CyberPower RMCARD205 Remote Management Card User Manual

June 3, 2024
CyberPower

CyberPower RMCARD205 Remote Management Card

Introduction

The CyberPower Remote Management Card RMCARD205 supports Modbus TCP protocol with firmware version 1.3.7 and above. The document describes the related setting and register roadmap.

Design Parameters

Design Parameters Value Remark
Role Server Response and execute the command
Port TCP/502 Standard port and fixed
Mode RTU MODBUS TCP
Unit ID/ Slave Address Arbitrary Can be any value. Recommend to be 0xFF or

0x00.

Exception Responses

The table below describes the exception codes along with their possible causes

Code Name Meaning
0lH ILLEGAL FUNCTION The function code received in the query is not an

allowable action for the slave. If a Poll Program Complete command was issued, this code indicates that no program function

preceded it.

02H| ILLEGAL

DATA ADDRESS

| The data address received in the query is not an allowable address for the slave.
03H| ILLEGAL DATA

VALUE

| A value contained in the query data field is not an allowable value for the slave.
04H| SLAVE DEVICE

FAILURE

| An unrecoverable error occurred while the slave was attempting to perform the requested

action.

Available Modbus Function Codes

The table below describes implemented MODBUS functions

Code Original Modbus Function
03H Read Holding Registers
10H Write Multiple Registers

Modbus Data Formats

16 bit Integer Values Values are stored in big-endian order per the MODBUS specification and consist of a single register. All integer values are documented a signed or unsigned. All signed values are represented using two’s-compliment.

Communication Example

The following tables contain the general command descriptions and example with Modbus RTU framing.

Function

code

| Address of first word to

read

| word count
---|---|---
1 byte| High byte| Low byte| High

byte

| Low

byte

Function

code

| Byte count| Bytes with contents of “n” words
---|---|---
1 byte| 1 byte| n * 2 bytes

Systems Modbus Register Map

Holding Registers (Function Code 03h)

Address

(Hex)

| Address

(Dec)

|

Parameter

|

Format

| Units

/Scale

|

Description

---|---|---|---|---|---

2000

|

8192

| Hardware fault

happen

|  |

Uint16

|

1:Yes, 0:No

2001| 8193| reserved|  | Uint16|
2002| 8194| reserved|  | Uint16|
2003| 8195| Battery-test

Last Result

|  | Uint16| 0: Pass, 1: Fail,

2:processing

2004| 8196| reserved|  | Uint16|

2005

|

8197

| Battery capacity is

lower than Low Battery Threshold

|  |

Uint16

|

1:Yes, 0:No

2006| 8198| Utility power status|  | Uint16| 1:Failure, 0:Normal
2007| 8199| Utility voltage out

of range

|  | Uint16| 1:Yes, 0:No
2008| 8200| Utility frequency

out of range

|  | Uint16| 1:Yes, 0:No
2009| 8201| Inverter is off|  | Uint16| 1:Yes, 0:No
200A~

200D

| 8202~

8205

|

reserved

|  |

Uint16

|
200E| 8206| battery not present|  | Uint16| 1:Yes, 0:No
---|---|---|---|---|---
200F~

2010

| 8207~

8208

| ****

reserved

|  | ****

Uint16

|


2011

| ****

8209

| Battery is

discharging

|  | ****

Uint16

| ****

1:Yes, 0:No

2012| 8210| Battery is charging|  | Uint16| 1:Yes, 0:No
2013| 8211| reserved|  | Uint16|


2014

| ****

8212

| Battery is fully

charged

|  | ****

Uint16

| ****

1:Yes, 0:No

2015~

201F

| 8213~

8223

| ****

reserved

|  | ****

Uint16

|


2020

| ****

8224

| Buzzer is muted at

present

|  | ****

Uint16

| ****

1:Yes, 0:No


2021

| ****

8225

| Remaining Runtime is lower than Low Battery Runtime

Threshold

|  | ****

Uint16

| ****

1:Yes, 0:No

2022| 8226| No output|  | Uint16| 1:Yes, 0:No
2023~

2229

| 8227~

12287

| ****

Reserved

|  |  |
229C| 8860| Over Temperature|  | Uint16| 1:Yes, 0:No
3000| 12288| Utility voltage| 0.lV| Uint16|
3001| 12289| Utility frequency| 0.lHz| Uint16|
3002~

301F

| 12290~

12319

| ****

Reserved

|  | ****

Uint16

|
3020| 12320| Output voltage| 0.lV| Uint16|
3021~

3026

| 12321~

12326

| Reserved|  | Uint16|
3027| 12327| Output load

percent

| 1%| Uint16|
3028~

3081

| 12328~

12417

| Reserved|  | Uint16|
3082| 12418| Battery capacity| 1%| Uint16|


3083

| ****

12419

| Remaining

Runtime.LowWord

| ****

0.lmin.

| ****

Uint16

| If Remaining Runtime.HighWord=2, Remaining Runtime.LowWord=18 then Remaining Runtime=(HighWord65 536+LowWord)0.lmin=

13109min



3084

| ****


12420

| ****


Remaining Runtime.HighWord

| ****


0.lmin.

| ****


Uint16

Write Multiple Registers (Function Code 10h)

CyberPower RMCARD205 Remote Management Card 1 CyberPower RMCARD205 Remote Management Card 2

CyberPower Systems, Inc.
www.cyberpowersystems.com
For USA and Canada: 4241 12th Ave East, Suite 400 Shakopee, MN 55379
Toll-free: 877-297-6937
For all other regions: Please visit our website for local contact information.

References

Read User Manual Online (PDF format)

Read User Manual Online (PDF format)  >>

Download This Manual (PDF format)

Download this manual  >>

Related Manuals