RenewAire EV130 Energy Recovery Ventilator Instruction Manual
- May 15, 2024
- RenewAire
Table of Contents
RenewAire EV130 Energy Recovery Ventilator Instruction Manual
Note: There are multiple control options designed to address individual climate conditions. Please consult your local installer for the best installation controls for your climate.
ELECTRICAL DATA
HP | Volts | Hz | Phase | Watts | FLA |
---|---|---|---|---|---|
0.1 | 120 | 60 | Single | 102 @ 130 CFM | 1.3 |
SPECIFICATIONS
Ventilation Type: Static plate, heat and humidity transfer
Typical Airflow Range: 50–140 CFM
Unit is HVI Tested/Certified per CSA C439
Protocol: Using one L-50-G5 Core
Standard Features:
White painted cabinet Line-cord power supply Low-voltage circuit for controls
Unit may be mounted in any orientation Cross-core differential pressure ports
Controls:
Onboard 24VAC transformer/relay package
Filters:
Total qty. 2, MERV 8, spun-polyester media: 10 1/2″ x 10 1/2″ x 1″
Unit Weight: 48 lbs.
Max. Shipping Dimensions & Weight (in carton):
32″ L x 22″ W x 18″ H 60 lbs.
UNIT PERFORMANCE
Airflow (CFM)| External Static Pressure (Inches Water
Column)
---|---
78| 0.60
104| 0.50
125| 0.40
136| 0.30
153| 0.20
163| 0.10
Units Per Pallet: 8
Motor(s):
Qty. 1, Double-shaft standard motor
Accessories:
Backdraft damper: 6″, 8″
Automatic balancing damper: 4″, 5″, 6″
Motorized Dampers: 6″, 8″
Concentric Vent: 6″ (CV6-110)
Louvered wall vent 6″: white, brown
Digital time clock: wall mount (TC7D-W), in exterior enclosure (TC7D-E)
Carbon dioxide sensor/control: wall mount (CO2-W), duct mount (CO2-D)
IAQ sensor : wall mount (IAQ-W), duct mount (IAQ-D)
Motion occupancy sensor/control:
ceiling mount (MC-C), wall mount (MC-W)
Percentage timer control (PTL)
Push-button point-of-use controls (PBL), PTL req’d.
Percentage timer control with furnace interlock (FM)
MERV 13 filter: OA airstream (shipped loose)
Electric duct heater: RH series (1–5 kW); designed for indoor ductwork
installation only
CORE PERFORMANCE
Airflow (CFM) | Temp EFF% | Total EFF% Winter/Summer |
---|---|---|
78 | 78 | 73/59 |
104 | 75 | 69/54 |
125 | 72 | 66/50 |
136 | 71 | 64/48 |
153 | 68 | 61/45 |
163 | 67 | 59/42 |
Note : These are core-only ratings and are not HVI certified. Total EFF% calculated at 35/33wb OA and 70/58wb RA (winter) and 98/78wb OA and 75/63wb RA (summer). HVI ratings apply to complete units only. This unit is HVI certified. See HVI certified ratings on pg. 47 of Single/Multi-Family Catalog and at hvi.org.
UNIT DIMENSIONS
AIRFLOW ORIENTATION
Available as shown in dimension drawing.
UNIT MOUNTING & APPLICATION
Can be mounted in any orientation. RA/EA airstream can be switched with OA/SA
airstream.
**TOP VIEW
LEFT VIEW
FRONT VIEW
RIGHT VIEW
**
ABBREVIATIONS
EA: Exhaust Air to outside
OA: Outside Air intake
RA: Room Air to be exhausted
SA: Supply Air to inside
INSTALLATION ORIENTATION
Unit may be installed in any orientation.
NOTE
- UNLESS OTHERWISE SPECIFIED, DIMENSIONS ARE ROUNDED TO THE NEAREST EIGHTH OF AN INCH.
- SPECIFICATIONS MAY BE SUBJECT TO CHANGE WITHOUT NOTICE