HYTRONIK HIR28DCVFC Flush Mount PIR Motion Sensor Instruction Manual

June 3, 2024
HYTRONIK

HYTRONIK - logo HIR28DCVFC Flush Mount PIR Motion Sensor
Instruction Manual

HIR28DCVFC Flush Mount PIR Motion Sensor

Flush Mount PIR Motion Sensor PIR
HIR28DCVFC HIR28DCVFC/R HIR28DCVFC/W HIR28DCVFC/H Low-bay Reinforced Low-bay Wide range Low-bay High-bay

Applications
Office, classroom and commercial interior spaces where on/off control is required.

  • Office / Commercial Lighting
  • Classrooms
  • Stairwells / Corridors

HIR28DCVFC with on/off relay control
HIR28DCVFC is a PIR standalone motion sensor, On/Off control with relay output.It’s voltage-free contact which is NO relay (normally on). Designed with a low profile  or aesthetically demanding architectural projects providing a high quality sensor for simple on/off occupancy control or providing semi-automatic (absence detection)  control.
An intelligent photocell is also included to prevent switching of the lights when natural daylight is availible.
Set-up of the sensor is carried out using a remote control handset with program memory allowing one-key commissioning where common settings are used for multiple devices.

Features

| On/Off control with ralay output
---|---
| VFC: Volt-free Contact/Dry Contact with NO relay − 24VDC@5A       − 250VAC@5A
| Ceiling/Surface mount box available as accessory
| Various PIR lens and blind inserts options
| User-friendly design for installation
| High bay version available (up to 15m in height)
| Store settings in the remote for easy commissioning when programming multiple sensors.
| Intelligent photocell – lights and sensors only operate when needed, natural light has proirity.
| 5-year warranty

Technical Data

Input Characteristics

Model No. HIR28DCVFC
Input 12-48VDC
Stand-by power <0.5W
Output (Loading) 24VDC≤5A   250VAC≤5A
Warming-up 10s

Safety and EMC
EMC standard (EMC)| EN61547
Safety standard (LVD)| EN60669-1, EN60669-2-1
Certication| CB, CE , LVD, RCM
Environment
Operation temperature| Ta: -20O C ~ +50ºC
IP rating| IP20

Sensor Data

Model No. HIR28DCVFC
Sensor Model PIR detection

Detection range (Max.)
HIR28DCVFC| Installation Height : 6m
Detection Range(Ø) :9m
Detection range (Max.)

HIR28DCVFC/R| Installation Height : 6m
Detection Range(Ø) :10m
Detection range (Max.)
HIR28DCVFC/W| Installation Height : 6m
Detection Range(Ø) :18m
Detection range (Max.)

HIR28DCVFC/H| Installation height :15m (forklift)
12m (person)
Detection range (Ø) :24m
Detection angle| 360º

  • For more details of detection range, please refer to “detection pattern” section.

Mechanical Structure & Dimensions

HYTRONIK HIR28DCVFC Flush Mount PIR Motion Sensor -
Dimensions

Wire Preparation

HYTRONIK HIR28DCVFC Flush Mount PIR Motion Sensor -
Dimensions1

  1. Ceiling (drill hole Ø 66~68mm)
  2. Carefully prise off the cable clamps.
  3. Make connections to the pluggable terminal blocks.
  4. Insert plug connectors and secure using the provided cable clamps, then clip terminal covers to the base.
  5. Fit detection blind (if required) and desired lens.
  6. Clip fascia to body.
  7. Bend back springs and insert into ceiling.

Pluggable screw terminal. It is recommended to make connections to the terminal before fitting to the sensor.

Big and small silicon gasket used to make IP54 degree protection when HIR28DCVFC series device mounted into HA03 housing for ceiling mount

Small silicon water-proof gasket dimension(size:mm)

Big silicon water-proof gasket dimension(size:mm)

Wiring Diagram

Detection Pattern & Optional Accessories

1. HIR28DCVFC (Low-bay)

HIR28DCVFC: Low-bay flat lens detection pattern for single person @ Ta = 20º C
(Recommended ceiling mount installation height 2.5m-6m)

Mount height Tangential (A) Radial (B)
2.5m max 50m2(Ø = 8m) max 13m2 (Ø = 4m)
3m max 64m2 (Ø = 9m) max 13m 2 (Ø = 4m)
4m max 38m2 (Ø = 7m) max 13m2 (Ø = 4m)
5m max 38m2 (Ø = 7m) max 13m2 (Ø = 4m)
6m max 38m2(Ø = 7m) max 13m2 (Ø = 4m)

Optional Accessory — Ceiling/Surface Mount Box: HA03

HYTRONIK HIR28DCVFC Flush Mount PIR Motion Sensor - Wiring
Diagram3

Optional Accessory — Blind Insert for Blocking Certain Detection Angles

HYTRONIK HIR28DCVFC Flush Mount PIR Motion Sensor - Wiring
Diagram4

HIR28DCVFC/R (Reinforced Low-bay)

HIR28DCVFC/W: Low-bay convex lens detection pattern for single person @ Ta = 20ºC
(Recommended ceiling mount installation height 2.5m-6m)

Mount height Tangential (A) Radial (B)
2.5m max 79m2(Ø = 8m) max 20m2 (Ø = 5m)
3m max 79m2 (Ø = 9m) max 20m 2 (Ø = 5m)
4m max 64m2 (Ø = 7m) max 20m2 (Ø = 5m)
5m max 50m2 (Ø = 7m) max 20m2 (Ø = 5m)
6m max 50m2(Ø = 7m) max 20m2 (Ø = 5m)

Optional Accessory — Ceiling/Surface Mount Box: HA03

HYTRONIK HIR28DCVFC Flush Mount PIR Motion Sensor - Wiring
Diagram3

Optional Accessory — Blind Insert for Blocking Certain Detection AnglesHYTRONIK HIR28DCVFC Flush Mount PIR Motion Sensor - Wiring
Diagram4

HIR28DCVFC/W (Wide range Low-bay)

HIR28DCVFC/W: Low-bay convex lens detection pattern for single person @ Ta = 20ºC
(Recommended ceiling mount installation height 2.5m-6m)

Mount height Tangential (A) Radial (B)
2.5m max 254m2(0 = 18m) max 28m2(0 = 6m)
3m max 254m2 (0 = 18m) max 28m2 (0 = 6m)
4m max 154m2 (0 = 14m) max 28m2 (0 = 6m)
5m max 113m2(0 = 12m) max 28m2(0 = 6m)
6m max 79m2(0 = 10m) max 13m2 (0 = 4m)

Optional Accessory — Ceiling/Surface Mount Box: HA03HYTRONIK HIR28DCVFC
Flush Mount PIR Motion Sensor - Wiring Diagram3

HIR28DCVFC/H (High-bay)

HIR28DCVFC/H: High-bay lens detection pattern for forklift @ Ta = 20ºC
(Recommended ceiling mount installation height 10m-15m)

Mount height Tangential (A) Radial (B)
10m max 380m 2 (Ø = 22m) max 201m2 (Ø = 16m)
11m max 452m 2 (Ø = 24m) max 201m 2 (Ø = 16m)
12m max 452m 2 (Ø = 24m) max 201m 2 (Ø = 16m)
13m max 452m 2 (Ø = 24m) max 177m 2 (Ø = 15m)
14m max 452m 2 (Ø = 24m) max 133m 2 (Ø = 13m)
15m max 452m 2 (Ø = 24m) max 113m 2 (Ø = 12m)

HIR28DCVFC/H: High-bay lens detection pattern for single person @ Ta = 20ºC
(Recommended ceiling mount installation height 2.5m-12m )

Mount height Tangential (A) Radial (B)
 2.5m max 50m2 (0 = 8m) max 7m2 (0 = 3m)
6m max 104m2 (0 = 11.5m) max 7m2(0 = 3m)
8m max 154m2 (0 = 14m) max 7m2 (0 = 3m)
10m max 227m2 (0 = 1 7m) max 7m2(O = 3m)
 llm max 269m2 (0 = 18.5m) max 7m2(0 = 3m)
12m max 314m2 (0 = 20m) max 7m2(0 = 3m)

Optional Accessory — Ceiling/Surface Mount Box: HA03

HYTRONIK HIR28DCVFC Flush Mount PIR Motion Sensor - Wiring
Diagram3

Optional Accessory — Blind Insert for Blocking Certain Detection Angles

HYTRONIK HIR28DCVFC Flush Mount PIR Motion Sensor - Wiring
Diagram4

Functions and Features

  1. On/ off Control
    This sensor is a motion switch, which turns on the light upon detection of motion, and turns off after a pre-selected hold-time when there is no movement. A daylight sensor is also built in to prevent the light from switching on when there is sufficient natural light.

  2. Intelligent Photocell (daylight detection prior to motion detection)
    The built-in photocell will also automatically turn off the light when the ambient natural light exceeds the programmed lux level for more than 5min, regardless of whether motion is detected or not.

With sufficient natural light, the light  does not switch on when presence is detected.

With insufficient natural light, the sensor switches on the light automatically when presence is detected.

The sensor switches off the light when natural light is sufficient, even with presence.

Settings (Remote Control HRC-12)

Permanent ON/OFF function
Press button “ON/OFF” to select permanent ON or permanent OFF mode.

  • Press button “AUTO”, “RESET” or “Ambient” to quit this mode.
    The mode will change to AUTO Mode after power failure.

HYTRONIK HIR28DCVFC Flush Mount PIR Motion Sensor -
remote

Reset Settings
Press button “RESET”, all settings go back to default values as below:
Detection range: 100%; Hold-time: 5min; Lux disabled

Sensor mode
Press “Auto Mode” button, the sensor starts to function and all settings remain the same as the latest status before the light is switched on/off.

SEMI-AUTO mode
This button is disabled.

Daylight threshold
Press buttons in zone “ Daylight threshold” to set daylight sensor at 2Lux/ 10Lux / 50Lux / 100Lux / 300Lux / 500Lux / Disable.
Ambient daylight threshold
Press button “Ambient”, the surrounding lux level is sampled and set as the new daylight threshold.
Hold-time
Press buttons in zone “hold-time” to set the hold-time at 5sec / 1min / 5min / 10min / 15min / 30min / 60min.

Additional Information / Documents

  1. Regarding precautions for PIR sensor installation and operation, please kindly refer to
    www.hytronik.com/download->knowledge->PIRSensors- Precautions for Product Installation and Operation

  2. Regarding Hytronik standard guarantee policy, please refer to www.hytronik.com/download->knowledge->Hytronik Standard Guarantee Policy

Subject to change without notice.
Edition: 19 Sep. 2022 Ver. A0 HYTRONIK - logo

References

Read User Manual Online (PDF format)

Read User Manual Online (PDF format)  >>

Download This Manual (PDF format)

Download this manual  >>

HYTRONIK User Manuals

Related Manuals