RenewAire BACNETFC-W Energy Recovery Ventilator ERV EV Premium XH User Guide
- May 15, 2024
- RenewAire
Table of Contents
RenewAire BACNETFC-W Energy Recovery Ventilator ERV EV Premium XH User
Guide
INTRODUCTION
The BACnet Fan Control accessory is a wall-mounted control accessory which allows the user to turn a Renew Aire Energy Recovery Unit (ERV) on and off through the keypad, through a digital input with a remote switch, or through a Building Management System (BMS) with BACnet MSTP
It will control both the supply fan and exhaust fan speeds independently according to settings made through the controller keypad or through the BMS.
MOUNTING INSTRUCTIONS
CAUTION
Whenever electrical wiring is connected, disconnected, or changed, the power supply to the unit and its controls must be disconnected. Lock and tag the disconnect switch or circuit breaker to prevent accidental reconnection of electric power.
A. Remove the captive screw that is holding the base and the front cover
of the unit together.
B. Lift the front cover of the unit to separate it from the base.
C. Pull all wires through the holes in the base.
D. Secure the base to the wall using wall anchors and screws (supplied).
Make the appropriate connections.
E. Mount the control module on the base and secure using the screw
SET-UP AND WIRING INSTRUCTIONS
If the accessory is located close enough to the ERV, it can be powered from the ERV 24VAC power source. For remote connections, wire needs to be 18 gauge.
Either wire in the interlock devices, such as a smoke detector, occupancy
sensor, or jumper from U1 to Common|
---|---
Set dip-switches in the correct positions, JP1 to “RUN”, JP2 to “AO1”, and JP3
to “NONE.”|
OPTION
WIRING SCHEMATICS
SCHEMATICS FOR HE-SERIES AND LE-SERIES UNITS
HE2X AND LARGER WITH VFDS
HE07/10/1.5 BOARD WIRING
HE1.5XIN WITH INDEPENDENT BLOWER CONTROL
HE1.5 AND LARGER WITH AC MOTORS
SCHEMATICS FOR SL-SERIES AND EV PREMIUM SERIES UNITS
NOTE : The wires can be connected direct- ly to the terminal in the controller. 18 gauge wire must be used
USER SETTINGS
If the unit has variable speed fans, a setting is required for each of the supply and exhaust fans to tell it how fast it should run.
To see the Fan Speed Settings, press the “FAN” button once, and then use the
“UP” and “DOWN” buttons to see them. The screen will time out to the main
status screen.|
---|---
Press the “FAN” button to select a value to change.|
Use the “UP” and “DOWN” buttons to change the value.|
Press the “FAN” button to confirm OR “HEAT/COOL” button to cancel and escape.|
To see the User On/Off setting, press the “HEAT/COOL” button. To change it,
press it a second time.|
PROGRAM SETTINGS
In order to set the program settings, the dip-switch must be set for Program
(PGM).|
---|---
Once done, you will see a wrench at the top of the screen, indicating Program
Mode.| ****
Press the “UP” and “DOWN” buttons to get to the screens you want to change.|
Press the “FAN” button to select a value to change.|
Use the “UP” and “DOWN” buttons to change the value.|
Press the “FAN” button to confirm OR “HEAT/COOL” button to cancel and escape.|
Make sure you put the dip-switch back in the “RUN” position when done.|
Choose BMS Enable “ON” if you want to turn the unit on and off by the BMS.
In doing so, all conditions need to be met to turn the unit on.
Supported Baud rates : 9600, 19200, 38400, 57600, 76800, 115200 bps.
You can set the light for active and inactive display
BACNET OBJECTS
INDEX| OBJECT NAME| OBJECT DESCRIPTION| UNIT/RANGE|
DEFAULT
---|---|---|---|---
AO 1| Supply Fan Command| Supply Fan Analog Output. Read-only| Unit: Voltage,
Range: 0.0V–10.0V, Resolution: 0.1V| N/A
AO 2| Exhaust Fan Command| Exhaust Fan Analog Output. Read-only| Unit:
Voltage, Range: 0.0V–10.0V, Resolution: 0.1V| N/A
AV 1| Supply Fan Setpoint| Setpoint for Supply Fan output. Write-able from
BACnet and HMI.| Unit: Voltage, Range: 0.0V–10.0V, Resolution: 0.1V| 5.0V
AV 2| Exhaust Fan Setpoint| Setpoint for Exhaust Fan output. Write-able from
BACnet and HMI.| Unit: Voltage, Range: 0.0V–10.0V, Resolution: 0.1V| 5.0V
AV 3| Network Activity Timeout| Network Activity Timeout delay. Write-able
from HMI in program mode.| Unit: Seconds, Range: 1sec– 120sec, Resolution:
1Sec| 60Sec
AV 7| Active Display Back-light| Active display back-light brightness. Write-
able from HMI in program mode.| Unit: Percentage, Range: 0%– 100%, Resolution:
5%| 50%
AV 8| Inactive Display Back-light| Inactive display back-light brightness.
Write-able from HMI in program mode.| Unit: Percentage, Range: 0%– 100%,
Resolution: 5%| 50%
BI 1| Interlock| Binary Input for remote on/off signal. Read-only| 0= Open, 1=
Closed| N/A
BO 1| Supply Fan Enable| Supply Fan Binary Output. Read-only| 0= Off, 1= On|
N/A
BO 2| Exhaust Fan Enable| Exhaust Fan Binary Output. Read-only| 0= Off, 1= On|
N/A
BO 3| Supply Damper| Supply Damper Binary Output. Read-only| 0= Off, 1= On|
N/A
BO 4| Exhaust Damper| Exhaust Damper Binary Output. Read-only| 0= Off, 1= On|
N/A
BV 1| Enable BMS| Enable control from BMS. Write-able from BACnet| 0= Off, 1=
On| N/A
BV 2| BMS On/Off| BMS control mode. Write-able from BACnet| 0= Off, 1= On| N/A
BV 3| User On/Off| User control mode. Write-able from BACnet and HMI.| 0= Off,
1= On| N/A
BV 4| Unit Status| Unit’s operation status. Read-only| 0= Off, 1= On| N/A
TROUBLESHOOTING
The main screen will show you the status of the unit.
There are three indicators that show Active for turning the unit on.
They are located in the bottom row in the three boxes.
- An “A” in the left box indicates the unit is turned on by the User setting.
- An “A” in the middle box indicates the unit is turned on by the BMS if that feature is enabled.
- An “A” in the right box indicates the unit is turned on by the interlock (or umpired).
INSTALLATION VIDEO RESOURCES
ERV Start Up with Integrated Programmable Controls
Connecting ERV to BACnet Fan Control
MSTP Integration to BACnet Fan Control
2024 © Renew Aire LLC 105802_001_FEB24
References
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>