CRESTRON DIN-4DIMFLV4 4 Channel 0-10V Dimmer DIN Rail Mount Instruction Manual

September 17, 2024
CRESTRON

DIN-4DIMFLV4 4 Channel 0-10V Dimmer DIN Rail Mount

“`html

Specifications:

  • Load Ratings Dimmer Channels Maximum Per Channel: 5 amps @ 120
    to 240 Vac, 50/60 Hz; 600 W @ 120 Vac; 1150 W @ 230 Vac; 1200 W @
    240 Vac, 0.5 HP

  • Module Total Dim Load Types Switch Load Types: 20 amps @ 120 to
    240 Vac, 50/60 Hz; 2400 W @ 120 Vac; 4600 W @ 230 Vac; 4800 W @ 240
    Vac

  • 0-10 V fluorescent ballast or LED driver (4-wire); Maximum of
    30 dimmable ballasts/drivers

  • Incandescent, magnetic low-voltage, electronic low-voltage,
    neon/cold cathode, fluorescent, motors

  • 4.2 W (0.18 amps) @ 24 Vdc

Wiring and Installation:

Important Instructions:

WARNING: To avoid fire, shock, or death, turn
off the power at the circuit breaker or fuse and test that the
power is off before wiring.

NOTES:

  • Observe the following points:

    • Install and use the DIN-4DIMFLV4 in accordance with appropriate
      electrical codes and regulations.

    • A licensed electrician must install the DIN-4DIMFLV4.

  • Before using the DIN-4DIMFLV4, ensure the device is using the
    latest firmware. Check for the latest firmware for the DIN-4DIMFLV4
    at www.crestron.com/firmware.

  • Firmware is loaded onto the device using the Crestron ToolboxTM
    software or Crestron Home application.

Product Usage Instructions:

Preparing and Connecting Wires:

  1. Turn off the power at the circuit breaker or fuse and verify it
    is off.

  2. Follow appropriate electrical codes and regulations for
    installation.

  3. Hire a licensed electrician to install the DIN-4DIMFLV4.

Installing the DIN-4DIMFLV4:

  1. Mount the DIN-4DIMFLV4 on a 35 mm DIN EN 60715 rail.
  2. Ensure a 45 mm front panel cutout for proper fit.
  3. The device occupies 9 DIN module spaces (162 mm).

Connections:

  1. Connect appropriate load types to the dimmer channels as per
    specifications.

  2. Follow wiring diagrams provided in the user manual for accurate
    connections.

Operation:

  1. Set Net ID for proper communication if using multiple
    devices.

  2. Control loads manually using the designated controls.

  3. Establish override mode levels for customized settings.

  4. Toggle override mode as needed for temporary adjustments.

  5. To reboot the DIN-4DIMFLV4, follow the specified procedure in
    the manual.

Troubleshooting:

Refer to the troubleshooting section in the manual for guidance
on resolving common issues with the DIN-4DIMFLV4.

FAQ:

Q: How can I update the firmware on the DIN-4DIMFLV4?

A: You can update the firmware by downloading
the latest version from www.crestron.com/firmware
and using Crestron ToolboxTM software or Crestron Home application
to load it onto the device.

“`

View this document in HTML crestron.com/docs/9507
Product Manual
DIN-4DIMFLV4
4 Channel 0-10V Dimmer, 4 Feeds, DIN Rail Mount
Crestron Electronics, Inc.

The original language version of this document is U.S. English. All other languages are a translation of the original document.
Crestron product development software is licensed to Crestron dealers and Crestron Service Providers (CSPs) under a limited nonexclusive, nontransferable Software Development Tools License Agreement. Crestron product operating system software is licensed to Crestron dealers, CSPs, and end-users under a separate End-User License Agreement. Both of these Agreements can be found on the Crestron website at www.crestron.com/legal/software_license_agreement.
The product warranty can be found at www.crestron.com/warranty.
The specific patents that cover Crestron products are listed online at www.crestron.com/legal/patents.
Certain Crestron products contain open source software. For specific information, please visit www.crestron.com/opensource.
Crestron, the Crestron logo, Cresnet, Crestron Home, and Crestron Toolbox are either trademarks or registered trademarks of Crestron Electronics, Inc. in the United States and/or other countries. Other trademarks, registered trademarks, and trade names may be used in this document to refer to either the entities claiming the marks and names or their products. Crestron disclaims any proprietary interest in the marks and names of others. Crestron is not responsible for errors in typography or photography.
©2024 Crestron Electronics, Inc.

Contents

Overview

1

Specifications

2

Wiring and Installation

3

Important Instructions

3

Preparing and Connecting Wires

3

Installing the DIN-4DIMFLV4

4

Connections

5

Important Instructions

5

Operation

8

Net ID

8

Manual Load Control

8

Establish Override Mode Levels

8

Toggle Override Mode

9

Reboot the DIN-4DIMFLV4

9

Troubleshooting

10

Resources

11

Crestron Support and Training

11

Programmer and Developer Resources

11

Product Certificates

11

Product Manual — Doc. 9507A

Contents · iii

Overview
The Crestron® DIN-4DIMFLV4 is a 4-channel lighting control module designed to dim 0-10 V drivers and ballasts. A single model supports both 120 V and 220 V to 240 V applications. The DIN-4DIMFLV4 may also be used for switching of non- dimmable lighting loads up to 5 amps (may not be compatible with some high inrush current loads) and 1/2 HP motors.

1 · DIN-4DIMFLV4

Product Manual — Doc. 9507A

Specifications

Load Ratings Dimmer Channels Maximum Per Channel
Module Total
Dim Load Types Switch Load Types1

4
5 amps @ 120 to 240 Vac, 50/60 Hz; 600 W @ 120 Vac; 1150 W @ 230 Vac; 1200 W @ 240 Vac, 0.5 HP 16 amps Resistive
20 amps @ 120 to 240 Vac, 50/60 Hz; 2400 W @ 120 Vac; 4600 W @ 230 Vac; 4800 W @ 240 Vac
0-10 V fluorescent ballast or LED driver (4-wire); Maximum of 30 dimmable ballasts/drivers
Incandescent, magnetic low-voltage, electronic low-voltage, neon/cold cathode, fluorescent, motors

Power Requirements Cresnet® Power Usage

4.2 W (0.18 amps) @ 24 Vdc

Enclosure
Light gray polycarbonate housing with polycarbonate label overlay, UL94 V-0 rated, 35 mm DIN EN 60715 rail mount, DIN 43880 form factor for enclosures with 45 mm front panel cutout, occupies 9 DIN module spaces (162 mm)

Environmental Temperature Humidity Heat Dissipation

32°F to 104°F (0°C to 40°C) 10% to 90% RH (noncondensing) 17 BTU/hr

Dimensions Height Width Depth

43.71 in. (95 mm) 6.26 in. (159 mm) 2.35 in. (60 mm)

Weight 9.2 oz (260 g)
Note:
1. May not be compatible with some high inrush current loads.

Product Manual — Doc. 9507A

DIN-4DIMFLV4 · 2

Wiring and Installation
Important Instructions
WARNING: To avoid fire, shock, or death, turn off the power at the circuit breaker or fuse and test that the power is off before wiring.
CAUTIONS: This equipment is for indoor use only. Mount in a well-ventilated area. The ambient temperature must be 0ºC to 40ºC (32ºF to 104ºF). The relative humidity must be 10% to 90% (noncondensing).
NOTES: l Observe the following points: o Install and use the DIN-4DIMFLV4 in accordance with appropriate electrical codes and regulations. o A licensed electrician must install the DIN-4DIMFLV4. l Before using the DIN-4DIMFLV4, ensure the device is using the latest firmware. Check for the latest firmware for the DIN-4DIMFLV4 at www.crestron.com/firmware. Firmware is loaded onto the device using the Crestron ToolboxTM software or Crestron Home application.
Preparing and Connecting Wires
When making the connections, strip the ends of the wires approximately 8 mm (1/3 in). Use care to avoid nicking the conductors. Tighten the connector to 0.5 – 0.6 Nm (5 in-lbs). The wire gauge should be 12 to 28 AWG.

3 · DIN-4DIMFLV4

Product Manual — Doc. 9507A

Installing the DIN-4DIMFLV4
The DIN-4DIMFLV4 should be used in a well-ventilated area. The venting holes should not be obstructed under any circumstances. The DIN-4DIMFLV4 is designed for installation on a DIN rail. Refer to the diagram when installing.

To install the DIN-4DIMFLV4:
1. Use a flat object (e.g., a flat-head screwdriver) to pull the DIN rail release downward. 2. Place the top of the DIN-4DIMFLV4’s rail mount over the top of the DIN rail. 3. Tilt the bottom of the DIN-4DIMFLV4 toward the DIN rail until it snaps into place.
To remove the DIN-4DIMFLV4 from the DIN rail, use a small, flat object (e.g., a flat-head screwdriver) to pull the DIN rail release, and tilt the bottom of the DIN-4DIMFLV4 away from the DIN rail.

Product Manual — Doc. 9507A

DIN-4DIMFLV4 · 4

Connections
Important Instructions
WARNING: Prior to connecting the device, turn off the power at the circuit breaker. Failure to do so may result in serious personal injury or damage to the device. Restore power after all connections have been made.
CAUTIONS: Connecting this device to the wrong type of load or short-circuiting the load can cause severe product damage. Each load should be tested to identify a short-circuit condition prior to wiring the load to the module.
NOTES: l Install in accordance with all local and national electric codes. l High-voltage connections accept 0.2 – 2.5 mm2 (28 – 12 AWG) wire. Wire should be stripped to 8 mm (1/3 in). Tighten terminal blocks to 0.5 – 0.6 N-m (5 in- lbs). l Use copper wire only. For high-voltage connections, use wires rated for at least 75°C (167°F). l Each channel of the DIN-4DIMFLV4 may be fed from a separate circuit breaker or a single, shared breaker.

5 · DIN-4DIMFLV4

Product Manual — Doc. 9507A

Product Manual — Doc. 9507A

DIN-4DIMFLV4 · 6

NOTE: Older wiring may be gray for DIM -.

7 · DIN-4DIMFLV4

Product Manual — Doc. 9507A

Operation
The DIN-4DIMFLV4 can be controlled via its front panel as well as from a control system. The following local controls are available.
Net ID
Use the NET ID buttons to change the Net ID of the DIN-4DIMFLV4.
Manual Load Control
The lighting level of each of the outputs can be manually controlled from the front panel. To toggle the light between off and 100% (on), tap an output button. The corresponding LED lights, and the output level is shown on the NET ID display (“oF” for off, “On” for on) for two seconds after the button is released. To ramp the lighting level up or down (until it reaches a limit), press and hold the output button. To change the ramp direction, release the output button, and then press and hold it again. The corresponding LED lights, and the output level is shown on the NET ID display as a percentage (01 to 99) for two seconds after the button is released.
NOTE: The control system program may change the settings if Override mode is not enabled.
Establish Override Mode Levels
Override mode disables the control system program and sets all of the lighting levels to the saved override values. The lighting level of each output can be saved as an override setting, which can be automatically recalled when the Override mode is enabled.
NOTE: The control system program has a setting that can prevent locally saving the override lighting level settings. If this setting is enabled, the display shows “Er” when saving the override lighting level settings.
To save the current lighting level as an override setting, set all of the load levels, and then press and hold the OVR button for three seconds. The OVR LED blinks to indicate that the new override setting has been saved.

Product Manual — Doc. 9507A

DIN-4DIMFLV4 · 8

Toggle Override Mode
To enable Override mode, press and release the OVR button. The OVR LED blinks slowly. Override mode can also be toggled via a remote contact closure attached to the OVERRIDE port.
NOTE: If Override mode is enabled from an external device (i.e. a contact closure connected to the OVERRIDE port), the OVR LED blinks quickly when the local OVR button is pressed. Pressing the local OVR button has no effect when Override mode is toggled via the remote connection.
To disable Override mode, press the OVR button again. The OVR LED extinguishes, and the lights return to the levels set by the control system program.
NOTE: If the override lighting levels have not been saved, the factory default override level is 100%.
Reboot the DIN-4DIMFLV4
To reboot the DIN-4DIMFLV4, press the RESET button. The outputs are set to the lighting levels currently specied by the control system program. If the control system does not provide any values, the outputs are set to the previously set lighting levels.

9 · DIN-4DIMFLV4

Product Manual — Doc. 9507A

Troubleshooting

The following table provides corrective actions for possible trouble situations. If further assistance is required, please contact a Crestron customer service representative.

TROUBLE
The device does not function.
The lamps stay at minimum intensity. The lamps stay at maximum intensity.

POSSIBLE CAUSE(S) The device is not receiving power from a Crestron power source. The device is not receiving sufficient power. There is electrostatic discharge due to improper grounding. The + or – wires are reversed or shorted.
The + or – wires are not connected.

CORRECTIVE ACTION Use a Crestron power source. Verify that the connections are correct. Use the Cresnet Power Calculator to help calculate how much power is needed for the system. Check that all the ground connections have been made properly. Verify that the polarity of the + and – wires at the ballasts/drivers and DIN-4DIMFLV4 are correct.
Verify that the polarity of the + and – wires at the ballasts/drivers and DIN- 4DIMFLV4 are correct.

Product Manual — Doc. 9507A

DIN-4DIMFLV4 · 10

Resources
The following resources are provided for the DIN-4DIMFLV4.
NOTE: You may need to provide your Crestron.com web account credentials when prompted to access some of the following resources.
Crestron Support and Training
l Crestron True Blue Support l Crestron Resource Library l Crestron Online Help (OLH) l Crestron Training Institute (CTI) Portal
Programmer and Developer Resources
l help.crestron.com: Provides help files for Crestron programming tools such as SIMPL, SIMPL#, and Crestron ToolboxTM software
l developer.crestron.com: Provides developer documentation for Crestron APIs, SDKs, and other development tools
Product Certificates
To search for product certificates, refer to the Product Certificates section of the Crestron Resource Library.

11 · DIN-4DIMFLV4

Product Manual — Doc. 9507A

Crestron Electronics, Inc. 15 Volvo Drive, Rockleigh, NJ 07647 Tel: 888.CRESTRON Fax: 201.767.7656 www.crestron.com

Product Manual — Doc. 9507A 09/11/24
Specifications subject to change without notice.

References

Read User Manual Online (PDF format)

Read User Manual Online (PDF format)  >>

Download This Manual (PDF format)

Download this manual  >>

CRESTRON User Manuals

Related Manuals