TOSHIBA MMD-UP0181VHG-UL Jogeshwari West Owner’s Manual
- September 22, 2024
- Toshiba
Table of Contents
- MMD-UP0181VHG-UL Jogeshwari West
- Product Specifications
- Product Usage Instructions
- Installation
- Power Connection
- Maintenance
- Optional Accessories
- Q: Can I use a different refrigerant other than R410A?
- Q: What is the maximum External Static Pressure supported by
- Q: How often should I clean or replace the filters?
MMD-UP0181VHG-UL Jogeshwari West
“`html
Product Specifications
INDOOR UNIT MODEL | MMD-UP0181VHG-UL |
---|---|
Cooling Rated Capacity (Btu/h) | 18,000 |
Heating Rated Capacity (Btu/h) | 20,000 |
Airflow (H / M / L) (CFM) | 670 / 640 / 600 |
Sound Data (H, M, L) (dBA) | 41.4 / 38.4 / 37.5 |
External Static Pressure (ESP) in. WG | 0.3 (Factory Default), 0.5 (Max.) |
Power Supply | V/Ph/Hz 208-230/1/60 |
MCA* | 2.8 A |
MOCP* | 15 A |
Full Load Amps (FLA)* | 2.2 A |
Pipe Connection Size – Liquid | 1/4 inches (brazed) |
Pipe Connection Size – Suction | 1/2 inches (brazed) |
Refrigerant | R410A |
Dimensions (H x W x D inches) | 46-7/8 x 17-3/4 x 22-1/4 |
Net Weight (lbs) | 164 |
Product Usage Instructions
Installation
1. Ensure the indoor unit is placed in a suitable location with
proper ventilation.
2. Connect the liquid and suction pipes according to the
specified sizes.
Power Connection
1. Connect the power supply to the unit following the V/Ph/Hz
specifications.
Maintenance
1. Regularly clean or replace filters as needed to maintain
optimal performance.
Optional Accessories
You may enhance the unit with optional accessories like wired
remote controls, central controllers, receivers, sensors, filter
boxes, plenums, and electric heaters.
Frequently Asked Questions (FAQ)
Q: Can I use a different refrigerant other than R410A?
A: No, the unit is designed for use with R410A refrigerant
only.
Q: What is the maximum External Static Pressure supported by
the unit?
A: The unit supports up to 0.5 inches WG of External Static
Pressure at maximum.
Q: How often should I clean or replace the filters?
A: Filters should be cleaned or replaced regularly, ideally
every 1-3 months depending on usage and environment.
“`
SMMSu/SHRMu VRF Indoor Unit MMD-UP0181VHG-UL / Vertical Air Handler
Submittal Data
Job Name ____ Location
___ Tag ____
STANDARD FEATURES · Dual Drainage Spouts · Three Fan Speeds – High, Medium and
Low · Unit Can Be Installed Standing Vertical or Laid Horizontally ·
Electronically Commutated Fan Motor (ECM) · Built In Pulse Modulating Valve
For Installation Ease · Removable Front Panel Provides Easy Access · Filter
MERV 3
INDOOR UNIT MODEL
MMD-UP0181VHG-UL
PERFORMANCE
Cooling Rated Capacity
Btu/h
18,000
Heating Rated Capacity
Btu/h
20,000
Airflow (H / M / L)
CFM
670/640/600
Sound Data (H, M, L)
dBA
41.4/38.4/37.5
External Static Pressure (ESP) in. WG
0.3 (Factory Default) 0.5 (Max.)
ELECTRICAL
Power Supply
V/Ph/Hz 208-230/1/60
MCA*
A
2.8
MOCP*
A
15
Full Load Amps (FLA)*
A
2.2
PHYSICAL DATA Pipe Connection Size – Liquid Pipe Connection Size Suction
Refrigerant
DIMENSIONS (inches)
NET WEIGHT
inches inches
H (in) W (in) D (in)
lbs
1/4 (brazed)
1/2 (brazed)
R410A 46-7/8 17-3/4 22-1/4
164
ACCESSORIES (Optional) Simple Wired Remote Control – RBC-ASCU11-UL Wired Remote Controller (Local Controller) – RBC-AWSU52-UL Touch Screen Central Controller – BMS-CT2560U-UL Stand Alone Receiver with Wireless Remote TCB- AX32UL Remote Sensor TCB-TC41U-UL Wired Remote Controller – RBC-AMT32UL Filter Box / 1″ MERV3 (TCB-FB2F241VDGUL) Plenum TCB-PL2S241VDGUL Electrical Heater (240V/208V):
1.0kW/0.8kW 3.0kW/2.3kW 5.0kW/3.8kW 6.0kW/4.5kW
TCB-HT101VDGUL TCB-HT301VDGUL TCB-HT501VDGUL TCB-HT601VDGUL
NOTES: * Does not include electric heater. Average / weighted sound values.
© 2024 Carrier Corporation. All rights reserved. A Carrier Company
Edition Date: 5/24 Printed in U.S.A.
Form No: MMD-UP0181VHG-UL_02 Replaces: MMD-UP0181VHG-UL_01
Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.
1
Dimensional Drawing Indoor Unit Vertical Air Handler MMD-UP0181VHG-UL
1-1/4
15-1/4 CENTER OF UNIT
4-5/8
16-3/8 19-1/2
10-1/4 1-5/8 COM ENTRY (OPT)
17-3/4
3/4
EH DISCONN COVER (OPT)
46-7/8
1.0
1-5/8 POWER ENTRY (OPT)
22-1/4
7-5/8 4
7/8 COM ENTRY (BOTH SIDES)
1-3/8 POWER ENTRY FOR EH
(BOTH SIDES)
7/8 COM ENTRY (BOTH SIDES-OPT)
5-3/8 4-3/8 2-5/8 1-1/2
Airflow
1/4 LIQ CNX.
3/8 SUCT CNX.
14-1/8
12-5/8
9-1/4
3 1-7/8
0
1-1/4
19
0 Cond and Aux Drain (3/4″ FPT)
NOTE: Dimensions shown in inches.
© 2024 Carrier Corporation. All rights reserved. A Carrier Company
Edition Date: 5/24 Printed in U.S.A.
Form No: MMD-UP0181VHG-UL_02 Replaces: MMD-UP0181VHG-UL_01
Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.