BLAUBERG VENTO Expert A30 W V.2 Single Room Reversible User Manual
- September 22, 2024
- BLAUBERG
Table of Contents
VENTO Expert A30 W V.2 Single Room Reversible
“`html
Specifications
-
Product Name: vento expert a30 W v.2
-
Product Type: Single-room reversible energy recovery
ventilator -
Manufacturer: Blauberg Ventilatoren
Product Information
The vento expert a30 W v.2 is a single-room reversible energy
recovery ventilator designed to provide fresh air while recovering
energy from the expelled air. The unit comes with various
components including an indoor unit, mounting frame, air duct,
assembled cartridge, outer ventilation hood, and necessary
installation accessories.
Safety Requirements
It is important to follow safety guidelines when using the vento
expert a30 W v.2. Make sure to connect the unit to the mains
through a disconnecting device and avoid back-flow of gases into
the room. When disposing of the product, ensure it is done
separately and not as unsorted domestic waste.
Technical Data
The vento expert a30 W v.2 operates on standard power mains with
a frequency band of 100-240 V ~ 50/60 Hz. It also features Wi-Fi
connectivity with IEEE 802.11 b/g/n support and WLAN safety
measures.
Design and Operating Principle
The ventilator design includes components like the outer
ventilation hood, mounting frame, indoor unit with touch buttons,
telescopic air duct, and cartridge assembly for air flow
generation, energy regeneration, and air cleaning. The unit is
equipped with features like an air humidity sensor and Boost mode
for enhanced functionality.
Product Usage Instructions
Installation
-
Refer to the provided user manual for detailed installation
instructions. -
Mount the indoor unit using the provided mounting frame on a
wall with a minimum thickness of 135 mm. -
Connect the air duct and assembled cartridge following the
designated key for proper alignment. -
Install the outer ventilation hood to protect the unit from
external elements.
Operation
-
Ensure the unit is connected to a suitable power source and
Wi-Fi network as per technical specifications. -
Use the touch buttons on the indoor unit to control ventilation
settings. -
Monitor the air humidity sensor for automatic speed adjustment
in Boost mode based on environmental conditions.
FAQ
Q: How do I dispose of the vento expert a30 W v.2 at the end of
its service life?
A: The product must be disposed of separately and not as
unsorted domestic waste. Contact local authorities or recycling
centers for proper disposal methods.
Q: Can I replace the supply cord if it gets damaged?
A: If the supply cord is damaged, it should be replaced by the
manufacturer, its service agent, or qualified persons to avoid
safety hazards. Do not attempt to repair it yourself.
“`
Single-room reverSible energy recovery ventilator
vento expert a30 W v.2
EN USER’S MANUAL
www.blaubergventilatoren.de
vento expert a30 W v.2
CONTENTS
Safety requirements………………………………………………………………………………………………………………………………………………… 2
Purpose………………………………………………………………………………………………………………………………………………………………………… 4
Delivery set…………………………………………………………………………………………………………………………………………………………………. 4
Designation key………………………………………………………………………………………………………………………………………………………… 4
Technical data……………………………………………………………………………………………………………………………………………………………. 5
Design and operating principle ………………………………………………………………………………………………………………………….
6 Mounting and set-up……………………………………………………………………………………………………………………………………………… 8
Connection to power mains ………………………………………………………………………………………………………………………………..
10 Technical maintenance…………………………………………………………………………………………………………………………………………..
16 Storage and transportation
regulations………………………………………………………………………………………………………….. 17 Manufacturer’s
warranty……………………………………………………………………………………………………………………………………….. 18 Certificate
of acceptance………………………………………………………………………………………………………………………………………. 19 Seller
information…………………………………………………………………………………………………………………………………………………….. 19
Installation certificate………………………………………………………………………………………………………………………………………………
19 Warranty card……………………………………………………………………………………………………………………………………………………………..
19
This user’s manual is a main operating document intended for technical,
maintenance, and operating staff. The manual contains information about
purpose, technical details, operating principle, design, and installation of
the VENTO Expert A30 W V.2 unit and all its modifications. Technical and
maintenance staff must have theoretical and practical training in the field of
ventilation systems and should be able to work in accordance with workplace
safety rules as well as construction norms and standards applicable in the
territory of the country.
SAFETY REQUIREMENTS
This unit is not intended for use by persons (including children) with reduced
physical, sensory or mental capabilities, or lack of experience and knowledge,
unless they have been given supervision or instruction concerning use of the
unit by a person responsible for their safety. Children should be supervised
to ensure that they do not play with the unit. This appliance can be used by
children aged from 8 years and above and persons with reduced physical,
sensory or mental capabilities or lack of experience and knowledge if they
have been given supervision or instruction concerning use of the appliance in
a safe way and understand the hazards involved. Cleaning and user maintenance
shall not be done by children without supervision. Children shall not play
with the appliance.
Connection to the mains must be made through a disconnecting device, which is
integrated into the fixed wiring system in accordance with the wiring rules
for design of electrical units, and has a contact separation in all poles that
allows for full disconnection under overvoltage category III conditions.
If the supply cord is damaged, it must be replaced by the manufacturer, its
service agent, or similarly qualified persons in order to avoid a safety
hazard.
Ensure that the unit is switched off from the supply mains before removing the
guard.
Precautions must be taken to avoid the back-flow of gases into the room from
the open flue of gas or other fuel-burning appliances.
2
vento expert a30 W v.2
www.blaubergventilatoren.de
All operations described in this manual must be performed by qualified personnel only, properly trained and qualified to install, make electrical connections and maintain ventilation units. Do not attempt to install the product, connect it to the mains, or perform maintenance yourself. This is unsafe and impossible without special knowledge. Disconnect the power supply prior to any operations with the unit. All user’s manual requirements as well as the provisions of all the applicable local and national construction, electrical, and technical norms and standards must be observed when installing and operating the unit. Disconnect the unit from the power supply prior to any connection, servicing, maintenance, and repair operations. Connection of the unit to power mains is allowed by a qualified electrician with a work permit for the electric units up to 1000 V after careful reading of the present user’s manual. Check the unit for any visible damage of the impeller, the casing, and the grille before starting installation. The casing internals must be free of any foreign objects that can damage the impeller blades. While mounting the unit, avoid compression of the casing! Deformation of the casing may result in motor jam and excessive noise. Misuse of the unit and any unauthorised modifications are not allowed. Do not expose the unit to adverse atmospheric agents (rain, sun, etc.). Transported air must not contain any dust or other solid impurities, sticky substances, or fibrous materials. Do not use the unit in a hazardous or explosive environment containing spirits, gasoline, insecticides, etc. Do not close or block the intake or extract vents in order to ensure the efficient air flow. Do not sit on the unit and do not put objects on it. The information in this user’s manual was correct at the time of the document’s preparation. The Company reserves the right to modify the technical characteristics, design, or configuration of its products at any time in order to incorporate the latest technological developments. Never touch the unit with wet or damp hands. Never touch the unit when barefoot. BEFORE INSTALLING ADDITIONAL EXTERNAL DEVICES, READ THE RELEVANT USER MANUALS.
THE PRODUCT MUST BE DISPOSED SEPARATELY AT THE END OF ITS SERVICE LIFE.
DO NOT DISPOSE THE UNIT AS UNSORTED DOMESTIC WASTE.
3
www.blaubergventilatoren.de
vento expert a30 W v.2
PURPOSE
The ventilator is designed to ensure continuous mechanical air exchange in
flats, cottages, hotels, cafés and other domestic and public premises. The
ventilator is equipped with a regenerator that enables supply of fresh
filtered air heated by means of extract air heat energy recovery. The
ventilator is designed for installation on external walls. The ventilator is
rated for continuous operation.
DELIVERY SET
Name Indoor unit of the ventilator Mounting frame Air duct Assembled cartridge
Outer ventilation hood Cardboard template Fastening set Foam wedges User’s
manual Mounting hood installation instruction Packing box
Quantity 1 pc. 1 pc. 1 pc. 1 pc. 1 pc. 2 pcs.
2 packs 1 set 1 pc. 1 pc. 1 pc.
DESIGNATION KEY
VENTO Expert A
30 L1.0 S10 W V.2
Wi-Fi version. V2: connection to PC is not required Control system type W: Wi-
Fi connection of ventilators Outer ventilation hood model S10: white plastic
hood AH-10 white 100 Air duct length _: 153(135) 500 mm L1.0: 153(135)
1000 mm Rated air capacity [m3/h] Air duct section shape A: round
Ventilator series
- Minimum wall thickness for the unit with a mounting frame
4
vento expert a30 W v.2
www.blaubergventilatoren.de
TECHNICAL DATA
The temperature in the room where the indoor unit of the ventilator is
installed must be in the range from +1 °C to +40 °C with relative humidity up
to 65 % (no condensation). The unit is rated as a class II electric appliance.
Hazardous parts access and water ingress protection rating is IP24. The unit
design is constantly being improved, so some models may be slightly different
from those ones described in this manual.
Speed Network parameters Power consumption [W] Current consumption [A] Max.
air flow [m3/h] (CFM) Transported air temperature [°C] Filters Sound pressure
level @ 1 m [dBA(Sones)] Sound pressure level @ 3 m [dBA(Sones)] Outdoor noise
level attenuation [dBA (Sones)] IP rating
Standard Frequency band [GHz] Transmission power [mW (dBm)] Power mains WLAN
safety
TECHNICAL DATA I 1.8
0.027 10 (6)
30 (1.1) 21 (0.4)
WI-FI TECHNICAL DATA
II 100-240 V ~ 50/60 Hz
3.0 0.037 20 (12) -15…+40 G3 (MERV 7); 37 (2.0) 28 (0.9) 42 (2.5) IP24
IEEE 802.11 b/g/n 2.4
100 (+20) DHCP
WPA. WPA2
III
4.40 0.051 30 (18)
40 (2.5) 31 (1.1)
Air duct length
The air duct length depends on the unit model, refer to the Designation Key. The supplied ventilation hood model depends on the ventilator model. The distance A and the overall dimensions of the outer ventilation hood are stated in the installation instruction. The overall dimensions of the front panel are stated below.
A
Outer ventilation hood
Front panel
OVERALL DIMENSIONS OF THE INDOOR UNIT [MM]
222
175
39
189 123
55 140
5
www.blaubergventilatoren.de
vento expert a30 W v.2
DESIGN AND OPERATING PRINCIPLE
The ventilator consists of an indoor unit with a decorative front panel, a
cartridge, an air duct and an outer ventilation hood. Cartridge is the basic
functioning part of the ventilator. The cartridge consists of a fan, a
regenerator and two filters that ensure rough air filtration and prevent
ingress of dust and foreign objects into the regenerator and the fan. The
indoor unit is equipped with a semi-automatic air damper that closes during
shutdown of the ventilator and prevents air backdraft.
VENTILATOR DESIGN
Outer ventilation hood Protects the unit from ingress of water and foreign
objects. Each ventilator model has a matching ventilation hood model.
Mounting frame Facilitates mounting of the ventilator in thin walls
with the thickness from 135 mm.
Indoor unit rear side The unit includes a circuit control board
and touch buttons.
Telescopic air duct Plastic air duct
Cartridge Assembly unit consisting of a fan, a regenerator and air filters.
Generates air flow, provides energy regeneration and air cleaning.
Indoor unit front panel Equipped with a semi-automatic air damper that closes
up the air duct at the ventilator power off.
VENTILATOR OPERATION MODES The ventilator has three operation modes:
Ventilation: the ventilator runs either in the air exhaust or air supply mode
at a set speed. Air supply (available from a mobile device only): all the
connected ventilation units in the network are in the air supply mode.
Regeneration: the ventilator operates in reversed mode with heat and moisture
regeneration, simultaneously cycling the direction of air flow. Cycle I. Warm
stale air is extracted from the room and flows through the ceramic
regenerator, which gradually absorbs heat and humidity. Cycle II. Fresh intake
air from outside flows through the ceramic regenerator, absorbs accumulated
moisture and is heated by the heat stored in the regenerator.
The ventilator is equipped with an air humidity sensor and a terminal for
connecting an external normally open contact (relay sensor). When either of
these devices is triggered, the ventilator switches to maximum speed (Boost
mode). When the humidity sensor or relay sensor returns to its original
position, the Boost mode deactivation delay timer is started.
In the relevant sections of the Blauberg Home mobile app, the following
ventilation parameters can be set: · activate or deactivate the humidity
sensor and relay sensor; · set the humidity sensor activation threshold; · set
the Boost mode turn-off delay time (default setting is 30 minutes); · set the
duration of the first speed timer («Night mode») (8 hours by default); · set
the duration of operation by timer of the third speed («Party mode») (by
default 4 hours).
6
vento expert a30 W v.2
www.blaubergventilatoren.de
If required, in the Schedule section of the Blauberg Home mobile app,
different ventilation speeds can be set at different intervals by day of the
week. For the weekly schedule to work correctly, the current date and time
must be set correctly in the «Date and time» section When simultaneously
activating several operation modes that exclude each other, the ventilator
selects the mode according to the following priority: 1. Night mode timer or
Party mode timer. 2. Standby. 3. Boost. 4. Weekly schedule. 5. Standard mode.
SEMI-AUTOMATIC AIR DAMPER OPERATING PRINCIPLE
The indoor unit of the ventilator is equipped with a front panel with a semi-
automatic air damper. During the ventilator operation the air damper opens and
lets the air flow freely through the ventilator. After switching off the
ventilator, close the damper by hand to prevent drafts.
The cover is closed
The cover is open
7
www.blaubergventilatoren.de
vento expert a30 W v.2
MOUNTING AND SET-UP
READ THE USER’S MANUAL BEFORE INSTALLING THE UNIT
DO NOT BLOCK THE AIR DUCT OF THE INSTALLED VENTILATOR WITH DUST ACCUMULATING
MATERIALS, SUCH AS CURTAINS, CLOTH SHUTTERS, ETC.
AS IT PREVENTS AIR CIRCULATION IN THE ROOM.
1. Prepare a round core hole in the outer wall. The hole size is shown in the
figure below.
A A-A
min 300
min 300
ø 120
min 300
A
2. Insert the air duct in the wall hole. For ease of installation use the
polystyrene wedges included in the delivery set. The air duct end must
protrude for the distance A that enables installation of the outer ventilation
hood. The distance A is stated in the installation instruction for the
ventilation hood.
Foam wedge
Fill the gaps between the wall and the hole with mounting
foam
Install the air duct with the minimum slope of 3 mm downwards to the outer
wall side.
To cut the air duct, either make preliminary calculations of the required duct
length or make sure to have access to the outer wall after fixation of the air
duct.
min 3 mm
A
3. Take the required mounting template and then fasten it to the indoor wall using the adhesive tape. The large opening in the template must be coaxial with the air duct. For aligning the template with respect to the horizon line it is recommended to use a builder’s level. Then mark the fastening holes for installation of the supplied dowels and drill the holes to a required depth. Route the power cable of the ventilator from the wall through the marked opening on the template.
Mounting template for the back part of the indoor unit
Mounting template for the mounting frame
50
220 188 Ø120
123
Ø10 Ø5
55 140 160
36 220 140
Ø120 Ø10
123 Ø5
55
124.3 160
8
vento expert a30 W v.2
www.blaubergventilatoren.de
4. Pull the lug on the bottom to disconnect the front panel of the indoor unit from the rear part. Attach the mounting frame on the wall if you use it. Fix the rear part of the indoor unit on the wall or on the mounting frame using the screws supplied with the mounting kit of the ventilator.
5. Remove the two screws that retain the terminal cover to enable access to
the connection terminals. Route the power cable as figured below and connect
the ventilator to power mains in compliance with the external wiring diagram,
see page 10. Fix the power cable and the control cables with a cable clamp.
After completion of the electrical connection re-install the transparent
terminal cover in site.
6. Insert the cartridge into the air duct and insert the plug cartridge to
the controller. Re-install the front panel of the indoor unit rear part.
9
www.blaubergventilatoren.de
vento expert a30 W v.2
CONNECTION TO POWER MAINS
POWER OFF THE POWER SUPPLY PRIOR TO ANY OPERATIONS WITH THE UNIT. THE UNIT
MUST BE CONNECTED TO POWER SUPPLY BY A QUALIFIED ELECTRICIAN.
THE RATED ELECTRICAL PARAMETERS OF THE UNIT ARE GIVEN ON THE MANUFACTURER’S
LABEL.
ANY TAMPERING WITH THE INTERNAL CONNECTIONS IS PROHIBITED AND WILL VOID THE WARRANTY.
The ventilator is rated for connection to single-phase AC 100240 V/50 (60)) Hz power mains. The routing of the Cable is shown in the “Mounting and set-up” section.
WIRING DIAGRAM
For electric installations use insulated, durable and heat-resistant electric
leads (cables, conductors) with the minimum cross section 0.5 up to 0.75 mm2
for the power cable and 0.25 mm2 for the control cables. The actual conductor
cross-section selection must be based on its type, maximum permissible
heating, insulation, length and installation method.
Use copper wires for all the electric connections!
Connect the unit to power mains via the terminal block in compliance with the
wiring diagram and terminal designation. Connect the ventilator to power mains
through an automatic circuit breaker with magnetic trip integrated into the
home wiring system. The trip current of the automatic circuit breaker or fuses
must exceed the maximum current consumption of the ventilator, refer to the
Technical data section.
It is recommended to select the rated current of the circuit breaker/ fuses
from the standard series, following the maximum current of the connected unit.
100-240V 50/60 Hz
QF S
L N
Terminal designation on the wiring diagram:
LT(1) L(2) N(3)
LT Boost mode activation circuit L line N neutral QF automatic circuit breaker S external relay sensor (switch for activating Boost mode)
10
vento expert a30 W v.2
www.blaubergventilatoren.de
VENTILATOR PRE-SETTING Prior to operating the ventilator set it up using the
DIP switch. It is located on the controller circuit board.
Remove the front panel of the indoor unit to access the DIP switch.
To reset to factory settings, hold the reset button under the front panel for
5 seconds until an acoustic signal sounds. It is also possible to reset using
a mobile app.
ON DIP
1234
DIP switch
Reset to factory settings button Cover opening sensor
USB socket
DIP SWITCH POSITION
Defining the role of the ventilator during group work OFF master unit (hereinafter referred to as «Control unit»).
11
ON slave unit (hereinafter referred to as «Slave unit»). Standby mode setup
OFF the ventilator is switched off in the Standby mode.
22
ON the ventilator operates at Speed I in the Standby mode. Ventilation mode
setup
OFF operation in the exhaust mode.
33
ON operation in the supply mode. OFF standard operation of the unit.
Programming mode
44
ON Programming mode. Caution! The programming mode is only switched by the service department.
11
www.blaubergventilatoren.de
vento expert a30 W v.2
VENTILATOR CONTROL WITH THE BUTTONS ON THE INDOOR UNIT The table below shows the buttons and indicators on the ventilator indoor unit with a description of their purpose and functionality.
ON/OFF
Speed The speed selection sequence is follows: I-II-III. All the units
integrated in a single network operate according to the speed settings of the
Master unit. I: permanent indicator glowing indicates operation of the unit at
Speed I. Indicator blinking indicates activation of the Night mode timer. I
and II: permanent glowing of these indicators indicates operation of the unit
at Speed II. I, II and III: permanent glowing of these indicators indicates
operation of the ventilation unit at Speed III. Simultaneous flashing of
indicators I, II and III indicates operation of the Party mode timer or Boost-
mode switch-off delay timer when the built-in humidity sensor or an external
relay sensor is triggered. Alternate blinking of the indicators I, II and III
indicates that the ventilator runs at the speed set with the mobile
application using the slider selector for manual speed setting or that the
Weekly Schedule mode is activated.
Regeneration mode The ventilator works in reverse mode. Heat recovery is
performed in this mode. To enable reverse phase operation of the ventilators,
change the position of the DIP switch No. 3.
Contamination indicator of filters. The indicator light will start flashing
after the preset number of days of continuous
ventilation operation (90 days by default) has elapsed.
In this case, clean or replace the filters (see section Technical
maintenance).
F In the relevant section of the app on the mobile device, you can restart the
filter timer and set the required length of time before the filter clogging
indicator comes on.
The filter timer can be restarted by holding down the until an acoustic signal sounds.
button on the room control unit of the ventilator for 5 seconds
Alarm indicator. In case of failure, the Alarm indicator on the indoor unit
glows or blinks.
Causes of constant illumination of the indicator light: · Alarm shutdown of
the ventilator. Stopped due to a faulty ventilator in the group.
Reasons of Alarm blinking: A · Battery charge is below the low level.
· No connection between the Master unit and the router. · Alarm shutdown of
the ventilator. This ventilator causes all ventilators in the group to stop.
In case of communication loss of the Master unit with the router for longer
than 20 seconds, the Master unit switches to Standby mode and the Slave units
will signal that there is no communication with the Master unit.
After resuming communication, the Slave units are automatically synchronised
with the Master unit.
Ventilation mode. The ventilator operates in the supply or extraction mode at
a set speed. The fan rotation direction depends on the position of the Speed
controller switch DIP No. 3.
No glowing of the indicators “Regeneration” and “Ventilation” indicates forced
operation of the ventilation unit in the air supply mode. This mode may be
activated only via the mobile device.
Permanent glowing of the indicator shows the leading unit (Master) in the
group. M Indicator blinking indicates the driven Slave unit) and no connection
to the Master unit.
No glowing of the lamp indicator means that this ventilation unit is a Slave
ventilation unit and it is connected to a Master unit. Synchronous blinking of
all the indicators on the casing of the ventilator indicates that the Setup
mode is enabled.
12
vento expert a30 W v.2
www.blaubergventilatoren.de
VENTILATOR CONTROL USING THE BLAUBERG HOME APP Download th Blauberg Home application and install it on the mobile device.
Blauberg Home App Store
Blauberg Home Play Market
The ventilator with factory settings works as a Wi-Fi access point with the name FAN: + 16 characters of the ID number shown on the casing under the front panel. Wi-Fi access point password: 11111111. Follow the instructions in the mobile app to connect. In the app, the ventilator can be set up to connect via a home Wi-Fi network and a cloud server.
13
www.blaubergventilatoren.de
vento expert a30 W v.2
VENTILATOR WIRELESS CONNECTION DIAGRAMS
Wiring diagram 1 Connection to eight devices (Slave ventilators or mobile
devices) to the control Master ventilator, which has its own access point.
Master with a Wi-Fi access point
Wiring diagram 2
The Master units, the Slave units and the mobile devices are connected to a
wireless access point of the Wi-Fi router.
In this case, the Master control unit can operate with the number N of Slave
units, limited by the technical characteristics of the router.
Slave No. 1
Slave No. 2
Slave No. N
Mobile device
Router with its wireless access point
Master
If the Wi-Fi router capacity is not enough to connect a required number of the
units, you may use an extra wireless access point to connect the other the
unit. Several Master units can optionally be connected to the network for
arranging a zone control.
Slave No. 1
Slave No. N
Mobile device
Mobile device
Router with its wireless access point
Master
Slave No. 1
Slave No. N
Mobile device
Mobile device
Extra wireless access point
Slave No. N+1
Slave No. N+N
Mobile device
Mobile device
14
vento expert a30 W v.2
www.blaubergventilatoren.de
VENTILATOR CONTROL VIA THE SMART HOME SYSTEM Connect the ventilators to the Smart Home system in accordance with the Smart Home system user manual.
AFTER CHANGING THE WI-FI PARAMETERS OF THE MASTER VENTILATOR REPEAT THE CONNECTION STEPS!
SPECIAL SETUP MODE
In the event of losing the Wi-Fi password or the master ventilator password or in other cases use the recovery Setup mode to restore
access to the ventilator functions. To enter the special Setup mode, press and hold the Ventilation casing for 5 seconds until the beep and blinking of all the LED lights.
button on the ventilator
The ventilator will continue in this mode for 3 minutes and then automatically revert to the previous settings. To exit the Setup mode
immediately, press and hold the Ventilation shutdown of all the LED lights.
button on the ventilator casing once again for 5 seconds until the beep and
In this mode the following settings are available: · Wi-Fi network name: Setup mode. · Wi-Fi password: 11111111. · The unit password is ignored.
WHILE COMPLETING THE CONNECTION MAKE SURE THAT THE SLAVE UNITS ARE WITHIN COVERAGE OF THE BUILT-IN WI-FI IN THE MASTER UNIT
CONNECTING MASTER AND SLAVE VENTILATORS To create a group of ventilators
linked together as Master and Slave, proceed as follows: · Set the DIP
switches on each ventilator to the position corresponding to its role in the
group (see section “DIP switch position”). · Then configure the Wi-Fi settings
of the Master ventilator by following the instructions in the Blauberg Home
mobile app. · Switch the ventilator to the special mode as indicated above and
all the LEDs on the ventilator casing will start flashing. Repeat the
steps with all the slave ventilators and wait for the beep when all the LEDs
stop blinking on each Slave unit. Set the Master unit to the normal operation
mode. Press and hold the Ventilation button. Wait for the beep when all the
LEDs stop blinking.
Note: if the home router works in conjunction with several Wi-Fi access points
requiring connection of ventilators to different access points: · Connect the
Master unit to the first Wi-Fi access point. · Complete the connection with
the first group of Slave units. · Connect the Master unit to the second Wi-Fi
access point. · Complete the connection with the second group of Slave units.
BATTERY REPLACEMENT The Alarm indicator on the unit casing will blink when the
battery is approaching the end of its life. The mobile app will also display
the warning and show the following message on pressing the indicator icon.
PLow battery power may cause disruptions in the weekly schedule operation.
Power off the unit before replacing the battery Ventilator. After replacing
the battery reset the time and date.
The battery is located on the control board. To replace the battery, power off
the ventilator, remove the front panel and the cover protecting the control
circuit board. Then remove the battery and install a new one. The battery type
is: CR1220.
15
www.blaubergventilatoren.de
vento expert a30 W v.2
TECHNICAL MAINTENANCE
DISCONNECT THE UNIT FROM POWER SUPPLY BEFORE ANY MAINTENANCE OPERATIONS!
MAKE SURE THE UNIT IS DISCONNECTED FROM POWER MAINS BEFORE REMOVING THE
PROTECTION.
Maintenance of the ventilator means regular cleaning of the ventilator
surfaces of dust or replacement of the filters. Clean the filters as often as
required, but at least 3 times a year. After 90 days of continuous operation
(default duration), the filter change indicator (Filter) lights up on the
ventilator. To access the main serviced units, disconnect the ventilator from
power mains using a circuit breaker or a power switch and follow the steps
below. 1. Press the lower latch of the indoor control unit to take off its
front panel. Please make sure the thermal actuator rod is in lower position
during reinstallation of the front panel. If the rod is up, please wait for
about 2 minutes until it goes down. 2. Disconnect the connector from the
circuit board. Do not remove the connector by pulling the wires. Use a flat
screwdriver to uplift it, if required. 3. Remove the cartridge from the
ventilation duct. 4. Remove the filters from the cartridge for cleaning. Wash
the filters and let those dry out completely. Install the dry filters in the
air duct. Vacuum cleaning is allowed. The filter rated service life is 3
years. 5. Perform all the above operations in the reverse order after
cleaning.
Remove the filters from the cartridge.
Do not pull the wires!
Use a flat screwdriver to disconnect the connector.
Restart the filter timer countdown in the Blauberg Home app on a mobile device or by holding down the unit for 5 seconds before the beep.
button on the room
Some dust may accumulate on the heat exchanger block even in case of regular
maintenance of the filters. · To maintain high heat recovery efficiency, the
regenerator should be cleaned regularly with a vacuum cleaner at least once a
year. · Vacuum clean the regenerator not less than once a year.
16
vento expert a30 W v.2
www.blaubergventilatoren.de
FAILURES AND TROUBLESHOOTING
Failure
Possible reasons
Troubleshooting
No power supply.
The fan does not get started
during turning on.
The motor is jammed, the impeller blades are
contaminated.
Circuit breaker tripping during turning of the
ventilator on.
Overcurrent as a result of a short circuit in the electric circuit.
Low set fan speed.
Make sure the power supply line is connected correct, otherwise eliminate the
connection error. Turn the ventilator off. Troubleshoot the motor jam and the
impeller clogging. Clean the blades. Turn the ventilator on.
Turn the ventilator off. Contact the Seller for further information.
Set the higher speed.
Low air flow.
The filters, the fan or the regenerator are contaminated.
Clean or replace the filter. Clean the fan and the regenerator.
Noise, vibration.
The impeller is contaminated.
Clean the impeller.
Loose screw connection in the ventilator casing or Tighten the screws of the ventilator or the outer
in the outer ventilation hood.
ventilation hood.
STORAGE AND TRANSPORTATION REGULATIONS
· Store the unit in the manufacturer’s original packaging box in a dry closed
ventilated premise with temperature range from +5 °C to + 40 °C and relative
humidity up to 70 %.
· Storage environment must not contain aggressive vapors and chemical mixtures
provoking corrosion, insulation, and sealing deformation.
· Use suitable hoist machinery for handling and storage operations to prevent
possible damage to the unit. · Follow the handling requirements applicable for
the particular type of cargo. · The unit can be carried in the original
packaging by any mode of transport provided proper protection against
precipitation and
mechanical damage. The unit must be transported only in the working position.
· Avoid sharp blows, scratches, or rough handling during loading and
unloading. · Prior to the initial power-up after transportation at low
temperatures, allow the unit to warm up at operating temperature for at least
3-4 hours.
17
www.blaubergventilatoren.de
vento expert a30 W v.2
MANUFACTURER’S WARRANTY
The product is in compliance with EU norms and standards on low voltage
guidelines and electromagnetic compatibility. We hereby declare that the
product complies with the provisions of Electromagnetic Compatibility (EMC)
Directive 2014/30/EU of the European Parliament and of the Council, Low
Voltage Directive (LVD) 2014/35/EU of the European Parliament and of the
Council and CE-marking Council Directive 93/68/EEC. This certificate is issued
following test carried out on samples of the product referred to above. The
manufacturer hereby warrants normal operation of the unit for 24 months after
the retail sale date provided the user’s observance of the transportation,
storage, installation, and operation regulations. Should any malfunctions
occur in the course of the unit operation through the Manufacturer’s fault
during the guaranteed period of operation, the user is entitled to get all the
faults eliminated by the manufacturer by means of warranty repair at the
factory free of charge. The warranty repair includes work specific to
elimination of faults in the unit operation to ensure its intended use by the
user within the guaranteed period of operation. The faults are eliminated by
means of replacement or repair of the unit components or a specific part of
such unit component.
The warranty repair does not include: · routine technical maintenance · unit
installation/dismantling · unit setup To benefit from warranty repair, the
user must provide the unit, the user’s manual with the purchase date stamp,
and the payment paperwork certifying the purchase. The unit model must comply
with the one stated in the user’s manual. Contact the Seller for warranty
service.
The manufacturer’s warranty does not apply to the following cases: · User’s
failure to submit the unit with the entire delivery package as stated in the
user’s manual including submission with missing
component parts previously dismounted by the user. · Mismatch of the unit
model and the brand name with the information stated on the unit packaging and
in the user’s manual. · User’s failure to ensure timely technical maintenance
of the unit. · External damage to the unit casing (excluding external
modifications as required for installation) and internal components caused
by the user. · Redesign or engineering changes to the unit. · Replacement and
use of any assemblies, parts and components not approved by the manufacturer.
· Unit misuse. · Violation of the unit installation regulations by the user. ·
Violation of the unit control regulations by the user. · Unit connection to
power mains with a voltage different from the one stated in the user’s manual.
· Unit breakdown due to voltage surges in power mains. · Discretionary repair
of the unit by the user. · Unit repair by any persons without the
manufacturer’s authorization. · Expiration of the unit warranty period. ·
Violation of the unit transportation regulations by the user. · Violation of
the unit storage regulations by the user. · Wrongful actions against the unit
committed by third parties. · Unit breakdown due to circumstances of
insuperable force (fire, flood, earthquake, war, hostilities of any kind,
blockades). · Missing seals if provided by the user’s manual. · Failure to
submit the user’s manual with the unit purchase date stamp. · Missing payment
paperwork certifying the unit purchase.
FOLLOWING THE REGULATIONS STIPULATED HEREIN WILL ENSURE A LONG AND TROUBLE-
FREE OPERATION OF THE UNIT
USER’S WARRANTY CLAIMS SHALL BE SUBJECT TO REVIEW ONLY UPON PRESENTATION OF
THE UNIT, THE PAYMENT DOCUMENT AND THE USER’S MANUAL WITH THE PURCHASE DATE
STAMP
18
vento expert a30 W v.2
www.blaubergventilatoren.de
CERTIFICATE OF ACCEPTANCE
Unit Type Model
Serial Number
Manufacture Date Quality Inspector’s Stamp
Single-room reversible energy recovery ventilator
SELLER INFORMATION
Seller Address Phone Number E-mail Purchase Date This is to certify acceptance
of the complete unit delivery with the user’s manual. The warranty terms are
acknowledged and accepted.
Customer’s Signature
Seller’s Stamp
INSTALLATION CERTIFICATE
The _____ unit is installed pursuant to the
requirements stated in the present user’s manual.
Company name
Address
Phone Number
Installation Technician’s Full Name
Installation Date:
Signature:
The unit has been installed in accordance with the provisions of all the applicable local and national construction, electrical and technical codes and standards. The unit operates normally as intended by the manufacturer.
Signature:
WARRANTY CARD
Unit Type Model
Serial Number
Manufacture Date Purchase Date Warranty Period Seller
Single-room reversible energy recovery ventilator
Installation Stamp Seller’s Stamp
19
www.blaubergventilatoren.de B133-5EN-04
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>