKIZOUTUL+RUIQ
(RGIQ]OXK –
Electric bolt lock Red wire +
(RGIQ]OXK –
Magnetic lock Red wire +
UPS- 2 E-lock+ 3
UPS- 2 E-lock+ 3
20
6.Wire diagram
Access keypad
Connect
Pink Pink Green White Grey Yellow Brown Red Black Blue Purple Orange
8 +24V 7 +12V 6 GND 5 Open A 4 Open B
21
}
} }
}
}
} }
}
6.Wire diagram
:569IGT5VKTGTJ)RUYK
)UTTKIZOUTUL:UVYIGT5VKTUVZK^5’-+*-+:
Power d<‘)) 9GLK:KYZU[ZV[Z C relay
6[RYKOTKXYOUT)RUYKYOJK
9GLK:KYZU[ZV[Z C relay
9ZUVV[RYK5VKTYOJK Output test
5VZOIGRIU[VRKX <URZGMK d<)
(+) (-) COM NC NO COM NC NO (+) (-)
1. White 2. Brown 3. Green 4. Yellow 5. Grey 6. Pink 7. Blue 8.Red 9. Black 10. Purple
9 +24V
10 +12V
11 GND
12
Anti-collision closing
13
Anti-collision opening
)UTTKIZOUTUL:UVYIGT)RUYK
Power d<‘)) 9GLK:KYZU[ZV[Z C relay
6[RYKOTKXYOUT)RUYKYOJK
9GLK:KYZU[ZV[Z C relay
9ZUVV[RYK5VKTYOJK Output test
5VZOIGRIU[VRKX <URZGMK d<)
(+) (-) COM NC NO COM NC NO (+) (-)
1. White 2. Brown 3. Green 4. Yellow 5. Grey 6. Pink 7. Blue 8.Red 9. Black 10. Purple
9 +24V
10 +12V
11 GND
12
Anti-collision closing
13
Anti-collision opening
22
7. Data setting
1.UPS+ 2.UPS3. E-lock+
4.OPEN B 5.OPEN A 6.GND 7.+12V 8.+24V
9.+24V 10.+12V 11.GND 12.Anti-collision closing 13.Anti-collision opening
14. Interlock input 15.COM 16.Interlock output
17.Synchronous input 18.GND 19.Synchronous output
Motor
DIP
1. UP-Lock automatically,DOWN-Lock by signal 2. UP-Push and goDOWN-Push no go 3. UP-Right opening DOWN-Left opening 4. UP-Master driveDOWN-Slave drive 5. Signal shielding
L1 .Remote setting indicator L2 .Master drive indicator L3 .Slave drive indicator
Close buffer distance
Close speed
MIN
MAX
Buffer speed
– Learn –
–
Test
Open buffer distance
Open
speed
L 3
Opening N 2
time
1
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19
FUSE
Close buffer distance: Distance increase clockwise Open buffer
distanceDistance increase clockwise Open speedOpen speed increase clockwise
Close speedClose speed increase clockwise Buffer speed Buffer speed increase
clockwise Open hold timeHold time increase clockwisec0-20s adjustable
DIP switchThe selection of dip only make sense after restart system
1.E-LOCK:UP-Lock automatically Down-Lock by signal 2.Push and go UP: Active
Down: Disable 3.L/R switchUP-right open Down-left opencPower onin the default
mode door move to the close direction is correctPlease change the position of
Dip switch if door in open direction 4.Master and slave UP-Master drive Down-
Slave drive 5,Signal shielding
Button on the controller Test: Test button Press to active one open-close
round LearnRemote setting button
LED Indicator
L1: Indicator of remote settingcBlue L2:Master drive indicatorLed flash 1 time
in 4secondcRed L3:Slave drive indicatorLed flash 1time in 4 secondcGreen
23
8.Function of remote
AB
FC04: A Always open B Automatic C:Open one time D Full lock
C
D
Add the remote Keep press the learning button on controllerL1 Blue Led is on
relese learn button and press A on remote Blue led flash 3 times remote is
added
Delet remote Keep press the learning button 9 secondL1 turn from blue to flash
all the remote is deletcattention while the process of deletlearning button
should keep press
Wireless push button Added and deleted wireless push button is same as remote.
Please check the DIP switch if it`s same as the image showncduring setting
process
Notes
1. Receiver has been built-in only need remote to approve the always open
automatic open one time full lock function and also fit with wireless push
button PB04 to open the door When controller is full lock PB04 still can
active the door 2. Exit only function:Connect outside sensor or button to
terminal”Open-B”, connect inside sensor or button to terminal “Open-A”.Then
press “full lock” button on remote 3.In double open mode connect Synchronous
line refer to the manual .power on ,make sure the setting is same If open and
close speed is not same,please adjust open /close speed, open/close buffer
speed,open hold time. 4.When double open, the transmitter should learn both
operators together.
5.In double open mode accessories should connect to both controller parallel
connection
24
9.LED instructions
Normal working Learning mode
Double open
Master drive
Red Led flash every 4seconds Meanwhile Green led off
Slave drive
Green Led flash every 4seconds Meanwhile Red led off
Red Led on 2secondsOff 2seconds within 4 secondsMeanwhile Green
Led off
Green Led on 2secondsOff 2 seconds within 4 secondsMeanwhile Red led off
Set both operator as main Buzzer not bip Red and green led flash 2times within 4seconds drive or slave drive
Not connect synchronous line or wrong connect
Buzzer not bipRed and green led flash 3times within 4seconds
Single open
Normal working Red and green LED alternately brighten,Red led light up while
green
off 1secondthen Green led light up while red off 1seconds
Leanring mode Red and green LED alternately brighten,Red led light up while
green
off 2secondthen Green led light up while red off 2seconds
Overcurrent protection Buzzer bip each 1 secondRed led and green led flash 5 times together within 4seconds Motor problem Buzzer bip each 2 secondsRed led and green led flash 4 times together within 4seconds
25
Read User Manual Online (PDF format)