HEATIT 5430581 WiFi6 Thermostat Black Matt Instruction Manual
- September 16, 2024
- HEATIT
Table of Contents
- HEATIT 5430581 WiFi6 Thermostat Black Matt
- INTRODUCTION
- QUICK START
- INSTALLATION DISCLAIMER
- CONNECTIONS
- INSTALLATION
- FACTORY RESET
- STARTUP
- PRINCIPLES OF REGULATION
- WATERBASED HEATING/ELECTRICAL HEATING
- LOCAL SETTINGS MENU
- STANDBY AND MAIN SCREEN
- SELECTING SENSOR VALUE
- ANTI-FREEZE FUNCTION
- SAFETY FEATURES
- THERMOSTAT DIMENSIONS
- THERMOSTAT CONTROLS
- CHART – DISPLAY MENU STRUCTURE
- PRODUCT INFO Heatit Pro Thermostat
- TECHNICAL DATA
- MAINTENANCE
- Read User Manual Online (PDF format)
- Download This Manual (PDF format)
HEATIT 5430581 WiFi6 Thermostat Black Matt
INTRODUCTION
Heatit Pro is an electronic thermostat designed for electrical heating, waterbased heating and cooling systems. The thermostat has a user-friendly interface that can be controlled from the buttons on the front of the thermostat. Heatit Pro has 2 modes; Heat and Cool. The thermostat fits in standard European junction boxes and may be used with most System 55 frames. It has a sturdy metal frame for secure fastening on the junction box. The thermostat has one built-in room temperature sensor. Two additional external temperature sensors may also be connected. Heatit Pro has the option of a weekly program and open window detection. The product has implemented ZeroX technology. This technology makes sure the relay switches at 0V when turning on and off. With this technology the thermostat will have a much longer lifetime. Heatit Pro has active power metering, which allows the user to see the real time power consumption. The thermostat can withstand a load of max 16A/3600W at 230VAC. We recommend a contactor for loads above 13A.
QUICK START
- Switch off the mains voltage (disable the fuse).
- Open the junction box.
- Connect the wires according to the description in the Chapter ”Connections”. Optional: Connect external wired sensors.
- After verifying the connections, switch on the mains voltage.
INSTALLATION DISCLAIMER
Installation must be done by a qualified electrician under national building codes. Before installation, disconnect the power to the device from the mains. During installation of the device, power to the device must be disconnected AT ALL TIMES!
CONNECTIONS
Max tightening torque for terminal screws: 2Nm. If the cable used has multiple strands, using an end sleeve is advised. The product allows for wiring of cables with a cross-section of up to 1×2.5mm2. The screw terminals are located at the back of the device and are accessible at all times.
- Floor sensor NTC type 6.8, 10, 12, 15, 22, 33, 47 or 100kΩ Default 10kΩ.
- External sensor NTC type 6.8, 10, 12, 15, 22, 33, 47 or 100kΩ. Default 10kΩ.
- Pilot Cooling/heating switchover in waterbased mode.
- N Power connection (Neutral) 230VAC.
- Heating N Heating cable N connection.
- L Power connection (Live) 230VAC.
- Heating L Heating cable L connection.
INSTALLATION
Position the thermostat and mount it into the junction box using 2 screws. Position the thermostat front over the part mounted in the junction box, then carefully press the front until it clicks into place. In order to get power metering values, the load needs to be connected to both heating L + N. Never change the front from one thermostat to another.
FACTORY RESET
Enter the menu by holding the center button for about 5 seconds, navigate in the menu with the “+” button til you see “ADVA”. Press the Center button once, then, navigate til you see “FACT”. Press the Center button until you see “– –” blinking in the display, then hold for about 5 seconds to perform a reset. You may also initiate a reset byholding the Left and Right buttons for 60 seconds. When either of these procedures has been performed, the thermostat will perform a complete factory reset. The device will display “RES” for 5 seconds while performing a factory reset. When “RES” is no longer displayed, the thermostat has been reset.
STARTUP
After powering up the device for the first time, all parameters will have default settings and the thermostat will start by asking for the date and time.
PRINCIPLES OF REGULATION
The thermostat uses temperature readings retrieved from the internal sensor and/or from external wired sensors to regulate the temperature. The thermostat will regulate the temperature using hysteresis or PWM, based on the setpoint temperature.
Hysteresis
Hysteresis will turn on and off the load based on the hysteresis value in
comparison to the setpoint. You can make changes to the thermostat hysteresis.
It may be changed by entering the local settings menu and pressing the Center
button when “HYST” is displayed. Here you can choose values between 0.5 and
10. The default setting is 0.5°C. When using waterbased heating we recommend a
hysteresis of 1.0°C.
Pulse-width modulation PWM
With PWM regulation enabled, the thermostat will regulate based on duty
cycles. The thermostat is turned on and off in percentage intervals of the
cycle. The amount of time the relay will be on is based on how far the
measured temperature is from the setpoint.
WATERBASED HEATING/ELECTRICAL HEATING
The thermostat can be set to be used with either electrical heating, or waterbased heating. Depending on which choice is made, some menu items and operations will be different.
Automatic valve exercise
Valve exercising is beneficial during longer periods of inactivity to ensure
the proper operability of the valves and prevent the valves from getting
stuck. If not exercised, corrosion or other buildup may result in the valve
becoming inoperable or prevent complete closure. NB! This function on by
default with 5 minutes timer when waterbased heating is active. If you do not
control an actuator, it is recommended to turn off this function.
Waterbased heating/NCNO
While in waterbased heating mode, you can change the NCNO menu option. Using
this menu option will change between Normally Open and Normally Closed.
Holding center button when NCNO is displayed will allow you to adjust
automatic valve exercise timer.
LOCAL SETTINGS MENU
To enter the settings menu, hold the Center button for 5 seconds. The display
will show “PROF”. You are now in the settings menu. You can now scroll up and
down using the Left and Right buttons. Some menu items are in the “ADVA”
(advanced) submenu. To navigate the submenus, press the Center button once to
enter or exit the submenu. Press the Left and Right buttons to find your
desired value and hold the Center button for 2 seconds to confirm your
selection. “STOR” will appear to indicate settings are stored.
DISPLAY MENU STRUCTURE
See flowchart at the end of this manual.
WEEKLY SCHEDULE
To enable the weekly schedule, enter the menu, navigate to “PROF” and select
“AUTO”. The following options are available, each with six different time
slots to configure the temperatures.
- WEE Mon-Fri and Sat-Sun program.
- WDA Mon-Sat and Sun program.
- WEN Same program whole week.
- DAY Each day individually programmed with 6 settings.
STANDBY AND MAIN SCREEN
When the thermostat remains untouched for a while, it will automatically go to the standby screen. By pressing any button once, you will see the thermostats setpoint. By pressing the Left or Right button multiple times, you will change the setpoint.
WEEKLY SCHEDULE AND ADAPATIVE FUNCTION
Weekly schedule
You can customize the thermostat to change its setpoint at different times
throughout the week. There are several weekly files and preset times available
that you can configure.
Setting a weekly schedule
Enter the menu and press the center button on “PROF”, then select “AUTO”, and
hold the center button to confirm the selection. After selecting “AUTO”, there
will be a “PROG” option in the menu. Press the center button to enter the
programming mode for the weekly schedule. There you can choose your program
type, and configure the times and temperatures.
Adaptive function
The adaptive function learns the time required to heat the room. The
thermostat will aim to reach the scheduled temperature at the specified time
in your weekly plan.
ACTIVE POWER METERING VALUES IN MENU
The device supports active power metering to give insight into the power
consumption of the heating. The active power metering information can be seen
from the menu. Navigate to “POW” under “ADVA” and press the Center button to
scroll through amps, voltage, watts and kWh.
SIZE OF LOAD
Hold the center button for 2 seconds while “POW” is displayed to manually set
the value of the connected load from 100W to 6500W with 100W increments.
CHOICE OF SENSOR
The thermostat has multiple sensors and sensor modes. This lets you
configure the thermostat to work correctly in most installations. The sensors
and modes may be selected from the local settings menu (“MODE”).
Available sensor modes:
- F Floor sensor
- A Internal room sensor
- AF Internal room sensor + Floor sensor
- A2 External room sensor
- A2F External room sensor + Floor sensor
NOTE: Some types of floor require that a floor sensor is connected in order to limit the floor temperature to a maximum of 27°C (check the manual from the floor manufacturer). When the thermostat is used in (AF or A2F) thefloor limiter FHI is automatically set to 27°C. When using anyother sensor type (A, F or A2) the minimum and maximum limits are 5°C and 40°C respectively.
SELECTING SENSOR VALUE
The thermostat allows the selection of multiple different resistance values of an NTC sensor and can be selected using the local settings menu. The supported sensor values are as follows: 6.8, 10, 12, 15, 22, 33, 47 or 100KΩ. The factory default value is 10kΩ. When connecting both the floor sensor and the external sensor, make sure to use sensors with the same Ohm value.
CALIBRATION
If the temperature sensor readout is not correct, you can make minor changes
to the temperature readout. The temperature readings can be calibrated by
±10°C. The temperature calibration can be performed from the menu using CAR,
CAE and CAF. The adjusted value will be displayed indicating what the
thermostat uses for regulation.
SENSOR TYPE IN MENU STRUCTURE
- Internal sensor CAR
- External sensor CAE
- Floor sensor CAF
BRIGHTNESS
Using the menu choices “BR1” and “BR2”, the brightness of the display in
Active and Standby state can be changed respectively.
DISPLAY ON/OFF (DON/DOFF)
The thermostat has a display ON/OFF function which decides whether the display
should turn completely off when in Standby. To enable/disable this function,
hold the Right and Center buttons for 10 seconds. The display will show “DOFF”
when the function is activated and “DON” when the function is disabled. When
operating any button, the display will light up.
DISPLAY ICONS
CHILD LOCK
The child lock function disables the buttons on the display. It will show “LOCK” when attempting to operate it while the function is enabled. To enable or disable the function, hold the Center and Left buttons for 10 seconds. Enabling the function will show “LOCK” in the display, disabling the function will show “OPEN”.
OPEN WINDOW DETECTION
Open Window Detection (OWD) is a function which will reduce the thermostat
setpoint on detection of an open window. This happens when the temperature
sensor registers a rapid temperature drop. When OWD is active, the setpoint is
reduced to 5°C in order not to waste energy. OWD will automatically be
cancelled if OWD has been active for more than 1 hour, or if thetemperature
increases by 3°C. OWD can also be cancelled manually by increasing/decreasing
the setpoint with the Left and Right buttons.By default, OWD is not enabled.
The feature may be enabled by selecting “OWD” from the menu. Choose between
options “OFF” and “ON”.
ANTI-FREEZE FUNCTION
Anti-freeze (ANTI) helps to reduce the chance of damage due to very low temperatures. When anti-freeze is active, you can choose a setpoint between 5°C and 10°C. The thermostat will start heating even when it is in OFF mode.
ERROR CODES
Err1 Internal error. Most probably a faulty unit. Contact support. Err3
Internal error. Most probably a faulty unit. Contact support. Err4 Floor
sensor error. You have chosen F, AF or A2F sensor mode without having a floor
sensor connected, or the sensor may be damaged. Err5 External sensor error.
You have chosen A2 or A2F sensor mode without having an external sensor
connected, or the sensor may be damaged. Err6 Overheating. Contact your
electrician. Err7 Overload. Contact your electrician.
SAFETY FEATURES
The device has safety features to ensure safe operation and warn the user of any faults/unexpected behavior. The device has an Overheat and Overload function. If the thermostat registers an Overheat or Overload incident, the thermostat will switch off and an error will appear in the display.
Overheating
The device features internal temperature sensors that detect overheating. It
warns the user and turns off the relay to prevent any damage.
When overheating is detected, the device will:
- Turn off the relay.
- Display Err6 in the display.
Overload
The device features a 16A overload protection. The overload is triggered if
there is a current draw of more than 16A.When overload is detected, the device
will:
- Turn off the relay.
- Display Err7 in the display.
Sensor failure
The device has the ability to detect when there is no sensor connected or the
sensor is broken or otherwise defective, causing an open circuit.
When the device detects the sensor error, the device will:
- Turn off the relay.
- Display an error in the display, changes based on which sensor is not connected/faulty.
To clear the “Sensor not connected” error the device has to be disconnected from the mains, and the wiring and sensor(s) need to be checked. When the fault is resolved the mains can be reconnected and the device will function normally again.
THERMOSTAT SETPOINT
The device supports 2 setpoints: Heating and Cooling. Supported setpoints are
from 5°C – 40°C with 0.5°C increments.
THERMOSTAT MODE
It is possible to change the operating mode of the thermostatin the Mode menu.
The accessible operating modes are: OFF Thermostat regulation and display
aredeactivated.Heating Mode Thermostat regulation is active. Cooling Mode
Thermostat regulation is inverted.
THERMOSTAT DIMENSIONS
THERMOSTAT CONTROLS
CHART – DISPLAY MENU STRUCTURE
- Hold the middle button for 5 seconds to enter menu.
Error messages in display
General display messages
PRODUCT INFO Heatit Pro Thermostat
FEATURES
- Internal room sensor
- External room sensor (wired by cable)
- Floor sensor
- Temperature limiter
- 2 modes; Heat and Cool
- Hysteresis 0.5°C – 10°C
- Temperature calibration
- ZeroX detection
- Open window detection
- Relay status icon
- Adjustable display brightness
- Single pole switch
- Lock mode/child lock
- Anti-freeze
- Works with NO and NC actuators
- Weekly schedule
- Adaptive function
- Internal clock
- Backup battery for internal clock
- Active power metering
TECHNICAL DATA
- Rated voltage 230VAC 50Hz
- Max load 3600W (resistive load) Contactor recommended for loads above 13A
- Max current 16A
- Power consumption <2W
- Ambient temperature 5°C to 40°C
- Temperature range 5°C to 40°C
- Storage temperature -30°C to 70°C
- Hysteresis 0.5°C to 10°C (default 0.5°C)
- Humidity 10% to 85% RH
- Compatible with NTCsensor with values 6.8, 10, 12, 15, 22, 33, 47 or 100kΩ @ 25°C
- Length NTC sensor Max. 15 meters
- Screw terminals Max. 2.5mm2 2Nm
- IP Code IP21
- Size (LxWxH) 84 x 84 x 52mm
- Approvals CE
MAINTENANCE
The device is maintenance-free. Indoor use only.
DISPOSAL GUIDELINES
Do not dispose of electrical appliances as unsorted municipal waste, use separate collection facilities. To prevent possible harm to the environment or human health from uncontrolled waste disposal, recycle it responsibly to promote the sustainable reuse of material resources. To return your used device, please use the return and collection systems or contact the retailer where the product was purchased. They can take this product for environmental safe recycling. We have designed this product in accordance with our strict quality requirements (ISO 9001) and environmental requirements (ISO 14001). All electrical installations must be carried out by an authorized electrical installer. The product must be installed in accordance with our installers manual and national building codes. Any wrongful installation, misuse or damage to the product is not covered under warranty. Heatit Controls AB can not be held liable for any type of errors or omittances in our product information. Product specifications may change without further notice.
Heatit Controls AB · Läkarvägen 4, 454 31 BRASTAD, SWEDEN Phone: +47 61 18 77 77 · post@heatit.com · heatit.com