RenewAire EV Premium XH Energy Recovery Ventilator Owner’s Manual

September 11, 2024
RenewAire

EV Premium XH Energy Recovery Ventilator

Specifications & Dimensions

Product: EV Premium X Energy Recovery
Ventilator

Unit Type: Residential/Light Commercial

Specifications

  • Ventilation Type: Static plate, heat and
    humidity transfer

  • HVI Certification: Tested/Certified per CSA
    C439 Protocol

  • Standard Features: White painted cabinet,
    Line-cord power supply or hardwired, Low-voltage circuit for
    controls, Cross-core differential pressure ports, Dial-A-Flow,
    Variable speed Boost-mode

  • Filters: 2 MERV 8 spun-polyester media
    filters

  • Unit Weight: 65 lbs.

  • Dimensions (in carton): 33″ L x 24″ W x 29″
    H

  • Motor(s): Qty. 2, 120V EC motorized
    impellers

  • Accessories: Backdraft damper, Automatic
    balancing damper, Motorized Dampers, Louvered wall vent, Digital
    time clock, Carbon dioxide sensor/control, IAQ sensor, Motion
    occupancy sensor/control

Electrical Data

  • Watts: 220V (FLA per motor: 2.7)
  • Volts: 120V
  • Hz: 60
  • Phase: 1
  • Minimum Circuit Amps: N/A

Product Usage Instructions

Installation

1. Consult with a local installer for the best installation
controls for your climate.

2. Mount the unit in any orientation.

Maintenance

1. Replace filters as recommended by the manufacturer.

2. Inspect and clean ventilation ports regularly.

Troubleshooting

If you encounter any issues with the unit’s performance, refer
to the user manual for troubleshooting steps or contact customer
support.

Frequently Asked Questions (FAQ)

Q: How often should I replace the filters?

A: Filters should be replaced according to the manufacturer’s
recommendations, typically every 3-6 months depending on usage.

Q: Can the unit be installed outdoors?

A: No, the unit is designed for indoor use only.

Q: What is the warranty period for the EV Premium X?

A: The warranty period varies, please refer to the warranty
information provided by the manufacturer or consult with your
installer.

RESIDENTIAL/LIGHT COMMERCIAL

SPECIFICATIONS & DIMENSIONS

EV PREMIUM X
NEW! INDOOR UNIT
Note: There are multiple control options designed to address individual climate conditions. Please consult your local installer for the best installation controls for your climate.

ENERGY RECOVERY VENTILATOR EC MOTOR

SPECIFICATIONS

Ventilation Type: Static plate, heat and humidity transfer
Typical Airflow Range: 100­390 CFM
Unit is HVI Tested/Certified per CSA C439 Protocol: Using one L-100-G5 Core
Standard Features: White painted cabinet Line-cord power supply or hard wired to junction box (H) Low-voltage circuit for controls Unit may be mounted in any orientation Cross-core differential pressure ports Dial-A-Flow: balance and airflow adjustment Variable speed Boost-mode
Controls: Onboard digital controller with independent
variable speeds
Filters: Total qty. 2, MERV 8, spun-polyester media:
10 1/2″ x 21 3/4″ x 1″
Unit Weight: 65 lbs.
Max. Shipping Dimensions & Weight (in carton): 33″ L x 24″ W x 29″ H 72 lbs.

Units Per Pallet: 4
Motor(s): Qty. 2, 120V EC motorized impellers
Accessories: Backdraft damper: 8″ Automatic balancing damper: 4″, 5″, 6″ Motorized Dampers: 8″ Louvered wall vent 8″: taupe vinyl, galvanized,
paintable galvanneal Louvered wall vent with 8″ round duct connection:
12″ W x 8″ H Hooded wall vent 8″: galvanized, paintable galvanneal Digital time clock: wall mount (TC7D-W),
in exterior enclosure (TC7D-E) Carbon dioxide sensor/control: wall mount (CO2-W),
duct mount (CO2-D) IAQ sensor: wall mount (IAQ-W), duct mount (IAQ-D) Motion occupancy sensor/control:
ceiling mount (MC-C), wall mount (MC-W) Push-button boost timer (PBT) Percentage timer control (PTL) Percentage timer control with furnace interlock (FM) Push-button point-of-use controls (PBL), PTL req’d. BACnet fan control: wall mount (BACNETFC-W) MERV 13 filter: OA airstream (shipped loose) Electric duct heater: RH series (1­11.5 kW);
designed for indoor ductwork installation only

EC MOTOR OPERATING RANGE AND CORE PERFORMANCE

3.2

2.8

2.4

2

ESP (in. H2O)

1.6

1.2

0.8

0.4

0

0

100

200

300

400

Airflow (CFM)

= Actual tested sample points
| = Operating curves, airflow is held constant as static pressure varies
Factory settings 1. High speed set to top curve 2. Low speed set to ~90CFM at 0.4 in. w.g. ESP

Airflow (CFM)
400 390 381 373 362 354 345 337 318 299 282 263 227 191
146 122 93

External Static Pressure
(Inches Water Column)
0.10 0.20 0.30 0.40 0.50 0.60 0.70 0.80 1.00 1.20 1.40 1.60 2.00 2.40
0.10 0.20 0.30

Unit Power Consumption
(Watts)
Max. Speed 339 338 340 337 337 337 337 336 337 336 336 344 349 359
Min. Speed 41 37 32

Sensible EFF%
64 64 65 65 66 66 67 68 69 70 71 72 74 77
80 81 83

Total EFF% Winter/Summer
55/38 56/39 57/40 57/40 58/41 59/42 59/43 60/44 61/46 63/47 64/49 66/51 68/54 71/57
75/62 77/64 79/66

AUGMENTED REALITY (AR)
Scan QR code to see life size version of EV Premium X, or view here: https://QR.Marketscale.com/EVPremiumX

Notes: 1. Watts is for the entire unit. 2. Airflow performance includes effect of clean, standard filter supplied with unit. 3. Refer to CORES for specific operating point electrical data. 4. These are core-only ratings and are not HVI certified. Total EFF% calculated at 35/33wb OA and 70/58wb RA
(winter) and 95/78wb OA and 75/63wb RA (summer). HVI ratings apply to complete units only. This unit is HVI certified. See HVI certified ratings on pg. 47 of Single/Multi-Family Catalog and at hvi.org.

ELECTRICAL DATA

Watts

Volts

Hz

220

120

60

Phase 1

FLA per motor
2.7

Minimum Circuit Amps
15

Max Overcurrent Protection
Device
15

Back to TOC

Subject to change without notice: RENEWAIRE.COM | 1.800.627.4499 21

Subject to change without notice: RENEWAIRE.COM | 1.800.627.4499 23

Back to TOC

EV PREMIUM XH ENERGY RECOVERY VENTILATOR EC MOTOR

2 1/4″ Typ.

24 3/8″ Overall
19 7/8″ Case

24V AC Control Terminal

TOP VIEW

7 1/4″

7/8″

Power Outlet Box 7/8″ Knockouts

OA

RA

14 1/8″ Typ.

25 3/8″ Case

29″ Overall (With Hanging Bracket)

EA

SA

5 7/8″

To Fit 8″ Duct Typ.

Pressure Ports (4) Typ.

2 5/8″

LEFT VIEW
AIRFLOW ORIENTATION
AMDvailraoabldewaesinslh:ogwEnVTinydPpimreeen:smioUninduraimtwinDgX.imH ension Version: NOV23

FRONT VIEW

11 3/4″ Typ.
24 1/4″ Overall (With Hanging
Bracket)

26″ Minimum Service Area

ABBREVIATIONS EA: Exhaust Air to outside OA: Outside Air intake RA: Room Air to be exhausted SA: Supply Air to inside INSTALLATION ORIENTATION Unit may be installed in any orientation. NOTE 1. UNLESS OTHERWISE SPECIFIED, DIMENSIONS ARE ROUNDED TO THE NEAREST EIGTH OF AN INCH. 2.SPECIFICATIONS MAY BE SUBJECT TO CHANGE WITHOUT NOTICE.

26″ Minimum Service Area (Door can be removed from
hinges)
Door Swing

23 5/8″ Case

28″ Overall

RIGHT VIEW
UNIT MOUNTING & APPLICATION Can be mounted in any orientation. RA/EA airstream can be switched with OA/SA airstream.

SPECIFICATIONS & DIMENSIONS

RESIDENTIAL/LIGHT COMMERCIAL