TRANE SWUD Commercial Self Contained Units Instruction Manual
- September 17, 2024
- Trane
Table of Contents
SWUD Commercial Self Contained Units
“`html
Product Specifications
Product Name: Commercial Self-Contained Units
SWUD
Model Number: PKG-SVX029A-EN
Refrigerant: R-454B (Flammable A2L)
Product Usage Instructions
Installation
1. Only qualified personnel should install the equipment.
2. Follow specific knowledge and training requirements for
installation.
3. Observe all precautions mentioned in the literature and on
equipment tags, stickers, and labels.
Operation
1. Read the manual thoroughly before operating the unit.
2. Pay attention to warnings, cautions, and notices provided in
the manual.
Maintenance
1. Regular maintenance is essential for proper functioning.
2. Follow safety advisories and precautions during maintenance
tasks.
Frequently Asked Questions (FAQ)
Q: Who should install and service the equipment?
A: Only qualified personnel should handle
installation and servicing to prevent hazards.
Q: What refrigerant does the equipment use?
A: The equipment uses R-454B refrigerant, which
is flammable (A2L). Use ONLY R454B rated service equipment and
components.
“`
Installation, Operation, and Maintenance
Commercial Self-Contained Units SWUD
R-454B 20 to 110 Tons
SWUD 20 to 110 Tons
SAFETY WARNING
Only qualified personnel should install and service the equipment. The
installation, starting up, and servicing of heating, ventilating, and air-
conditioning equipment can be hazardous and requires specific knowledge and
training. Improperly installed, adjusted or altered equipment by an
unqualified person could result in death or serious injury. When working on
the equipment, observe all precautions in the literature and on the tags,
stickers, and labels that are attached to the equipment.
May 2024
PKG-SVX029A-EN
Introduction
Read this manual thoroughly before operating or servicing this unit.
Warnings, Cautions, and Notices
Safety advisories appear throughout this manual as required. Your personal
safety and the proper operation of this machine depend upon the strict
observance of these precautions.
The three types of advisories are defined as follows:
WARNING
Indicates a potentially hazardous situation which, if not avoided, could result in death or serious injury.
CAUTION NOTICE
Indicates a potentially hazardous situation which, if not avoided, could
result in minor or moderate injury. It could also be used to alert against
unsafe practices.
Indicates a situation that could result in equipment or property-damage only
accidents.
Important Environmental Concerns
Scientific research has shown that certain man-made chemicals can affect the
earth’s naturally occurring stratospheric ozone layer when released to the
atmosphere. In particular, several of the identified chemicals that may affect
the ozone layer are refrigerants that contain Chlorine, Fluorine and Carbon
(CFCs) and those containing Hydrogen, Chlorine, Fluorine and Carbon (HCFCs).
Not all refrigerants containing these compounds have the same potential impact
to the environment. Trane advocates the responsible handling of all
refrigerants.
Important Responsible Refrigerant Practices
Trane believes that responsible refrigerant practices are important to the
environment, our customers, and the air conditioning industry. All technicians
who handle refrigerants must be certified according to local rules. For the
USA, the Federal Clean Air Act (Section 608) sets forth the requirements for
handling, reclaiming, recovering and recycling of certain refrigerants and the
equipment that is used in these service procedures. In addition, some states
or municipalities may have additional requirements that must also be adhered
to for responsible management of refrigerants. Know the applicable laws and
follow them.
WARNING
Proper Field Wiring and Grounding Required!
Failure to follow code could result in death or serious injury. All field
wiring MUST be performed by qualified personnel. Improperly installed and
grounded field wiring poses FIRE and ELECTROCUTION hazards. To avoid these
hazards, you MUST follow requirements for field wiring installation and
grounding as described in NEC and your local/state/national electrical codes.
WARNING
Personal Protective Equipment (PPE) Required!
Failure to wear proper PPE for the job being undertaken could result in death
or serious injury. Technicians, in order to protect themselves from potential
electrical, mechanical, and chemical hazards, MUST follow precautions in this
manual and on the tags, stickers, and labels, as well as the instructions
below:
· Before installing/servicing this unit, technicians MUST put on all PPE
required for the work being undertaken (Examples; cut resistant gloves/
sleeves, butyl gloves, safety glasses, hard hat/ bump cap, fall protection,
electrical PPE and arc flash clothing). ALWAYS refer to appropriate Safety
Data Sheets (SDS) and OSHA guidelines for proper PPE.
· When working with or around hazardous chemicals, ALWAYS refer to the
appropriate SDS and OSHA/GHS (Global Harmonized System of Classification and
Labelling of Chemicals) guidelines for information on allowable personal
exposure levels, proper respiratory protection and handling instructions.
· If there is a risk of energized electrical contact, arc, or flash,
technicians MUST put on all PPE in accordance with OSHA, NFPA 70E, or other
country-specific requirements for arc flash protection, PRIOR to servicing the
unit. NEVER PERFORM ANY SWITCHING, DISCONNECTING, OR VOLTAGE TESTING WITHOUT
PROPER ELECTRICAL PPE AND ARC FLASH CLOTHING. ENSURE ELECTRICAL METERS AND
EQUIPMENT ARE PROPERLY RATED FOR INTENDED VOLTAGE.
©2024 Trane
PKG-SVX029A-EN
WARNING
Follow EHS Policies!
Failure to follow instructions below could result in death or serious injury.
· All Trane personnel must follow the company’s Environmental, Health and
Safety (EHS) policies when performing work such as hot work, electrical, fall
protection, lockout/tagout, refrigerant handling, etc. Where local regulations
are more stringent than these policies, those regulations supersede these
policies.
· Non-Trane personnel should always follow local regulations.
WARNING
R-454B Flammable A2L Refrigerant!
Failure to use proper equipment or components as described below could result
in equipment failure, and possibly fire, which could result in death, serious
injury, or equipment damage. The equipment described in this manual uses
R-454B refrigerant which is flammable (A2L). Use ONLY R454B rated service
equipment and components. For specific handling concerns with R-454B, contact
your local representative.
Introduction
Copyright
This document and the information in it are the property of Trane, and may not
be used or reproduced in whole or in part without written permission. Trane
reserves the right to revise this publication at any time, and to make changes
to its content without obligation to notify any person of such revision or
change.
Trademarks
All trademarks referenced in this document are the trademarks of their
respective owners.
Agency Listing
Unit is listed with ETL as a modular/cassette product and ships as such.
Individual assemblies are tested and meet the requirements as such, but is not
tested as a completed unit. Important: Installer is responsible for proper
installation
and for properly following assembly instructions found in this IOM.
PKG-SVX029A-EN
3
Table of Contents
Overview. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. 7
R-454B Compressors . . . . . . . . . . . . . . . . . . . . . . 7
SWUD Components . . . . . . . . . . . . . . . . . . . . . . . 7 Standard
Controls. . . . . . . . . . . . . . . . . . . . . . 7 TD-7 Touch Screen
Display. . . . . . . . . . . . . . 7 Symbio 500 Unit Controller . . . . . . .
. . . . . . . 7 Optional Controls . . . . . . . . . . . . . . . . . . . . . .
7 Unit Nameplate . . . . . . . . . . . . . . . . . . . . . . . . 8
Model Number Description . . . . . . . . . . . . . . . . . . . 9
General Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
Pre-Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
Receiving. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
Receiving Checklist . . . . . . . . . . . . . . . . . . . 12 Ship-Separate
Accessories. . . . . . . . . . . . . 12 Contractor Installation
Responsibilities . . . . . . . . . . . . . . . . . . . . . . . 12 Unit
Inspection. . . . . . . . . . . . . . . . . . . . . . . . 12 Exterior
Inspection . . . . . . . . . . . . . . . . . . . . 12 Inspection for Concealed
Damage. . . . . . . 12 Repair . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . 13 Unpacking . . . . . . . . . . . . . . . . . . . . . . . . . .
. 13
Dimensional Data. . . . . . . . . . . . . . . . . . . . . . . . . . . 14
Service Clearances . . . . . . . . . . . . . . . . . . . . . . . 17
Weights . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. 18
Installation Mechanical . . . . . . . . . . . . . . . . . . . . 19
Unit Handling . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
Installation Preparation . . . . . . . . . . . . . . . . . . . . 20
Unit Vibration Isolator Option . . . . . . . . . . . . . . . 20
Unit Isolator Installation Procedure . . . . . . . . . . 20
Duct Connections. . . . . . . . . . . . . . . . . . . . . . . . . 20
Water Piping . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21
Condenser Connections . . . . . . . . . . . . . . . 21 Condensate Drain
Connections . . . . . . . . . 21 General Waterside Recommendations for Cooling
Towers . . . . . . . . . . . . . . . . . . . . 22 Waterside Piping
Arrangements. . . . . . . . . 22 Water Temperature Requirements . . . . . . .
22 Water Piping Verification . . . . . . . . . . . . . . . 22
Installating the Hydronic Coil . . . . . . . . . . . . . . . 22 Refrigerant
System. . . . . . . . . . . . . . . . . . . . 22
Installation – Electrical. . . . . . . . . . . . . . . . . . . . . . . 23
Unit Wiring Diagrams. . . . . . . . . . . . . . . . . . . . . . 23
Supply Power Wiring . . . . . . . . . . . . . . . . . . . . . . 23 Voltage
Range. . . . . . . . . . . . . . . . . . . . . . . . 23 Voltage Imbalance . .
. . . . . . . . . . . . . . . . . . 23 Phase Monitor . . . . . . . . . . . . .
. . . . . . . . . . . 23 Control Power . . . . . . . . . . . . . . . . . . . .
. . . . 23
Selection Procedures . . . . . . . . . . . . . . . . . . . . . 24 Determine
Minimum Circuit Ampacity (MCA) . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . 24
Static Pressure Transducer Installation (VAV Units Only). . . . . . . . . . .
. . . . . . . . . . . . . . . 25
Transducer Inlet Location . . . . . . . . . . . . . . 25 Installing the
Transducer . . . . . . . . . . . . . . . 25
Zone Sensor Option used for Discharge Air Reset by Space Temperature. . . . .
. . . . . . . . . . 26
Zone Temperature Sensor, BAYSENS077 (Optional Item) . . . . . . . . . . 26
Zone Sensor Installation . . . . . . . . . . . . . . . . . . . 26 Mounting
Location . . . . . . . . . . . . . . . . . . . . 26 Mounting the Subbase . . .
. . . . . . . . . . . . . . 26 Wiring . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . 26 Standard Remote Sensor (BAYSENS077) . . . . . . . . .
. . . . . . . . . . . . . . 27
Operating Principles . . . . . . . . . . . . . . . . . . . . . . . . 28
Control Sequences of Operation . . . . . . . . . . . . 28 Occupied/Unoccupied
Switching . . . . . . . . 28 Compressor Lead/Lag . . . . . . . . . . . . . . .
. . 28 Emergency Stop Input . . . . . . . . . . . . . . . . . 28 External
Auto/Stop Input . . . . . . . . . . . . . . . 28 Local Auto Stop. . . . . . .
. . . . . . . . . . . . . . . . 28 Head Pressure Control . . . . . . . . . . .
. . . . . 28 Water Purge. . . . . . . . . . . . . . . . . . . . . . . . . . 28
Supply Air Temperature Control Unit Sequence of Operation . . . . . . . . . .
. . . . . . . . . . 28
Discharge Air High Temp Limit Software Alarm (Software) . . . . . . . . . . .
. . 28 Condenser Water Low Temperature Alarm (Software) . . . . . . . . . . .
. . . . . . . . . . . 28 Leaving Air Low Temperature Alarm . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . 28 Occupied Fan Operation . . . . .
. . . . . . . . . . 28 Heat/Cool Mode . . . . . . . . . . . . . . . . . . . .
. . 28 Cooling/Waterside Economizer . . . . . . . . . 29
4
PKG-SVX029A-EN
Table of Contents
Thermostatic Expansion Valve. . . . . . . . . . . . . . 29
Fan Operation. . . . . . . . . . . . . . . . . . . . . . . . . . . . 29 Supply
Air Static Pressure High Limit . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . 29
Compressors . . . . . . . . . . . . . . . . . . . . . . . . . . . . 29
Compressor Oil . . . . . . . . . . . . . . . . . . . . . . . 29 High Pressure
Cutout Switch (HPC) . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . 29 Compressor Pressure Sensors . . . . . . . . . 29 Compressor Suction
Temperature . . . . . . . 30 Fixed Speed Compressor (FS) . . . . . . . . . .
30 Compressor Safety Circuit . . . . . . . . . . . . . 30 Compressor Limit
Conditions . . . . . . . . . . . 30 Compressor Staging. . . . . . . . . . . .
. . . . . . . 31 Compressor Control . . . . . . . . . . . . . . . . . . . 31
Waterside Components. . . . . . . . . . . . . . . . . . . . 31 Water Purge. .
. . . . . . . . . . . . . . . . . . . . . . . . 31 Water Piping Options . . .
. . . . . . . . . . . . . . . 31 Water Flow Switch Option . . . . . . . . . .
. . . . 31 Water-Cooled Condensers . . . . . . . . . . . . . 31 Waterside
Economizer Option . . . . . . . . . . 32 Heat Mode . . . . . . . . . . . . . .
. . . . . . . . . . . . . 32 Dirty Air Filter Sensor Option . . . . . . . . .
. . 32 Supply Air Static Pressure High Limit . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . 32
Airside Components . . . . . . . . . . . . . . . . . . . . . . 32 Two-Position
Damper Interface . . . . . . . . . 32 Airside Economizer Interface with OA
Reference . . . . . . . . . . . . . . . . . . . . . . . . . . . 32 Airside
Economizer Interface with Comparative Enthalpy . . . . . . . . . . . . . . . .
. 32
Controls. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. 34
Unit Controller. . . . . . . . . . . . . . . . . . . . . . . . . . . . 34
Navigating the TD-7. . . . . . . . . . . . . . . . . . . . . . . 37 TD-7 Home
Screen. . . . . . . . . . . . . . . . . . . . 37
TD-7 Reports . . . . . . . . . . . . . . . . . . . . . . . . . . . . 37 Unit
Status Report . . . . . . . . . . . . . . . . . . . . 37 All Points Report . .
. . . . . . . . . . . . . . . . . . . . 37
Starting the Unit . . . . . . . . . . . . . . . . . . . . . . . . . . 37 Local
Auto/Stop Value . . . . . . . . . . . . . . . . . 37 Setpoint Adjustments . .
. . . . . . . . . . . . . . . . 38
Unit Setpoints . . . . . . . . . . . . . . . . . . . . . . . . . . . . 38
Unit Setup . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 39
Reports. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 39
Compressor Alarms . . . . . . . . . . . . . . . . . . . 39 Fan Alarms. . . . .
. . . . . . . . . . . . . . . . . . . . . . 39 General Alarms . . . . . . . .
. . . . . . . . . . . . . . . 40
Water Purge . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 40
Pre-Startup. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
41
Pre-Startup Checklist . . . . . . . . . . . . . . . . . . . . . 41
Supply Fan . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 41
Ductwork . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 41
Water-Cooled Unit Piping . . . . . . . . . . . . . . . . . . 41
Units with Hydronic Heat. . . . . . . . . . . . . . . . . . . 41
Electrical . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 41
Components . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 41
Start-Up. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. 42
Final Refrigerant Charge. . . . . . . . . . . . . . . . . . . 42
Start-Up Procedure . . . . . . . . . . . . . . . . . . . . . . . 42 Operating
and Programming Instructions . . . . . . . . . . . . . . . . . . . . . . . . .
. 43 Start-Up Log . . . . . . . . . . . . . . . . . . . . . . . . . 43
Maintenance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 44
Service Access . . . . . . . . . . . . . . . . . . . . . . . . . . . 44
Air Filters . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 44
Inspecting and Cleaning the Drain Pan . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . 44
Compressors . . . . . . . . . . . . . . . . . . . . . . . . . . . . 45 Scroll
Compressor Failure Diagnosis and Replacement . . . . . . . . . . . . . . . . .
. . . . 45
Refrigerant System . . . . . . . . . . . . . . . . . . . . . . . 45
Refrigerant Leak Test Procedure . . . . . . . . 45 Brazing Procedures . . . .
. . . . . . . . . . . . . . . 46 System Evacuation Procedures . . . . . . . .
. 46
Compressors . . . . . . . . . . . . . . . . . . . . . . . . . . . . 48 Scroll
Compressor Failure Diagnosis and Replacement . . . . . . . . . . . . . . . . .
. . . . 48
Components . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 48
Cleaning Coil Fin. . . . . . . . . . . . . . . . . . . . . . 48
Piping Components . . . . . . . . . . . . . . . . . . . . . . . 50 Water
Valves . . . . . . . . . . . . . . . . . . . . . . . . . 50 Water Flow Switch
. . . . . . . . . . . . . . . . . . . . 50
Maintenance Periodic Checklists. . . . . . . . . . . . 50
PKG-SVX029A-EN
5
Table of Contents
Monthly Checklist . . . . . . . . . . . . . . . . . . . . . 50 Semi-Annual
Maintenance . . . . . . . . . . . . . 51 Annual Maintenance. . . . . . . . . .
. . . . . . . . . 51
Diagnostics . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 52
Troubleshooting . . . . . . . . . . . . . . . . . . . . . . . . . . 52 System Checks . . . . . . . . . . . . . . . . . . . . . . . 52
6
PKG-SVX029A-EN
Overview
Note: One copy of this document ships inside the control panel of each unit
and is customer property. It must be retained by the unit maintenance
personnel.
This manual describes proper installation, operation, and maintenance
procedures for water cooled systems. By carefully reviewing the information
within this manual and following the instructions, the risk of improper
operation and/or component damage will be minimized. It is important that
periodic maintenance be performed to help support trouble free operation. A
maintenance schedule is provided at the end of this manual. Should equipment
failure occur, contact a qualified service organization with qualified,
experienced HVAC technicians to properly diagnose and repair this equipment.
R-454B Compressors
· Use crankcase heaters which must be energized 24 hours prior to compressor
start. Note: This unit is equipped with stator heating capabilities that
eliminates the need for a crankcase heater on the variable speed compressor
only. All fixed speeds must utilize a crankcase heater.
· Contains POE oil which readily absorbs potentially damaging moisture from
air.
· Control box includes a phase monitor to detect phase loss, line voltage
imbalance, and reversal.
SWUD Components
SWUDs are complete HVAC systems used in floor-by-floor applications.
· A single piece cabinet design to target new constructions.
· Left hand power connections.
· Left or right hand water connections.
· Factory installed options.
The hermetically sealed scroll compressor motors utilize internal motor
protection and time delays to prevent excessive cycling.
Units utilize two refrigerant circuits and ship with a R-454B charge and full
oil charge. Each circuit includes filter drier, pressure relief valve,
moisture indicating sight glass, thermostatic expansion valve with sensing
bulb and externally equalized, and high pressure cutout. The water cooled
condensers are shell and tube. It is recommended to clean the condenser
mechanically, but the condenser can be cleaned chemically.
Fan array consists of 1-7 direct drive plenum fans with each fan equipped with
ECM motors.
PKG-SVX029A-EN
Figure 1. SWUD components
Standard Controls
Standard controls supplied with the unit include SymbioTM 500 unit controls
and the TD-7 touch screen display. All basic setup parameters are preset from
the factory.
TD-7 Touch Screen Display
· TD-7 is unit mounted and accessible without opening the unit front panel.
· Use the TD-7 touch screen for easy setpoint adjustment.
· The TD-7 displays all unit operating parameters and conditions in a backlit
color screen.
Symbio 500 Unit Controller
The SymbioTM 500 provides smart unit control with safety features and control
relays for external devices. The Symbio 500 utilizes BACnet® MSTP to
communicate to a front end Building Automation System (BAS). The SWUD self-
contained unit is controlled by a microelectronic programmable control system
programmed from the factory specifically for the application. If additional
input or output points are needed, expansion modules can be used. For more
detailed information on the control points provided, see the Owners section of
this manual.
Optional Controls
Optional controls include a disconnect switch, dirty filter switch, water flow
switch, supply air temperature reset, or external setpoint inputs. Morning
warm-up operation is available on all units with heat or with downstream VAV
boxes with heat. Note: A water flow switch is required for the installation,
either supplied from the factory or field-provided. The static pressure probe,
supply air temperature reset sensor options ship separate, but with the unit
for field
7
Overview
installation. For more detailed unit control options, see the Owners section
of this manual.
Unit Nameplate
The unit nameplate identifies the unit model number. It is located on the door
of the starter panel.
8
PKG-SVX029A-EN
Model Number Description
Digit 1, 2, 3, 4 — Unit Model
SWUD = Self-Contained Water-Cooled Unitary Device
Digit 5 — Refrigerant
5 = R-454B
Digit 6, 7, 8 — Capacity
020 = 20 Tons 025 = 25 Tons 030 = 30 Tons 035 = 35 Tons 040 = 40 Tons 045 = 45
Tons 050 = 50 Tons 055 = 55 Tons 060 = 60 Tons 065 = 65 Tons 070 = 70 Tons 075
= 75 Tons 085 = 85 Tons 090 = 90 Tons 100 = 100 Tons 110 = 110 Tons
Digit 9 — Unit Voltage
F = 208230/60/3 4 = 460/60/3 5 = 575/60/3
Digit 10, 11 — Design Sequence
**
Digit 12 — Fan Type
1 = 1 Fan 2 = 2 Fans 3 = 3 Fans 4 = 4 Fans 5 = 5 Fans 6 = 6 Fans 7 = 7 Fans
Digit 13 — Compressor Technology
F = Fixed Speed
Digit 14 — Control Valves
0 = None H = Head Pressure Control Valves
Digit 15 — Future Use
0 = None
Digit 16 — Economizer
0 = No Economizer W = With Water Side Economizer H = 2-position Damper
Ventilation Interface J = Airside Economizer Interface K = Airside Economizer
Interface W/Comparative Enthalpy
Digit 17 — Water Connections
L = Left Hand Connections with Flow Switch R = Right Hand Connections with
Flow Switch
Digit 18 — Unit Water Connections
1 = Victaulic
Digit 19 — Air Discharge
H = Horizontal Discharge V = Vertical Discharge
Digit 20 — Electrical Connections
L = Left Hand Connections
Digit 21 — Unit Electrical Connections
1 = Disconnect Switch 2 = Terminal Block Digit 22 — Drain Pan
G = Galvanized Drain Pan S = Stainless Steel Drain Pan Digit 23 — Future Use
0 = None
Digit 24 Filter Type
A = 2 inch – MERV 8 B = 4 inch – MERV 8 C = 2 inch – Pre-MERV 8, 4 inch, Post-
MERV 13 D = 2 inch – MERV 13 E = 4 inch – MERV 13 F = 6 inch – MERV 15 Digit
25 — Heater
0 = None 4 = Hydronic Remote 5 = Electric Remote (3 stages max, on/off)
Digit 26 — Shipping Method
S = Single Piece
Digit 27– Unit Isolators
0 = None A = Isopads
Digit 28 — Air Volume/Temp Control
A = VAV Control Scheme (Fixed DA Temp) B = VAV Control Scheme (Return Air
Reset) C = VAV Control Scheme (Space Temp Reset) D = CV Control Scheme (Fixed
DA Temp) Digit 29 — Agency Listing
0 = None E = ETL listing Digit 30 — Options
0 = None 2 = Compressor Service Valves Digit 31 — Space Sensor Options
0 = None 1 = Space Sensor Only Digit 32 — Future Use
0 = None
Digit 33 — Industrial Options
0 = None A = Protective Coating Evaporator Coil B = Protective Coating
Evaporator Coil + WSE Digit 34 — Discharge Plenum
0 = None S = Standard Plenum with Field-Cut Holes Digit 35 — Future Use
0 = None
Digit 36 — Future Use
0 = None
Digit 37 — Controller
3 = SymbioTM 500
Digit 38 — Future Use
0 = None
Digit 39 — Major Design Version
A = 1.0
Digit 40 — Design Special
0 = None S = Design Special
PKG-SVX029A-EN
9
General Data
Table 1. SWUD water-cooled self-contained
Tonnage
20 25 30 35 40 45 50 55 60 65 70 75 85 90 100 110
Compressor Data
Quantity Nominal Ton/Comp Circuits
4
4
4
4
4
4
4
4
4
4
4
4
4
4
4
4
5 6.25 7.5 8.75 10 11.25 12.5 13.75 15 16.25 17.5 18.75 21.25 22.5 25 27.5
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
Evaporator Coil Data
Rows Sq. Ft. Fins/in Number of Coils
2
2
3
3
3
3
3
3
3
3
3
3
3
3
3
3
28.65 28.65 28.65 28.65 35.42 37.5 39.58 40.63 40.63 50 51.11 52.78 52.78 68.33 68.33 68.33
12.0 12.0 12.0 12.0 12 12 12 12 12 12 12 12 12 12 12 12
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
Condenser Data
Minimumum GPM w/o Econ
(a)
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
Minimum GPM w/ Econ Maximum GPM
N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A
Evaporator Fan Data
Quantity Diameter Power consumption kW Minimum Design cfm(b) Maximum Design cfm
1 500 4.5 4000 7600
1
2
2
2
2
3
3
4
4
4
4
5
5
6
7
500 500 500 500 500 500 500 500 500 500 500 500 500 500 500
4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5
5000 6000 7000 7400 8600 10000 10800 12000 13000 13600 15200 16600 18000 20400 22600
9500 11400 13300 14060 16340 19000 20520 22800 24700 25840 28880 31540 34200 38760 42940
Refrigerant Charge, lbs. R-454B(c)
Circuit A Circuit B Total
10.0 12.5 15.0 17.5 20.0 22.5 25.0 27.5 30.0 32.5 35.0 37.5 42.5 45.0 50.0 55.0 10.0 12.5 15.0 17.5 20.0 22.5 25.0 27.5 30.0 32.5 35.0 37.5 42.5 45.0 50.0 55.0 20.0 25.0 30.0 35.0 40.0 45.0 50.0 55.0 60.0 65.0 70.0 75.0 85.0 90.0 100.0 110.0
Filter Data, Water-Cooled Units
Number – Size (in.)
9-20″x24″
12-20″x24″
15-20″x24″
21-20″x24″
Number of Compressor Tandems
8T Fixed Speed Tandem
2
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
10T Fixed Speed Tandem
0
2
0
0
0
0
0
0
0
0
0
0
0
0
0
0
13T Fixed Speed Tandem
0
0
2
1
0
0
0
0
0
0
0
0
0
0
0
0
15T Fized Speed Tandem
0
0
0
1
2
1
0
0
0
0
0
0
0
0
0
0
20T Fixed Speed Tandem
0
0
0
0
0
1
2
1
0
0
0
0
0
0
0
0
23T Fixed Speed Tandem
0
0
0
0
0
0
0
1
1
0
0
0
0
0
0
0
26T Fixed Speed Tandem
0
0
0
0
0
0
0
0
1
2
1
1
0
0
0
0
30T Fixed Speed Tandem
0
0
0
0
0
0
0
0
0
0
1
0
1
0
0
0
37T Fixed Speed Tandem
0
0
0
0
0
0
0
0
0
0
0
1
1
2
1
0
45T Fixed Speed Tandem
0
0
0
0
0
0
0
0
0
0
0
0
0
0
1
2
Number of Fans/Unit
No. of fans
1
2
3
4
5
6
7
Note: All performance data is provided in the Performance Selection Program.
Contact Trane Sales at 770-988-8338 for
more information.
(a) All performance data is provided in the Performance Selection Program.
Contact MJC Sales at 770-988-8338 for
more information. (b) Minimum air flow at part load is 35% of full load design
CFM. (c) Refrigerant charge shown is a general guideline, charge to sub-
cooling as described in IOM. Note that occasionally a TXV adjustment may need
to be made but only after
adequate sub-cooling has been reached.
10
PKG-SVX029A-EN
General Data
Table 2. EER/IEER ratings
Tonnage 20
Model Number SWUD5020
EER 18.7
IEER 21.3
AHRI Net Cooling Capacity (MBH)
252
25
SWUD5025
16.7
19.9
292
30
SWUD5030
17.9
22.6
387
35
SWUD5035
18.2
22.0
411
40
SWUD5040
18.2
21.9
458
45
SWUD5045
17.9
22.1
536
50
SWUD5050
18.8
22.8
625
55
SWUD5055
18.3
22.1
665
60
SWUD5060
18.2
21.7
743
65
SWUD5065
17.7
21.2
775
70
SWUD5070
17.3
21.7
839
75
SWUD5075
16.5
20.4
920
85
SWUD5085
16.6
20.6
987
90
SWUD590F
16.4
20.1
1096
100
SWUD5100
16.5
20.3
1234
110
SWUD5110
16.2
19.6
1371
Notes: 1. Cooling only. 2. Cooling performance is rated at 80F EDB/67F EWB with 85 EWT for water-cooled performance and 95F Ambient for air-cooled performance. 3. EER, IEER, and AHRI Net Cooling Capacity are tested in accordance with the AHRI 340/360 (I-P) and certified to 10 CFR Part 431 from the US Department of Energy.
PKG-SVX029A-EN
11
Pre-Installation
Receiving
Receiving Checklist
Complete the following checklist immediately after receiving unit shipment to
detect possible shipping damage:
· Inspect individual cartons before accepting. Check for rattles, bent carton
corners, or other visible indications of shipping damage.
· If a unit appears damaged, inspect it immediately before accepting the
shipment. Make specific notations concerning the damage on the freight bill.
Do not refuse delivery.
· Inspect the unit for concealed damage before it is stored and as soon as
possible after delivery. Report concealed damage to the freight line within
the allotted time after delivery. Check with the carrier for their allotted
time to submit a claim.
· Do not move damaged material from the receiving location. It is the
receivers responsibility to provide reasonable evidence that concealed damage
did not occur after delivery.
· Do not continue unpacking the shipment if it appears damaged. Retain all
internal packing, cartons, and crate. Take photos of damaged material if
possible.
· Notify the carrier of the damage immediately by phone and mail. Request an
immediate joint inspection of the damage by the carrier and consignee. Note:
Notify your Trane representative of the damage and arrange for repair. Have
the carrier inspect the damage before making any repairs to the unit.
Ship-Separate Accessories
Field installed components ship separately inside cassette labeled Ship-With
Components or on individual pallet.
Contractor Installation Responsibilities
Complete the following checklist before beginning final unit installation:
· Verify the unit size and tagging with the unit nameplate.
· Make certain the floor or foundation is level, solid, and sufficient to
support the unit and accessory weights. Level or repair the floor before
positioning the unit if necessary.
· Allow minimum recommended clearances for routine maintenance and service.
Allow space at end of the unit for servicing. Refer to the unit submittals for
dimensions. See also the “Service Clearances,” p. 17 section in the
“Dimensional Data,” p. 14.
· Electrical connection knockouts are on the top, of the starter panel.
12
· Allow adequate space for piping access and panel removal. Locate and
properly identify condenser water piping, refrigerant piping, and condensate
drain connections depending upon your application. Note: Unit height and
connection locations will change if using vibration isolators.
· Electrical supply power must meet specific balance and voltage requirements
as described in “Installation Mechanical,” p. 19.
· The installer is responsible for providing a condenser main, standby water
pump, cooling tower, pressure gauges, and all components for waterside piping.
Unit Inspection
To protect against loss due to damage incurred in transit, perform inspection
immediately upon receipt of the unit.
Exterior Inspection
If the job site inspection reveals damage or material shortages, file a claim
with the carrier immediately. Specify the type and extent of the damage on the
bill of lading before signing. Notify the appropriate sales representative.
Important: Do not proceed with installation of a damaged
unit without sales representative approval. · Visually inspect the complete
exterior for signs of
shipping damages to unit or packing material. · Verify the nameplate data
matches the sales order and
bill of lading. · Verify the unit is properly equipped and there are no
material shortages. · Verify the power supply complies with the unit
nameplate specifications.
Inspection for Concealed Damage
Visually inspect the components for concealed damage as soon as possible after
delivery and before it is stored. If concealed damage is discovered: · Notify
the carriers terminal of the damage immediately
by phone and by mail. · Concealed damage must be reported within 15 days. ·
Request an immediate, joint inspection of the damage
with the carrier and consignee. · Stop unpacking the unit. · Do not remove
damaged material from receiving
location. · Take photos of the damage, if possible. · The owner must provide
reasonable evidence that the
damage did not occur after delivery.
PKG-SVX029A-EN
Repair
Notify the appropriate sales representative before arranging unit installation
or repair. Important: Do not repair unit until the damage has been
inspected by the carrier’s representative.
Pre-Installation
Unpacking
SWUD units ship fully assembled in a single piece. Some accessories are
shipped inside an additional box.
PKG-SVX029A-EN
13
Dimensional Data
Figure 2. Unit dimensions (in inches)
Depth
Depth
Discharge Opening C
Width
Top
Discharge Opening D Width
The Top view drawing is a general representation. The number of fans varies according to capacity. See the general data table for fan quantity.
Airflow
Left (Control Box Side)
Height
Water Pipe
Airflow
Front (Fan side) – Vertical discharge
F
E
Right (Water Connection Side)
Discharge Opening A
21.857 Front Discharge Opening Height
Front (Fan Side) – Horizontal discharge
14
PKG-SVX029A-EN
Dimensional Data
Table 3. Unit dimensions (in inches)
Unit Size
Dimension
20, 25, 30, and 35T 40, 45, 50, 55, and 60T 65, 70, 75, and 85T
Width (in.)
70.00
Depth (in.)
65.00
Height (in.)
92.00
Discharge Opening – Vertical discharge
Discharge Opening C (in.)
21.42
Discharge Opening D (in.)
36.17
Discharge Opening – Horizontal discharge
Discharge Opening A (in.)
36.24
95.00 80.00 92.00
36.50 61.22
61.24
111.00 80.00 92.00
36.50 77.16
79.09
90, 100, and 110T 140.00 80.00 92.00
36.50 106.00
107.96
Dimension Water Pipe Ø
E F
20, 25, 30, and 35T
2.50 NPT 20.60 12.83
40T
2.50 NPT 30.00 12.87
Figure 3. Condensate drain pipe location
Unit Size 45, 50, 55, 60, and 65T
3.00 NPT 30.00 11.76
70T
3.00 NPT 30.00 13.73
75, 85, 90, 100, and 110T
4.00 NPT 30.00 14.82
6.4
34.3
1.5-in. Dia Condensate
Drain Pipe
Left
(Control Box Side)
Note: Condensate drain connection always on the LEFT (Control Box) side.
PKG-SVX029A-EN
15
Dimensional Data
Figure 4. Standard plenum (option)
A B
Note: Custom height plenums available upon request.
Table 4. Standard plenum (option)
Unit Size 20, 25, 30, and 35T 40, 45, 50, 55, and 60T 65, 70, 75, and 85T 90,
100, and 110T
Dim A (in.) 42.92 67.77 83.77 112.63
Dim B (in.) 28.55 43.40 43.40 43.40
Height (in.) 30.00 30.00 30.00 30.00
16
PKG-SVX029A-EN
Service Clearances
Figure 5. Service clearance
Back – Air Inlet
18″
Dimensional Data
Left Side
42″
- Low Voltage (Control Panel)
Right Side
24″
- High Voltage Starter Control
Electrical conduit penetrations (recommended)
Table 5. Service/code clearance requirements
Side
Distance – in. (mm)
Front
42
Left
42
Right
24
Back
18
Front
42″
Purpose NEC Code Requirements; Fan, Compressor, Condenser, Service/Removal
NEC Code Requirements Door Clearance
Provides Uniform Airflow
PKG-SVX029A-EN
17
Weights
Table 6. Unit weights
Unit Size
20 25 30 35 40 45 50 55 60 65 70 75 85 90 100 110
Base Weight (lbs) 2763 2813 2915 2965 3423 3489 3654 3734 3904 4231 4240 4367 4466 5137 5237 5336
Waterside Economizer (lbs) 459 459 459 468 578 602 626 638 649 679 777 796 796 1055 1055 1055
18
PKG-SVX029A-EN
Installation Mechanical
Unit Handling
WARNING
Improper Unit Lift!
Failure to properly lift unit in a LEVEL position could result in unit
dropping and possibly crushing operator/technician which could result in death
or serious injury, and equipment or property-only damage. Test lift unit
approximately 24 inches (61 cm) to verify proper center of gravity lift point.
To avoid dropping of unit, reposition lifting point if unit is not level.
· Use spreader bars to avoid unit damage.
· Spreader bar must be a minimum of 11 feet for 20 to 85 ton units and 12 feet
for 90 to 110 tons. Chains must not bear on top of unit.
· Run straps through fork pockets to connect to the spreader bar. See detail
in Figure 6, p. 19 and Figure 8, p. 20.
· Lift using overhead crane only. Adjust rigging for unit center of gravity.
· Unit center of gravity will fall within center of gravity block at various
locations depending on unit options.
· See unit nameplate for unit weights.
· Unit has built-in fork pockets for easy forklift maneuverability.
· Do not stack units.
Figure 7. Gravity Block Dimensions 20 to 80 tons, in.
Figure 6. Detail of how to run straps through fork pockets to connect spreader
bar on self-contained
Spreader bar
Straps
Fork Pockets
Table 7. Gravity block dimensions 20 to 80 tons, in.
Unit Size (Tons)
20 to 35
40 to 60
65 to 85
90 to 110
Dim A 26.8 34.8 35.4 35.3
Dim B 36.2 35.9 35.7 36.7
Dim C 34.8 47.5 53.9 70.6
Dim D 65.0 80.0 80.0 80.0
Dim E 70.0 95.0 111.0 140.0
92.0 B
C E
UNIT CENTER OF GRAVITY
AIRFLOW
A D
PKG-SVX029A-EN
19
Installation Mechanical
Figure 8. Gravity block location and dimensions for 90 to 110 ton units
Installation Preparation
Before installing the unit, perform the following procedures to confirm proper
unit operation. 1. Position the unit and pallet in its final location. 2. Test
lift the unit to determine exact unit balance and
stability before hoisting it to the installation location. See “Unit
Handling,” p. 19 for proper rigging procedures and cautions. 3. Remove the
protective shipping covers from the unit.
Unit Vibration Isolator Option
Important: Vibration isolation is not necessary for the unit since the factory
internally isolates the fan and compressor, thus creating double isolation.
Trane strongly recommends consulting a vibration specialist when considering
double isolation. Trane does not recommend doubleisolation.
Unit Isolator Installation Procedure
Use the following procedure to install isolators: 1. Position the isolators
under the unit base referring to
the isolator placement sheet that ships with the unit isolators. Lift one end
of the unit at a time to position the isolators. 2. Shim as required to level
the unit. It must be less than 1/8-inch per foot difference. Note: The unit is
equipped with a positively sloped drain
pan to help indoor air quality (IAQ) and does not require one corner of the
unit to be pitched.
Duct Connections
Return air enters the rear of the unit and conditioned supply air discharges
through the top.
20
Notes: ·
·
Attach supply air ductwork directly to the unit top panel, around the fan discharge opening. A duct collar is not provided. Units equipped with flexible horizontal discharge plenum option may include a duct collar when holes are factory cut.
Install all air ducts according to the National Fire Protection Association standards for the Installation of Air Conditioning and Ventilation Systems other than Residence Type (NFPA 90A) and Residence Type Warm Air Heating and Air Conditioning Systems (NFPA 90B).
Make duct connections to the unit with a flexible material such as heavy canvas. If a fire hazard exists, Trane recommends using Flexweave 1000, type FW30 or equivalent canvas. Use 3 inches for return duct and 3 inches for discharge duct. Keep material loose to absorb fan vibration.
· If using return ductwork to the unit, secure it with 3 inches of flexible duct connector.
· Extend discharge duct upward without change in size or direction for at least three fan diameters.
· Use 3-inch flexible duct connection on discharge ductwork.
Note: Compressors and fan assembly are internally isolated. External isolation
devices (spring mounting isolators) are at discretion of a vibration
specialist consulted by building or HVAC system designer.
Run the ductwork straight from the opening for a minimum of three fan diameters. See Figure 9, p. 21. Extend remaining ductwork as far as possible without changing size or direction. Do not make abrupt turns or transitions near the unit due to increased noise and excessive static losses. Use elbows with splitters or turning vanes to minimize static losses.
Poorly constructed turning vanes may cause airflow generated noise. Align the fan outlet properly with the ductwork to decrease noise levels in the duct and to increase fan performance. To complete trunk ductwork to the VAV terminal units, refer to the VAV box manuals for
PKG-SVX029A-EN
specific requirements. Check total external static pressures against fan
characteristics to be sure the required airflow is available throughout the
ductwork.
To achieve maximum acoustical performance, minimize the duct static pressure
setpoint.
Figure 9. Duct connection recommendations
Discharge Duct
3-inch Flexible Duct
3 Fan Diameters
Return Air
Installation Mechanical
1. Install the vent plugs in the economizer coil headers and condenser
manifolds. See Figure 10, p. 21. These plugs ship in a bag with the condenser
drain plugs.
2. Attach the water supply line to the inlet connection, and the return line
to the outlet connection. Entering and leaving water connections for all
condensers are factory manifolded and require only single connections for
entering and leaving water. If the unit has a waterside economizer and/or
control valves, the factory pipes between these components.
3. If using a cooling tower, refer to Figure 11, p. 22 for a typical piping
circuit from the unit.
4. Confirm the water pressure to the unit does not exceed 150 psig.
Note: To prevent water pump damage, design system piping to provide relief
when using energy saving waterside economizer valves.
Figure 10. Economizer coil vent and condenser cleanout/drain plugs
Water Piping
Condenser Connections
WARNING
High Pressure Water!
Failure to follow instructions below could result in death or serious injury,
and equipment damage. Provide relief valve on system water piping to prevent
instantaneous release of high pressure water.
NOTICE
Proper Water Treatment Required!
The use of untreated or improperly treated water could result in scaling,
erosion, corrosion, algae or slime. Use the services of a qualified water
treatment specialist to determine what water treatment, if any, is required.
Trane assumes no responsibility for equipment failures which result from
untreated or improperly treated water, or saline or brackish water.
All field-installed piping must conform to applicable local, state, and
federal codes. To complete condenser water connections follow the procedure
below. Note: Four (4) condenser waterline drain plugs ship in a
bag in the left end of the unit. The installer must field install these four
plugs using pipe thread sealer. An additional plug is provided for units with
a waterside economizer.
PKG-SVX029A-EN
Condensate Drain Connections
Note: Unit is not internally trapped. Installer will need to provide an
external trap for unit to operate properly.
Locate condensate drain on the unit. Connect condensate drain piping to the
1-1/4-inch NPT internal fitting, using at least 7/8-inch OD copper or 3/4-inch
OD iron pipe. Pitch the condensate line downward a minimum of 1/2-inch for
each 10feet of horizontal run, away from the unit. Be sure to install the
condensate drain ptrap drain plug. Before starting the unit, fill the trap
with water to prevent negative pressure in the fan section from impeding
condensate flow.
21
Installation Mechanical
To facilitate drain pipe cleaning, install plugged tees in place of 90°
elbows.
General Waterside Recommendations for Cooling Towers
Cooling tower control affects the unit cycle rates. Condenser water
temperature swings from 10°F to15°F may cause excessive compressor, water
valve, and unit cycling. Set the tower controls to minimize compressor/unit
cycling.
Waterside Piping Arrangements
Install a condenser water pump between the cooling tower (either open or
closed) and the self-contained unit. Lay out the remainder of the system
condenser piping in reverse returns. This helps balance the system by
equalizing the length of supply and return pipes. Multi-story buildings may
use a direct return system with balancing valves at each floor.
Install the supply riser and its return in close proximity. Furnish both with
permanent thermometers to check the waterside balance during start-up and
routine maintenance checks.
Include strainers at each pump inlet and unit. Install drain valves at the
riser base to allow drainage points for system flushing during start-up and
routine maintenance. For condenser draining and header removal, include a
shutoff/ balancing valve on the entering and leaving waterside pipes, drain
tees, and unions of each unit. Note: Unit does not have floor drains.
Figure 11. Condenser water piping components for cooling tower system
Water Temperature Requirements
Do not allow the entering water temperature to go below 54°F (12.2°C) on units
with constant water flow (basic piping).This will cause the compressors to
shutdown and the mechanical cooling function will lockout. The economizer (if
enabled) will continue to function. The compressors will reset when the
entering water temperature reaches 58°F (15°C).
Units with variable water flow (intermediate piping) have a modulating
condensing pressure control valve that allows compressor operation down to
entering water temperatures of 37°F (3°C). Note: Units with a waterside
economizer can be set from
the human interface panel for variable or constant water flow.
Water Piping Verification
· Make return and supply water connections to the unit and/or waterside
economizer piping package with recommended valves and piping components.
· Install unions to allow waterside maintenance.
· Install cooling tower and standby pumps.
· Treat water to prevent algae, slime, and corrosion.
· Prevent refrigerant piping from rubbing against other objects.
Installating the Hydronic Coil
Refrigerant System
Trane Water Cooled Commercial Self-Contained units ship factory charged with
R-454B refrigerant.
22
PKG-SVX029A-EN
Installation – Electrical
Unit Wiring Diagrams
Specific unit wiring diagrams are provided on the inside of the control panel
door. Use these diagrams for connections or trouble analysis.
Supply Power Wiring
It is the responsibility of the installer to provide power supply wiring to
the unit terminal block or the non-fused disconnect switch option. Wiring
should conform to NEC and all applicable code requirements.
Bring the supply wiring through the top of the starter panel. The hole will be
field cut at the electrician’s discretion. Connect the three phase wires to
the power terminal block or the non-fused disconnect switch in the control box
terminals. Refer to specific wiring diagrams and fuse information in the
control panel.
WARNING
Hazardous Service Procedures!
Failure to follow all precautions in this manual and on the tags, stickers,
and labels could result in death or serious injury. Technicians, in order to
protect themselves from potential electrical, mechanical, and chemical
hazards, MUST follow precautions in this manual and on the tags, stickers, and
labels, as well as the following instructions: Unless specified otherwise,
disconnect all electrical power including remote disconnect and discharge all
energy storing devices such as capacitors before servicing. Follow proper
lockout/tagout procedures to ensure the power can not be inadvertently
energized. When necessary to work with live electrical components, have a
qualified licensed electrician or other individual who has been trained in
handling live electrical components perform these tasks.
NOTICE
Use Copper Conductors Only!
Failure to use copper conductors could result in equipment damage as the
equipment was not designed or qualified to accept other types of conductors.
NOTICE
Motor Damage!
Correct phase sequence is critical. If phase sequence of the incoming line
voltage is not correct, it could result in motor damage.
Voltage Range
Voltages must be within ±10% the nameplate voltage. Confirm the unit voltage
is balanced by measuring at the compressor terminals. Voltage imbalance on
three phase systems can cause motor overheating and premature failure. Maximum
allowable imbalance is 2.0 percent.
Voltage Imbalance
Read the voltage at the compressor terminals to determine if it is balanced.
Voltage imbalance on three phase systems can cause motor overheating and
premature failure. The maximum allowable imbalance is 2.0 percent. Voltage
imbalance is defined as 100 times the sum of the deviation of the three
voltages from the average (without regard to sign) divided by the average
voltage. For example, if the three measured voltages are 221, 230, and 227,
the average voltage would be:
(221 + 230 + 227) / 3 = 226 volts
The percentage of voltage imbalance is then: 100 x (226 221) / 226 = 2.2%
Phase Monitor
Unit is equipped with a phase monitor in the control box. The phase monitor
will protect against phase loss, imbalance and reversal of line voltage. If a
fault occurs, the unit will be locked out until the phase is corrected.
Control Power
NOTICE
Component Damage!
Failure to follow instructions below could result in immediate or premature
component failures. Unit transformers are sized to provide power to the unit
only. Do not use these transformers to supply power to field equipment.
In this example, 2.2 percent imbalance is not acceptable. When a voltage
imbalance of more than 2.0 percent exists, check the voltage at the unit
disconnect switch. If the imbalance at the unit disconnect switch does not
exceed 2.0 percent, faulty unit wiring is causing the imbalance. Conduct a
thorough inspection of the unit electrical wiring connections to locate the
fault, and make any repairs necessary.
Access the connection terminal block through the control panel on the upper
left side of the unit. All wiring should conform to NEC and applicable local
code requirements.
Confirm all wiring connections are secure. Reference the unit specific
diagrams inside the control panel. Note: Unit transformers IT1, IT3, IT4 and
IT5 are sized to
provide power to the unit only.
PKG-SVX029A-EN
23
Installation – Electrical
Selection Procedures
· RLA = Rated Load Amps · Compressor LRA = Locked Rotor Amps · Fan Motor LRA =
Locked Rotor Amps, N.E.C. Table
430 -150 · FLA = Full Load Amps, N.E.C. Table 430 -150 · Voltage utilization
range is ±10%
Determine Minimum Circuit Ampacity (MCA)
MCA = 1.25 x largest motor amps/VFD amps (FLA or RLA) + the sum of the
remaining motor amps.
Determine Max Fuse (MFS) and Max Circuit Breaker (MCB) Sizes
MFS and MCB = 2.25 x largest motor amps (FLA or RLA) + the sum of the
remaining motor amps.
For units with the dual power option, there are two electrical circuits that
need calculations using the previous formulas:
· Circuit #1 fans
· Circuit #2 compressors
If the rating value determined does not equal a standard current rating of
over current protective device, use the next lower standard rating for the
marked maximum rating.
Table 8. Electrical service sizing data — motors
Digit 9 – Unit Voltage
460/60/3
Digit 9 4
Tonnage Comp 1
20
7.1
Comp 2 7.1
460/60/3
4
25
9.1
9.1
460/60/3
4
30
11.9
11.9
460/60/3
4
35
12.4
12.4
460/60/3
4
40
12.4
12.4
460/60/3
4
45
15.4
15.4
460/60/3
4
50
15.4
15.4
460/60/3
4
55
19.4
19.4
460/60/3
4
60
20.6
20.6
460/60/3
4
65
20.6
20.6
460/60/3
4
70
24.0
24.0
460/60/3
4
75
32.8
32.8
460/60/3
4
85
32.8
32.8
460/60/3
4
90
32.8
32.8
460/60/3
4
100
38.5
38.5
460/60/3
4
110
38.5
38.5
208-230/60/3
F
20
16.0
16.0
208-230/60/3
F
25
21.2
21.2
208-230/60/3
F
30
24.4
24.4
208-230/60/3
F
35
28.7
28.7
208-230/60/3
F
40
28.7
28.7
208-230/60/3
F
45
33.3
33.3
208-230/60/3
F
50
33.3
33.3
208-230/60/3
F
55
40.8
40.8
208-230/60/3
F
60
45.9
45.9
208-230/60/3
F
65
45.9
45.9
208-230/60/3
F
70
49.0
49.0
208-230/60/3
F
75
62.1
62.1
208-230/60/3
F
85
62.1
62.1
208-230/60/3
F
90
62.1
62.1
Comp 3
7.1 9.1 11.9 11.9 12.4 12.4 15.4 15.4 19.4 20.6 20.6 20.6 24.0 32.8 32.8 38.5
16.0 21.2 24.4 24.4 28.7 28.7 33.3 33.3 40.8 45.9 45.9 45.9 49.0 62.1
Comp 4 Fan FLA Qty Fans
7.1
7.1
1.00
9.1
7.1
1.00
11.9
7.1
2.00
11.9
7.1
2.00
12.4
7.1
2.00
12.4
7.1
2.00
15.4
7.1
3.00
15.4
7.1
3.00
19.4
7.1
4.00
20.6
7.1
4.00
20.6
7.1
4.00
20.6
7.1
4.00
24.0
7.1
5.00
32.8
7.1
5.00
32.8
7.1
6.00
38.5
7.1
7.00
16.0
13.5
1.00
21.2
13.5
1.00
24.4
13.5
2.00
24.4
13.5
2.00
28.7
13.5
2.00
28.7
13.5
2.00
33.3
13.5
3.00
33.3
13.5
3.00
40.8
13.5
4.00
45.9
13.5
4.00
45.9
13.5
4.00
45.9
13.5
4.00
49.0
13.5
5.00
62.1
13.5
5.00
Misc 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 2.00 2.00 2.00 2.00 2.00 2.00 2.00 2.00 2.00 2.00 2.00 2.00 2.00 2.00
MCA 38 47 66 67 68 75 88 97 115 117 124 144 158 176 196 214 84 105 133 142 151 161 184 201 241 251 258 287 307 333
MOP 45 56 77 79 80 90 103 116 135 137 148 177 191 208 234 253 100 127 157 171 179 195 218 242 287 297 307 349 369 395
24
PKG-SVX029A-EN
Installation – Electrical
Table 8. Electrical service sizing data — motors (continued)
Digit 9 – Unit Voltage
208-230/60/3
Digit 9 F
Tonnage Comp 1
100
83.1
Comp 2 83.1
Comp 3 62.1
Comp 4 62.1
208-230/60/3
F
110
83.1
83.1
83.1
83.1
Fan FLA Qty Fans
13.5
6.00
13.5
7.00
Misc 2.00 2.00
MCA 394 450
MOP 477 533
575/60/3
5
20
6.4
6.4
6.4
6.4
5.7
1.00
0.75
34
40
575/60/3
5
25
7.7
7.7
7.7
7.7
5.7
1.00
0.75
39
47
575/60/3
5
30
9.4
9.4
9.4
9.4
5.7
2.00
0.75
52
61
575/60/3
5
35
9.0
9.0
9.4
9.4
5.7
2.00
0.75
51
60
575/60/3
5
40
9.0
9.0
9.0
9.0
5.7
2.00
0.75
50
59
575/60/3
5
45
12.9
12.9
9.0
9.0
5.7
2.00
0.75
59
72
575/60/3
5
50
12.9
12.9
12.9
12.9
5.7
3.00
0.75
73
86
575/60/3
5
55
13.7
13.7
12.9
12.9
5.7
3.00
0.75
75
88
575/60/3
5
60
14.5
14.5
13.7
13.7
5.7
4.00
0.75
84
98
575/60/3
5
65
14.5
14.5
14.5
14.5
5.7
4.00
0.75
85
100
575/60/3
5
70
19.2
19.2
14.5
14.5
5.7
4.00
0.75
96
115
575/60/3
5
75
24.0
24.0
14.5
14.5
5.7
4.00
0.75
107
131
575/60/3
5
85
24.0
24.0
19.2
19.2
5.7
5.00
0.75
122
146
575/60/3
5
90
24.0
24.0
24.0
24.0
5.7
5.00
0.75
131
155
575/60/3
5
100
27.1
27.1
24.0
24.0
5.7
6.00
0.75
144
171
575/60/3
5
110
27.1
27.1
27.1
27.1
5.7
7.00
0.75
156
183
Notes: 1. MCA: Minimum Circuit Ampacity is 125 percent of the largest compressor RLA or Drive input current, plus 100 percent of the other compressor (s) RLA, plus the sum of the condenser fan RLA, plus any other load rated at 1 AMP or more. 2. Maximum Breaker Overcurrent Protection (MOP): 225 percent of the largest compressor RLA or VSD drive Input, plus 100% of the other compressor(s) RLA, plus the sum of the condenser fan Motor/Drive FLA, plus any other load rated at 1 AMP or more. 3. Recommended disconnect switch: 110 percent to 115 percent of the sum of the RLA of the compressors, VSD drive input, fan motor/drive, and controls FLA. 4. RLA: Rated in accordance with UL standard 1995. 5. Local codes may take precedence. 6. Fix speed compressor are across the line starting, the VSD compressors are controlled by VSD drive. Compressors will never start simultaneously. 7. Voltage utilization range is ±10 percent.
Static Pressure Transducer Installation (VAV Units Only)
Supply air static pressure controls the ECM fans. A static pressure bulkhead
connector ships separate in control panel for field installation in the supply
air duct work. Installer is responsible for providing pneumatic tubing.
Transducer Inlet Location
Place bulkhead connector in an area of ductwork that will provide an average
and evenly distributed airflow pattern. Use the following guidelines to
determine an appropriate installation location.
1. Locate static bulkhead connector approximately 2/3 to 3/4 the way down
longest duct run, in an area approximately 10 duct diameters downstream and 2
duct diameters upstream of major interferences, turns, or changes in duct
diameter.
2. When installing pneumatic tubing between head assembly and transducer in
control panel, do not
exceed 250 feet for 1/4-inch OD tubing or 500 feet for 3/8-inch OD tubing.
Installing the Transducer
Use the following procedure to properly install the static pressure
transducer:
1. Connect the pneumatic tubing from the sensing head to the push-on tubing
connection in the control panel. Use a plastic static pickup tubing. Do not
exceed 250 feet for 1/4-inch OD tubing or 500 feet for 3/8-inch OD tubing.
Transducer inside control panel picks up low side or reference pressure. Note:
If plastic tubing pulls away from a connection, trim it
back before replacing it on the fitting. Stretched tubing may leak and cause
faulty control.
PKG-SVX029A-EN
25
Installation – Electrical
Figure 12. Static pressure sensor installation
Static Pressure Head Assembly
Duct
Connector for 1/4-inch Tubing
Connector for 1/4-inch Tubing
Airflow
Note: Place Sensor Inlet Perpendicular to Airflow
Zone Sensor Option used for Discharge Air Reset by Space Temperature
Zone Temperature Sensor, BAYSENS077 (Optional Item)
Figure 13. Zone temperature sensor
This zone sensor includes an internal thermistor and should be mounted in the
zone, Model Number Digit 31=1. This sensor is available for use with all zone
sensor options to provide remote sensing capabilities.
Zone Sensor Installation WARNING
Hazardous Voltage w/Capacitors!
Failure to disconnect power and discharge capacitors before servicing could
result in death or serious injury. Disconnect all electric power, including
remote disconnects and discharge all motor start/run capacitors before
servicing. Follow proper lockout/ tagout procedures to ensure the power cannot
be inadvertently energized. For variable frequency drives or other energy
storing components provided by Trane or others, refer to the appropriate
manufacturer’s literature for allowable waiting periods for discharge of
capacitors. Verify with a CAT III or IV voltmeter rated per NFPA 70E that all
capacitors have discharged.
26
NOTICE
Use Copper Conductors Only!
Failure to use copper conductors could result in equipment damage as the
equipment was not designed or qualified to accept other types of conductors.
Note: For additional information regarding the safe discharge of capacitors,
see Discharging Capacitors in HVAC Systems Service Bulletin (PROD-SVB06*EN).
All sensor options ship in the main control panel and are field installed.
Programmable option installation procedures.
Mounting Location
Mount the sensor on the wall in an area with good air circulation at an
average temperature. Avoid mounting space temperature sensor is areas subject
to the following conditions:
· Drafts or dead spots behind doors or in corners
· Hot or cold air from ducts
· Radiant heat from the sun or appliances
· Concealed pipes and chimneys
· Unheated or non-cooled surfaces behind the sensor, such as outside walls
· Airflows from adjacent zones or other units
To mount the sensors, remove the dust cover and mount the base on a flat
surface or 2-inch x 4-inch junction box. Sensors ship with mounting screws.
Mounting the Subbase
Remove the zone sensor cover from subbase, and mount subbase on the wall or on a 2-inch x 4-inch junction box. Route wires through the wire access hole in the subbase. See Figure 14, p. 27. Seal the hole in the wall behind the subbase.
Notes: ·
·
Guidelines for wire sizes and lengths are shown in Table 9, p. 27. The total resistance of these low voltage wires must not exceed 2.5 ohms per conductor. Any resistance greater than 2.5 ohms may cause the control to malfunction due to excessive voltage drop. Do not run low-voltage control wiring in same conduit with high-voltage power wiring.
Wiring
1. Run wires between the unit control panel and the zone sensor subbase. To
determine the number of wires required, refer to the unit wiring diagrams.
2. Connect the wiring to the appropriate terminals at the unit control panel
and at the zone sensor subbase. In general, zone sensor connections to the
unit use the
PKG-SVX029A-EN
Installation – Electrical
convention of connecting zone sensor terminals to like numbered unit terminals
(1 to 1, 2 to 2).The connection detail is shown on the unit wiring diagrams
located in the unit control panel.
3. Replace the zone sensor cover back on the subbase and snap securely into
place.
Standard Remote Sensor (BAYSENS077)
When using the remote sensor, BAYSENS077, mount it in the space that is to be
controlled. Wire according to the interconnecting wiring diagrams on the unit.
Table 9. Zone sensor maximum lengths and wire size
Distance from Unit to Controller
0-150 feet
Recommended Wiring Size 22 gauge
151-240 feet
20 gauge
241-385 feet
18 gauge
386-610 feet
16 gauge
611-970 feet
14 gauge
Figure 14. Typical zone sensor installation
Mounting Directly to the Wall
Mounting to Junction Box
Junction
PKG-SVX029A-EN
27
Operating Principles
Control Sequences of Operation
Occupied/Unoccupied Switching
There are three ways to switch occupied/unoccupied:
1. Field-supplied contact closure [hardwired binary input to field wiring
terminal block (2TB3)] – This input accepts a field supplied switch or
contacts closure such as a time clock. Open Contacts = Unoccupied and Closed
Contacts = Occupied.
2. BACnet® MSTP control system can control the occupied/unoccupied request of
the unit.
3. Through the TD-7 display via the on-board schedule.
Compressor Lead/Lag
Compressor lead/lag is present in the controls for all units. This is used to
balance the run hours between all the compressors by putting the highest run
hours to run last.
Emergency Stop Input
A binary input is provided on the units field wiring terminal block (2TB3) for
installation of a field-provided switch or contacts to immediately shutdown
all unit functions. An open contact will indicated an emergency shutdown
condition exist and shut down the unit and generate a manual reset alarm. A
closed set of contacts will indicate a normal condition. After the contacts
are closed, the manual reset alarm must be cleared to resume unit operations.
External Auto/Stop Input
A binary input is provided on the unit’s field wiring terminal block (2TB3)
for installation of a field-provided switch or contacts to safely shutdown all
unit functions. An Open contact will indicate a Stop condition exist and the
unit will shutdown and generate an automatic reset alarm. A Closed contact
will indicate an Auto condition and allow the unit to operate.
Local Auto Stop
A binary value is located on the TD-7 which allows the user to start and stop
the unit in a safe manner for maintenance. On the TD-7 home screen in the
upper right hand corner the unit can be put into Auto to perform normally or
Stop to perform a controlled shutdown and keep the unit off.
Head Pressure Control
Water-cooled condensers: Units are ordered with the optional flow control
valves and configured for variable water flow will modulate a water valve to
maintain a userdefined condensing pressure setpoint and compressor refrigerant
pressure differential. Condensing pressure and pressure differential will be
referenced utilizing factory installed suction and discharge pressure sensors
located on each circuit.
28
Water Purge
This user-definable feature allows the user to select a purge schedule to
automatically circulate water through the economizer and condensers
periodically during nonoperational times. This allows fresh chemicals to
circulate in waterside heat exchangers. Note: Only available on units with
condenser valves.
Supply Air Temperature Control Unit Sequence of Operation
Discharge Air High Temp Limit Software Alarm (Software)
When the discharge air temperature is above the discharge air high temperature
cutout setpoint of 100 degrees for 5 minutes, the unit will perform a
controlled shutdown. A Manual Reset alarm will generate and must be cleared
before the unit can resume operating.
Condenser Water Low Temperature Alarm (Software)
When either the entering or leaving condenser water temperature is below the
condenser water low temperature cutout setpoint of 35 degrees for 5 minutes,
the unit will perform a controlled shutdown. All condenser water valves will
be commanded open if installed, and a manual reset diagnostic will be
generated and need to be cleared before the unit can resume operation.
Leaving Air Low Temperature Alarm
When the discharge air temperature is below the discharge air temperature
cutout for 5 minutes, the unit will perform a controlled shutdown. A Manual
Reset alarm will be generated and need to be cleared before the unit can
resume operation.
Occupied Fan Operation
When all alarms are cleared, the unit is occupied, and the local auto stop is
in auto, all fans that are available will start up and operate at 30 percent
speed for 45 seconds. For CV, fans will then release to control to the fan
fixed speed setpoint.
VAV
The fans will then release to control to the duct static pressure setpoint.
The fans will modulate to maintain the duct static pressure at the duct static
pressure setpoint. The fans are commanded off during the unoccupied mode.
Heat/Cool Mode
The unit is in Cooling mode by default. The front end Building Automation
System will switch the Heat/Cool
PKG-SVX029A-EN
Mode request multistate value between the Heating and Cooling modes to get the
desired control.
Cooling/Waterside Economizer
During occupied cooling mode, the waterside economizer option and mechanical
cooling are used to control the supply air temperature. The supply air
temperature setpoint is user defined at the human interface panel.
After the fans run for 5 minutes, and a call for cooling is calculated, the
Cooling Tower/Pump Command is turned ON. After the Condenser Water flow switch
closes proving flow, the Compressors and/or Economizer will be allowed to
start.
Waterside economizing enables when the unit entering water temperature is less
than the entering mixed air temperature. This is set at Waterside Economizer
Enable Offset setpoint. The factory default is 7°F, but can be adjusted by the
user at the TD-7 or via BACnet.
The economizer acts as the first stage of cooling. If the economizer is unable
to maintain the supply air setpoint, the compressor module will bring on the
compressors as required to meet the setpoint. If the unit does not include an
economizer, only mechanical cooling will satisfy cooling requirements.
Thermostatic Expansion Valve
NOTICE
Compressor Damage!
Do not operate with water loops with less than five minutes circulation time
as it could result in poor superheat control and compressor damage.
Refrigerant system reliability and performance is heavily dependent upon
proper superheat. The importance of maintaining the proper superheat cannot be
overemphasized. Accurate measurements of superheat will provide the following
information:
· How well the expansion valve is controlling the refrigerant flow.
· The efficiency of the evaporator coil.
· The amount of protection the compressor is receiving against flooding.
The expected range for superheat is 11-15°F at full load conditions. At part
load, expect a properly adjusted expansion valve to control to 8-12°F
superheat.
Systems operating with lower superheat could cause serious compressor damage
due to refrigerant floodback.
Fan Operation
Multiple, identical fans are arranged in the fan cabinet to meet the customer
airflow and static requirements. Each fan speed, start/stop command, and fault
status are controlled and monitored individually by the unit controller.
However, all fans receive the same fan speed signal to
PKG-SVX029A-EN
Operating Principles
meet airflow and static demand, and all fans are commanded On upon Unit
Controller status transition to Occupied Mode.
Each fan assembly has its own motor with integrated electronically commutated
motor (ECM). Each fan ECM varies the speed of the fan proportional to a 0-10
Vdc signal supplied by the XM90.1 module (and XM30.2 on 85 to 100 units /
XM30.3 on 110 ton units). The ECM starts and stops the fan according to the
Enable/ Disable Binary Output from the XM90.1 module. If the ECM is faulted it
annunciates this via a dry contact that is sensed by the unit controller on
the XM90.1 module (and XM30.2 on 85 to 100 units / XM30.3 on 110 ton units).
Supply Air Static Pressure High Limit
During normal operation, the supply air static is monitored. If at any time
the static pressure exceeds the software high static limit (defaulted at 2.0
inches from the factory) the unit will immediately shut down and generate a
diagnostic.
In order for the unit to resume operation, the Alarm Reset must be toggled
from the TD-7. The software high static limit can be user adjusted at the
TD-7.
Compressors
SWUD uses fixed speed (FS) compressors and a balanced starts routine.
Compressor Oil
All compressors have an Oil Sight Glass. Confirm oil is visible in the sight
glass when the compressor is off or running.
High Pressure Cutout Switch (HPC)
Each FS compressor has an HPC installed in its discharge line. The switch is
set to open at 553 psi +/-15 and re-close at 424 +/-30.
Table 10. Pressure cutouts (open/close)
Unit Model SWUD
High Pressure Cutout
553/424
Low Pressure Cutout
49/74
Note: Update with MSC high pressure cutout. No low pressure cutout for .
On the fixed speed compressors, if an HPC opens, the 24 Vac power that
energizes the compressor start contactor is interrupted and the compressor
will turn off. The unit controller will detect this and lock the circuit out
on a high pressure cutout.
Compressor Pressure Sensors
Each circuit has its own set of suction and discharge pressure sensors. The
sensors are powered by the 5 Vdc power supply 2U1. Their range is 0-600 psig
and their
29
Operating Principles
voltage output is linearly proportional to the sensed pressure.
The discharge pressure sensor is used by the unit controller to do the
following:
· Compute circuit differential pressure.
· Warn the user if a high discharge pressure condition occurs.
The suction pressure sensor is used by the unit controller to do the
following:
· Detect low suction pressures.
· Compute circuit suction superheat.
· Compute circuit differential pressure.
Compressor Suction Temperature
Each circuit has its own suction temperature thermistor. It is used to compute
circuit suction superheat. If superheat is less than 4 degrees for 5 minutes,
or more than 25 degrees for 1 O minutes, the circuit is locked out on a fault
and a diagnostic is annunciated.
Fixed Speed Compressor (FS)
Each FS compressor has two 24 Vac, 30W crankcase heaters. The power for these
heaters is routed through a NC auxiliary contact on it’s respective start
contactor. This way the heater is energized whenever the compressor is Off.
In each FS compressor motor junction box is a 24 Vac powered CoreSenseTM
compressor protection module (MCSP). This module displays compressor status
and diagnostics and provides the following protections:
· Motor temperature protection.
· Missing phase protection.
· Reverse phase protection.
· Low control circuit voltage protection.
· Short cycling detection and alert.
If the CoreSense module detects a fault condition it opens a dry contact on
the module interrupting power to that compressors run contactor coil. The
power interruption is detected by the Unit Controller, which disables the
compressor and annunciates a Compressor Safety Circuit diagnostic. After the
cause of the fault is remedied, a latching fault can be cleared by cycling 24
Vac module power.
Compressor Safety Circuit
Each fixed speed compressor has a Compressor Safety Circuit intended to
protect the circuit from a variety of fault conditions and to distinguish
those failures from HPC trips.
For each FS compressor, 24 Vac power is routed in order from the control power
transformer (CPT) through its respective:
1. HPC
30
2. MCSP dry contact 3. Circuit breaker auxiliary – 1CB1, 1CB2, 1CB3 or 1CB4
4. Start/Stop NO contact on the SymbioTM 500 binary
output module 5. Compressor start contactor coil – 1K1, 1K2, 1K3 or 1K4 6.
From the compressor start contactor coil, the same 24
Vac signal is routed through the contactor NO auxiliary to an isolating relay
– 2K2, 2K4, or 2K8 If any of these devices contacts should open, 24 Vac is
interrupted from the compressor start contactor and the compressor will shut-
off. The unit controller can distinguish between an HPC switch opening and any
of the other devices in the circuit opening. It will annunciate either High
Pressure Cutout Compressor X or Compressor Safety Circuit X.
Compressor Limit Conditions
Because the SWUD uses suction and discharge pressure sensors rather than limit
switches, the Unit Controller can sense when a refrigerant circuit is
approaching a high or low pressure limit condition. Low Pressure Limit
conditions can be caused by the following: · Low discharge air temperature ·
Low airflow · Dirty air filters · TXV malfunction · Low refrigerant charge ·
Faulty suction pressure sensor High Pressure Limit conditions can be caused by
the following: · Low condenser water flow · High entering condenser water
temperature · Fouled entering condenser water strainer · TXV malfunction ·
Refrigerant over charge · Faulty discharge pressure sensor The Unit Controller
TD-7 will annunciate a Limit Condition if an FS compressor circuit enters one.
PKG-SVX029A-EN
Figure 15. Fixed speed compressor protection module (MCSP)
Compressor Staging
Fixed speed compressors cycle to maintain the operating state required by the
temperature controls. In the event of a compressor failure, the next available
compressor turns on. During normal conditions, compressors will not turn on
until they have been off for at least three minutes. Normal operating
conditions are established on an individual compressor basis. When a
compressor starts, its timer also starts.
Compressor Control
Steps of mechanical cooling are control based on supply air or zone
temperature. Compressor staging is based upon a proportional, integrating (PI)
control algorithm.
Waterside Components
Waterside components consist of water piping, water valves, water flow switch
option, water cooled condenser, and the economizer option.
Water Purge
NOTICE
Proper Water Treatment Required!
The use of untreated or improperly treated water could result in scaling,
erosion, corrosion, algae or slime. Use the services of a qualified water
treatment specialist to determine what water treatment, if any, is required.
Trane assumes no responsibility for equipment failures which result from
untreated or improperly treated water, or saline or brackish water. This user-
definable feature allows the user to select a purge schedule to automatically
circulate water through the economizer and condensers periodically during
nonoperational times. This allows fresh chemicals to circulate
PKG-SVX029A-EN
Operating Principles
in waterside heat exchangers. This feature is on all units and is defined at the TD-7.
Water Piping Options
Water piping is factory-installed with left-hand (standard) and right hand
(optional) connections on units.
If equipped, the unit water cooled condenser uses 24 VAC powered water
regulating ball valve to control flow through the condenser. the unit
controller modulates the condenser flow to limit discharge pressure, help
prevent high pressure cutout trips, and maintain a circuit minimum
differential pressure.
The valve can also be used for condenser system chemical purge and condenser
cooling loop system balance.
This option provides condensing temperature control when the unit is
configured (user defined at the HI) for variable water flow with or without a
waterside economizer. A twoway modulating control valve is wired and installed
in the unit to maintains a specific range of water temperature rise through
the condenser when entering fluid temperature is less than 58°F (15°C).This
option allows the compressor to operate with entering fluid temperature down
to 35°F (2°C). The minimum valve position to maintain minimum condenser flow
rates is user-defined at the HI. This valve drives closed if the unit shuts
down or if a power failure occurs.
With Compatible piping configurations, the unit can be set to the following
control schemes at the TD-7.
· Constant water flow or
· Variable water flow
Constant water flow is for condenser pumping systems that are not capable of
unloading the water-pumping system. Variable water flow maximizes energy
saving by unloading the water pumping system.
Water Flow Switch Option
A water flow switch is factory installed in the condenser water pipe within
the unit. Whenever the flow switch detects a water flow loss prior to or
during mechanical cooling, compressor operation locks out and a diagnostic
code displays. If water flow is restored, the compressor operation
automatically restores.
Water-Cooled Condensers
Units that are set up for variable water flow will modulate a water valve to
maintain a user-defined condensing temperature setpoint. Condensing
temperature will be referenced utilizing factory installed sensors located at
each condenser.
Table 11. Condenser water piping connection sizes
Water Pipe (inlet and outlet)
20 to 40 tons
2.50 NPT
45 to 70 tons
3.00 NPT
75 to 110 tons
4.00 NPT
31
Operating Principles
Waterside Economizer Option
The waterside economizer option takes advantage of cooling tower water to
either precool the entering air to aid the mechanical cooling process or, if
the water temperature is low enough, provide total system cooling. Waterside
economizing enables when the unit’s entering water temperature is below the
unit’s entering mixed air temperature by a minimum of 4°F plus the
economizer’s approach temperature. The approach temperature default is 4°F.
Waterside economizing disables when the unit’s entering water temperature is
not below the unit’s entering mixed air temperature by at least the water
economizer approach temperature. The approach temperature defaults to 4°F. The
economizer acts as the first stage of cooling. If the economizer is unable to
maintain the supply air setpoint, the unit control module brings on
compressors as required to meet the setpoint. The waterside economizer
includes a coil, modulating valves, controls, and piping with cleanouts. The
coil construction is ½-inch (13 mm) OD seamless copper tubes expanded into
aluminum fins. The evaporator and economizer coils share a common sloped (IAQ)
drain pan. Drain pan options are either galvanized or stainless steel, and are
insulated and internally trapped. The tubes are arranged in a staggered
pattern to maximize heat transfer. The coil has round copper supply and return
headers with removable clean-out and vent plugs. Figure 16. Waterside
economizer flow control
UNIT
C
WSE
Heat Mode
The BAS HEAT option supports remote heat (hot water coil or electric heat).
When the SWUD Operating Mode is set to BAS HEAT, the unit controller ends any
Cooling Mode operation (Mechanical and/or Water Side Economizer) and
transitions to control Discharge Air Temperature to the BAS HEAT setpoint
temperature. The unit controller does this by opening and closing the heating
ball valve or staging the electric. The Fan Array is controlled normally to
maintain static pressure to the Static Pressure Setpoint.
32
If the Discharge Air Temperature exceeds 104°F a Manually Resettable High
Discharge Air Temperature Diagnostic is annunciated.
Dirty Air Filter Sensor Option
A factory installed differential pressure sensor senses the pressure
differential across the filters. When the differential pressure exceeds a user
selectable setting will display a diagnostic. The unit will continue to run
until you replace the air filters.
Supply Air Static Pressure High Limit
During normal operation, the Supply Air Static is monitored. If at any time
the static pressure exceeds the software high static limit (defaulted at 2.0
inches from the factory) the unit will immediately shut down and generate a
diagnostic.
In order for the unit to resume operation, the Alarm Reset must be toggled
from the TD-7. The software high static limit can be user adjusted at the
TD-7.
Airside Components
Two-Position Damper Interface
Units with two-position damper ventilation interface are equipped with the
necessary control sequences to allow opening of a two-position outdoor air
damper to deliver ventilation air to the return air stream of the unit.
When the unit is in the occupied mode and the supply fans are running, a
binary output will turn on sending 24 Vac to the two-position damper to allow
ventilation air into the unit.
Airside Economizer Interface with OA Reference
Units with airside economizer interface are equipped with the necessary
control sequences to allow using outside air for the first stage of cooling,
in occupied or unoccupied mode and when ambient conditions are favorable for
economizing. Inherent in the unit controller is the ability to suppress the
setpoint below the normal unit setpoint. This allows the building to improve
comfort levels when possible, and at the same time, optimize building
mechanical cooling operation for peak operating efficiency. An outside air
temperature and relative humidity sensor are field sourced and installed.
Economizer operation enables when the outside air enthalpy is less than 25
BTU’s/lb. (adjustable 19 to 28 BTU’s/lb). During occupied mode, the outside
air damper opens to 15 percent (adjustable 0 to 50%) for ventilation purposes.
An analog 2 to 10 Vdc output is provided to modulate the field-provided and
installed damper actuators.
Airside Economizer Interface with Comparative Enthalpy
Units with airside economizer interface and comparative enthalpy are equipped
with the necessary control
PKG-SVX029A-EN
sequences to allow using outside air for the first stage of cooling, in occupied or unoccupied mode and when ambient conditions are favorable for economizing. Inherent in the unit controller is the ability to suppress the setpoint below the normal unit setpoint. This allows the building to improve comfort levels when possible, and at the same time, optimize building mechanical cooling operation for peak operating efficiency. Outdoor and Return Air
Operating Principles
temperature and relative humidity sensors are field sourced and installed.
Economizer operation enables when the outside air enthalpy is 3 BTU’s/lb. less
than the return air enthalpy. During occupied mode, the outside air damper
opens to 15 percent(adjustable 0 to 100%) for ventilation purposes. An analog
2 to 10 Vdc output is provided to modulate the field provided and installed
damper actuators.
PKG-SVX029A-EN
33
Controls
Unit Controller
The SWUD uses the SymbioTM 500 control platform for monitoring and control. XM
expansion modules are used to expand the Symbio 500 I/O capabilities.
In the control panel, the following modules are used:
· Symbio 500
· TD-7
· XM90.1 · XM30.2 · XM30.3 · XM30.4 Note: The number after the dot in the name
(example:
XM30.#) is the IMC bus address, which is set using the rotary switches on the
module.
34
PKG-SVX029A-EN
Table 12. Points list
Hardware Connection BO1
BO2
BO3
BO4
BO5
BO6
BO7
BO8
BO9
AI1
Symbio 500
AI2
(Requires 50VA
AI3
Transformer)
AI4
AI5
UI1
UI2
BI1
BI2
BI3
AO1/BI4
AO2/BI5
PI1
PI2
Point Name Cooling Tower Pump Request Unit Alarm Output Command
VAV Box Command Open Compressor 1 Command Compressor 2 Command Compressor 3
Command Compressor 4 Command Supply Fan Start Stop Command Supply Fan Start
Stop Command 2 Discharge Air Temperature Return Air Temperature Local
Condenser Water Entering Temperature Condenser Water Leaving Temperature
Evaporator Coil Leak Detector Signal
Occupancy Input Space Tempertaure Sensor
Emergency Stop Circuit 1 High Pressure Cutout Circuit 2 High Pressure Cutout
Ventilation Input Status Outdoor Air Damper Command
Duct Static Pressure Local Air Filter Differential Pressure
Controls
Point Setup Open = Off, Closed = On Open Normal, Closed = Alarm Open =Normal
Operation, Closed = Drive Max Position Open = Off, Closed = On Open = Off,
Closed = On Open = Off, Closed = On Open = Off, Closed = On Open = Off, Closed
= On Open = Off, Closed = On 10k Ohm Resistor Trane Type 2 10k Ohm Resistor
Trane Type 2 10k Ohm Resistor Trane Type 2 10k Ohm Resistor Trane Type 2 Open
= Normal, Closed = Leak Open = Unoccupied, Closed = Occupied 10k Ohm Resistor
Trane Type 2 Open = Normal, Closed = Emergency Stop Open = Alarm, Closed =
Normal Open = Alarm, Closed = Normal Open = Normal, Closed = Ventillation Mode
2 vdc = 0%, 10 vdc = 100% Honeywell Pressure Sensor Honeywell Pressure Sensor
PKG-SVX029A-EN
35
Controls
Table 12. Points list (continued)
Hardware Connection
BO1
BO2
BO3
BO4
BO5
BO6
BO7
BO8
UI1
UI2
UI3
UI4
UI5
UI6
XM9.1 (Requires 50VA
Transformer)
UI7 UI8 UI9 UI10
UI11
UI12
UI13
UI14
UI15
UI16
AO1/UI17
AO2/UI18
AO3/UI19
AO4/UI20
AO5/UI21
AO6/UI22
AO7/UI23
AO8/UI24
AO1/UI1
XM30.2 XM30.3
AO2/UI2 AO3/UI3 AO4/UI4 AO1/UI1 AO2/UI2 AO3/UI3 AO4/UI4
AO1/UI1
XM30.4
AO2/UI2 AO3/UI3 AO4/UI4
Point Name Heat Output 1 Heat Output 2 Heat Output 3 Outdoor Air Damper (2
Position) Supply Fan Status Output
— — — Compressor 1 Safety Circuit Status Compressor 2 Safety Circuit Status
Compressor 3 Safety Circuit Status Compressor 4 Safety Circuit Status Circuit
1 Suction Temperature Circuit 1 Discharge Pressure Sensor Circuit 1 Suction
Pressure Sensor Circuit 2 Discharge Pressure Sensor Circuit 2 Suction Pressure
Sensor Circuit 2 Suction Temperature Supply Fan 1 ECM Fault Supply Fan 2 ECM
Fault Supply Fan 3 ECM Fault Supply Fan 4 ECM Fault Condenser Water Flow
Switch External Auto Stop Input Status Compressor Coil Leak Detector Signal
Supply Fan 1 Speed Command Supply Fan 2 Speed Command Supply Fan 3 Speed
Command Supply Fan 4 Speed Command Condenser Water Valve Heating Output 1
Command Phase Monitor Status Supply Fan 5 ECM Fault
Supply Fan 5 Speed Command Supply Fan 6 ECM Fault
Supply Fan 6 Speed Command Supply Fan 7 ECM Fault
Supply Fan 7 Speed Command — —
Outdoor Air Temperature Local
Outdoor Air Relative Humidity Local Return Air Humidity Local
Mixed Air Low Temperature Cutout Alarm
Point Setup Open = Off, Closed = On Open = Off, Closed = On Open = Off, Closed
= On Open = Off, Closed = On Open = Off, Closed = On
— — — Open = Circuit Open, Closed = Circuit Closed Open = Circuit Open, Closed
= Circuit Closed Open = Circuit Open, Closed = Circuit Closed Open = Circuit
Open, Closed = Circuit Closed 10k Ohm Resistor Trane Type 2 0.5 Vdc = 0 PSI,
4.5Vdc = 667 PSI 0.5 Vdc = 0 PSI, 4.5Vdc = 667 PSI 0.5 Vdc = 0 PSI, 4.5Vdc =
667 PSI 0.5 Vdc = 0 PSI, 4.5Vdc = 667 PSI 10k Ohm Resistor Trane Type 2 Open =
Normal, Closed = Fault Open = Normal, Closed = Fault Open = Normal, Closed =
Fault Open = Normal, Closed = Fault Open = No Flow, Closed = Flow Open = Auto,
Closed = Exterior Stop Open = Normal, Closed = Leak 0 vdc = 0%, 10 vdc = 100%
0 vdc = 0%, 10 vdc = 100% 0 vdc = 0%, 10 vdc = 100% 0 vdc = 0%, 10 vdc = 100%
0 vdc = 0%, 10 vdc = 100% 0 vdc = 0%, 10 vdc = 100% Open = Fault, Closed =
Normal
Open = Normal, Closed = Fault (only on units 85 tons and above)
0 vdc = 0%, 10 vdc = 100% Open = Normal, Closed = Fault
0 vdc = 0%, 10 vdc = 100% Open = Normal, Closed = Fault (only on 110 ton
units)
0 vdc = 0%, 10 vdc = 100% — —
10k Ohm Resistor Trane Type 2 (only on units with economizer interfaces)
4 ma = 0, 20 ma = 100% 4 ma = 0, 20 ma = 100%
Open = Alarm
36
PKG-SVX029A-EN
Controls
Navigating the TD-7
TD-7 Home Screen
To access the TD-7 home screen, press the Home button in the upper left of the
screen.
Screen Element
A B C D E F G H
I
J
Description
Home button
Displays the local Auto Stop button and displays the occupancy, Heat/Cool
Mode, and Unit Information.
Displays information about the Air Filter.
Displays the Discharge Air Temperature, Setpoint, and Return Air Temperature.
A red light displays if the sensor fails.
Displays when cooling is active and indicates the % of cooling capacity
currently utilized. The Water Side Econ Info tile is included on units with an
economizer installed. Displays a snapshot of economizer operations and the
mode of the economizer. Displays fan status (on, off), duct static pressure
setpoint and actual, and fan percentage. Compressor 1 is always the lead
compressor. This tile displays the compressor pressures, superheat, VFD
signal, condenser water values (if included), and operating mode. Tiles for
compressors 2-4 display, depending on the number of compressors installed. The
VFD compressor is always the lead compressor. The fixed speed compressors
rotate to even out run time. Compressor tiles displays the compressor
pressures, superheat, VFD signal, condenser water values (if included), and
operating mode. Displays the entering and leaving temperatures, pump command,
flow status, and the condenser alarm status.
TD-7 Reports
Unit Status Report
The Unit Status report provides an overview of how the unit is running and
includes all available points that were predefined for the unit. To access the
Unit Status report: 1. Press the Reports button at the bottom of the screen.
2. Press Unit Status button. Use the up and down arrows in the bottom right to
scroll through the report. Figure 17. Unit status report
All Points Report
The All Points report provides details for all points for a unit. To access
the All Points report: 1. Press the Reports button at the bottom of the
screen. 2. Press the All Points Report button. Use the up and down arrows in
the bottom right to scroll through the report.
Figure 18. All points report
Starting the Unit
Before starting the unit, confirm: · All checks are complete · Alarms are
cleared · Compressors that you want to run are made available
or locked out.
Local Auto/Stop Value
The Local Auto/Stop Value is used to stop by unit in a safe manner either
locally in Tracer TU or at the TD-7 display. The factory default is set to
Auto. 1. Navigate to the Home screen. 2. In the upper left tile, press the
arrow next to either Stop
or Auto. 3. To stop the unit, press the Stop button, or to put the
unit in Auto default mode, press Release Override.
PKG-SVX029A-EN
37
Controls
Figure 19. Local Auto/Stop
Figure 20. Stop or release override
Setpoint Adjustments
This section details control setpoints that can be modified from factory
defaults and how to modify those setpoints.
Unit Setpoints
Table 13. Unit setpoints that can be modified in the TD-7
Setpoint Name
Condenser Purge Time (on units with condenser valves only)
Description
The amount of time (in minutes) that the compressor will open its condenser
valve during purge mode when the unit is not operating.
Factory Default 20 minutes
Discharge Air Cooling Setpoint BAS
Used as the cooling setpoint on fixed setpoint units and on units that reset their discharge air temperature setpoint as the low value in the reset equation. This value should be set to the desired temperature needed for startup.
55°F
Discharge Air Cooling Setpoint Max BAS (reset DAT units only)
Discharge Air Heating Setpoint BAS (Units with Heat Only)
Discharge Air Low Temperature Cutout
Duct Static Pressure Setpoint BAS
Duct Static Pressure Safety Lockout
Dirty Air Filter DP
Occupied Offset (DAT Reset Units Only)
Occupied Standby Offset (DAT Reset Units Only)
Sets the upper limit in the Reset Equation in Cooling Mode. This value can be
adjusted to the desired maximum setpoint the discharge air should reach during
cooling mode.
Used as the heating setpoint when the unit is in heating mode. This value
should be set to the desired temperature needed for startup.
Value that triggers a diagnostic when the discharge air temperature is below
this value for 10 minutes. This value can be adjusted to the desired low air
temperature, which triggers the diagnostic.
The duct static pressure setpoint is set by the analog value named duct static
pressure setpoint BAS. This value should be set to the desired pressure needed
for startup.
Shuts down the unit if the duct static exceeds this setpoint. It should be set
to the desired pressure needed for startup. Generates a diagnostic for a dirty
air filter when the differential pressure exceeds the setpoint. Determines the
occupied cooling and heating setpoints when the unit resets the discharge air
temperature off either return or space temperature.
Determines the occupied cooling and heating setpoints when the unit resets the
discharge air temperature off either return or space temperature and is the
occupied standby mode.
65°F 90°F 35°F
1 in (H2O) 2 in (H2O) 10 in (H2O)
2°F 4°F
Space Temperature Setpoint BAS (DAT Reset by Space Temp Air Units Only)
Sets the space setpoint when the unit is selected to do discharge air reset based off the space temperature. This value is used to determine the occupied heating and cooling temperatures which reset the discharge air temperature setpoint.
72°F
38
PKG-SVX029A-EN
Controls
Table 13. Unit setpoints that can be modified in the TD-7 (continued)
Setpoint Name
Description
Factory Default
Return Temperature Setpoint BAS (DAT Reset by Return Temp Air Units Only)
Sets the return setpoint when the unit is selected to do discharge air reset based off the return temperature. This value is used to determine the occupied heating and cooling temperatures which reset the discharge air temperature setpoint.
72°F
Water Side Economizer Enable Offset (Units with Water Side Economizer Only)
The temperature that the condenser entering water must be below the return air temperature before it will enable the economizer.
7°F
Water Side Economizer Sample Time (Units with Water Side Economizer Only)
Time that the controller will sample the water temperature for and compare it against the return air temperature to determine if the economizer can be enabled.
2 minutes
To modify any of the setpoints in the table above:
1. Press Reports at the bottom of the screen. 2. Press the Unit Setpoints
button. 3. On the Setpoint report, locate the point in the menu.
Use the arrows to scroll through the report if needed.
4. Use the up and down arrows to change the value, or press inside the box
and type in the desired setpoint.
5. Press Save.
Unit Setup
Table 14. Unit setup setpoints that can be modified in the TD-7
Setpoint Name Condenser Control % of Design
Condenser Tee Strainer Sensor Calibration
Condenser Purge Status (On Units with Condenser Valves Only)
Description
Percent of the condenser pressure design the unit will control to and is user
adjustable between 50-100%. The condenser water tee high and low pressure
sensor can be calibrated to match the gauge readings or recorded readings by
the balancer.
Each compressor has its own condenser purge status value which indicates when
the condenser valve is open in the purge mode. It can also be used to manually
initiate the purge mode for each compressor.
Factory Default
90%
0
Off
Condenser Water Flow Type (On Units with Condenser Valves Only)
Indicates if the unit is a constant or variable volume flow type unit. Even with the condenser water regulating valves installed on each compressor, the flow type can be changed. When the flow is changed from variable flow to constant flow, the water regulating valve will open to its maximum position when the unit is occupied. This can be done for constant volume flow systems that do not include a VFD Pump.
Variable flow
Water Side Economizer Lockout BAS (Units with Water Side Economizer Only)
Compressor Lockout BAS
Fan Lockout BAS
The water side economizer can be locked out by the controls system.
Each compressor can be locked out individually by the controls system. Each
fan can be locked out individually by the controls system. Fans should be made
available prior to startup.
Available Available Available
To modify any of the setpoints in the table above: 1. Press Reports at the
bottom of the screen. 2. Press the Unit Setup button. 3. On the Setup report,
locate the point in the menu. Use
the arrows to scroll through the report if needed. 4. Use the up and down
arrows to change the value, or
press inside the box and type in the desired setpoint. 5. Press Save.
Reports
To access Alarms, press the Alarms button in the lower left corner of the
screen. If the Alarm tab is not blinking red, there are no alarms present.
Figure 21. Alarms tab
Compressor Alarms
If there is a compressor alarm, it will need to be manually reset after it is
resolved. Each compressor needs to be reset manually:
1. Press Reports at the bottom of the display. 2. Press Unit Setup. 3. In the
Setup report, locate the appropriate point. Use
the arrows to scroll through the report if needed.
4. Select the specific compressor.
5. Change the value from Normal to Reset. 6. Press Save. The point will
automatically revert to its
default setting (Off).
Fan Alarms
If there is a fan alarm, it will need to be manually reset after it is
resolved. There is one fan reset for the entire wall fan.
PKG-SVX029A-EN
39
Controls
1. Press Reports at the bottom of the display. 2. Press Unit Setup. 3. In the
Setup report, press Supply Fan Failure Reset.
Use the arrows to scroll through the report if needed. 4. Press Reset. 5.
Press Save. 6. When you want the fan to be available, press the
Release Override button in the top left.
General Alarms
General alarms are alarms that are not tied to fans or compressors. They
require a manual reset, and there is one alarm reset for these alarms. To
reset a general alarm: 1. Press Reports at the bottom of the display. 2. Press
Unit Setup. 3. In the Setup report, press Alarm Reset. Use the
arrows to scroll through the report if needed. 4. Press Reset. 5. Press Save.
Water Purge
NOTICE
Proper Water Treatment Required!
The use of untreated or improperly treated water could result in scaling,
erosion, corrosion, algae or slime. Use the services of a qualified water
treatment specialist to determine what water treatment, if any, is required.
Trane assumes no responsibility for equipment failures which result from
untreated or improperly treated water, or saline or brackish water.
During the unoccupied mode, water-cooled units will periodically circulate
water through the condensers and waterside economizer if the user has enabled
the purge function at the HI. The water purge function circulates water to
introduce fresh water-treatment chemicals and help prevent water stagnation.
The number of hours between each periodic purge, or purge duration, is
userdefined at the HI between 1-999 hours. If the periodic purge timer expires
while the unit is in occupied mode, it will wait for the next available
unoccupied time before initiating water purge.
Contrary, if a request for cooling occurs during a purge sequence, purge will
terminate and cooling will commence.
40
PKG-SVX029A-EN
Pre-Startup
Before starting up units, perform the following procedure to confirm proper
unit operation.
Pre-Startup Checklist
Complete this checklist after installing unit to verify all recommended
installation procedures are complete before start-up. This does not replace
the detailed instructions in the appropriate sections of this manual. Always
read the entire section carefully to become familiar with the procedures.
Supply Fan
Confirm the fan rotates freely.
Ductwork
· Confirm trunk ductwork to VAV boxes is complete and secure to prevent leaks.
· Verify that all ductwork conforms to NFPA 90A or 90B and all applicable
local codes.
Water-Cooled Unit Piping
Verify condensate drain, water piping drain plugs, economizer header, strainer
pressure transducers, and condenser vent plug are installed.
Units with Hydronic Heat
Verify the entering water temperature sensor is installed upstream of the
hydronic coil.
Electrical
Verify electrical connections are tight.
Components
· Verify liquid line service valve, and suction and discharge service valves
if present, are open at startup. Note: Each compressor suction line contains a
low pressure sensor that will shut the compressor down in low pressure
situations.
· Confirm system components are properly set and installed.
PKG-SVX029A-EN
41
Start-Up
WARNING
Live Electrical Components!
Failure to follow all electrical safety precautions when exposed to live
electrical components could result in death or serious injury. When it is
necessary to work with live electrical components, have a qualified licensed
electrician or other individual who has been properly trained in handling live
electrical components perform these tasks.
NOTICE
Compressor Damage!
Failure to follow instructions below will cause the compressor to operate in a
vacuum and result in compressor damage. Never manually or automatically pump
down system below 7 psig.
NOTICE
Compressor Damage!
Failure to follow instructions could result in compressor damage. Keep
crankcase heaters on whenever refrigerant is in the system. If crankcase
heaters have not been on with refrigerant in the system, turn the crankcase
heaters on for a minimum of 24 hours before starting compressors.
To start the unit, complete the following steps in order.
Review “Refrigerant System,” p. 22, if applicable. Confirm all steps were
completed.
Final Refrigerant Charge
If full charge was not used during installation, follow these steps:
1. Determine remaining charge required by subtracting charge added during
“Refrigerant System,” p. 22 from the total.
2. With all circuit compressors running, SLOWLY meter remaining R-454B into
the suction line from the LIQUID charging connection.
NOTICE
Compressor Damage!
Overcharging system could result in compressor failure and/or reduced
compressor life. Do not overcharge system. Excessive refrigerant charging can
cause compressor liquid slugging at startup, and conditions where compressors
and/or condenser fans short cycle.
42
NOTICE
Compressor Damage!
Failure to follow instructions below could result in compressor failure and/or
reduced compressor life. To prevent compressor liquid slugging, only add
liquid in the suction line when the compressor is running. Use extreme caution
to meter liquid refrigerant into the suction line slowly. If liquid is added
too rapidly, compressor oil dilution and oil pumpout could occur.
3. Use an accurate scale to measure and record amount of R-454B added.
4. After unit has been operating for approximately 30 minutes at full load,
measure and record operating pressures.
5. Repeat for other circuits.
6. Confirm, and adjust charge, if necessary, by checking subcooling at AHRI
340/360 full load operating conditions (80°/67°F db/wb entering evaporator,
~300 cfm/ton, 85°/95°F EWT/LWT).
Some TXV superheat adjustment may be necessary, but only, after adequate
subcooling has been reached. Note: Water-cooled subcooling should be 10.5°F to
12.5°F.
Start-Up Procedure
Using the start-up log on the following pages, establish nominal conditions
for consistent measurements as follows:
· Leaving air greater than 60°F
· Entering air temperature = 70 to 90°F
· Entering water temperature > 60°F
With all compressors running at full load:
1. Compute superheat from the suction line pressure and temperature at the
compressor on each circuit. Adjust the thermal expansion valve settings if
necessary. Superheat should be between 14°F and 20°F.
2. Inspect refrigerant flow in the liquid line sight glass. Flow should be
smooth and even, with no bubbles once the system has stabilized. Note: Sight
glass moisture indicator may show caution or wet at start-up. May need up to
12 hours of operation for system to reach equilibrium and correctly show
moisture.
Normal startup will occur provided Tracer® Summit is not controlling the
module outputs or the generic BAS is not keeping the unit off. To prevent
Tracer Summit from affecting unit operation, remove Tracer wiring and make
required changes to setpoint and sensor sources.
PKG-SVX029A-EN
Operating and Programming Instructions
See IntelliPakTM Commercial Self-Contained Signature Series 20 to 110 Ton,
Modular Series 20 to 35 Ton Programming Guide (PKG-SVP01*-EN) for available
unit operating setpoints and instructions. A copy ships with
Unit:
Unit Location:
Unit Voltage
Start-Up
each unit. For units with VFD option, see installer guide that ships with each
VFD.
Start-Up Log
Evaporator fan motor horsepower:
Evaporator fan motor amps:
Evaporator fan rpm (actual):
Evaporator system static (from test and balance report or actual readings)
Evaporator system cfm (test and balance sheet or actual tested):
Evaporator Supply duct static:
Return duct static:
Dry-bulb °F: Wet-bulb °F:
Evaporator Air Conditioners (with all compressor operating)
Entering
Leaving
Dry-bulb °F:
Wet-bulb °F:
Entering water temp °F
Leaving water temp °F
Entering water pressure psig
Leaving water pressure psig
Circuit A
Water-Cooled Units Circuit B
Circuit C
Circuit D
PKG-SVX029A-EN
43
Maintenance
Service Access
All service accessible areas are provided with hinged doors that allow doors
to swing open or be removed completely.
To use as a hinge, simply open hinge handle, depress Y latch and swing door
open.
To remove completely, open hinge handle and depress Y latch on back side of
hinge. Work door off of unit being careful to not drop door.
Note: Evaporator door is 75 lbs and requires two-man lift to remove safely.
Access unit controls through the front. The panel is secured with two quick
release hinges. Hinged panels allow access to the fans and also the compressor
and condensers. Hinges also allow for complete removal of panel. Left and
right hinges allow for access to evaporator section and also allow for
removable of the entire panel. Expansion valves and filter driers are easily
accessible from here. Filters are accessible via a hinged panel.
Power is accessible through a hinged door on the unit (left hand is standard
and right hand is optional). Hinge also allows for panel to be removed.
Air Filters
WARNING
Hazardous Voltage w/Capacitors!
Failure to disconnect power and discharge capacitors before servicing could
result in death or serious injury.
Disconnect all electric power, including remote disconnects and discharge all
motor start/run capacitors before servicing. Follow proper lockout/ tagout
procedures to ensure the power cannot be inadvertently energized. Verify with
a CAT III or IV voltmeter rated per NFPA 70E that all capacitors have
discharged.
Filter access doors are shared with the evaporator cassette access door. To replace throwaway filters, remove the dirty elements and install new filters with the filter directional arrows pointing toward the fan. Verify no air bypasses the filters. See Table 15, p. 44 for proper filter placement.
Table 15. Unit filter sizes
Unit size
Qty
Filter size
20 to 35
9
40 to 60 65 to 85
12 20 x 24 inches
15
90 to 110
21
Inspecting and Cleaning the Drain Pan
Check the condensate drain pan and drain line to confirm the condensate drains
properly at least every six months or as dictated by operating experience.
If evidence of standing water or condensate overflow exists, take steps to
identify and remedy the cause immediately. Refer to the “Troubleshooting,” p.
52 for possible causes and solutions.
WARNING
Hazardous Voltage w/Capacitors!
Failure to disconnect power and discharge capacitors before servicing could
result in death or serious injury. Disconnect all electric power, including
remote disconnects and discharge all motor start/run capacitors before
servicing. Follow proper lockout/ tagout procedures to ensure the power cannot
be inadvertently energized. For variable frequency drives or other energy
storing components provided by Trane or others, refer to the appropriate
manufacturer’s literature for allowable waiting periods for discharge of
capacitors. Verify with a CAT III or IV voltmeter rated per NFPA 70E that all
capacitors have discharged.
Clean drain pans using the following procedure:
1. Disconnect all electrical power to the unit.
2. Don the appropriate personal protective equipment (PPE).
3. Remove all standing water.
4. Use a scraper or other tools to remove and solid matter. Remove solid
matter with a vacuum device that utilizes high efficiency particulate
arrestance (HEPA) filters with a minimum efficiency of 99.97% at 0.3 micron
particle size.
5. Thoroughly clean the contaminated area(s) with a mild bleach and water
solution or an EPA-approved sanitizer specifically designed for HVAC use.
Carefully follow the sanitizer manufacturer’s instructions regarding product
use.
6. Immediately rinse the drain pan thoroughly with fresh water to prevent
potential corrosion from the cleaning solution.
7. Allow the unit to dry thoroughly before putting the system back into
service.
8. Properly dispose of all contaminated materials and cleaning solution.
44
PKG-SVX029A-EN
Compressors
Scroll Compressor Failure Diagnosis and Replacement
If compressor failure is suspected, refer to CSHD and CSHN/CSHL Compressors
Installation and Service Installation Instructions (COM-SVN01*-EN) for
detailed information regarding compressor failure diagnosis and replacement of
scroll compressors.
Refrigerant System
If refrigerant system repair is required, Leak Test, Brazing and Evacuation
Procedures are described. Preliminary charging is described in the
Installation Mechanical section, “Refrigerant System,” p. 22 and final
charging is described in the Start-Up section, “Final Refrigerant Charge,” p.
42. Refrigerant systems that have been opened must have filter driers replaced
and complete leak test and evacuation before recharging. Unit is equipped with
replaceable filter core option for easy maintenance.
Refrigerant Leak Test Procedure
WARNING
Confined Space Hazards!
Failure to follow instructions below could result in death or serious injury.
Do not work in confined spaces where refrigerant or other hazardous, toxic, or
flammable gas may be leaking. Refrigerant or other gases could displace
available oxygen to breathe, causing possible asphyxiation or other serious
health risks. Some gases may be flammable and/or explosive. If a leak in such
spaces is detected, evacuate the area immediately and contact the proper
rescue or response authority.
WARNING
Explosion Hazard!
Failure to follow safe leak test procedures below could result in death or
serious injury or equipment or property-only-damage. Never use an open flame
to detect gas leaks. Use a leak test solution for leak testing.
PKG-SVX029A-EN
Maintenance
WARNING
Explosion Hazard!
Failure to follow these instructions could result in death or serious injury
or equipment or property-only damage. Use only dry nitrogen with a pressure
regulator for pressurizing unit. Do not use acetylene, oxygen or compressed
air or mixtures containing them for pressure testing. Do not use hydrogen
mixtures containing refrigerant and air above atmospheric pressure for
pressure testing as they may become flammable and could result in an
explosion. Refrigerant, when used as a trace gas should only be mixed with dry
nitrogen for pressurizing units.
WARNING
Explosion Hazard!
Failure to follow instruction below could result in death or serious injury.
Do not exceed unit nameplate design pressures when leak testing system.
WARNING
Refrigerant under High Pressure!
Failure to follow instructions below could result in an explosion which could
result in death or serious injury or equipment damage. System contains
refrigerant under high pressure. Recover refrigerant to relieve pressure
before opening the system. See unit nameplate for refrigerant type. Do not use
non-approved refrigerants, refrigerant substitutes, or refrigerant additives.
Note: These service procedures require working with refrigerant. Do not
release refrigerant to the atmosphere. The service technician must comply with
all federal, state, and local laws.
When leak-testing refrigerant systems, observe all safety precautions. Leak
test only one circuit at a time to minimize system exposure to potentially
harmful moisture in the air.
System Repair
1. Connect R-454B refrigerant cylinder to charging port, add refrigerant to
reach pressure of 12 to 15 psig.
2. Disconnect refrigerant cylinder. Connect dry nitrogen cylinder to high
side charging port and increase pressure to 150 psig. DO NOT exceed unit
nameplate design pressures. If testing complete system, low side design
pressure is maximum.
3. Check piping and/or components as appropriate for leaks.
4. Recommend using electronic detector capable of measuring 0.1 oz/year leak
rate.
5. If a leak is located, use proper procedures to remove
45
Maintenance
the refrigerant/nitrogen mixture, break connections and make repairs. Retest
for leaks.
6. Confirm all service valves are open.
Brazing Procedures
WARNING
Explosion Hazard and Deadly Gases!
Failure to follow all proper safe refrigerant handling practices could result
in death or serious injury. Never solder, braze or weld on refrigerant lines
or any unit components that are above atmospheric pressure or where
refrigerant may be present. Always remove refrigerant by following the
guidelines established by the EPA Federal Clean Air Act or other state or
local codes as appropriate. After refrigerant removal, use dry nitrogen to
bring system back to atmospheric pressure before opening system for repairs.
Mixtures of refrigerants and air under pressure may become combustible in the
presence of an ignition source leading to an explosion. Excessive heat from
soldering, brazing or welding with refrigerant vapors present can form highly
toxic gases and extremely corrosive acids.
Proper brazing techniques are essential when installing refrigerant piping.
The following factors should be kept in mind when forming sweat connections:
1. When heating copper in the presence of air, copper oxide forms. To prevent
copper oxide from forming inside the tubing during brazing, sweep an inert
gas, such as dry nitrogen, through the tubing. A nitrogen flow of 1 to 3 cubic
feet per minute is sufficient to displace the air in the tubing and prevent
oxidation of the interior surfaces. Use a pressure regulating valve or flow
meter to control the flow.
2. Confirm the tubing surfaces requiring brazing are clean, and that the tube
ends are carefully reamed to remove any burrs.
3. Confirm the inner and outer tubes of the joint are symmetrical and have a
close clearance, providing an easy slip fit. If the joint is too loose, the
connection tensile strength is significantly reduced. Confirm the overlap
distance is equal to the inner tube diameter.
4. Wrap each refrigerant line component with a wet cloth to keep it cool
during brazing. Excessive heat can damage the internal components. Note: Use
40-45% silver brazing alloy (BAg-7 or BAg28) on dissimilar metals. Use BCup-6
brazing alloy on copper-to-copper joints.
5. If using flux, apply it sparingly to the joint. Excess flux will
contaminate the refrigerant system.
6. Apply heat evenly over the length and circumference of the joint.
7. Begin brazing when the joint is hot enough to melt the brazing rod. The
hot copper tubing, not the flame,
46
should melt the rod.
8. Continue to apply heat evenly around the joint circumference until the
brazing material is drawn into the joint by capillary action, making a
mechanically sound and gas-tight connection.
9. Visually inspect the connection after brazing to locate any pinholes or
crevices in the joint. Use a mirror if joint locations are difficult to see.
System Evacuation Procedures
· Each refrigeration circuit must be evacuated before the unit can be charged
and started.
· Use a rotary type vacuum pump capable of pulling a vacuum of 100 microns or
less.
· Verify that the unit disconnect switch and the system control circuit
switches are OFF.
· Oil in the vacuum pump should be changed each time the pump is used with
high quality vacuum pump oil. Before using any oil, check the oil container
for discoloration, which usually indicates moisture in the oil and/or water
droplets. Moisture in the oil adds to what the pump has to remove from the
system, making the pump inefficient.
· When connecting vacuum pump to refrigeration system, it is important to
manifold vacuum pump to both high and low side of system (liquid line access
valve and suction line access valve). Follow pump manufacturer’s directions
for proper methods of using vacuum pump.
· Lines used to connect the pump to the system should be copper and of the
largest diameter that can practically be used. Using larger line sizes with
minimum flow resistance can significantly reduce evacuation time.
· Rubber or synthetic hoses are not recommended for system evacuation. They
have moisture absorbing characteristics that result in excessive rates of
evaporation, causing pressure rise during standing vacuum test. This makes it
impossible to determine if system has a leak, excessive residual moisture, or
continual or high rate of pressure increase due to hoses.
· Install an electronic micron vacuum gauge in the common line ahead of the
vacuum pump shutoff valve, as shown in Figure 22, p. 47. Close valves B and C,
and open Valve A.
· Start vacuum pump. After several minutes the gauge reading will indicate the
maximum vacuum the pump is capable of pulling. Rotary pumps should produce
vacuums of 100 microns or less.
PKG-SVX029A-EN
Maintenance
NOTICE
Motor Winding Damage!
Failure to follow instructions below could result in compressor motor winding
damage. Do not use a megohm meter or apply voltage greater than 50 VDC to a
compressor motor winding while it is under a deep vacuum.
· Open valves B and C. Evacuate system to a pressure of 300 microns or less.
As vacuum is being pulled on system, it may appear that no further vacuum is
being obtained, yet pressure is high. It is recommended during evacuation
process to break vacuum to facilitate evacuation.
· To break the vacuum, shut valves A, B, and C and connect a refrigerant
cylinder to charging port on manifold. Purge air from hose. Raise standing
vacuum pressure in system to zero (0 psig) gauge pressure. Repeat process two
or three times during evacuation.
Note: It is unlawful to release refrigerant into the atmosphere. When service
procedures require working with refrigerants, the service technician must
comply with all Federal, State, and local laws.
Standing Vacuum Test
Once 300 microns or less is obtained, close valve A and leave valves B and C
open to allow the vacuum gauge to read the actual system pressure. Let system
equalize for approximately 15 minutes. This is referred to as a standing
vacuum test where time versus pressure rise. Maximum allowable rise over a 15
minute period is 200 microns. If pressure rise is greater than 200 microns but
levels off to a constant value, excessive moisture is present. If pressure
steadily continues to rise, a leak is indicated. Figure 23, p. 47 illustrates
three possible results of standing vacuum test.
If a leak is encountered, repair the system and repeat the evacuation process
until the recommended vacuum is obtained. Once the system has been evacuated,
break the vacuum with refrigerant and complete the remaining PreStart
procedures before starting the unit.
Figure 22. Typical vacuum pump hookup
Figure 23. Evacuation time vs. pressure rise
1600
1400
Continously increasing pressure indicates the presence of leaks, moisture, or both.
1200 1000
800
State of equilibrium indicates the true amount of moisture left in the system. It indicates that no leaks, but requires further evacuation.
Pressure in Microns
600
400
Initial evacuation pressure.
200
State of equilibrium indicates the true amount of moisture left in the system. It indicates that no leaks are present and the system is properly evacuated.
-10
0
10
20
30
40
50
60
70
80
90
Time in Minutes
PKG-SVX029A-EN
47
Maintenance
Compressors
Scroll Compressor Failure Diagnosis and Replacement
If compressor failure is suspected, refer to CSHD and CSHN/CSHL Compressors
Installation and Service Installation Instructions (COM-SVN01*-EN) for
detailed information regarding compressor failure diagnosis and replacement of
scroll compressors.
Components
Cleaning Coil Fin
WARNING
Hazardous Chemicals!
Failure to follow this safety precaution could result in death or serious
injury. Coil cleaning agents can be either acidic or highly alkaline and can
burn severely if contact with skin or eyes occurs. Handle chemical carefully
and avoid contact with skin. ALWAYS wear Personal Protective Equipment (PPE)
including goggles or face shield, chemical resistant gloves, boots, apron or
suit as required. For personal safety refer to the cleaning agent
manufacturer’s Materials Safety Data Sheet and follow all recommended safe
handling practices.
WARNING
Hazardous Voltage w/Capacitors!
Failure to disconnect power and discharge capacitors before servicing could
result in death or serious injury. Disconnect all electric power, including
remote disconnects and discharge all motor start/run capacitors before
servicing. Follow proper lockout/ tagout procedures to ensure the power cannot
be inadvertently energized. Verify with a CAT III or IV voltmeter rated per
NFPA 70E that all capacitors have discharged.
NOTICE
Coil Damage!
Failure to follow instructions below could result in coil damage. Do not clean
the refrigerant coil with hot water or steam as it could cause high pressure
inside the coil tubing. Do not use acidic chemical coil cleaners. Also, do not
use alkaline chemical coil cleaners with a pH value greater then 8.5 (after
mixing) without using an aluminum corrosion inhibitor in the cleaning
solution.
· Keep coils clean to maintain maximum performance. For operation at its
highest efficiency, clean the refrigerant coil often during periods of high
cooling
48
demand or when dirty conditions prevail. Clean the coil a minimum of once per
year to prevent dirt buildup in the coil fins, where it may not be visible.
· Remove large debris from the coils and straighten fins before cleaning.
Remove filters before cleaning.
· Clean refrigerant coils with cold water and detergent, or with one of the
commercially available chemical coil cleaners. Rinse coils thoroughly after
cleaning.
· Economizer and evaporator coils are installed so the evaporator is directly
behind the economizer. To clean between the coils, remove the sheet metal
block off. Access the block off by removing the corner panels on the left or
right rear side of the unit.
· If the refrigerant coil is installed back to back with the waterside
economizer coil, use a cleaner that is acceptable for cleaning both types of
coils.
Inspecting and Cleaning Coils
Coils become externally fouled as a result of normal operation. Coil surface
dirt reduces heat transfer ability and can cause comfort problems, increased
airflow resistance and thus increased operating energy costs.
Inspect coils at least every six months or more frequently as dictated by
operating experience. Cleaning frequently is dependent upon system operating
hours, filter maintenance, efficiency, and dirt load. Following is the
suggested method for cleaning steam and hot water coils.
Hot Water Coils
WARNING
Hazardous Voltage w/Capacitors!
Failure to disconnect power and discharge capacitors before servicing could
result in death or serious injury. Disconnect all electric power, including
remote disconnects and discharge all motor start/run capacitors before
servicing. Follow proper lockout/ tagout procedures to ensure the power cannot
be inadvertently energized. Verify with a CAT III or IV voltmeter rated per
NFPA 70E that all capacitors have discharged.
1. Disconnect all electrical power to the unit.
2. Wear appropriate personal protective equipment (PPE).
3. Access both sides of the coil section.
4. Use a soft brush to remove loose debris from both sides of the coil.
5. Use a steam cleaning machine, starting from the top of the coil and
working downward. Clean the leaving air side of the coil first, then the
entering air side. Use a block-off to prevent steam from blowing through the
coil and into a dry section of the unit.
6. Repeat Step 5 as necessary. Confirm that the drain line is open following
completion of the cleaning process.
PKG-SVX029A-EN
7. Allow the unit to dry thoroughly before putting the system back into
service.
8. Straighten any coil fins that may be damaged with a fin rake.
9. Replace all panels and parts and restore electrical power to the unit.
10. Confirm contaminated material does not contact other areas of the
equipment or building. Properly dispose of all contaminated materials and
cleaning solutions.
Refrigerant Coils
WARNING
Hazardous Voltage w/Capacitors!
Failure to disconnect power and discharge capacitors before servicing could
result in death or serious injury. Disconnect all electric power, including
remote disconnects and discharge all motor start/run capacitors before
servicing. Follow proper lockout/ tagout procedures to ensure the power cannot
be inadvertently energized. Verify with a CAT III or IV voltmeter rated per
NFPA 70E that all capacitors have discharged.
1. Disconnect all electrical power to the unit.
2. Wear the appropriate personal protective equipment (PPE).
3. Access to the coil section of the unit (both sides).
4. Use a soft brush to remove loose debris from both sides of the coil.
5. Mix a high quality coil cleaning detergent with water according to the
manufacturer’s instructions. If the detergent is strongly alkaline after
mixing (pH 8.5 or higher), it must contain an inhibitor. Carefully follow the
cleaning solution manufacturer’s instructions regarding product use.
6. Place the mixed solution in a garden pump-up sprayer or high pressure
sprayer. If using a high pressure sprayer note the following:
· Maintain a minimum nozzle spray angle of 15°.
· Spray perpendicular to the coil face.
· Protect other areas of the equipment and internal controls from contact with
moisture or the cleaning solution.
· Keep the nozzle at least 6 inches from the coil.
· Do not exceed 600 psig.
Maintenance
Draining the Waterside Economizer Coil
NOTICE
Coil Freeze-Up!
Failure to follow instruction below could result in equipment damage. Drain
and vent coils when not in use. Trane recommends glycol protection in all
possible freezing applications. Use a glycol approved for use with commercial
cooling and heating systems and copper tube coils.
Drain plugs are in the piping below supply and return header for each coil.
Use these plugs to drain the coil and piping. When draining the coil, open the
vents at the top of the supply and return headers. Also, a drain plug is at
the bottom of the inlet condenser manifold and in the outlet pipe near the
left side of the unit. Remove these plugs to drain the condensers. Be sure to
open the vent plugs at the top of the condenser inlet and outlet manifold.
When refilling the condenser/waterside economizer coil system with water,
provide adequate water treatment to prevent the formation of scale or
corrosion.
Chemical Cleaning of Economizer Coil
NOTICE
Proper Water Treatment Required!
The use of untreated or improperly treated water could result in scaling,
erosion, corrosion, algae or slime. Use the services of a qualified water
treatment specialist to determine what water treatment, if any, is required.
Trane assumes no responsibility for equipment failures which result from
untreated or improperly treated water, or saline or brackish water.
Chemical cleaning removes scale deposits built up by minerals in the water.
For a suitable chemical solution, consult a water treatment specialist. The
condenser water circuit is composed of copper, steel, and cast iron. The
chemical supply house should approve or provide all materials used in the
external circulating system, along with the quantity of cleaning material,
duration of cleaning time, and safety precautions necessary for handling the
cleaning agent.
PKG-SVX029A-EN
49
Maintenance
Piping Components
Water Valves
WARNING
Hazardous Voltage w/Capacitors!
Failure to disconnect power and discharge capacitors before servicing could
result in death or serious injury. Disconnect all electric power, including
remote disconnects and discharge all motor start/run capacitors before
servicing. Follow proper lockout/ tagout procedures to ensure the power cannot
be inadvertently energized. For variable frequency drives or other energy
storing components provided by Trane or others, refer to the appropriate
manufacturer’s literature for allowable waiting periods for discharge of
capacitors. Verify with a CAT III or IV voltmeter rated per NFPA 70E that all
capacitors have discharged.
Water valves have a stern packing nut. If there is evidence of water leakage
at the valve stem, proceed as follows:
1. Remove actuator motor from support plate.
2. Remove shaft coupling.
3. Torque the packing nut to 10-ft.-lbs. of torque.
4. Replace shaft coupling.
5. Replace actuator motor.
Water Flow Switch
A water flow switch is required to be installed in the condenser water pipe
within the unit. It is a standard feature and supplied from the factory.
When the flow switch detects a water flow loss prior to or during mechanical
cooling, the compressor operation locks out and a diagnostic code displays. If
water flow is restored, the compressor operation automatically restores.
Maintenance Periodic Checklists
WARNING
Hazardous Service Procedures!
Failure to follow all precautions in this manual and on the tags, stickers,
and labels could result in death or serious injury. Technicians, in order to
protect themselves from potential electrical, mechanical, and chemical
hazards, MUST follow precautions in this manual and on the tags, stickers, and
labels, as well as the following instructions: Unless specified otherwise,
disconnect all electrical power including remote disconnect and discharge all
energy storing devices such as capacitors before servicing. Follow proper
lockout/tagout procedures to ensure the power can not be inadvertently
energized. When necessary to work with live electrical components, have a
qualified licensed electrician or other individual who has been trained in
handling live electrical components perform these tasks.
Monthly Checklist
The following check list provides the recommended maintenance schedule to keep
the commercial selfcontained equipment running efficiently.
1. Inspect unit air filters. Clean or replace if airflow is blocked or if
filters are dirty.
2. Inspect coils for excess moisture or icing. Icing on the coils may
indicate low airflow supply, restricted airflow from dirty fins, evaporator
frost protection sensor problems, or a shortage of refrigerant flowing through
the coil.
3. Check that condensate from the evaporator and economizer coils flows
freely through the condensate piping, traps, drain pan, and drainage holes.
Remove algae and or any airflow obstructions.
4. Check the liquid line sight glasses during operation. Bubbles in the sight
glasses indicate a possible shortage of refrigerant or an obstruction in the
liquid lines, e.g. dirty liquid line filter driers.
5. Inspect filter driers for leaks, flow obstructions, or temperature drop
across the filter drier. A noticeable temperature differential, e.g. 5°F, in
the liquid line may indicate an obstruction. Replace the filter drier if it
appears clogged.
6. Inspect the optional waterside economiz
References
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>