BROAN B33DHW Dehumidifier
SAFETY INSTRUCTIONS
READ THE INSTALLATION, OPERATION AND MAINTENANCE INSTRUCTIONS CAREFULLY BEFORE INSTALLING AND OPERATING THIS DEVICE. PROPER ADHERENCE TO THESE INSTRUCTIONS IS ESSENTIAL TO OBTAIN MAXIMUM BENEFIT FROM THIS DEHUMIDIFIER.
WARNING
THIS SYMBOL MEANS IMPORTANT INSTRUCTIONS. FAILURE TO HEED THEM CAN RESULT IN
SERIOUS INJURY OR DEATH.
CAUTION
THIS SYMBOL MEANS IMPORTANT INSTRUCTIONS. FAILURE TO HEED THEM CAN RESULT IN
INJURY OR MATERIAL PROPERTY DAMAGE.
Registrations
The B33DHW conforms to unified standard UL 60335-2-40 and CSA Standard
C22.2.60335-2-40.
WARNING
120 VOLTS MAY CAUSE SERIOUS INJURY FROM ELECTRIC SHOCK. TURN OFF CIRCUIT
BREAKER BEFORE STARTING INSTALLATION OR SERVICING, AND LEAVE CIRCUIT BREAKER
OFF UNTIL INSTALLATION OR SERVICE IS COMPLETED.
CAUTION
READ ALL INSTRUCTIONS BEFORE BEGINNING INSTALLATION.
ALWAYS USE CAUTION AND WEAR CUT RESISTANT GLOVES WHEN HANDLING SHEET METAL.
ALL STATE AND NATIONAL ELECTRICAL AND PLUMBING CODES MUST BE ADHERED TO FOR
PROPER UNIT OPERATION AND WARRANTY COMPLIANCE.
IMPROPER INSTALLATION MAY CAUSE PROPERTY DAMAGE OR INJURY.
INSTALLATION, SERVICE, AND MAINTENANCE MUST BE PERFORMED BY A QUALIFIED
SERVICE TECHNICIAN.
DEHUMIDIFIER IS HEAVY. HANDLE WITH CARE AND FOLLOW INSTALLATION INSTRUCTIONS.
THIS APPLIANCE IS INTENDED FOR USE AT ELEVATIONS BELOW 4000 M (13,000 FT).
THIS APPLIANCE IS NOT INTENDED FOR USE BY PERSONS (INCLUDING CHILDREN) WITH
REDUCED PHYSICAL, SENSORY OR MENTAL CAPABILITIES, OR LACK OF EXPERIENCE OR
KNOWLEDGE, UNLESS THEY HAVE BEEN GIVEN SUPERVISION OR INSTRUCTION CONCERNING
THE USE OF THE APPLIANCE BY A PERSON RESPONSIBLE FOR THEIR SAFETY. CHILDREN
SHOULD BE SUPERVISED TO ENSURE THAT THEY DO NOT PLAY WITH THE APPLIANCE.
DEHUMIDIFIER SET UP
Important Precautions
- If used near a water source, be certain that there is no chance the unit could get splashed. Connecting the unit to a dedicated circuit with Ground Fault Circuit Protection is recommended. Electrical wires must be properly grounded, and with the capability to be disconnected to provide for service.
- The device is designed to be installed indoors in a space that is protected from rain and flooding.
- Tamper proof fasteners provide access to the front of the device for operation, maintenance and service.
- Avoid directing discharge air at occupants.
- DO NOT place sides, top or bottom of cabinet in direct contact with structural building members or unwanted noise may result. Unit is designed to be suspended by side mounting flanges only.
- Drain hose must be routed with downward slope from unit drain connection to appropriate location. Consult local building codes for acceptable condensate drain connections.
Location Considerations
-
Install the unit on or inside of an interior wall and with direct connection to building electrical service.
A 15 Amp circuit must be provided. Install the unit in a location that is near a power supply. -
Electrical and plumbing rough-in must be provided to installation location, adhering to any applicable local codes.
-
Install the unit in a central location to maximize air circulation and efficiency. Do not locate inside a closet or mechanical room with the diffuser cover facing inward where both supply and return air will be limited.
-
Install the unit such that discharge air is directed away from thermostats and not installed inside of a wall cavity that contains a thermostat.
-
The unit generates condensate. Install the unit with nearby access to a drain or determine if there will be a need for a condensate pump.
-
The unit will fit within 16″ O.C. stud walls. If walls are more or less than 16″, consideration must be given to providing additional support.
-
Rough opening must be a minimum of 2″ off the floor, 6″ from the ceiling, and 10″ from an inside corner.
-
Check that there are no hidden wires or pipes inside the wall where unit is to be installed. Contact a certified electrician or plumber before removing any wires or pipes inside the wall.
DRAIN INSTALLATION CONSIDERATIONS
Consult local building codes for condensate drain restriction and additional
requirements. The B33DHW is provided with 10′ of 3/4″ I.D. drain hose. Verify
drain hose length is appropriate for application.
The hose must be connected to the drain port and routed down the wall cavity
and into the air conditioning condensate drain or other acceptable drainage.
- For gravity drainage, the bottom of the unit must be at, or above the drain height.
- Avoid any entrapment of stagnant water within the hose.
- Consider 1/4″ drop for every foot of drain hose.
- Codes may dictate that a drain trap is necessary before or near to the main building drain.
Be sure to install the metal cover over the top of the hose. This prevents air from entering the unit through the wall cavity.
ELECTRICAL REQUIREMENTS
A 10′ long power cord is included for installations where a plug in connection
is permitted in accordance with the National Electrical Code and local codes
and ordinances. A dedicated 15A circuit and GFCI receptacle are recommended.
Electrical connections inside the device are made with the included wire nuts.
Route the cord through the appropriate knockout and secure with the non-
metallic cable clamp.If not using
the included 10′ power cord, ensure that the electrical connection and wire
size are adequate and in conformance with the National Electrical Code,
ANSI/NFPA 70 – latest edition and all local codes and ordinances. Use
flexible, armored, or non-metallic sheathed, copper wire with grounding
conductor. Use the included non-metallic cable clamp as required.
- The B33DHW requires 120-volt, 60 Hz, AC-only, 15 amp, fused and grounded electrical supply.
- A visible circuit breaker or disconnect switch near the unit is required for maintenance and service.
- A dedicated circuit is recommended.
- Use of a UL listed or CSA approved strain relief is required.
DEHUMIDIFIER INSTALLATION
The B33DHW can be installed in a variety of applications:
- 2×6 16″ O.C. Stud Wall Installation
- 2×4 16″ O.C. Stud Wall Installation
- If penetrating both walls and the opposite side is a mechanical room, no additional accessories are needed.
- If back wall is functional space, installation requires 2×4 Wall Mount Bezel Kit (PN 4037767).
- If the other side of the wall goes into an unconditioned space, it may require the 2×4 Rear Panel Kit (PN 4037768) to add a layer of insulation to prevent condensation.
- Surface Mount Installation
- Surface Mount Kit (PN 4037766) required for installation.
Surface Mount, Bezel Kit and Rear Panel installations can be viewed at www.inwalldehumidifier.com/accessories
Items Included in Box:
- B33DHW Dehumidifier
- Diffuser Cover with Filter
- B33DHW Installation Instructions
- Drain Hose (10′)
- Power Cord (10′)
- Hose Clamp
- Grommet for Drain Hose
- Non-Metallic Cable Clamp
- Bag A: #10 Wood Screws (5)
- Bag B: #8 Sheet Metal Screws (5)
- Bag C: Tamper Resistant Screws for Diffuser Cover (5) and 1/4″ Hex T-15 Torx Security Bit
- Bag D: Phillips Screws for Diffuser Cover (5)
Tools Required:
- Phillips Screwdriver
- 1/4″ Hex Nut Screwdriver
- Level
- Square or Ruler
- Stud Finder
- Wire Stripper
- Drywall Saw
- Side Cutters or Carpenters Knife
- Tape Measure
- Pen or Pencil
Other Materials To Consider:
- Electrical wire (depends on installation and distance of wiring requirements)
- Additional hose length or PVC pipe (depends on drain location)
- Materials to repair drywall (depends on installation)
- Condensate Pump Kit (depends on drain location)
- GFCI Outlet (if using supplied power cord)
WARNING
SHUT OFF BREAKER / POWER BEFORE BEGINNING INSTALLATION.
-
Step 1. Remove the shipping bracket by carefully cutting the two zip ties with side cutters or shears. Remove the four screws from the shipping bracket using a 1/4″ hex nut screwdriver.
-
Step 2. Remove electrical box cover from the unit by removing the two screws on the cover using a 1/4″ hex nut screwdriver.
-
Step 3. There are three electrical knock outs, one on the back and two on the bottom of the unit. Remove appropriate knock out and install non-metallic cable clamp with clamp screws inside of unit oriented so they are accessible for tightening later.
-
If using included power cord, insert cord through non-metallic cable clamp so that a minimum of ½” insulation jacket is inside of cabinet before tightening non-metallic cable clamp screws. Make electrical connections using included wire nuts.
-
Step 4. The drain hose can exit through the back, side, or bottom of the unit. Once the location is determined, remove the appropriate knock out.
If exiting through the bottom, remove the access cover to facilitate routing of the drain line.
Save access cover for reinstallation after drain line is routed. -
Step 5. After installation location has been determined, use a stud finder, locate and mark stud walls.
-
Step 6. Using measuring tape and pencil, measure 14 1/2″ across and 30 1/4″ down and draw a line.
-
Step 7. Using a square or ruler, score the lines and cut with drywall saw.
Depending on installation, both walls may need to be cut through. -
Step 8. If not using included power cord, route the electrical wire from the circuit breaker or disconnect switch through the wall cavity and extend out of the opening by 14″ to 20″.
Use the 10′ drain hose provided or the appropriate length of hose to come through the wall cavity or back of the unit and extend out of the opening by 14″.
If cutting through both walls, electrical wiring and drain hose may be routed differently. Use appropriate routing for your installation. It is recommended to have two people to lift the unit. Place one hand under the drain pan to support the unit during this step. -
Step 9. Lift the unit and place it near the wall opening to route electrical wires and drain hose through appropriate knock outs.
-
If access cover was not removed, insert grommet into knock out hole and snap into place before routing drain hose through.
-
Step 10. Once electrical and drain hose are routed through the unit, set the unit into the wall.
CAUTION: THE UNIT IS NOT SECURED YET.
Before securing the unit into place, make sure it is level. Level or slightly forward is acceptable, but never backwards. -
Step 11. Insert the dehumidifier into the center of the opening, allowing for a minimum of 1/8″ clearance from framing on both sides. Additional insulation or sound dampening material (not provided) may be required if the dehumidifier cabinet contacts the studs, especially in applications involving metal studs.
Fasten the unit to the framing by inserting four of the #10 (wood) or #8 (sheet metal) screws into the slotted holes.
Top and bottom blocking is not necessary for securing the dehumidifier. Any existing blocking, headers or framing should not intrude into the rough opening and be a minimum of 1/2″ away from the cabinet.
The cabinet is designed to create 1/2″ clearance to the back wall when installed inside a standard 2×6 stud space with 1/2″ minimum drywall sheathing.
For alternate installations, maintain 1/2″ clearance to back of wall of dehumidifier cabinet. -
Step 12. If the drain access cover was removed, reinstall it by routing the drain hose through the appropriate knock out and reattach the screw. Route the grommet over the drain hose and snap into place at the knock out.
Use 1/4″ hex nut screwdriver to apply hose clamp to the drain hose and secure onto the drain port hose barb. -
Step 13. Complete electrical connections:
- white to white
- green to green
- black to black
Screw wire nuts back onto each electrical connection.
Then tighten clamp screws on non-metallic cable clamp.
-
Step 14. Tuck the electrical wires in and reinstall electrical cover with its two screws using 1/4″ hex nut screwdriver. Be sure none of the electrical wires are pinched.
Make sure drain hose is routed to the appropriate location before turning on the unit. -
Step 15. Turn breaker / power back on.
-
Step 16. Set the digital controller to desired RH. See Controls Section on page 12.
-
Step 17. Install diffuser cover by aligning the lower tabs first, then setting the cover back against the wall. Insert the included four tamper resistant or philips screws to secure the diffuser cover.
MAINTENANCE
WARNING
BE SURE THE UNIT IS POWERED OFF AND UNPLUGGED OR CIRCUIT BREAKER IS TURNED OFF
BEFORE REMOVING THE FRONT COVER TO SERVICE THE UNIT; IF THE SUPPLY CORD IS
DAMAGED, IT MUST BE REPLACED BY THE MANUFACTURER, ITS SERVICE AGENT OR
SIMILARLY QUALIFIED PERSONS IN ORDER TO AVOID A HAZARD.
Filter Maintenance
The B33DHW comes with a washable filter. Check filter every two months. Clean
or replace the filter as necessary.
Removing the Filter:
Remove the screws on the front cover and then push the front cover up gently
to free the cover hooks from the chassis. Filter is located on the back side
of the front cover. Gently remove the filter by lifting the bottom side
corners first to prevent bending it.
Filter Cleaning:
The filter can be vacuumed with a wet / dry vac or washed with warm water.
Reinstalling the Filter:
Insert the filter into the tabs on top of mount and flex the filter to insert
it into the bottom tabs. Reinstall the cover by lining up the tabs, sliding
down into place, and secure with included tamper resistant or phillips screws.
Diffuser Maintenance
It is recommended to use a mild detergent to clean the surface of the
diffuser, especially around the edges where the return air is flowing into the
unit (see illustration below). This is where air is being drawn into the
filter and may collect dust. Do not use harsh solvents on the diffuser.
The diffuser can be painted to blend in with interior aesthetics. Use only
paint that is recommended for polycarbonate surfaces and follow the
manufacturer’s recommendations for surface prep and application.
AIR FLOW
The B33DHW functions by drawing moist air in through the bottom portion of the
diffuser and returning dried air to the space out the top portion of the
diffuser.
Note: Avoid blocking the return and supply air flow to maximize unit
performance and prevent heat build up. Furniture must be at least 6″ away from
the diffuser.
CONTROLS
The B33DHW has an illuminated display, user selectable setpoint, and a power
ON / OFF button located behind the diffuser. The diffuser is fastened with
tamper resistant screws to limit access to the control. The diffuser can also
be fastened with the included phillips screws if limiting access to the
control is not needed.
When turning power on for the first time, the set point will be at the factory
setting of 55% RH. In the event of a power outage, the dehumidifier restarts
at the previous set point when power is restored.
Pressing the middle button (the power button), the control will toggle the
B33DHW to turn ON or OFF.
If the unit is on and power button is pressed, control will turn compressor
and fan off. As a result, both DISPLAY and LED will go off.
If the unit is off and power button is pressed, control will turn fan on. As a
result, both DISPLAY and LED will go on.
If there is an error, the unit will shut down and indicator LED will turn to
red and display will show an error code (see page 13 for error codes).
Sequence of Operation
-
Press the ON / OFF button to turn the dehumidifier control on. The display will show “00” for a couple of seconds and then it will display the RH level of the room and the dehumidifier blower will turn on to start sampling the air for one minute.
Indicator LED, located above display, will be green, showing the unit is operating normally. -
Pressing either of the arrow keys will cause the DISPLAY to flash and indicate the current set point. The RH set point can be adjusted from a minimum of 35% to a maximum of 99% in 1% increments. Adjust the humidity set point as desired. The recommended initial setting is 55%.
Pressing the DOWN arrow key below the 35% set point on the control will cause the display to read “00” and the B33DHW will run continuously. After 10 seconds, it will go back to display room RH level.
Ten seconds after making an adjustment, from either UP or DOWN arrow keys, the display will go back to show the room RH level. -
If the sensor detects a reading above the set point, it will run the fan to sample the return air for a period of one minute. The sampled humidity of the return air will be compared to the RH setting. If the humidity is above the setting, the dehumidifier compressor turns on. The compressor remains on until the measured humidity falls 3%below the RH setting. If the sampled humidity is below the setting, the compressor and blower turn off and the display returns to showing the RH setting. The dehumidifier will sample again every 15 minutes.
Diagnostic, Maintenance and Servicing
Error codes:
- “1” = Prompting a bad RH sensor.
- “2” = Condensate pump or external float switch is installed in the drain line and is detecting a closed switch.
- “3” = The delta temperature between ambient and evaporator coil not wide enough to reflect a normal operating condition.
Unit will turn off and try to restart after an hour.
Evaporator Temperature Mode
To enter evaporator temperature mode, press and hold both arrow buttons for >5
seconds and the LED will change to Blue.
The display will flash at twice the rate of “set point” mode, and display the
evaporator coil temperature. Press any button to exit evaporator temperature
mode.
Ambient Temperature Mode
To enter ambient temperature mode, press and hold the up arrow and power
buttons for >5 seconds and the LED will change to Purple.
The display will flash at twice the rate of “set point” mode and display the
ambient temperature.
Press any button to exit ambient temperature mode.
SERVICE
CAUTION
TROUBLESHOOTING SHOULD BE PERFORMED BY A QUALIFIED HVAC TECHNICIAN.
WARNING
ELECTRICAL SHOCK HAZARD: ELECTRICAL POWER MUST BE PRESENT TO PERFORM SOME
TESTS. THESE TESTS SHOULD BE PERFORMED BY A QUALIFIED SERVICE PERSON.
120 VOLTS MAY CAUSE SERIOUS INJURY FROM ELECTRIC SHOCK. TURN OFF CIRCUIT
BREAKER BEFORE STARTING INSTALLATION OR SERVICING, AND LEAVE CIRCUIT BREAKER
OFF UNTIL INSTALLATION OR SERVICE IS COMPLETED.
Troubleshooting
| |
---|---|---
Symptom| Possible Reason| Troubleshooting Procedure
Neither blower nor compressor is running and display is off.|
- No power to unit, circuit breaker tripped
- Power board wiring or connector loose
- Control board wiring or connector loose
- Circuit board failure
|
- Locate circuit breaker and reset if necessary.
- Check all circuit board connections for loose plugs or wires.
- Replace control board and power board.
Neither blower nor compressor is running and display is on.|
- No call for dehumidification
- Wiring or connectors loose
|
-
Press down arrow until setpoint reads “00”,
wait 1 minute, fan and compressor should run. -
Check wiring and connectors for damage or loose connections.
Blower is running and compressor is cycling on and off while ambient humidity is high.|
- Unit is defrosting
- Ambient temperature is too low
- Defrost sensor malfunction
- Poor airflow
- Failing compressor relay
- Compressor or sealed system failure
|
- Check setpoint, if setting is “00” increase setpoint to 55%.
- Cold ambient conditions will cause unit to go in and out of defrost (this is normal).
- Press and hold both arrow buttons for >5 seconds to display the defrost sensor temperature, replace sensor if reading is in error.
- Verify airflow over the coils is not blocked or restricted, clean filter and/or coils as required
Replace power board.
- Note that sealed system is not generally field serviceable.
Blower is not spinning humidity is high and compressor is running.|
- Wiring or connectors loose
- Blower relay failure
- Blower capacitor failure
- Blower failure
|
- Check wiring and connectors for damage or loose connections.
- Check power to blower circuit, replace power board if no power is detected.
- Replace blower capacitor if failed.
- Replace blower (note requires unit be removed from installation).
Blower is running and compressor is off while ambient humidity is high (evaporator coil is warm).|
- Wiring or connectors loose
- Compressor relay failure
- Compressor capacitor failure
- Compressor failure
|
- Check wiring and connectors for damage or loose connections.
- Check power to compressor circuit, replace power board if no power is detected.
- Replace compressor capacitor if failed.
- Note that sealed system is not generally field serviceable.
Poor dehumidification performance and evaporator coil is covered in ice or frost.|
- Defrost sensor or connection is defective
- Poor airflow
- Low refrigerant charge
|
- Check circuit board connection for loose plug or wires.
- Press and hold both arrow buttons for >5 seconds to display the defrost sensor temperature, replace sensor if reading is an error. See diagnostic – Error code “ 1”
- Verify airflow over the coils is not blocked or restricted, clean filter and/or coils as required.
- Note that sealed system is not generally field serviceable
- See diagnostic – Error code “3”
Poor dehumidification performance, compressor is running and evaporator coil is not cooling.|
- Failed compressor or low refrigerant charge
|
- See diagnostic – Error code “3”
- Note that sealed system is not generally field serviceable.
Leak or standing water in drain pan.|
- Kink in drain line
- Drain line clogged
- Clog in small vinyl tubing that connects the drain pan to drain port
|
- Verify there are no kinks in the drain line.
- Verify there are no clogs in drain line. If clogged pour mixture of household vinegar (diluted 1:3) with water directly into the front edge of the drain pan.
- Verify no clogs in small vinyl tubing that connects drain pan to drain port by pouring a small amount of water into the front edge of the drain pan to make sure it flows through the drain port. If water does not come through verify MD33 is plumb and not leaning forward or out of level.
WARRANTY
Limited Warranty
Broan, LLC (“Broan”) warrants as follows: (i) the B33DHW dehumidifier
(“Product”) will be free of material defects in workmanship or materials for a
period of one (1) year (“One-Year Warranty”) following the date of initial
purchase
of such Product by an original customer purchasing from Broan or an authorized
reseller (“Customer”); and (ii) the Product’s components will be free of
material defects in workmanship or materials for a period of four (4) years
following the date of initial purchase of such Product by a Customer.
Limitation of Remedies
CUSTOMER’S SOLE AND EXCLUSIVE REMEDY UNDER THE ABOVE LIMITED WARRANTY AND
BROAN’S ENTIRE LIABILITY THEREUNDER, SHALL BE, AT THE SOLE OPTION OF BROAN,
REPLACEMENT OR REPAIR OF SUCH PRODUCT OR ITS COMPONENTS (“COMPONENTS”) BY
BROAN OR BROAN’S AGENTS ONLY. REFRIGERANT, PIPING, SUPPLIES, TRANSPORTATION
COSTS, LABOR COSTS INCURRED IN REPAIR OR REPLACEMENT OF SUCH COMPONENTS ARE
NOT INCLUDED. THIS DISCLAIMER AND EXCLUSION SHALL APPLY EVEN IF THE EXPRESS
WARRANTY AND LIMITED REMEDY SET FORTH HEREIN FAILS OF ITS ESSENTIAL PURPOSE.
CUSTOMER ACKNOWLEDGES THAT NO REPRESENTATIVE OF BROAN OR OF ITS AFFILIATES OR
RESELLERS IS AUTHORIZED TO MAKE ANY REPRESENTATION OR WARRANTY ON BEHALF OF
BROAN OR ANY OF ITS AFFILIATES OR RESELLERS THAT IS NOT IN THIS AGREEMENT.
Notwithstanding the above, during the term of the One-Year Warranty only,
Broan will provide, free of charge to Customer, all Components and labor
(except costs related to removal and installation of Product) required to
fulfill its obligations under such One-Year Warranty.
Disclaimer of Warranties
EXCEPT FOR ABOVE LIMITED WARRANTY, WHICH IS THE SOLE AND EXCLUSIVE WARRANTY
PROVIDED WITH RESPECT TO THE PRODUCT AND ITS COMPONENTS, BROAN HEREBY
DISCLAIMS ALL EXPRESS AND IMPLIED WARRANTIES, INCLUDING, WITHOUT LIMITATION,
THE IMPLIED WARRANTIES OF MERCHANTABILITY AND FITNESS FOR A PARTICULAR
PURPOSE.
Warranty Limitations
The foregoing limited warranty extends only to a Customer and shall be null
and void upon attempted assignment or transfer. A “defect” under the terms of
the limited warranty shall not include problems resulting from Customer’s or
Customer’s employees’, agents’, invitees’ or a third party’s misuse, improper
installation, improper design of any system in which the Product is included,
abuse, lack of normal care, failure to follow written instructions, tampering,
improper repair, or freezing, corrosion, acts of nature or other causes not
arising out of defects in Broan’s workmanship or material. If a Product or
Component is replaced while under warranty, the applicable limited warranty
period shall not be extended beyond the original warranty time period. The
limited warranty does not cover any costs related to changes to a Product or
Component that may be required by any codes, laws, or regulations that may
become effective after initial purchase of the Product by Customer.
Customer Responsibilities
As a further condition to obtaining warranty coverage hereunder, the
Customer must send a valid warranty claim to Broan such that Broan receives
such claim prior to the end of the applicable warranty period. Broan shall
have no obligation hereunder with respect to any claim received by Broan after
the expiration of the applicable warranty period. As a further condition to
obtaining warranty coverage hereunder, the Customer must present forms of
invoices evidencing proof of purchase of a Product. If such invoices do not
clearly indicate the date of initial purchase by a Customer, the applicable
Product’s date of manufacture will be used instead of the date of initial
purchase for the purpose of calculating the commencement of the applicable
warranty period. Warranty service must be performed by Broan or a servicer
authorized by Broan. In order to obtain warranty service, the Customer should
call Broan at 1-800-558.1711 and ask for the Broan Products Service
Department, which will then arrange for applicable warranty service. Warranty
service will be performed during customary, daytime working hours. If the
Product must be shipped for service, Customer shall be solely responsible for
properly packaging the Product, for all freight charges, and for all risk of
loss associated with shipment.
Limitation of Liability
IN NO EVENT SHALL BROAN, IN CONNECTION WITH THE DESIGN, SALE, INSTALLATION,
USE, REPAIR, REPLACEMENT OR PERFORMANCE OF ANY PRODUCT, COMPONENT, PART
THEREOF OR WRITTEN MATERIAL PROVIDED THEREWITH, BE LIABLE, TO THE EXTENT
ALLOWED UNDER APPLICABLE LAW, UNDER ANY LEGAL THEORY FOR ANY SPECIAL, DIRECT,
INDIRECT, COLLATERAL OR CONSEQUENTIAL DAMAGES OF ANY KIND. NOTWITHSTANDING THE
ABOVE LIMITATIONS AND WARRANTIES, THE SOLE AND EXCLUSIVE LIABILITY OF BROAN,
REGARDLESS OF THE NATURE OR THEORY OF THE CLAIM, SHALL UNDER NO CIRCUMSTANCES
EXCEED THE PURCHASE PRICE OF THE PRODUCT, COMPONENT OR PART UPON WHICH THE
CLAIM IS PREMISED.
Applicable Law and Venue
ANY ARBITRATION, ENFORCEMENT OF AN ARBITRATION OR LITIGATION RELATED TO THE
PRODUCT WILL BE BROUGHT EXCLUSIVELY IN DANE COUNTY, WISCONSIN, AND CUSTOMER
CONSENTS TO THE JURISDICTION OF THE FEDERAL AND STATE COURTS LOCATED THEREIN,
SUBMITS TO THE JURISDICTION THEREOF AND WAIVES THE RIGHT TO CHANGE VENUE.
CUSTOMER FURTHER CONSENTS TO THE EXERCISE OF PERSONAL JURISDICTION BY ANY SUCH
COURT WITH RESPECT TO ANY SUCH PROCEEDING.
Miscellaneous
If any term or condition of this Limited Warranty is found by a court of
competent jurisdiction to be invalid, illegal or otherwise unenforceable, the
same shall not affect the other terms or conditions hereof or thereof or the
whole of this Limited Warranty. Any delay or failure by Broan to exercise any
right or remedy will not constitute a waiver of Broan to thereafter enforce
such rights.
References
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>