RenewAire LE8XIN Energy Recovery Ventilator Instruction Manual
- June 10, 2024
- RenewAire
Table of Contents
- RenewAire LE8XIN Energy Recovery Ventilator
- Product Information
- Product Usage Instructions
- IMPORTANT SAFETY INFORMATION
- UNIT INFORMATION
- CONFIGURATION CODE FOR LE8XIN MODELS
- SPECIFICATIONS
- ELECTRICAL DATA
- OVERVIEW
- COMPONENT DESCRIPTION
- UNIT PLACEMENT
- INSTALLATION
- 22 #20 #18 #16 #14 #12
- MAINTENANCE
- References
- Read User Manual Online (PDF format)
- Download This Manual (PDF format)
RenewAire LE8XIN Energy Recovery Ventilator
Product Information
The LE8XIN Energy Recovery Ventilator (ERV) is a ventilation system designed for general ventilating purposes in finished structures. The ERV is also available as separate modules for field assembly. It is manufactured by RenewAire and is intended to be installed following industry best practices and all applicable codes. The unit is not to be used until after all construction has been completed, and construction debris and dust are cleaned from the occupied space. The ERV should not be used to exhaust hazardous or explosive materials and vapors and should not be connected to range hoods, fume hoods or collection systems for toxics.
Product Usage Instructions
- Before working within the unit cabinet, allow the blower motor and other electrical components to cool. Wear protective gloves and arm protection when working on or near hot blower motors and electrical components.
- Disconnect all local and remote power supplies, verify with a voltmeter that electric power is off, and all fan blades have stopped rotating before working on the unit.
- Do not operate this unit with any cabinet panels removed or prior to assembly of the modules.
- Whenever electrical wiring is connected, disconnected or changed, the power supply to the ERV and its controls must be disconnected. Lock and tag the disconnect switch or circuit breaker to prevent accidental reconnection of electric power.
- Whenever working within the ERV cabinet, protect the enthalpic cores from accidental damage. The core media is subject to damage from dropped tools or other foreign objects.
- If this unit is installed in an area where it may draw air from a nearby fuel-burning device such as a gas furnace or water heater, verify that the air being extracted by the ERV does not conflict with proper operation of the fuel-burning device.
- See separate SHIPPING & RIGGING manual for information on shipping considerations, rigging, moving and lifting the unit as separate modules or as a complete unit.
- Maintain written records of unit maintenance and/or repairs in the space provided in Section 11.9, Maintenance Records. Develop a maintenance schedule to incorporate monthly and seasonal maintenance and include start-up maintenance tasks as described in this manual.
INSTALLATION, OPERATION & MAINTENANCE MANUAL ENERGY RECOVERY VENTILATOR
LE8XIN
Model LE8XINV Shown (also available as separate modules for field assembly)
WWW.RENEWAIRE.COM
LE8XIN ERV
IMPORTANT SAFETY INFORMATION
WARNING
ARC FLASH AND ELECTRIC SHOCK HAZARD
Arc flash and electric shock hazard. Disconnect all electric power supplies,
verify with a voltmeter that electric power is off and wear protective
equipment per NFPA 70E before working within electric control enclosure.
Failure to comply can cause serious injury or death. Customer must provide
earth ground to unit, per NEC, CEC and local codes, as applicable. Before
proceeding with installation, read all instructions, verifying that all the
parts are included and check the nameplate to be sure the voltage matches
available utility power. The line side of the disconnect switch contains live
high-voltage. The only way to ensure that there is NO voltage inside the unit
is to install and open a remote disconnect switch and verify that power is off
with a volt meter. Refer to unit electrical schematic. Follow all local codes.
CAUTION
RISK OF CONTACT WITH HOT SURFACES
The blower motor and other electrical components are extremely hot during
operation. Allow sufficient time for them to cool before working within the
unit cabinet. Use extreme caution and wear protective gloves and arm
protection when working on or near hot blower motors and electrical
components.
CAUTION
RISK OF CONTACT WITH HIGH SPEED MOVING PARTS.
Disconnect all local and remote power supplies, verify with a voltmeter that
electric power is off and all fan blades have stopped rotating before working
on the unit. Do not operate this unit with any cabinet panels removed or prior
to assembly of the modules
CAUTION
RISK OF ELECTRIC SHOCK OR EQUIPMENT DAMAGE
Whenever electrical wiring is connected, disconnected or changed, the power
supply to the ERV and its controls must be disconnected. Lock and tag the
disconnect switch or circuit breaker to prevent accidental reconnection of
electric power.
CAUTION
RISK OF DAMAGE TO ENTHALPIC CORES
Whenever working within the ERV cabinet, protect the enthalpic cores from
accidental damage. The core media is subject to damage from dropped tools or
other foreign objects.
NOTICE
This unit is intended for general ventilating only. Do not use to exhaust
hazardous or explosive materials and vapors. Do not connect this equipment to
range hoods, fume hoods or collection systems for toxics.
NOTICE
This equipment is to be installed by following Industry Best Practices and all
applicable codes. Any damage to components, assemblies, subassemblies or the
cabinet which is caused by improper installation practices will void the
warranty.
NOTICE
This unit is for ventilating finished structures only. It is not to be used
until after all construction has been completed and construction debris and
dust are cleaned from the Occupied Space.
2 RENEWAIRE.COM INSTALLATION, OPERATION AND MAINTENANCE MANUAL 1.800.627.4499
LE8XIN ERV IMPORTANT USER INFORMATION
READ AND SAVE THIS MANUAL/LIRE ET CONSERVER CE MANUEL
IMPORTANT
If this unit is installed in an area where it may draw air from a nearby fuel-
burning device such as a gas furnace or water heater, verify that the air
being extracted by the ERV does not conflict with proper operation of the
fuel-burning device.
IMPORTANT
This unit can be delivered in two modules for on-site assembly or as a
completely assembled unit (additional charges apply). See separate SHIPPING &
RIGGING manual for information on shipping considerations, rigging, moving and
lifting the unit as separate modules or as a complete unit.
IMPORTANT
This manual contains space for maintaining written records of unit maintenance
and / or repairs. See Section 11.9, Maintenance Records. At the time the ERV
is commissioned, a maintenance schedule should be developed by the user to
incorporate monthly and seasonal maintenance and include start-up maintenance
tasks as described in this manual.
UNIT INFORMATION
In the unlikely event that factory assistance is ever required, information
located on the unit label will be needed.
Configuration (Option) Code
Unit Label (typical)
1.800.627.4499 INSTALLATION, OPERATION AND MAINTENANCE MANUAL RENEWAIRE.COM 3
LE8XIN ERV
TABLE OF CONTENTS
IMPORTANT SAFETY INFORMATION
UNIT INFORMATION
CONFIGURATION CODE FOR LE8XIN MODELS
LE8XINH SUBMITTAL SPECIFICATIONS
LE8XINH DIMENSIONS
LE8XINV SUBMITTAL SPECIFICATIONS
LE8XINV DIMENSIONS
1.0 OVERVIEW 1.1 DESCRIPTION 1.2 FACTORY ASSEMBLY OF MODULES 1.3 MODELS 1.3.1
LE8XINH 1.3.2 LE8XINV
2.0 COMPONENT DESCRIPTION 2.1 CABINET CONSTRUCTION 2.1.1 Cabinet Paint 2.2 FAN
MOTORS 2.3 FAN SPEED CONTROL 2.4 DAMPERS 2.5 ENTHALPIC CORE 2.6 FILTERS 2.6.1
Filter Monitors 2.7 CONTROLS 2.7.1 Integrated Microprocessor Controls 2.7.2
Variable Frequency Drive 2.8 OPTIONAL CONTROL ACCESSORIES 2.8.1 Carbon Dioxide
Control 2.8.2 Digital Time Clock 2.8.3 Indoor Air Quality Sensor (IAQ) 2.8.4
Motion Occupancy Control 2.8.5 Smoke Detector
3.0 UNIT WEIGHTS 3.1 LE8XINH CORNER WEIGHTS 3.2 LE8XINV CORNER WEIGHTS
4.0 SHIPPING / RECEIVING / HANDLING 4.1 UNIT WEIGHTS / DIMENSIONS 4.1.1 Unit
Dimensions and Weight 4.1.2 Shipping Dimensions and Weight 4.2 RECEIVING 4.3
RIGGING 4.4 HANDLING AND STORAGE
5.0 UNIT PLACEMENT 5.1 SOUND ATTENUATION OUTSIDE THE BUILDING 5.2 PLACEMENT
CAUTIONS 5.3 SERVICE CLEARANCES
6.0 INSTALLATION 6.1 ASSEMBLY OF MODULES 6.2 DUCT CONNECTIONS 6.3 INDOOR SOUND
ATTENUATION 6.4 ELECTRICAL CONNECTIONS
6.4.1 Factory-Recommended Electric Service Entry 21
6.5 WIRING SCHEMATICS
22
2 6.6 CONTROL CONNECTIONS
24
3 7.0 CONTROL CONTRACTOR INFORMATION
24
6
7.1 24 VAC CLASS II POWER SUPPLY 7.2 MOTOR PROTECTION
24 25
7
7.2.1 Units Equipped with Motor Starters
25
8
7.2.2 Units With Variable Frequency Drives (VFDs) 26
7.3 EXTERNAL CONTROL CONNECTIONS
26
9
7.3.1 Single 2 – Wire Control, Unpowered
26
10
7.3.2 Single 2 – Wire Control, Separate Power
27
11 11
7.3.3 Control Sending 24 VAC “ON” Signal
27
7.3.4 External Control Using ERV Power Supply
27
11
7.3.5 Control with 2 Non-Powered Relay Contacts 27
11
7.3.6 Control with 2 “ON” Signals, External Power 28
11 7.4 SEQUENCE OF OPERATION
28
12 8.0 PRE START-UP
30
13 13
13 13 13 13 13 13
8.1 VERIFY VOLTAGES 8.2 VERIFY TRANSFORMER WIRING 8.3 INSPECT FILTERS 8.4 INSPECT FOAM GASKETING 8.5 INSPECT MOTOR VIBRATION ISOLATORS 8.6 INSPECT BELTS AND VERIFY SHEAVE ALIGNMENT 8.7 INSPECT FAN 8.8 INSPECT AND CLEAN THE INTERIOR 8.9 INSPECT DUCTWORK CONNECTIONS
30 30 30 30 30 30 30 30 30
13
14 9.0 START-UP
31
14 9.1 VERIFY CORRECT FAN ROTATION DIRECTION
31
15 9.2 BASIC OPERATIONAL CHECK
31
15
9.2.1 Motor Starter Units
31
15
9.2.2 VFD Units
31
15 9.3 ADJUST MOTOR SHEAVES
32
16 10.0 MAINTENANCE
32
16 10.1 MAINTENANCE 24 HRS. AFTER START-UP
32
16 10.2 MAINTENANCE 30 DAYS AFTER START-UP
32
17 17 17
10.3 MAINTENANCE SCHEDULE 10.4 FILTERS 10.5 ELECTRIC MOTOR MAINTENANCE
10.5.1 Belt Tension
32 32 33
33
18
10.5.2 Sheave Condition
33
18
10.5.3 Motor Cleanliness
33
18
10.5.4 Motor Lubrication
33
18 10.6 PILLOW BLOCKS
35
18 10.7 ENTHALPIC CORE MAINTENANCE
36
18
10.7.1 Removal of Enthalpic Cores
36
18
10.7.2 Reinstallation of Enthalpic Cores
36
19 10.8 SERVICE PARTS
37
19 11.0 MAINTENANCE REFERENCE
38
19 11.1 PLENUM DIVIDERS
38
19 11.2 FAN / MOTOR REMOVAL
38
20 11.3 VIBRATION ISOLATOR ADJUSTMENT
38
20 11.4 RISK OF CORE DAMAGE
39
20 11.5 FILTER REPLACEMENT PRACTICES
39
20 11.6 DOOR LATCH ADJUSTMENT
40
21 11.7 MEASURING AIRFLOW
40
4 RENEWAIRE.COM INSTALLATION, OPERATION AND MAINTENANCE MANUAL 1.800.627.4499
TABLE OF CONTENTS (cont’d)
11.8 SHEAVE ADJUSTMENT 11.9 MAINTENANCE RECORDS
LE8XIN ERV
TABLE OF WIRING SCHEMATICS
41 Single Phase Wiring Schematic
22
42 Three Phase Wiring Schematic
23
Single 2-Wire Control, Unpowered
26
24 VAC From External Source
27
External Control Using ERV 24 VAC
27
Control with 2 Non-Powered Relay Contacts
28
Control with 2 “ON” Signals, External Power
28
TABLE OF ILLUSTRATIONS
Unit Label (typical) LE8XINH SUBMITTAL SPECIFICATIONS LE8XINH DIMENSIONS
LE8XINV SUBMITTAL SPECIFICATIONS LE8XINV DIMENSIONS LE8XINH Standard Duct
Configuration LE8XINH Alternate Duct Configuration LE8XINV Standard Duct
Configuration LE8XINV Alternate Duct Configuration RenewAire Microprocessor
Controller Premium Microprocessor Controls Installed RenewAire Microprocessor
Controller Expansion Board Carbon Dioxide Sensor, Room/Wall Mount Time Clock,
Panel Mount VFDs Mounted Inside ERV Time Clock, Exterior Enclosure Carbon
Dioxide Sensor, Duct Mount VFD Keypads Found in E-Box Time Clock, Exterior IAQ
Sensor, Room/Wall Mount Ceiling Mount Occupancy Sensor Smoke Detector IAQ
Sensor, Duct Mount Wall Mount Occupancy Sensor LE8XINH Corner Weights LE8XINV
Corner Weights Double-Flange Duct Connection E-Box Main Disconnect Switch
E-Box with Knockouts on Bottom E-Box Low Voltage Terminal Strip 24 VAC Power
Supply Transformer Dry Contactors and Overload Relays Clean Filter Pressure
Drop Table (in. w.g.) Fan Belt Tensioning Fan Pillow Block End View of Core
Support Assembly LE8XINH and LE8XINV Service Parts Fan and Motor Sled Plenum
Divider Panels Filter Extractor Hook Typical Spring-Type Vibration Isolator
Filter Spacers Air Flow Test Port Door Latch Adjustment Air Flow Test Port
Location Table of Sheave Adjustments Two-Belt Adjustable Sheave (typ)
3 7 8 9 10 11 11 12 12 14 14 14 15 15 15 15 15 15 15 16 16 16 16 16 17 17 20
21 21 21 24 26 32 33 35 36 37 38 38 39 39 39 40 40 40 41 41
1.800.627.4499 INSTALLATION, OPERATION AND MAINTENANCE MANUAL RENEWAIRE.COM 5
LE8XIN ERV
CONFIGURATION CODE FOR LE8XIN MODELS
Note: Not all options are available on every model.
MODEL NUMBER DIGIT NUMBER
LE
J
—
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25
Digits 15: “LE-6X” “LE-8X” “LE10X”
Model
Digits 78: Location “IN” = Indoor “RT” = Rooftop
Digit 9:
Orientation
“V”, “H” (Indoor Units)
“V”, “H”, “R”, “F” (Rooftop Units)
Digit 10:
Vibration Isolation
“N” = Neoprene Isolators
“S” = Spring Isolators
Digit 11:
Wall Type
“S” = Single
“D” = Double
Digit 18:
Flow Control
“-” = No Isolation Damper
“D” = Motorized Damper both Airstreams
“E” = Motorized Damper EA or RA Airstream
“F” = Motorized Damper FA or OA Airstream
Digit 19:
Unit Control (see Restrictions 6 & 7)
“A” = Standard Unit Control Wiring
“V” = Onboard VFD Both Airstreams
Digit 20:
Disconnect
“N” = Non-Fused (Standard)
“F” = Fused
Digit 21:
Unit Control Enhancements
“T” = Transformer with Isolation Relay (Standard)
“1” = Enhanced Controls
“2” = Premium Controls
“3” = Enhanced Controls with BACnet License
“4” = Premium Controls with BACnet License
Digit 12:
Phase (See Restriction 2)
“1” = Single Phase
“3” = Three Phase
Digit 22:
Filter Options (see Restriction 8)
“-” = None (Standard)
“F” = Filter Monitor Both Airstreams
Digit 13:
Voltage (see Restriction 1)
“4” = 460V
“5” = 208230V
“8” = 575V
Digit 14:
FA Horsepower (see Restrictions 2, 3 & 4)
“D” = 3 HP Low Speed
“F” = 3 HP Medium Speed
“G” = 3 HP High Speed
“J” = 5 HP Low Speed
“K” = 5 HP Medium Speed
“L” = 5 HP High Speed
“M” = 7.5 HP Low Speed
“N” = 7.5 HP Medium Speed
“P” = 7.5 HP High Speed
“Q” = 10 HP Medium Speed
“R” = 10 HP High Speed
Digit 23:
Flexible Packaging
“A” = Assembled (single piece flat bed)
“M” = Modular (two pieces for enclosed trailer)
Digit 24:
Paint and Customization
“-” = None
“W” = White Paint
“C” = Custom Paint
“X” = Custom Unit
Digit 25:
Safety Listing (see Restriction 5)
“L” = Listed
“N” = Non-Listed
Digit 15:
EA Horsepower (see Restrictions 2, 3 & 4)
“D” = 3 HP Low Speed
“F” = 3 HP Medium Speed
“G” = 3 HP High Speed
“J” = 5 HP Low Speed
“K” = 5 HP Medium Speed
“L” = 5 HP High Speed
“M” = 7.5 HP Low Speed
“N” = 7.5 HP Medium Speed
“P” = 7.5 HP High Speed
“Q” = 10 HP Medium Speed
“R” = 10 HP High Speed
NOTE: When the Configuration Code is printed on the unit label, it is identified as the “Option Code”. See illustration on Page 3.
*NOTES: Digit 6 “J” = G5 Core Type. Digits 16 and 17 are not used in these models.
Restrictions: 1: Voltage Codes “4” & “8” only available with Phase Code “3”
(Three-Phase). 2: Phase Code “1” only available in Motor Codes “D”, “F”, &
“G”. 3: Motor Code “P” (7.5 HP High Speed) not available in LE-6X. 4: Motor
Codes “Q” and “R” (all 10 HP Speeds) not available in LE-6X & LE-8X. 5: Some
units with Customization Code “X” are not safety listed. 6: Unit Control Code
“V” only available with Motor Codes “G”, “L”, & “N” in LE-6X. 7: Unit Control
Code “V” only available with Motor Codes “G”, “L”, “P”, & “R” in LE-8X &
LE10X. 8: Filter Code “F” not available with Unit Control Enhancements Codes
“1”, “2”, “3”, & “4”. Filter Monitor is provided with those options.
6 RENEWAIRE.COM INSTALLATION, OPERATION AND MAINTENANCE MANUAL 1.800.627.4499
HLEE 8XINH
Energy Recovery Ventilator Standard
INDOOR UNIT
SPECIFICATIONS
LE8XINV shown Energy Recovery Core is AHRI Certified®
AIRFLOW PERFORMANCE
Ventilation Type: Static plate, heat and humidity transfer
Typical Airflow Range: 2,000-8,800 CFM
AHRI 1060 Certified Core: Eight L125-G5
Standard Features: TEFC Premium efficiency motors Motor starters Non-fused
disconnect 24 VAC transformer/relay package Cross-core differential pressure
ports
Filters: Total qty. 16, MERV 8: 20″ x 25″ x 2″
Unit Weight: Modular (per module) 1,214-1,672 lbs., varies by option(s)
Assembled (1-piece) 2,479-3,279 lbs., varies by option(s)
Max. Shipping Dimensions & Weight (on pallet): Modular (2-modules) 100″ L x
90″ W x 78″ H
Module 1 – 1,852 lbs., Module 2 – 1,789 lbs. Assembled (1-piece) 200″ L x 90″
W x 78″ H –
3,638 lbs.
Motor(s): Qty. 2, Belt drive blower/standard motor packages
with choice of adjustable sheaves for low, medium or high blower speed (see
table below)
Options: Spring vibration isolators Onboard variable frequency drives (VFDs) –
both airstreams Shaft grounding ring on motors with VFDs Fused disconnect
Integrated programmable controls –
enhanced, premium Class 1 low leakage motorized isolation dampers –
OA, RA or both airstreams Qty. 2, Factory mounted filter alarms –
both airstreams Double wall construction Exterior paint – white, custom colors
Accessories: Filters – MERV 13, 2″ or 4″; MERV 8, 4″ (shipped loose) Automatic
balancing damper – 4″, 5″, 6″ Digital time clock – wall mount (TC7D-W),
in exterior enclosure (TC7D-E) Carbon dioxide sensor/control –
wall mount (CO2-W), duct mount (CO2-D) IAQ sensor – wall mount (IAQ-W),
duct mount (IAQ-D) Motion occupancy sensor/control –
ceiling mount (MC-C), wall mount (MC-W) Smoke Detector – duct mount (SD-D)
Electric duct heater – EK series (1175 kW) Indirect gas-fired duct furnace –
GH series
(50-400 MBH), installed downstream of any fans
External Static Pressure (in.w.g.)
Airflow CFM
0.00
0.25
0.50
BHP RPM BHP RPM BHP RPM
0.75
1.00
BHP RPM BHP RPM
3 HP LOW SPEED
1.25
BHP RPM 3 HP MED SPEED
2000
1.0 680 1.3 790 1.5 870
3000
1.1 640 1.4
4000
1.6 710 1.9
4500
1.5 660 1.8 740 2.2
5000
1.7 690 2.1 770 2.5
5500
1.7 650 2.0 730 2.4 800 2.8
6000
1.9 690 2.3 760 2.7 830 3.1
6250 6500 6750 7000
3 HP LOW SPEED
2.1 2.3 2.4 2.6
710 720 740 760
2.5 2.7 2.9 3.1
780 790 810 830
2.9 3.1 3.3 3.5
840 860 870 890
3.3 3.6 3.8 4.0
7250
2.8 780 3.3 850 3.7 910 4.3
7500
3.0 800 3.5 860 4.0 920 4.5
7750
3.2 820 3.7 880 4.2 940 4.8
8000
3.5 840 4.0 900 4.5 960 5.1
8250 5 HP 3.7 860 4.2 920 4.8 970 5.4
8500 LOW 4.0 880 4.5 930 5.1 990 5.7 8800 SPEED 4.3 900 4.9 960 5.5 1010 6.1
5 HP MED 7.5 HP LOW
SPEED
SPEED
Note: Airflow performance includes effect of clean, standard filter supplied with unit.
740 1.7 820 2.0 790 2.2 860 2.6 810 2.5 880 2.9 840 2.8 900 3.2 860 3.2 930
3.6 890 3.6 950 4.0 910 3.8 960 4.3 920 4.0 980 4.5 930 4.3 990 4.8 950 4.5
1000 5.0 960 4.8 1020 5.3 980 5.0 1030 5.6 990 5.3 1050 5.9 1010 5.6 1060 6.2
1030 5.9 1080 6.5 1040 6.3 1090 6.9 1060 6.7 1110 7.3
7.5 HP MED SPEED
890 920 940 960 980 1010 1020 1030 1040 1060 1070 1080
1100 1110 1120 1140 1150
1.50
1.75
2.00
BHP RPM BHP RPM BHP RPM
3 HP HIGH SPEED
1.8 940 2.0 1000 2.2 1060
2.3 960 2.6 1020 2.9 1070
2.9 3.2 3.6 4.0
990 1000 1020 1040
3.2 3.6 4.0 4.5
1040 1060 1070 1090
3.6 4.0 4.5 4.9
1100 1110 1130 1140
5 HP HIGH SPEED
4.5 1060 5.0 1110 5.5 1160 7.5 HP
4.7 1070 5.2 1120 5.7 1170
5.0 5.3 5.6 5.8
1080 1100 1110 1120
5.5 5.8 6.1 6.4
1130 1140 1160 1170
6.0 6.3 6.6 7.0
1180 1190 1200 1210
7.5 HP HIGH SPEED
6.2 1130 6.7 1180 7.3 1220
6.5 1140 7.1 1190
6.8 1160 7.4 1200 7.1 1170 7.5 1180
ELECTRICAL DATA
Standard Electrical Specifications
Max.
HP
Volts
HZ
Phase
FLA Min. Cir. per motor Amps
Overcurrent Protection
Device
3.0 208-230 60 Single 14.7-14 33.1
40
208-230 60 Three 9.38-8.48 21.1
25
3.0 460 60 Three 4.24
9.5
15
575 60 Three
3.3
7.4
15
208-230 60 Three 14.5-13.4 32.6
45
5.0 460 60 Three
6.7
15.1
20
575 60 Three
5.3
11.9
15
208-230 60 Three 21.0-19.0 47.3
60
7.5 460 60 Three
9.5
21.4
25
575 60 Three
7.6
17.1
20
Optional Factory Installed VFD Electrical Specifications
FLA per motor
Min. Cir. Amps
Max. Overcurrent Protection
Device
9.38-8.48 40.2
45
9.38-8.48 23.2
25
4.24
10.5
15
3.3
8.2
15
14.5-13.4 35.9
45
6.7
16.6
20
5.3
13.1
15
21.0-19.0 52.0
60
9.5
23.5
25
7.6
18.8
20
1.800.627.4499 INSTALLATION, OPERATION AND MAINTENANCE MANUAL RENEWAIRE.COM 7
8 RENEWAIRE.COM INSTALLATION, OPERATION AND MAINTENANCE MANUAL 1.800.627.4499
LE8XINH Energy Recovery Ventilator Standard
69 3/4″ Minimum Service Area
Door Door Swing Swing
EA
OA
FA
RA
ABBREVIATIONS EA: Exhaust Air to outside OA: Outside Air intake RA: Room Air to be exhausted FA: Fresh Air to inside INSTALLATION ORIENTATION Unit must be installed in orientation shown. NOTE 1.UNLESS OTHERWISE SPECIFIED, DIMENSIONS ARE ROUNDED TO THE NEAREST EIGHTH OF AN INCH. 2.SPECIFICATIONS MAY BE SUBJECT TO CHANGE WITHOUT NOTICE. 3.MIN. DUCT CLEARANCE FROM DAMPER BLADES WHEN FULLY OPENED TO BE 2″. SMACNA RULES APPLY.
36″ E-Box Minimum Service Area
Door Door Swing Swing
78 1/2″ Minimum
Blower Service Area Typ.
48″ X 24″ Duct Receiving
Flange Typ.
13 3/8″ X 15 1/2″ Electrical Connection Cover
64 5/8″
27 3/4″
E-Box
Disconnect Switch
53 1/2″
71 1/8″ Overall 69 5/8″ Case 41 1/8″
27 3/4″
CL 11 3/8″ (5) 1 1/8 Knockouts
LEFT VIEW
AIRFLOW ORIENTATION
MAovadilaeblle: aLsEs8hoXwInNinHdimension drawing. Drawing Type: Unit
Dimension Version: MAY18
29 5/8″
CL 5 1/4″ (2) 7/8″ Knockouts
111″ Minimum Service Area
TOP VIEW
80 3/8″ Overall 5″ Damper
Frames Typ.
EA
Pressure Ports (4) Typ.
OA
RA Inlet 48″ X 24″ Duct Receiving Flange
164 7/8″ Overall
161 3/8″ Case
OA Inlet 48″ X 24″ Duct Receiving Flange
OA Damper Location (Optional)
41 5/8″
8 7/8″ Typ.
4 ”
FA
2″ CL 2 1/4″
Wiring
69 1/4″ Case CL 73 3/8″ Lift Lugs
FRONT VIEW
RA
2″ Typ.
27 3/8″
RA Damper Location (Optional)
27 3/8″
RIGHT VIEW
UNIT MOUNTING & APPLICATION
Must be mounted as shown. RA/EA airstream can be switched with OA/FA airstream
unless certain options are selected.
HLEE 8XINV
Energy Recovery Ventilator Standard
INDOOR UNIT
SPECIFICATIONS
Energy Recovery Core is AHRI Certified® AIRFLOW PERFORMANCE
Ventilation Type: Static plate, heat and humidity transfer
Typical Airflow Range: 2,000-8,800 CFM
AHRI 1060 Certified Core: Eight L125-G5
Standard Features: TEFC Premium efficiency motors Motor starters Non-fused
disconnect 24 VAC transformer/relay package Cross-core differential pressure
ports
Filters: Total qty. 16, MERV 8: 20″ x 25″ x 2″
Unit Weight: Modular (per module) 918-1,984 lbs., varies by option(s)
Assembled (1-piece) 2,495-3,295 lbs., varies by option(s)
Max. Shipping Dimensions & Weight (on pallet): Modular (2-modules) 100″ L x
90″ W x 78″ H
Module 1 – 2,164 lbs., Module 2 – 1,493 lbs. Assembled (1-piece) 200″ L x 90″
W x 78″ H –
3,654 lbs.
Motor(s): Qty. 2, Belt drive blower/standard motor packages
with choice of adjustable sheaves for low, medium or high blower speed (see
table below)
Options: Spring vibration isolators Onboard variable frequency drives (VFDs) –
both airstreams
Shaft grounding ring on motors with VFDs Fused disconnect Integrated
programmable controls –
enhanced, premium Class 1 low leakage motorized isolation dampers –
OA, RA or both airstreams Qty. 2, Factory mounted filter alarms –
both airstreams Double wall construction Exterior paint – white, custom colors
Accessories: Filters – MERV 13, 2″ or 4″; MERV 8, 4″ (shipped loose) Automatic
balancing damper – 4″, 5″, 6″ Digital time clock – wall mount (TC7D-W),
in exterior enclosure (TC7D-E) Carbon dioxide sensor/control –
wall mount (CO2-W), duct mount (CO2-D) IAQ sensor – wall mount (IAQ-W),
duct mount (IAQ-D) Motion occupancy sensor/control –
ceiling mount (MC-C), wall mount (MC-W) Smoke Detector – duct mount (SD-D)
Electric duct heater – EK series (1175 kW) Indirect gas-fired duct furnace –
GH series
(50-400 MBH), installed downstream of any fans
External Static Pressure (in.w.g.)
Airflow CFM
0.00 BHP RPM
0.25 BHP RPM
0.50 BHP RPM
0.75
1.00
BHP RPM BHP RPM
3 HP LOW SPEED
1.25
BHP RPM 3 HP MED SPEED
2000
1.0 680 1.3 790 1.5 870
3000
1.1 640 1.4 740 1.7 820 2.0 890
4000
1.6 710 1.9 790 2.2 860 2.6 920
4500
1.5 660 1.8 740 2.2 810 2.5 880 2.9 940
5000
1.7 690 2.1 770 2.5 840 2.8 900 3.2 960
5500
1.7 650 2.0 730 2.4 800 2.8 860 3.2 930 3.6 980
6000
1.9 690 2.3 760 2.7 830 3.1 890 3.6 950 4.0 1010
6250 6500 6750 7000
3 HP LOW SPEED
2.1 2.3 2.4 2.6
710 2.5 780 720 2.7 790 740 2.9 810 760 3.1 830
2.9 3.1 3.3 3.5
840 860 870 890
3.3 910 3.6 920 3.8 930 4.0 950
3.8 960 4.3 1020 4.0 980 4.5 1030 4.3 990 4.8 1040 4.5 1000 5.0 1060
7250
2.8 780 3.3 850 3.7 910 4.3 960 4.8 1020 5.3 1070
7500
3.0 800 3.5 860 4.0 920 4.5 980 5.0 1030 5.6 1080
7750
3.2 820 3.7 880 4.2 940 4.8 990 5.3 1050 5.9 1100
8000
3.5 840 4.0 900 4.5 960 5.1 1010 5.6 1060 6.2 1110
8250 5 HP 3.7 860 4.2 920 4.8 970 5.4 1030 5.9 1080 6.5 1120
8500 LOW 4.0 880 4.5 930 5.1 990 5.7 1040 6.3 1090 6.9 1140
8800 SPEED 4.3 900 4.9 960 5.5 1010 6.1 1060 6.7 1110 7.3 1150
5 HP MED SPEED
7.5 HP LOW SPEED
7.5 HP MED SPEED
Note: Airflow performance includes effect of clean, standard filter supplied with unit.
1.50
1.75
2.00
BHP RPM BHP RPM BHP RPM
3 HP HIGH SPEED
1.8 940 2.0 1000 2.2 1060
2.3 960 2.6 1020 2.9 1070
2.9 3.2 3.6 4.0
990 1000 1020 1040
3.2 3.6 4.0 4.5
1040 1060 1070 1090
3.6 4.0 4.5 4.9
1100 1110 1130 1140
5 HP HIGH SPEED
4.5 1060 5.0 1110 5.5 1160 7.5 HP
4.7 1070 5.2 1120 5.7 1170
5.0 5.3 5.6 5.8
1080 1100 1110 1120
5.5 5.8 6.1 6.4
1130 1140 1160 1170
6.0 6.3 6.6 7.0
1180 1190 1200 1210
7.5 HP HIGH SPEED
6.2 1130 6.7 1180 7.3 1220
6.5 1140 7.1 1190
6.8 1160 7.4 1200
7.1 1170
7.5 1180
ELECTRICAL DATA
Standard Electrical Specifications
Max.
HP
Volts
HZ
Phase
FLA per motor
Min. Cir. Amps
Overcurrent Protection
Device
3.0 208-230 60 Single 14.7-14 33.1
40
208-230 60 Three 9.38-8.48 21.1
25
3.0 460 60 Three 4.24
9.5
15
575 60 Three
3.3
7.4
15
208-230 60 Three 14.5-13.4 32.6
45
5.0 460 60 Three
6.7
15.1
20
575 60 Three
5.3
11.9
15
208-230 60 Three 21.0-19.0 47.3
60
7.5 460 60 Three
9.5
21.4
25
575 60 Three
7.6
17.1
20
Optional Factory Installed VFD Electrical Specifications
FLA per motor
Min. Cir. Amps
Max. Overcurrent Protection
Device
9.38-8.48 40.2
45
9.38-8.48 23.2
25
4.24
10.5
15
3.3
8.2
15
14.5-13.4 35.9
45
6.7
16.6
20
5.3
13.1
15
21.0-19.0 52.0
60
9.5
23.5
25
7.6
18.8
20
1.800.627.4499 INSTALLATION, OPERATION AND MAINTENANCE MANUAL RENEWAIRE.COM 9
10 RENEWAIRE.COM INSTALLATION, OPERATION AND MAINTENANCE MANUAL 1.800.627.4499
LE8XINV Energy Recovery Ventilator Standard
69 3/4″ Minimum Service Area
Door Door Swing Swing
RA
OA
FA
EA
36″ E-Box Minimum Service Area
Door Swing
Door Swing
34″ Minimum Service Area
ABBREVIATIONS EA: Exhaust Air to outside OA: Outside Air intake RA: Room Air to be exhausted FA: Fresh Air to inside INSTALLATION ORIENTATION Unit must be installed in orientation shown. NOTE 1.UNLESS OTHERWISE SPECIFIED, DIMENSIONS ARE ROUNDED TO THE NEAREST EIGHTH OF AN INCH. 2.SPECIFICATIONS MAY BE SUBJECT TO CHANGE WITHOUT NOTICE. 3.DUCT CLEARANCE FROM DAMPER BLADES WHEN FULLY OPENED TO BE 2″. SMACNA RULES APPLY.
78 1/2″ Minimum Blower
Service Area
RA Inlet 48″ X 24″ Duct Receiving
Flange
26 1/4″
13 3/8″ X 15 1/2″ Electrical Connection Cover
64 5/8″
27 3/4″
111″ Minimum Service Area
TOP VIEW
E-Box
Disconnect Switch
5″ Damper Frames Typ.
RA
81 1/2″ Overall
Pressure Ports (4) Typ.
OA
9″ Typ.
4 ”
53 1/2″
71 1/8″ Overall 69 5/8″ Case
RA Damper Location (Optional)
CL 11 3/8″ (5) 1 1/8 Knockouts
LEFT VIEW
MDAAvIraoRailadFwbLleeiOnal:sW gLshEToO8wyRXnpiIIneNEd:NVimUTenAnsTiitoInODdNirmawiengn. sion Version: MAY18
29 5/8″
CL 5 1/4″ (2) 7/8″ Knockouts
FA
CL 2 1/4″ Wiring
69 1/4″ Case CL 73 3/8″ Lift Lugs
FRONT VIEW
EA
2″ Typ. 2″ Duct Flange Typ.
27 5/8″
OA Damper Location (Optional)
164 7/8″ Overall 161 3/8″ Case
OA Inlet 48″ X 24″ Duct Receiving Flange
41 3/4″ Typ.
48″ X 24″ Duct Receiving Flange Typ.
RIGHT VIEW
26 1/4″
UNIT MOUNTING & APPLICATION
Must be mounted as shown. RA/EA airstream can be switched with OA/FA airstream
unless certain options are selected.
OVERVIEW
LE8XIN ERV
1.0 OVERVIEW
1.1 DESCRIPTION
The LE8XIN ERV is a total enthalpy energy recovery ventilator. It recovers
both sensible and latent energy from a building Exhaust Airstream and
transfers that energy into a fresh Outdoor Air stream, which it then
introduces into the building Supply Air. The result is a constant supply of
fresh outdoor air in the Occupied Space with very little energy loss,
enhancing Indoor Air Quality (IAQ). Each ERV has enthalpic cores through which
both the EA and SA airstreams pass and each air stream has its own fan
motor/blower. Each ERV has a high voltage control panel and a separate low
voltage terminal strip for connection to user-specified control devices.
Fan speed can be adjusted either by means of adjustable sheaves on the fan
motors, by means of an optional VFD or a combination of microprocessor
controls and a VFD. Several control options are offered for the unit. See
Section 2.7 Optional Control Accessories.
1.2 FACTORY ASSEMBLY OF MODULES The LE8XIN ERV is built as two modules that
are to be assembled in the field. The customer may optionally order the
modules to be assembled into one unit in the factory. See Digit 23 of the
Configuration Code.
1.3 MODELS
The LE8XIN is offered in two different models, the LE8XINH and the LE8XINV.
The LE8XINH and the LE8XINV are both for indoor installations and differ from
each other in the location of the air stream ducting. Each of the indoor
models has an optional alternate duct connection. See below.
1.3.1 LE8XINH The LE8XINH features Outside Air (OA) and Room Air (RA) on one
side of the unit and Exhaust Air (EA) and Fresh Air (FA) on the other side.
The standard duct configuration and the optional alternate duct configurations
are shown below.
RA = Room Air into unit OA = Outside Air into unit FA = Fresh Air to inside EA
= Exhaust Air to outside
NOTE: This unit is an Energy Recovery Ventilator. It is commonly referred to
throughout this manual as an “ERV”.
NOTE: There is also a rooftop version of this ERV, known as the LE8XRT. It has
a separate manual.
EA
OA FA
RA
FA
RA EA
OA
Duct Connections as Labeled
LE8XINH Standard Duct Configuration
Room Air (RA) enters lower right side of unit. Exhaust Air (EA) exits upper
left side of unit. Outside Air (OA) enters upper right side of unit. Fresh Air
(FA) exits lower left side of unit.
Alternate Duct Connections
LE8XINH Alternate Duct Configuration
Room Air (RA) enters upper right side of unit. Exhaust Air (EA) exits lower
left side of unit. Outside Air (OA) enters upper left side of unit. Fresh Air
(FA) exits lower right side of unit.
The LE8XINH is always supplied from the factory in the Standard Configuration, as shown above. If the optional Alternate Duct Configuration is desired, specify FA and EA dampers and motor horsepower for the “opposite” airstreams. Keep this reversal in mind when making control connections. Also note that the addition of certain options to the unit may not permit selection of the alternate duct connections.
1.800.627.4499 INSTALLATION, OPERATION AND MAINTENANCE MANUAL RENEWAIRE.COM 11
LE8XIN ERV
1.3.2 LE8XINV The LE8XINV features Outside Air (OA) and Exhaust Air (EA) on
one side of the unit and Room Air (RA) and Fresh Air (FA) on the other side.
The standard duct configuration and the optional alternate duct configurations
are shown below.
RA = Room Air into unit OA = Outside Air into unit FA = Fresh Air to inside EA
= Exhaust Air to outside
RA
OA OA
RA
FA
EA
EA
FA
Duct Connections as Labeled
LE8XINV Standard Duct Configuration
Room Air (RA) enters upper left side of unit. Exhaust Air (EA) exits lower
right side of unit. Outside Air (OA) enters upper right side of unit. Fresh
Air (FA) exits lower left side of unit.
Alternate Duct Connections
LE8XINV Alternate Duct Configuration
Room Air (RA) enters upper right side of unit. Exhaust Air (EA) exits lower
left side of unit. Outside Air (OA) enters upper left side of unit. Fresh Air
(FA) exits lower right side of unit.
The LE8XINV is always supplied from the factory in the Standard Configuration, as shown above. If the optional Alternate Duct Configuration is desired, specify FA and EA dampers and motor horsepower for the “opposite” airstreams. Keep this reversal in mind when making control connections. Also note that the addition of certain options to the unit may not permit selection of the alternate duct connections.
12 RENEWAIRE.COM INSTALLATION, OPERATION AND MAINTENANCE MANUAL 1.800.627.4499
COMPONENT DESCRIPTION
LE8XIN ERV
COMPONENT DESCRIPTION
CABINET CONSTRUCTION
The LE8XIN is available in either single-wall or double-wall construction. See
Digit 11 of the Configuration Code. The sheet metal exterior of the unit is
constructed of 20 gauge galvanized steel, if left unpainted. All units are
lined with 2 inches of high density fiberglass insulation in the floor of the
unit and 1 inch of insulation elsewhere. The insulation used has an R-value of
4.3 per inch. All units are equipped with lifting lugs for hoisting by a crane
and all units have integral openings located in the unit base for use of a
fork lift. Each unit is equipped with hinged access doors on both ends.
2.1.1 Cabinet Paint
Three options are offered for exterior finishes of the unit. See Digit 24 of
the Configuration Code. · None (galvanized) · White paint · Custom paint
2.2 FAN MOTORS
Each LE8XIN unit is equipped with 2 belt-drive blower / motor packages as
standard. The motors are TEFC Premium Efficiency. Motor sizes are specified by
the customer at time of order. See Digits 14 and 15 of the Configuration Code.
The motor and blower assembly is mounted on rails with either neoprene
vibration isolators or spring vibration isolators, depending on the option
selected at time of order. See Digit 10 of the Configuration Code.
2.3 FAN SPEED CONTROL
Fan speed control is accomplished by either adjustable sheaves on the fan
motors, by an optional VFD or a combination of a VFD and microprocessor
controls. Units equipped with VFDs have fixed-diameter sheaves. See Digit 19
of the Configuration Code. 2.4 DAMPERS
Dampers are specified by the customer at time of order. Order options are: ·
None · Dampers both airstreams · Damper EA/RA airstream · Damper FA/OA
airstream
See digit 18 of the Configuration Code.
2.5 ENTHALPIC CORE
Every LE8XIN ERV is equipped with eight L125-G5 enthalpic cores. All cores are
similar in construction. See Digit 6 of the Configuration Code.
2.6 FILTERS
Filters are an essential part of the ERV and the ERV should never be operated
without properly installed filters. Filters are typically shipped loose inside
the unit. The standard filter is a 2 inch thick MERV 8. Optionally available
are 4 inch thick MERV 8, 2 inch thick or 4 inch thick MERV 13 filters.
2.6.1 Filter Monitors
LE8XIN ERVs can be ordered with optional filter monitors. When the monitor
system detects increased pressure drop across the filters, it provides an
indication that the air filters are partially clogged and require changing.
See digit 22 of the Configuration Code. Note that units ordered with
integrated programmable controls have filter monitoring supplied.
The cores used in all ERVs are 5th generation, static plate enthalpic cores. They are commonly referred to in this manual as “cores”.
1.800.627.4499 INSTALLATION, OPERATION AND MAINTENANCE MANUAL RENEWAIRE.COM 13
COMPONENT DESCRIPTION
LE8XIN ERV
2.7 CONTROLS
RenewAire offers five different control options for the ERV, ranging from the
basic factory-installed 24 VAC, 75 VA transformer with isolation relay to a
Premium Integrated Microprocessor control package with BACnet license. See
digit 21 of the Configuration Code. For further information on RenewAire
microprocessor controls, see the RenewAire Integrated Microprocessor Controls
manual.
When using the standard factory-installed transformer with an isolation relay,
the ERV can be configured with a number of different control accessories that
must be field-installed and wired to the low voltage terminal strip. See
Section 2.8 Optional Control Accessories. These accessories serve as simple
ON/OFF control devices. Example: The digital time clock will simply activate
and deactivate the unit at user-selected times.
When optional VFDs are ordered and there is no microprocessor controller, the
optional CO2 sensor or the optional IAQ sensor may be wired directly to the
VFD, producing modulation of the unit. The sensors must be wired in accordance
with instructions provided with the factory-installed VFD package.
2.7.1 Integrated Microprocessor Controls RenewAire offers an integrated
microprocessor controller as an option for ERVs. It is available in either an
Enhanced or a Premium version. See the RenewAire Integrated Microprocessor
Controls Manual for further information. The controller is a multi-function
device that monitors both the operation of the ERV and air conditions in the
Occupied Space. It evaluates conditions such as temperatures, air flows and
air quality and then modulates the operation of the ERV to meet owner-
specified set points. The controller can function as a stand-alone device or
it can also be connected to a BMS.
RenewAire Microprocessor Controller
RenewAire Microprocessor Controller Expansion Board
Premium Microprocessor Controls Installed 14 RENEWAIRE.COM INSTALLATION, OPERATION AND MAINTENANCE MANUAL 1.800.627.4499
COMPONENT DESCRIPTION
LE8XIN ERV
2.7.2 Variable Frequency Drive
Optional VFD control of the fans provides continuous modulation of fan speed.
VFDs can be ordered for either the EA or the FA fan, or for both. The VFDs can
be used as stand-alone speed controllers or they can be used in conjunction
with either a BMS or with the Integrated Microprocessor Controls package. See
digit 19 of the Configuration Code.
Any fan motor that is controlled by a VFD will have a fixed sheave instead of a variable sheave.
Further information on the optional VFDs is to be found in the VFD manual supplied with the unit. If optional microprocessor controls are also ordered, the VFD manual is not included.
VFDs Mounted Inside ERV
VFD Keypads Found in E-Box
2.8 OPTIONAL CONTROL ACCESSORIES
RenewAire offers a number of control accessories as options that are to be field-installed and wired directly to the ERV low voltage terminal strip. When wired to the ERV low voltage terminal strip, each device functions as an ON/OFF switch for the ERV but they will not modulate the ERV. All of the optional control accessories shown in this section may also be ordered as part of an integrated microprocessor controls package. If they are ordered as part of a controls package, they are to be wired according to instructions provided with the Integrated Microprocessor Controls package. When they are used as part of a controls package, they will modulate the ERV or function as ON/OFF devices, depending on user programming.
2.8.1 Carbon Dioxide Control
RenewAire offers two different types of CO2 sensors as optional control accessories: room/wall mount and duct mount. These sensors can be wired directly to the low-voltage terminal strip and function as ON/OFF switching controllers or can modulate ERVs equipped with VFDs. See the description in Section 2.7 Controls. The CO2 sensor uses 4.44 VA.
Carbon Dioxide Sensor, Room/Wall Mount
Carbon Dioxide Sensor, Duct Mount
2.8.2 Digital Time Clock
A digital time clock is offered as an optional control device. It is available in either a panel mount or an exterior enclosure. Time clocks can be wired directly to the low voltage terminal strip and function as ON/OFF switching controllers. The time clock draws 2.4 VA.
Time clocks are typically not used when VFDs are installed. VFDs have an internal time clock.
Time Clock, Panel Mount
Time Clock, Exterior 1.800.627.4499 INSTALLATION, OPERATION AND MAINTENANCE MANUAL RENEWAIRE.COM 15
COMPONENT DESCRIPTION
LE8XIN ERV
2.8.3 Indoor Air Quality Sensor (IAQ) An Indoor Air Quality Sensor can be
purchased to continuously monitor indoor air quality based on levels of total
VOCs and function as an ON/OFF switch for the ERV or can modulate ERVs that
are equipped with a VFD. See the description in Section 2.7 Controls. It uses
0.84 VA.
IAQ Sensor, Room/Wall Mount
IAQ Sensor, Duct Mount
2.8.4 Motion Occupancy Control
A motion occupancy sensor is available as an optional control device in either ceiling mount or wall mount styles. These sensors can be wired directly to the low voltage terminal strip in the ERV and function as ON/OFF controllers. It uses 0.7 VA.
Ceiling Mount Occupancy Sensor
Wall Mount Occupancy Sensor
2.8.5 Smoke Detector
A duct-mounted smoke detector is available to monitor for smoke and act as an ON/OFF switch for the ERV. It draws 2.3 VA.
Smoke Detector 16 RENEWAIRE.COM INSTALLATION, OPERATION AND MAINTENANCE MANUAL 1.800.627.4499
3.0 UNIT WEIGHTS 3.1 LE8XINH CORNER WEIGHTS
COMPONENT DESCRIPTION
LE8XIN ERV
69.8″ Mounting Hole Centers
3/8″ Pre-drilled Mounting Holes
BASIC UNIT WEIGHTS (lbs.)
Motors
UNIT LF LR RR RF
73.5″ Lifting Lug LR
73.5″ Lifting Lug
LR
RR
BASIC UNIT WEIGHTS (lbs.)
MotorsRR
UNIT LF
LR
RR
3 HP
2480
732
637
517
5 HP
2493
724
693
526
3 HP
80
732
637
517
594
RF 5 HP
BA24S93IC U72N4 IT W693EIG5H26 TS 5(5l0bs.)
594 7.5 HP
2611
769
737
541
564
550MADoDtoITrIsONAL WEIGHUTSNFIOTR OPTLIOFNS (lbs.) LR
RR
RF
72.0″
Module Mounting Hole Centers
152.0″ Mounting Hole Centers
LR
RR
7.5 HP
2611
769
737
541
564Op3tiHonPs
UNIT 24L8F0 LR732 RR 6R37F
517
594
ADDITIONAL WEIGHTS FOR OPTIONS (lbs.) Double Wall
524
131
131
131
131
Options
UNIT LF
LR
RR
RF V5FDHsP
12 241903
1 724 0
6913
526
550
159.5″ Lifting Lug
Double Wall VFDs
RA or EA Damper
524
131
131
131
R1A31or7E.5A DHamPper
66 26311
1 769 20 73427
541
564
12
10
1
0
OA1 or FA Damper
66
1
3
42
20
66
3
1
20 ADDITIONAL Tota4l2Selected Weights WEIGHTS FOR OPTIONS (lbs.)
72.0″
Module Mounting Hole Centers
“A”
OA or FA Damper
66
1
Total Selected Weights
3
Options UNIT LF LR 42 Add t2h0e additional weights for options to the Basic Unit weights determined by motor size to determine Unit and Corner weights for a specific unit.
RR
RF
Add the additional weights for options to the Basic Unit weights determineDd
boyuble Wall
motor size to determine Unit and Corner weights for a specific unit.
524
131
131
131
131
Center of gravity: A=32″ B=80″ (+/- 2″)
VFDs
12
10
1
0
1
159.5″ Lifting Lug
“B”
LF
SPECIFICATIONS SUBJECT TO CHANGE WITHOUT NOTICE.
R”FA”
1/31/2014 MF
LF
RF
RA or EA Damper
66
3
1
20
42
CORNER WEIGHTS AT BASE RAIL MOUNTING HOLES
OA or FA Damper
66
1
3
42
20
CORNER WEIGHTS AT LIFTING LUGSTotal Selected Weights
SPECIFICATIONS SUBJECT TO CHANGE WITHOUT NOTICE.
1/31/2014 MF
Do not scale drawing
LE-8X-INH Corner Weights
DoAndotdsctahleedraadwidngitional weightsShfoereot p2toiofn4s to the Basic Unit weights determined by
RemneowtAoirre sLLizCe to determine ULnEi-t8Xa- nINdH_CCoOrRnNeErR_wWeEiIgGhHtTsS_foMrAYa18s.dpwegcific unit.
LE-8X-INH Sheet 1 of
Corner 4
WeCigehnttser
of
gravity:
A=32″
B=80″
(+/-
2″)
RenewAire LLC
LE-8X-INH_CORNER_WEIGHTS_MAY18.dwg
“B” LE8XINH Corner Weights
3.2 LE8XINV CORNER WEIGHTS
LF
RF
CORNER WEIGHTS AT LIFTING LUGS
73.5″ Lifting Lug
73.5″ Lifting LugMounting6H9.o8le”MCoteonrstersBASICUUNNM3IT/Io8Tu ”WnPtrELineFIg-GdHHriloTlelSedLs(Rlbs.) RR
BASBICAUSNIITCWUEINGHITTSW(lbEs.)IGHTS (lbs.)
RF Motors
UNIT LF LR RR RF
STOPECCHIFLARINCGATEIOWNITSHSOUUBTJENCOTRTIRCE.
LR
1/31/2014 MF LR
RR
3 HP
RR
5 HP
2495
727
2509
733
524
521
723 M3 HoPtors
524Do no52t2scale73d0ra5w3HinPHgP
2495 U7N31ILTE-5820XL-FIN51H7 CLo7R2r7ner WReRightsRF
2509 2743985She52e0 7t217 5o17f 4 572344
521
723
7.5 HP
2627
787
530
527
783 7.5 HP
2627
793
524
521
789
ADDITIONAL
WEIGHTS
FOR
RenewAire OPTIONS (lbs.)
LLCAD5DHITPIONAL
WEIGHT2S5F0O9LRE-O8PXT-I7INO3HN3S_C(lbOsR.) N52E4R_WEIG52H2TS_MA7Y3108.dwg
72.0″
Module Mounting Hole Centers
152.0″ Mounting Hole Centers
Options
Double Wall VFDs
UNIT LF
LR
RR
RFOp7t.io5nHs P
UNIT 2L6F27 LR 787 RR 5R3F0
527
783
524
131
131
131
131Double Wall
524
131
131
131
131
12
10
1
0
1 AVFDDsDITION1A2 L WE10IGHT1 S FO0R OP1TIONS (lbs.)
159.5″ Lifting Lug
159.5″ Lifting Lug
“A” “B”
RA or EA Damper
66
20
42
3
R1A oOr EpA tDiaomnpesr
66 UN20 IT 42 LF 3 LR1
OA or FA Damper
66
1
3
42
O2A0 or FA Damper
66
1
3
42
20
Total Selected Weights
Double Wall
Total Selected Weights
524
131
131
Add the additional weights for options to motor size to determine Unit and Corner
wtheeigBhatssicfoUr naitspweecigifhictsundiet.termmAdiondteodtrhsbeiyzaedtdVoitFidoenDtaeslrmweinigehUtsniftoar nodptCioonrsnetor
1wthe2eigBhatssicfoUr naitswp1eec0igifhictsundiet.termine1d
by
Center of gravity: A=32″ B=75″ (+/- 2″)
RA or EA Damper
66
20
42
72.0″
Module Mounting Hole Centers
OA or FA Damper
66
1
3
RR
131 0 3 42
RF
131 1 1 20
“A”
LF
RF
Total Selected Weights
LF
CORRFNER WEIGHTS AT LIFTING LUGSAdCdOthReNaEdRdWitioEnIGalHwTeSigAhTtsBfAoSrEopRtAioInLsMtOo UthNeTBINaGsicHOULnEitSweights determined by
motor size to determine Unit and Corner weights for a specific unit.
SPECIFICATIONS SUBJECT TO CHANGE WITHOUT NOTICE.
1/31/2014 MF
SPECIFICATIONS SUBJECT
1/31/42014 MF
TO CHANGE WITHOUT NOTDICoEn. ot scale drawing
“B”
RenewAire LLC
Center of gravity: A=32″ B=75″ (+/- 2″)
LE-8X-INV Sheet 1 of
Corner 4
WDoenigothstcsale
drawing
LE-8X-INV_CORNER_WEIRGeHnTeSw_AMirAe YL1L8C.dwg
LE-8X-INV Corner Weights Sheet 2 of 4
LE-8X-INV_CORNER_WEIGHTS_MAY18.dwg
LF
SPECIFICATIONS SUBJECT TO CHANGE WITHOUT NOTICE.
RF
1/31/2014 MF
CORNER WEIGHTS AT LIFTING LUGS
LE8XINV Corner Weights
1.800.627.44D9o9noINt SsTcaAlLeLdArTaIwOiNng, OPERATION ANDLSMEhA-IeN8eTXtE- N1IANoNVCf E4CMoArNnUeArLWREeNiEgWhAtsIRE.COM 17
RenewAire LLC
LE-8X-INV_CORNER_WEIGHTS_MAY18.dwg
SHIPPING / RECEIVING
LE8XIN ERV
4.0 SHIPPING / RECEIVING / HANDLING All ERVs are palletized and then shipped
by common carrier. It is the installer’s / customer’s responsibility to
coordinate delivery and properly handle the shipment during unloading and
storage. RenewAire also provides a manual for shipping, rigging, lifting and
assembly of LE units that is available online at
www.renewaire.com.
CAUTION
RISK OF DAMAGE TO ERV CABINET Whenever the ERV is rigged for hoisting, ALL
LIFTING LUGS must be used. If the ERV modules have already been joined, all
eight lifting lugs must be used to avoid wracking or twisting the cabinet. See
the shipping, rigging, lifting and assembly manual for detailed information.
4.1 UNIT WEIGHTS / DIMENSIONS 4.1.1 Unit Dimensions and Weight For unit
dimensions and weight, see the RenewAire product submittal. Also see Sections
3.3 and 3.4 Corner Weights in this manual. 4.1.2 Shipping Dimensions and
Weight For unit shipping dimensions and weight, see the RenewAire product
submittal. Also see Sections 3.3 and 3.4 Corner Weights in this manual. 4.2
RECEIVING Upon delivery of the ERV, inspect it carefully for shipping damage
and completeness. Verify the presence of any accessories such as external
hoods that are to be field-installed or filters that are shipped loose. If
shipping damage is discovered, take digital pictures and note the visible
damage on the shipping manifest. Notify your RenewAire dealer immediately. 4.3
RIGGING For rigging instructions, refer to the LE manual for shipping,
rigging, lifting and assembly that is also available online at
www.renewaire.com.
4.4 HANDLING AND STORAGE ERVs that are delivered to a job site should ideally
be placed and installed immediately. If the ERV cannot be installed
immediately, the unit should be protected from the weather, either by moving
it indoors or by covering with tarps. When placing the ERV on the ground, the
placement area should be flat and level. Take care to avoid twisting or
wracking of the unit.
18 RENEWAIRE.COM INSTALLATION, OPERATION AND MAINTENANCE MANUAL 1.800.627.4499
UNIT PLACEMENT
LE8XIN ERV
5.0 UNIT PLACEMENT 5.1 SOUND ATTENUATION OUTSIDE THE BUILDING The exhaust hood
is the primary source of noise outside the building. When practical, orient
the exhaust air hood on external building walls to point away from houses or
public areas. 5.2 PLACEMENT CAUTIONS ERVs are typically placed in a location
specified by others. There are a number of situations that may demand
relocation: · The outside air intake must be at least 10′ away from exhausts
such as dryer vents, chimneys,
furnace and water heater exhausts or other sources of contamination or carbon
monoxide. · Do not locate outside air intake where vehicles may be serviced or
left idling. · Never locate the outside air inlet inside a structure. · Do not
install the unit inside a garage or parking structure.
NOTICE
This ERV must be installed in compliance with SMACNA guidelines and all
applicable local building codes. 5.3 SERVICE CLEARANCES See Section 3.0 Unit
Drawings for required service clearances.
1.800.627.4499 INSTALLATION, OPERATION AND MAINTENANCE MANUAL RENEWAIRE.COM 19
UNIT PLACEMENT
LE8XIN ERV
Ducts inside a building that are connected to the outside must be insulated with a sealed vapor barrier on both the inside and the outside of the insulation.
INSTALLATION
ASSEMBLY OF MODULES Many ERVs are ordered pre-assembled at the factory. For
those units that are to be assembled in the field, follow the assembly
instructions found in the accompanying LE Models: Shipping, Rigging, Lifting,
Assembly manual, to be found in the documentation package shipped with each
unit and available online at www.renewaire.com.
6.2 DUCT CONNECTIONS
All duct connections to the sides of the unit are equipped with double-flanged
duct connections. These allow for connection of ductwork insulated on the
inside or the outside, or for installation of lined ducts.
If the unit has factory-installed dampers on the sides of the unit, no duct
flanges are provided at the dampers. Ducts can be attached directly to the
dampers.
Double-Flange Duct Connection
6.3 INDOOR SOUND ATTENUATION
Duct stiffness: Make sure the ductwork at the unit outlets is stiff enough to
resist the flexing and resulting booming noise associated with system start-up
and shutdown, as well as the turbulent flow conditions at the blower outlets.
In general, provide smooth transitions from the ERV outlets to the duct. The
ducts connecting to the outlets should be straight for a sufficient distance ,
with gradual transitions to the final duct size. These guidelines are
consistent with SMACNA recommended duct layout practices for efficient and
quiet air movement.
Radiated noise: LE units are insulated with high density fiberglass. This
provides significant attenuation of radiated sound from the unit itself.
The outlet ducts can be significant sources of radiated sound, as well. The FA
duct should be insulated for sound control. This insulation should start at
the unit. At a minimum, the first ten feet of duct should be insulated. All
parts of the FA and RA ducts located in a mechanical space with noise-
generating equipment should also be insulated for sound control, both to
minimize sound radiation out of the FA and RA ducts and also to control sound
radiation into both ducts.
20 RENEWAIRE.COM INSTALLATION, OPERATION AND MAINTENANCE MANUAL 1.800.627.4499
ELECTRICAL CONNECTIONS
LE8XIN ERV
6.4 ELECTRICAL CONNECTIONS
WARNING
ARC FLASH AND ELECTRIC SHOCK HAZARD
Arc flash and electric shock hazard. Disconnect all electric power supplies,
verify with a voltmeter that electric power is off and wear protective
equipment per NFPA 70E before working within electric control enclosure.
Failure to comply can cause serious injury or death. Customer must provide
earth ground to unit, per NEC, CEC and local codes, as applicable. Before
proceeding with installation, read all instructions, verifying that all the
parts are included and check the nameplate to be sure the voltage matches
available utility power. The line side of the disconnect switch contains live
high-voltage. The only way to ensure that there is NO voltage inside the unit
is to install and open a remote disconnect switch and verify that power is off
with a volt meter. Refer to unit electrical schematic. Follow all local codes.
6.4.1 Factory-Recommended Electric Service Entry
The underside of the E-Box has a set of knockouts for installation of high
voltage and low voltage wiring. High voltage wiring is to go through the
bottom of the E-box and be terminated on the terminals located on the top of
the disconnect switch.
Unit Fusing
Knockouts for Entry of High Voltage Service
Knockout for Entry of Low Voltage Control Wiring
Every ERV has an
electrical junction
box,
commonly
referred to as an
“E-Box”.
Grounding Lug
E-Box with Knockouts on Bottom
Low Voltage Terminal Strip
Disconnect Switch
Low Voltage In E-Box Low Voltage Terminal Strip
High Voltage In
E-Box Main Disconnect Switch
1.800.627.4499 INSTALLATION, OPERATION AND MAINTENANCE MANUAL RENEWAIRE.COM 21
Single Phase Wiring Schematic 22 RENEWAIRE.COM INSTALLATION, OPERATION AND MAINTENANCE MANUAL 1.800.627.4499
1 2 3 4 5 6 7 8 9 10 11 12 13
A
B
C
Input Power 208-230 VAC, 1 Phase
L1 L2 L3 GND
RD
BU
RD
BU F1
BK BK
RD
Exhaust
Contactor
Overload
1L1
2T1
3L2
4T2
RD
5L3
6T3
BU
24 VAC
A1 A2
95
YL RD
96 BU
Exhaust Relay
4
8
12
24 VAC
13 14
RD
YL
RD
Supply
Contactor
Overload
1L1
2T1
3L2
4T2
5L3
6T3
Transformer RD
24 VAC A1 A2
95 96
YL RD
Supply Relay
4
8
12
24 VAC
13 14 YL RD
BU
COM 24V
REV.
DATE
NAME
CHANGES
2
1/7/2019
austine
1
6/18/2018
austine
Added Wire Color Labels Updated Wire Colors
D
E
RD BU
Exhaust Fan
1 2 3 4 5
RD
BU
M
Supply Fan
Family Description
RenewAire
LE-6_LE10XJxxx-x15xx–xAxTx-xx No Dampers
of specific configurations.
Service for wiring diagrams
Customer
RenewAire
is as-built. Contact
attached to the unit
wiring schematic
reference only. The
This schematic is for
ELECTRICAL CONNECTIONS
LE8XIN ERV
6.5 WIRING SCHEMATICS
Three Phase Wiring Schematic 1.800.627.4499 INSTALLATION, OPERATION AND MAINTENANCE MANUAL RENEWAIRE.COM 23
1 2 3 4 5 6 7 8 9 10 11 12 13
A
B
C
D
E
Input Power
208-230 VAC, 3 Phase
460 VAC, 3 Phase
L1 L2 L3 GND
RD YL BU
RD YL BU F1
Exhaust
Contactor 1L1
Overload 2T1
RD
3L2
4T2
YL
5L3
6T3
BU
24 VAC A1 A2
95 96
GN
YL RD
BK
BK
Exhaust Relay
4
8
12
24 VAC
13 14
RD YL
Supply
Contactor 1L1
Overload 2T1
3L2
4T2
5L3
6T3
Transformer RD
24 VAC
A1 A2
95 96
YL RD
BU
Supply Relay
4
8
12
24 VAC
13 14 YL RD
BU
COM 24V
REV.
DATE
NAME
CHANGES
2
1/7/2019
austine
1
6/18/2018
austine
0
3/20/2018
austine
Added Wire Color Labels Updated Wire Colors New
RD
Exhaust Fan
YL
M
BU
GN
1 2 3 4 5
RD
Supply Fan
YL
BU
M
RenewAire
Family Description Config
RenewAire
LE-6_LE10XJxxx-x34,35xx–xAxTx-xx No Dampers LE-6_LE10XJxxx-x34,35xx—AxTx-
xx_002
of specific configurations.
Service for wiring diagrams
Customer
is as-built. Contact
attached to the unit
wiring schematic
reference only. The
This schematic is for
ELECTRICAL CONNECTIONS
LE8XIN ERV
ELECTRICAL CONNECTIONS
LE8XIN ERV
6.6 CONTROL CONNECTIONS Control wiring is to enter the E-Box through a
knockout at the bottom of the E-Box and is then terminated on the low voltage
terminal strip. See Section 6.5 Wiring Schematics for further information.
7.0 CONTROL CONTRACTOR INFORMATION Prior to connection and activation of any
external controls, the ERV is to be tested for correct operation. Verify that
all Pre Start-Up and Start-Up steps as described in Sections 8 and 9 of this
manual have been completed.
7.1 24 VAC CLASS II POWER SUPPLY This unit is equipped with a Class II 24 VAC
power supply transformer (see image below) that operates the unit’s
contactors, dampers and / or relays. The ERV’s 24 VAC, 75VA power supply can
also be used to power externally installed control systems requiring less than
8 VA of power. More power may be available on units not equipped with factory-
installed dampers. The transformer is located in the unit’s E-Box.
The unit’s power supply system includes isolation relays with contact ratings
as low as 50 mA (1.2 VA). It is also possible to operate the isolation relays
with 24 VAC power from an external source.
A built-in circuit breaker on the 24 VAC transformer prevents damage to the
transformer and other low voltage components in the event of a short-circuit
or overload. The transformer itself is designed to fail safely in extreme
cases.
Circuit Breaker Reset Button
24 VAC Power Supply Transformer
Transformer Specifications: Nominal output voltage under load: 24 VAC Typical
output voltage at no load: 29 – 31 V Minimum contact rating for connected
control device: 50 mA (1.2 VA) Circuit breaker trip point: 3.75 A
Limits of Class II Power Output: Control devices drawing a total of 8 VA may
be connected to the blue and red wires. More than one device may be connected.
Observe the following wire guidelines:
Wire Gauge
22 #20 #18 #16 #14 #12
Circuit Length 100′ 150′ 250′ 400′ 700′ 1000′
Resetting the Circuit Breaker: If the transformer is subjected to excessive load or a short circuit, the integral circuit breaker will trip.
Shut off the primary-side power to the unit and remove the excessive load or the short circuit. The circuit breaker can be reset about 15 seconds after it trips.
24 RENEWAIRE.COM INSTALLATION, OPERATION AND MAINTENANCE MANUAL 1.800.627.4499
ELECTRICAL CONNECTIONS
LE8XIN ERV
CAUTION
RISK OF DAMAGE TO POWER SUPPLY AND CONNECTED COMPONENTS UNITS WITH 230 VAC
POWER SOURCE: The ERV is shipped from the factory with the transformer set for
208 VAC primary power. If the actual power source is 230 VAC, move the black
primary-side lead from the transformer’s “208 V” terminal to the transformer’s
“230 V” terminal.
Connect only to components intended for use with a 24 VAC power supply.
Do not interconnect the unit’s Class II power supply with an external Class II
power supply.
Do not use undersized low voltage wiring to connect this device. Observe the
wire gauge / wire length chart on the previous page.
Do not overload the power supply. Verify that the combined load of all devices
connected to the power supply do not exceed 8 VA.
Any external 24 VAC power supply connected to this device must be connected to
the terminals as shown on the wiring schematics. Connect only Class II power
to the terminals on this unit.
This unit is not designed to accept analog control signals unless the unit is
equipped with Integrated Microprocessor controls and/or VFDs.
This unit is not designed to communicate directly with a Building Management
System (BMS) such as BACnet unless the unit is equipped with microprocessor
controls. The unit can be controlled by powered or non-powered contacts
operated by any kind of control system.
Units that are equipped with VFDs or optional Integrated Microprocessor
Controls can communicate directly with BACnet systems.
7.2 MOTOR PROTECTION 7.2.1 Units Equipped with Motor Starters Units that are
not equipped with optional VFD drives are supplied with IEC-style motor
starters to operate the motors and to protect the motors against overload.
IEC-style motor starters use overload relays (see image on following page) to
detect excessive current and interrupt the control circuit that engages the
motor’s contactors.
The overload relays are sized to Full Load Amp (FLA) rating of the protected
motor and can be adjusted to trip the control circuit at a specific setting
within a range. Overload relays should initially be set at the FLA rating of
the controlled motor. See the unit rating label. If the overload relays trip
at unit startup, they can be adjusted to trip at no higher than 115% of the
motor’s FLA rating.
NOTE: Units are factory-wired so that if one blower motor is shut down due to
starter overload, the second motor will also be shut down.
Terminals 96 and 97 on the overload relays and terminals 14 and 13 of the
contactors are Normally Open (NO) dry contacts and may be used to signal that
the contactors are closed and / or that the overload relays have tripped.
1.800.627.4499 INSTALLATION, OPERATION AND MAINTENANCE MANUAL RENEWAIRE.COM 25
ELECTRICAL CONNECTIONS
LE8XIN ERV
Dry Contactors
Relay Manual Reset Button
Overload Adjusting Screws
Dry Contactors and Overload Relays
Overload Relays
7.2.2 Units With Variable Frequency Drives (VFDs)
In units equipped with a VFD(s), motor overload protection is provided by the VFD. See separate documentation supplements.
NOTE: Some units are equipped with only one VFD, which controls a single motor. The second motor (without a VFD) is then protected by an overload relay as described before.
7.3 EXTERNAL CONTROL CONNECTIONS
External control wiring is to be terminated on the low voltage terminal strip
in the E-Box as shown in Section 6.4.1 of this manual.
7.3.1 Single 2 – Wire Control, Unpowered
Use the schematic below if the control requires no power from the ERV and acts
as a simple ON / OFF switch. The control must not supply any power to the ERV.
· Install jumper (provided) between terminals 2 and 3. · Connect the control’s
contacts to terminals 1 and 4 to operate the isolation relays for OA / FA
blower. · Install jumper between terminals 4 and 5 to operate the ERV’s
isolation relays for the RA / EA
blower.
A SWITCH OR NON-POWERED CONTROL USING UNIT’S 24VAC POWER SUPPLY
Connect Terminals 2 & 3 Connect Switch between Terminals 1 & 4
Connect Terminals 4 & 5
UNIT INTERNAL CONTROL WIRING (SIMPLIFIED)
Unit’s 24VAC
1
Power Supply
2
3
4
C Isolation Relay Coil (Fresh Air)
5
C Isolation Relay Coil (Exhaust Air)
Single 2-Wire Control, Unpowered
26 RENEWAIRE.COM INSTALLATION, OPERATION AND MAINTENANCE MANUAL 1.800.627.4499
ELECTRICAL CONNECTIONS
LE8XIN ERV
7.3.2 Single 2 – Wire Control, Separate Power
Use the schematic shown in Section 7.3.1 if the control is on a separate power
supply with no power present at control output. 7.3.3 Control Sending 24 VAC
“ON” Signal Use the schematic below if a 24 VAC “ON” signal is to be sent from
an external power source to the ERV. · Verify that a jumper is NOT installed
between terminals 2 and 3. 24 VAC can be safely applied to terminals 3 and 4
to operate the ERV’s isolation relay for the OA / FA blower. · Install a
jumper (provided) between terminals 4 and 5 to operate the ERV’s isolation
relay for the
RA / EA blower. · Supply only 24 VAC (not VDC) from a Class II power source.
24VAC FROM AN EXTERNAL SOURCE
UNIT INTERNAL CONTROL WIRING (SIMPLIFIED)
Connect Switch between Terminals 3 & 4 Connect Terminals 4 & 5
Unit’s 24VAC
1
Power Supply
2
3
4
C Isolation Relay Coil (Fresh Air)
5
C Isolation Relay Coil (Exhaust Air)
24 VAC From External Source
7.3.4 External Control Using ERV Power Supply
Use the schematic below if external control is to be applied using 24 VAC from
the ERV power supply. · External control system must not draw more than 8 VA.
· Install jumper (provided) between terminals 2 and 3. · Connect the switched
output of the control to terminal 4 to operate the ERV’s isolation relay for
the OA / FA blower. · Install jumper between terminals 4 and 5 to operate the
ERV’s isolation relay for the RA / EA
blower.
AN EXTERNAL CONTROL USING UNIT’S 24VAC POWER SUPPLY
24VAC Available at Terminals 1 & 2
MPU
Connect Terminals 2 & 3
Connect Terminals 4 & 5
UNIT INTERNAL CONTROL WIRING (SIMPLIFIED)
Unit’s 24VAC
1
Power Supply
2
3
4
C Isolation Relay Coil (Fresh Air)
5
C Isolation Relay Coil (Exhaust Air)
External Control Using ERV 24 VAC
7.3.5 Control with 2 Non-Powered Relay Contacts
Use the following schematic if the external control system provides no voltage
or current at its output contacts. · Install jumper between terminals 2 and 3.
· Connect one side of each of the output contacts to terminal 1. · Connect the
other side of the output contact to terminal 4 in order to control the FA
blower. · Connect the other side of the output contact to terminal 5 in order
to control the EA blower.
1.800.627.4499 INSTALLATION, OPERATION AND MAINTENANCE MANUAL RENEWAIRE.COM 27
ELECTRICAL CONNECTIONS
LE8XIN ERV
A SWITCH OR NON-POWERED CONTROL USING UNIT’S 24VAC POWER SUPPLY
Connect Terminals 2 & 3
UNIT INTERNAL CONTROL WIRING (SIMPLIFIED)
Unit’s 24VAC
1
Power Supply
2
3
4
C Isolation Relay Coil (Fresh Air)
5
C Isolation Relay Coil (Exhaust Air)
Control with 2 Non-Powered Relay Contacts
7.3.6 Control with 2 “ON” Signals, External Power
Use the following schematic if the controller is sending two 24 VAC “ON”
signals from an external power source. · Verify there is NO jumper between
terminals 2 and 3. · Apply one 24 VAC signal to terminals 3 and 4 to operate
the isolation relay for the FA blower. · Apply the second 24 VAC signal to
terminals 3 and 5 to operate the isolation relay for the EA
blower. · Verify that the polarity of each wire connected to terminal 3 is the
same.
TWO EXTERNAL RELAY CONTACTS SUPPLYING 24VAC FROM AN EXTERNAL SOURCE
UNIT INTERNAL CONTROL WIRING (SIMPLIFIED)
Unit’s 24VAC
1
Power Supply
2
3
4
C Isolation Relay Coil (Fresh Air)
5
C Isolation Relay Coil (Exhaust Air)
Control with 2 “ON” Signals, External Power
7.4 SEQUENCE OF OPERATION Basic Sequence of Operation (SOO)
Operating sequences are different, depending on whether the unit is:
· Controlled for simultaneous blower operation, as in Sections 7.3.1 through
7.3.4 in this manual, or controlled for independent blower operation, as
Sections 7.3.5 and 7.3.6.
· Factory-provided with OA – FA Damper, EA – RA Damper, or both; · Factory-
provided with VFD control of one or both motors. · Simultaneous or Independent
Blower Operation:
When set up for Simultaneous Blower Operation, both blowers should respond to
a call for unit operation at the same time, unless only one of the blowers is
controlled by a VFD or unless only one of the blowers is in an airstream with
a Damper.
When set up for Independent Blower Operation, each blower will follow an
independent operating sequence.
28 RENEWAIRE.COM INSTALLATION, OPERATION AND MAINTENANCE MANUAL 1.800.627.4499
ELECTRICAL CONNECTIONS
LE8XIN ERV
Dampers When one or both of the airstreams are factory-provided with Dampers,
the control sequence for that airstream’s blower is as follows: · External
control calls for operation and damper immediately starts to open. · After
about 30 seconds, damper is open fully and the damper actuator end switch
closes. · The damper actuator end switch completes a low-voltage circuit that
turns on the appropriate
blower, either through the blower’s motor starter, or through the blower’s
VFD. · If that blower is controlled by a motor starter, it starts immediately
Variable Frequency Drives (VFDs) When one or both of the blowers are factory-
provided with VFDs, the response of the Blower Motor depends on the VFD’s
settings and connected control signal. Typically, the VFD will be connected to
a control device which provides a variable analog signal (0-10VDC or 4-20mA)
as an input to the VFD. The VFD must be set to respond to this input with
appropriate motor operating speeds. Alternately, the VFD might be controlled
by a Time Clock, which defines different operating periods (e.g. “occupied”
and “unoccupied”). Each period calls on one of up to three different VFD
presets to provide different motor speeds in different operating periods.
1.800.627.4499 INSTALLATION, OPERATION AND MAINTENANCE MANUAL RENEWAIRE.COM 29
PRE START-UP
LE8XIN ERV
8.0 PRE START-UP 8.1 VERIFY VOLTAGES Using a voltmeter, test the input
voltages as supplied to the disconnect switch. Refer to Digit 13 of the unit
Configuration Code to find the rated voltage. The supplied voltage must be
within +/- 10% of the rated voltage. 8.2 VERIFY TRANSFORMER WIRING Units with
230VAC power source are shipped with the transformer wired for 208VAC. If the
unit is receiving 230VAC, make sure the black primary-side wire on the
transformer’s 208V terminal has been moved to the 230V terminal. 8.3 INSPECT
FILTERS Filters must be installed prior to fan start-up. Filters must be clean
and butted tightly against each other, allowing no air circulation around
them. A total of four filter spacers must be installed with the foam gasketing
positioned toward the filter. One filter retainer is used for each set of four
filters in LE8X units, positioned as shown in the installation instructions.
8.4 INSPECT FOAM GASKETING Proper installation of foam gasketing inside the
ERV is critical to proper operation. Inspect the gasketing to make sure that
it is present where indicated in the installation instructions and that it is
in good condition. There should be no gaps allowing air movement around the
cores or the filters. 8.5 INSPECT MOTOR VIBRATION ISOLATORS The optional
spring-type motor vibration isolators are adjustable in height. The height
adjustment is for holding the fan assembly sled at a uniform height. Verify
that the fan sled height is uniform at all the spring-loaded vibration
isolators if they are present. 8.6 INSPECT BELTS AND VERIFY SHEAVE ALIGNMENT
Prior to shipment from the factory, sheaves are carefully aligned and belts
are tensioned. Inspect the motor mount to verify that it did not shift during
shipment of the unit. Verify that belts are still properly tensioned and that
they track correctly in the sheaves. 8.7 INSPECT FAN Prior to start-up, the
fan should be rotated by hand to make sure that the impeller is not rubbing
anywhere and that it turns freely. 8.8 INSPECT AND CLEAN THE INTERIOR During
the construction and installation phases of a project, dust, dirt and debris
will often accumulate inside a unit. Thoroughly clean the inside of the unit
by vacuuming and/or wiping metal surfaces with a damp rag. 8.9 INSPECT
DUCTWORK CONNECTIONS Ducts attached to the ERV must be firmly attached, sealed
and supported in accordance with installation instructions and SMACNA
guidelines.
30 RENEWAIRE.COM INSTALLATION, OPERATION AND MAINTENANCE MANUAL 1.800.627.4499
START-UP
LE8XIN ERV
9.0 START-UP 9.1 VERIFY CORRECT FAN ROTATION DIRECTION The first time power is
applied to the fan motors, it should be just a brief pulse so that the fans
will begin spinning. Verify that the fans are turning the correct direction.
If a fan is turning the wrong direction, it will be because a three-phase
power source has been improperly connected.
9.2 BASIC OPERATIONAL CHECK
PREPARE FOR TESTING · Disconnect power to the unit at the branch circuit
supply. Lock and tag the disconnect. Place the
unit disconnect switch (on the front of the E-Box) in the OFF position. ·
Remove the cover to the E-Box. · Confirm that internal wiring from the Unit
E-Box to the Exhaust Air Blower is complete. · If optional Exhaust Air or
Fresh Air Outside Air Dampers are provided, confirm that internal wiring
from the Unit E-Box to the Damper Actuators has been connected. · Confirm
Overload Relays on the Motor Starters are set correctly. · At the low-voltage
terminals, install a jumper between terminals 2 & 3. Install jumpers between
terminals 1 and 4, and between 4 and 5. This will call for unit operation as
soon as power is supplied to the unit. See wiring schematics in Section 6.5 of
this manual. · Reinstall the E-Box cover. If the ERV has any VFDs, remove the
upper portion of the E-Box cover, which houses the VFD keypads. · Turn on the
branch circuit supply power at the fuse box.
· Turn the Disconnect Switch on the face of the E-Box to the ON position.
9.2.1 Motor Starter Units
Units without dampers – both motors should begin running immediately.
Units with dampers – dampers should begin opening immediately. After about 30
seconds, damper actuator end switches will engage and provide a call for
operation to the appropriate motor starter. The controlled motor should then
start.
· Turn Disconnect Switch on the face of the E-Box to the OFF position.
Disconnect power at the branch circuit supply. Lock and tag the disconnect.
· Disconnect jumper from terminal 1 to terminal 4, but otherwise leave the
jumpers in place for the convenience of following contractors.
9.2.2 VFD Units
· Turn the Disconnect Switch on the face of the E-Box to the ON position.
Units without dampers – if there is only one VFD, the motor that is not
controlled by a VFD should begin to run immediately. Any motor controlled by a
VFD will not start until the VFD is activated. · To activate a controlling
VFD, wait for a display to appear on the keypad(s), located near the
top of the E-Box. · On each keypad, press the HAND button. The controlled
motor should begin running at a slow
speed. · On each keypad, press the UP / DOWN hard buttons to set the motor
speed as desired.
· Verify that the motor’s amps are no greater than the motor FLA as listed on
the nameplate.
Units with dampers the dampers should start opening immediately. After about
30 seconds the damper actuator end switches will engage.
· Turn Disconnect Switch on the face of the E-Box to the OFF position.
Disconnect power at the branch circuit supply. Lock and tag the disconnect.
· Disconnect jumper from terminal 1 to terminal 4, but otherwise leave the
jumpers in place for the convenience of following contractors.
ERVs that are equipped with dampers should be tested at startup to verify that the dampers will open fully.
1.800.627.4499 INSTALLATION, OPERATION AND MAINTENANCE MANUAL RENEWAIRE.COM 31
MAINTENANCE
LE8XIN ERV
9.3 ADJUST MOTOR SHEAVES
Many units are equipped with adjustable sheaves on the fan motors. Any motor
that is not controlled by a VFD will have an adjustable sheave. All adjustable
sheaves are pre-set at the factory to turn the fans at a slower speed in order
to reduce the possibility of over-amping at start-up . The sheaves have been
turned out 2 full turns and they must be re-set after start-up to achieve the
desired fan speed. Changes to a building’s air handling system or even changes
in the Occupied Space may demand a change in fan speed. Using the pressure
test ports on the cabinet doors, check the pressure drop across the core in
the OA/FA and RA/EA airstreams and determine if the motor sheaves need to be
readjusted. When checking the core pressure drop, make sure that clean filters
are in place. See Sections 11.7 and 11.8 for more detailed adjustment
information.
10.0 MAINTENANCE RenewAire ERVs are built to operate with minimal maintenance.
After unit commissioning, the primary areas of attention are the air filters
and periodic lubrication of the fan motors and fan bearings.
10.1 MAINTENANCE 24 HRS. AFTER START-UP 24 hours after unit start-up: ·
Readjust the tension on the motor drive belts. · In new installations, check
the air filters since they will often collect dust, dirt and debris at time
of start-up.
10.2 MAINTENANCE 30 DAYS AFTER START-UP After 30 days of operation: · Tighten
all electrical connections, paying special attention to VFD wiring (if
present). · Readjust the tension on motor drive belts. · Check the air filters
as part of the normal monthly maintenance.
10.3 MAINTENANCE SCHEDULE
Experience on the part of the service person is the most important issue in
establishing a maintenance schedule. There will be times of the year when
frequent inspection of the filters will be required, such as spring and summer
when there may be pollen, dust, dirt or debris from budding trees and bushes
that can clog the filters. Also see Section 11.9 Maintenance Records in this
manual.
10.4 FILTERS Filter cleanliness and replacement is the most important and
frequent maintenance issue. Dirty filters will cause an immediate reduction in
operating efficiency of the ERV. Normally, filters should be inspected and
changed when they are dirty. Paper filters are not to be cleaned, they are to
be replaced. In general, if a filter looks dirty, replace it. The best
indication of dirty filters is to check the pressure drop across the filter
banks with an optional filter monitor. If it is not possible to check the
pressure drop, the rule of thumb would be to change the filters every two
months.
Clean Filter Pressure Drop Table (in. w.g.)
LE8X Airflow (CFM) 2″ MERV 8 2″ MERV 13 4″ MERV 8 4″ MERV 13
2000 0.03 0.04 0.01 0.03
2500
3000
3500
4000
4500
5000
5500
6000
6500
7000
0.04
0.05
0.06
0.07
0.08
0.09
0.10
0.11
0.12
0.13
0.05
0.06
0.07
0.08
0.10
0.11
0.12
0.14
0.15
0.17
0.01
0.02
0.02
0.03
0.03
0.04
0.04
0.05
0.05
0.06
0.04
0.05
0.06
0.07
0.08
0.09
0.10
0.12
0.13
0.14
NOTE: Pressure drop of clean 2″ MERV 8 filters is included in the Unit Performance Ratings Table
7500 0.14 0.18 0.07 0.16
8000 0.16 0.20 0.08 0.17
8500 0.17 0.22 0.09 0.19
32 RENEWAIRE.COM INSTALLATION, OPERATION AND MAINTENANCE MANUAL 1.800.627.4499
MAINTENANCE
LE8XIN ERV
10.5 ELECTRIC MOTOR MAINTENANCE
The most important issues in motor maintenance are: · Belt condition and belt
tension · Sheave condition · Motor cleanliness · Motor lubrication
10.5.1 Belt Tension
Premature or frequent belt failures can be caused by improper belt tension
(either too loose or too tight) or misaligned sheaves. Abnormally high belt
tension or drive misalignment will cause excessive bearing loads and may
result in failure of the fan and / or motor bearings. Conversely, loose belts
will cause squealing on start-up, excessive belt flutter, slippage and
overheated sheaves. Both loose and tight belts can cause fan vibration.
When replacing belts on multiple groove drives, all belts should be changed to
provide uniform drive loading. Do not pry belts on or off the sheave. Loosen
belt tension until the belts can be removed by simply lifting the belts off
the sheaves. After replacing belts, ensure that slack in each belt is on the
same side of the drive. Belt dressing should never be used.
The proper belt setting is the lowest tension at which the belts will not slip
under peak load operation. For initial tensioning, set the belt deflection at
1/64-inch for each inch of belt span (measured half-way between sheave
centers). Example: If the belt span is 16 inches, the belt deflection should
be 16/64 inch, or 1/4 inch (using moderate thumb pressure at mid-point of the
drive). Check belt tension two times during the first 24 hours of operation
and periodically thereafter.
Deflection Equals 164 inch per inch of Belt Span
Measure to Nearest Inch (Belt Span)
10.5.2 Sheave Condition
Fan Belt Tensioning
Do not install new belts on worn sheaves. If the sheaves have grooves worn in them, they must be replaced before new belts are installed.
10.5.3 Motor Cleanliness
Removing dust and grease buildup on the motor housing assists proper cooling. Never wash-down the motor with high pressure spray.
10.5.4 Motor Lubrication
High efficiency motors have unique maintenance requirements that vary from motor to motor. Many smaller horsepower motors have sealed bearings that do not require periodic greasing. Larger horsepower motors come equipped with grease fittings. Before greasing any motor, consult the motor manufacturer’s web site to determine the correct maintenance and greasing schedule.
Each motor manufacturer specifies the frequency of maintenance and the amount and type of grease to use on the bearings. Do not mix different types of grease. Check the manufacturer’s web site for each specific motor.
1.800.627.4499 INSTALLATION, OPERATION AND MAINTENANCE MANUAL RENEWAIRE.COM 33
MAINTENANCE
LE8XIN ERV
The high-efficiency electric motors used in RenewAire ERVs require greater
care than what was needed years ago. Improper bearing lubrication can result
in: · Failed bearings due to under-lubrication · Catastrophic motor failure
due to over-lubrication
Smaller motors often have permanently lubricated bearings and do not require
any lubrication at all.
In all cases, read the motor manufacturer’s operating and maintenance
instructions for each motor.
Before attempting to lubricate any motor, · Identify the type of grease that
the motor manufacturer recommends for each motor. · Either purchase a new
grease gun that is to be used only for these motors or else clean any old
grease from an existing grease gun. · Calibrate the grease gun so that you
know the actual amount of grease being pumped out with
each stroke. Tag the grease gun with this information. · Determine how much
grease is needed for each bearing and establish a lubrication schedule.
Do not use general purpose or EP type greases. Do not mix different types of
grease.
Different types of greases are formulated for different application
requirements such as shaft speed and shaft size, operating temperature and the
load on the bearing. Grease is basically a carrier for specific oils that are
needed for each application. Greases are made with different thickeners and
these thickeners are often incompatible with other types of thickeners, so
once the correct grease has been determined, you must continue with that
grease.
Determine the correct grease: First examine the data plate on each motor. The
data plate may have lubrication instructions that supersede instructions that
are found online.
Go to the motor manufacturer’s web site and find the operating instructions
for each motor, referencing the frame and motor type.
The most commonly used motors in RenewAire ERVs are made by Baldor. If you are
viewing this document on a computer connected to the internet, click the
button below to go directly to their web site.
http://www.baldor.com/support/
For other motor manufacturers, verify the manufacturer name and go to their
site manually.
Determine a lubrication schedule: The same web site will have information
needed for determining a lubrication schedule. Some of the needed information
will change periodically, such as the duty cycle of the motor. Example: a fan
used for heated Supply Air may only run in the winter and its lubrication
needs are not the same in the summer.
Record the manufacturer’s lube requirements in Section 11.6 Maintenance
Records. Show the lube requirements separately for each fitting (there may be
a different lube requirement for front or rear bearings).
34 RENEWAIRE.COM INSTALLATION, OPERATION AND MAINTENANCE MANUAL 1.800.627.4499
MAINTENANCE
LE8XIN ERV
Greasing process: · Run the motor and get it up to normal operating
temperature. · Make sure the grease gun has the correct type of grease. ·
Clean the areas around the grease fill fittings. · Grease the bearing with the
correct amount of grease as shown on the lubrication schedule you
have determined. Inject the grease very slowly to avoid damaging the seals. ·
Remember that a grease gun can produce up to 15,000 pounds of pressure, which
can blow out
seals or pump the grease to areas where it should not go. · If you are re-
greasing when the motor is out of service, run the motor until the bearing is
at
normal operating temperature. This will allow for thermal expansion of the
grease. · After greasing, run the motor for a while (at least five minutes) to
allow the motor to discharge
any excess grease. 10.6 PILLOW BLOCKS LE model ERVs use pillow block bearings
to support the fan shaft. Maintenance requirements for pillow blocks depend on
a combination of shaft size and shaft RPMs. The fan shaft diameter is
typically 1.44 inches.
Fan Pillow Block To grease pillow blocks, the fan should be at normal
operating speed and temperature prior to greasing. · The recommended interval
for greasing of pillow block bearings is 3 – 6 months, based on 1,000
to 2,000 hours of operation. · The recommended grease is Mobil Polyrex. If
Mobil Polyrex is not available, use an NGLI#2 grease
that is compatible with a lithium thickener, mineral base oil and a
temperature range of -10 to + 260 degrees F. · The recommended amount of
grease is 2 grams. · Clean the grease fitting (zerk) before attaching the
grease gun. · Grease slowly and stop when the first sign of grease seepage
from the bearing’s seals is observed. · Leave a small amount of grease on the
zerk as a protective coating. · In all cases, Industry Best Practices should
be observed. Maintain a record of every lubrication and the type of lubricant
used.
1.800.627.4499 INSTALLATION, OPERATION AND MAINTENANCE MANUAL RENEWAIRE.COM 35
MAINTENANCE
LE8XIN ERV
When cores are removed from the ERV, they should be immediately protected from accidental damage, water, high heat or flames.
10.7 ENTHALPIC CORE MAINTENANCE
The enthalpic core media is a fibrous material that must be kept clean at all
times. As a minimum, cores should be cleaned once per year.
· DO NOT WASH OR ALLOW THE ENTHALPIC CORES TO GET WET. · DO NOT EXPOSE THE
ENTHALPIC CORES TO HIGH HEAT OR FLAMES. · DO NOT DIRECT COMPRESSED AIR AT THE
CORE MEDIA. · DO NOT REMOVE THE ENTHALPIC CORES FROM THE ERV UNLESS NECESSARY.
· USE CAUTION WHEN WORKING AROUND THE ENTHALPIC CORES. DO NOT DROP TOOLS OR
OTHER OBJECTS ON THE CORES, DO NOT BUMP OR TWIST THE CORES.
To access enthalpic cores for cleaning, remove the air filters.
To clean enthalpic cores, all exposed surfaces must be vacuumed with an attachment having long, soft bristles. The greatest buildup of dirt and dust will normally be on the leading 1 – 2 inches of the inlet side (closest to the air filters).
10.7.1 Removal of Enthalpic Cores
There are two sets of four cores in each LE8X ERV. Four cores are in the front
module and four are in the back module. Each set of three cores can be removed
for major motor or blower repairs by opening the access doors on the end of
the module, removing the filters to provide better access and then the support
members that secure the cores. Carefully pull out the cores one at a time.
Remove Filters
Remove Support Members
End View of Core Support Assembly
10.7.2 Reinstallation of Enthalpic Cores To reinstall the cores, reverse the
process shown above.
36 RENEWAIRE.COM INSTALLATION, OPERATION AND MAINTENANCE MANUAL 1.800.627.4499
10.8 SERVICE PARTS
MAINTENANCE
LE8XIN ERV
www.renewaire.com (800) 627- 4499
LE8XINH and LE8XINV Service Parts 1.800.627.4499 INSTALLATION, OPERATION AND MAINTENANCE MANUAL RENEWAIRE.COM 37
MAINTENANCE
LE8XIN ERV
11.0 MAINTENANCE REFERENCE 11.1 PLENUM DIVIDERS
CAUTION
RISK OF DAMAGE TO PLENUM DIVIDERS Whenever working within the ERV cabinet, do
not place significant weight on the plenum dividers. They are not intended to
be load-bearing. Inside each ERV, there are two vertical and two horizontal
metal panels that separate the plenums. These panels are not intended to be
load-bearing. When performing maintenance on the ERV, do not crawl on or place
significant weight on these divider panels! If it is necessary to go inside
the ERV cabinet for maintenance purposes, it is recommended that the cores be
removed to provide access. The floor of the ERV is reinforced to accept a
person’s weight.
Plenum Divider Panels
(Keep Off!)
Plenum Divider Panels 11.2 FAN / MOTOR REMOVAL The fan and fan motor are part
of an assembly that is mounted on a “sled”, which is then installed in the ERV
on vibration isolators. See the Service Parts illustration on the preceding
page. Also see photograph below. If it is ever necessary to remove a fan, it
may be easier to remove the entire sled from the ERV. For some maintenance
issues, it may be easier to remove the enthalpic cores and go inside the ERV.
Fan and Motor Sled 11.3 VIBRATION ISOLATOR ADJUSTMENT Spring-type vibration
isolators can optionally be used in LE model ERVs. Depending on fan and motor
size, either four or six isolators are installed on each motor and blower sled
assembly. Two different isolator spring strengths may be used and they cannot
be interchanged. Each isolator has a support 38 RENEWAIRE.COM INSTALLATION,
OPERATION AND MAINTENANCE MANUAL 1.800.627.4499
MAINTENANCE
LE8XIN ERV
disc that is threaded and will move up or down on the threaded bolt. The up or
down movement determines the upward force on the sled. With age, the
supporting springs may require adjustment by repositioning the support disc.
Rotate Support Disc as Needed to Level the Fan and Motor Sled
Typical Spring-Type Vibration Isolator 11.4 RISK OF CORE DAMAGE
CAUTION
RISK OF DAMAGE TO ENTHALPIC CORES Whenever working within the ERV cabinet,
protect the enthalpic cores from accidental damage. The core media is subject
to damage from dropped tools or other foreign objects. The core media is a
fibrous material that is subject to damage through careless work habits.
Whenever foreign objects such as tools are taken inside the ERV cabinet, the
core media should be protected by placing stiff cardboard or some other
protective material on top. Make certain the protective material is clean and
dust-free before placing it on the media. 11.5 FILTER REPLACEMENT PRACTICES
RenewAire has provided a filter replacement tool called a filter extractor
hook. See picture below. In addition, the filter spacers have a tab on the
ends where a pull cord can be inserted. With a cord installed in the tab
holes, it is possible to simply pull the cords and withdraw six filters at
once. See image below. When installing the filter spacers, the foam strip is
to be placed against the filter.
Note that when new filters are installed, the filter spacers may tend to fall
off the end of the filter receiving channels. If this happens, simply install
the spacers between the first two filters in from the door, instead of
locating them against the access doors.
Tabs with Holes for Pull Cord
Filter Extractor Hook
Filter Spacers
If filter thickness is ever changed from 2″ to 4″ or from 4″ to 2″ thickness, each of 8 filter receivers will need to be adjusted up or down to accomodate the desired filter thickness. To make this adjustment, remove the second bolt set in from the door on each filter receiver and slide the moveable filter receiver up or down against the fixed filter receiver bracket, following the “C” channel paths and replace the positioning bolt set in the proper hole that lines up at the other end of the “C” channel paths. The same filter spacers are used with either 2″ or 4″ filters.
1.800.627.4499 INSTALLATION, OPERATION AND MAINTENANCE MANUAL RENEWAIRE.COM 39
MAINTENANCE
LE8XIN ERV
11.6 DOOR LATCH ADJUSTMENT With age and use, the door gaskets may become
compressed and no longer provide a complete seal against air leakage. The door
latches can be easily adjusted by changing the position of the swing arm on
the inside of the door. See photo below.
Swing Arm
Set Screw
Door Latch Adjustment 11.7 MEASURING AIRFLOW On every LE8X unit, a set of four
air flow test ports are installed on the end doors of both the front and rear
modules. See images below.
Air Flow Test Ports (4)
Tubing should be inserted into the test port about 1 inch.
Air Flow Test Port
Air Flow Test Port Location
Equipment required: · A magnehelic gauge or other device capable of measuring 0 to 1.0 in w.g.. · 2 pieces of natural rubber latex tubing, 1/8″ I.D., 1/16″ wall thickness.
Procedure: · The differential static pressures (DSP) can be measured using the
installed pressure test ports
shown above. Airstream pressure readings are to be taken across the cores by
testing at diagonally-located test ports. · To read the SCFM of Fresh Air
(FA), install the “high” pressure side (+) of the measuring device in the
Outside Air (OA) port and the “low” pressure side (-) in the FA port. · To
read the SCFM of Room Air (RA), install the “high” pressure side of the
measuring device in the RA port and the “low” pressure side in the Exhaust Air
(EA) port. · Use the reading displayed on the measuring device to cross
reference the CFM output using the following conversion chart.
Be sure to reinsert the test port cap when air flow measuring is finished.
Motors that are controlled by factory-installed VFDs are equipped with fixed sheaves. The entire speed range that can be obtained with variable sheaves can be obtained by adjusting the VFD.
40 RENEWAIRE.COM INSTALLATION, OPERATION AND MAINTENANCE MANUAL 1.800.627.4499
MAINTENANCE
LE8XIN ERV
LE8XIN
Differential Pressure Measured Across Core 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1.0
FA Airflow (CFM) 2160 3110 4030 4930 5800 6660 7510 8350 9170
RA Airflow (CFM) 2160 3110 4030 4930 5800 6660 7510 8350 9170
11.8 SHEAVE ADJUSTMENT
All fan motors that are not controlled by a VFD are equipped with an
adjustable sheave. These adjustable sheaves must be re-set in the field to
attain optimum performance of the ERV. This adjustment is to be done after all
ductwork is connected.
Adjustable sheaves are held in position on the drive motor shaft by a set
screw that is normally hidden until the belt(s) is removed. One flange is
fixed-position, the others are adjustable-position. The adjustable flanges of
the sheave have a set screw located in an exposed position on the collar of
the flange.
Use only BX-type cogged drive belts.
To adjust the flanges: · Remove the drive belt(s) · Loosen the set screws on
both adjustable flanges · IN HALF-TURN INCREMENTS, turn the adjustable flanges
in or out the same number of turns · Tighten the set screws on the adjustable
flanges, making certain that the set screws are landing
on the machined “flat” on the sheave.
Motor Blower HP Speed
3 HP LOW 633 3 HP MED 755 3 HP HIGH 878
Blower RPM Available by Variable Motor Sheave Adjustment
655 676 695 714 735 755 776 796 817 776 796 817 837 858 878 898 918 939 902
925 949 972 996 1020 1044 1067 1091
Motor Blower Sheave Sheave
837 1VP44 BC90 959 1VP50 BC90 1115 1VP50 BK80
5 HP LOW 755 776 796 817 837 858 878 898 918 939 959 2VP50 D4900 5 HP MED 878 902 925 949 972 996 1020 1044 1067 1091 1115 2VP50 D4780 5 HP HIGH 1000 1021 1041 1062 1082 1102 1122 1143 1163 1184 1204 2VP62 D4900
7.5 HP LOW 878 898 918 939 959 980 1000 1021 1041 1062 1082 2VP56 D4900 7.5 HP
MED 1000 1021 1041 1062 1082 1102 1122 1143 1163 1184 1204 2VP62 D4900 7.5 HP
HIGH 1122 1143 1163 1184 1204 1225 1245 1266 1286 1306 1326 2VP68 D4900
Table of Sheave Adjustments
Note that Low, Medium and High Blower RPM sheave settings overlap allowing some adjustability into lower or higher blower speed zones.
Fixed Position Flange
Loosen Set Screw on Each Adjustable Flange
Adjustable Flanges
Two-Belt Adjustable Sheave (typ) 1.800.627.4499 INSTALLATION, OPERATION AND MAINTENANCE MANUAL RENEWAIRE.COM 41
MAINTENANCE
LE8XIN ERV
11.9 MAINTENANCE RECORDS AIR FILTER REPLACEMENT RECORD FILTERS REPLACED DATE:
ENTHALPIC CORES CLEANING RECORD CORES CLEANED DATE:
42 RENEWAIRE.COM INSTALLATION, OPERATION AND MAINTENANCE MANUAL 1.800.627.4499
EA FAN MOTOR MOTOR TYPE: REQUIRED LUBRICANT (from motor manufacturer’s
website): FRONT BEARING LUBE REQUIREMENTS: REAR BEARING LUBE REQUIREMENTS:
LUBRICATION PERFORMED DATE:
MAINTENANCE
LE8XIN ERV
EA FAN PILLOW BLOCKS REQUIRED LUBRICANT (from pillow block manufacturer’s
website): BEARING LUBE REQUIREMENTS: LUBRICATION PERFORMED DATE:
FA FAN MOTOR MOTOR TYPE: REQUIRED LUBRICANT (from motor manufacturer’s
website): FRONT BEARING LUBE REQUIREMENTS: REAR BEARING LUBE REQUIREMENTS:
LUBRICATION PERFORMED DATE:
FA FAN PILLOW BLOCKS REQUIRED LUBRICANT (from pillow block manufacturer’s
website): BEARING LUBE REQUIREMENTS: LUBRICATION PERFORMED DATE:
1.800.627.4499 INSTALLATION, OPERATION AND MAINTENANCE MANUAL RENEWAIRE.COM 43
USA 800-627-4499 FAX:
608-221-2824 201 RAEMISCH ROAD
WAUNAKEE, WISCONSIN 53597 USA WWW.RENEWAIRE.COM
CANADA 905-475-8989 FAX:
905-475-5231 WWW.MITSUBISHIELECTRIC.CA
MEXICO, CENTRAL &SOUTH AMERICA
52 (222) 2 233 911 FAX: 52 (222) 2 233 914 WWW.SOLER-PALAU.MX
4444
ABOUT RENEWAIRE
For over 30 years, RenewAire has been a pioneer in enhancing indoor air
quality (IAQ) in commercial and residential buildings of every size. This is
achieved while maximizing sustainability through our fifth-generation, static-
plate, enthalpic-core Energy Recovery Ventilators (ERVs) that optimize energy
efficiency, lower capital costs via load reduction and decrease operational
expenses by minimizing equipment needs, resulting in significant energy
savings. Our ERVs are competitively priced, simple to install, easy to use and
maintain and have a quick payback. They also enjoy the industry’s best
warranty with the lowest claims due to long-term reliability derived from
innovative design practices, expert workmanship and Quick Response
Manufacturing (QRM).
As the pioneer of static-plate core technology in North America, RenewAire is
the largest ERV producer in the USA. We’re committed to sustainable
manufacturing and lessening our environmental footprint, and to that end our
Waunakee, WI plant is 100% powered by wind turbines. The facility is also one
of the few buildings worldwide to be LEED and Green Globes certified, as well
as having achieved ENERGY STAR Building status. In 2010, RenewAire joined the
Soler & Palau (S&P) Ventilation Group in order to provide direct access to the
latest in energy-efficient air-moving technologies. For more information,
visit: renewaire.com
RENEWAIRE LLC COPYRIGHT © MAY 2022 LE8XINMan_138233_004_AUG22
References
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>