HE SERIES ERV
Installation, Operation and Maintenance Manual
HE4XINH
HE Series ERV HE4XINH Energy Recovery Ventilator
WARNING
ARC FLASH AND ELECTRIC SHOCK HAZARD
Arc flash and electric shock hazard. Disconnect all electric power supplies,
verify with a voltmeter that electric power is off and wear protective
equipment per NFPA 70E before working within electric control enclosure.
Failure to comply can cause serious injury or death. Customer must provide
earth ground to unit, per NEC, CEC and local codes, as applicable. Before
proceeding with installation, read all instructions, verifying that all the
parts are included and check the nameplate to be sure the voltage matches
available utility power. The line side of the disconnect switch contains live
high- voltage. The only way to ensure that there is NO voltage inside the unit
is to install and open a remote disconnect switch and verify that power is off
with a volt meter. Refer to unit electrical schematic. Follow all local codes.
IMPORTANT
This equipment is to be installed by following Industry Best Practices and all
applicable codes. Any damage to components, assemblies, sub assemblies or the
cabinet which
is caused by improper installation practices will void the warranty.
IMPORTANT
Air ducts connecting this ERV to the Occupied Space must be installed in
accordance with the Standards of the National Fire Protection Agency for the
installation of Air- Conditioning and Ventilating Systems (Pamphlet No. 90A)
and Warm-Air Heating and Air-Conditioning Systems (Pamphlet No. 90B).
CAUTION
RISK OF CONTACT WITH HIGH SPEED MOVING PARTS
Disconnect all local and remote power supplies, verify with a voltmeter that
electric power is off and all fa
n blades have stopped rotating before working on the unit. Do not operate this
unit with any cabinet panels removed.
CAUTION
RISK OF ELECTRIC SHOCK OR EQUIPMENT DAMAGE
Whenever electrical wiring is connected, disconnected or changed, the power
supply to the ERV and its controls must be disconnected. Lock and tag the
disconnect switch or circuit breaker to prevent accidental re connection of
electric power.
IMPORTANT
This unit is intended for general ventilating and heating only. Do not use to
exhaust hazardous or explosive materials and vapors. Do not connect this
equipment to range hoods, fume hoods or collection systems for toxic.
IMPORTANT
This unit is for ventilating finished structures only. It is not to be used
until after all construction has been completed and construction debris and
dust are cleaned from the Occupied Space.
SAVE THIS MANUAL
NOTICE
This manual contains space for maintaining written records of unit maintenance
and/ or repairs. See Section 7.7 Maintenance Records. At the time the ERV is
commissioned, amaintenance schedule should be developed by the user to
incorporate monthly and seasonal maintenance and include start-up maintenance
tasks as described in this manual.
UNIT INFORMATION
Record information as shown below.
In the unlikely event that factory assistance is ever required, information
located on the unit label will be needed.
Locate the Renew Aire unit label found on the outside of the unit.
NOTE: This information is for purposes of identifying the unit-specific
option data from the Option Code.
NOTE: This page is to be completed by the installing contractor. The
completed document is to be turned over to the owner after start-up.
INDOOR UNIT
SPECIFICATIONS
Ventilation Type:
Static plate, heat and humidity transfer
Typical Airflow Range: 1,000-4,400 CF
HAIR 1060 Certified Core: Four L125-G5
Standard Features:
TEFL Premium efficiency motors Motor starters
Non-fused disconnect 24 VAC transformer/relay package
Cross-core differential pressure ports
Filters:
Total qty. 8, MERV 8: 20″ x 20″ x 2″
Unit Weight:
723-1,092 lbs., varies by option(s)
Max. Shipping Dimensions & Weight (on pallet): 80″ L x 90″ W x 50″ H 1,228
lbs.
Motor(s):
Qty. 2, Belt drive blower/standard motor packages with adjustable sheaves (see
table below)
Options:
Onboard variable frequency drives (Feds) – both air streams
Shaft grounding ring on motors with Feds Fused disconnect
Integrated programmable controls enhanced, premium
Bypass economizer damper (see bypass DIM drawing) dry-bulb temperature
controls (standard), enthrall controls (option)
Class 1 low leakage motorized isolation dampers – PA, RA or both air streams
Qty.2,
Factory mounted filter alarms both air streams
Double wall construction
Exterior paint – white, custom colors
Accessories:
Filters – MERV 13, 2″ (shipped loose)
Automatic balancing damper – 4″, 5″, 6″
Digital time clock – wall mount (TC7D-W),
in exterior enclosure (TC7D-E)
Carbon dioxide sensor/control –
wall mount (CO2-W), duct mount (CO2-D)
IAQ sensor – wall mount (IAQ-W),
duct mount (IAQ-D)
Motion occupancy sensor/control –
ceiling mount (MC-C), wall mount (MC-W)
Smoke Detector – duct mount (SD-D)
Electric duct heater – EK series (1–175 kW )
Indirect gas-fired duct furnace – GH series
(50-400 MBH), installed downstream of any fans
AIRFLOW PERFORMANCE
Note: Brake Horse Power (BHP) is for one blower motor package only. Operation
in this zone will likely exceed FLA limits. Operation in this zone outside of
core airflow limits.
Note: Airflow performance includes effect of clean, standard filter
supplied with unit.
ELECTRICAL DATA
Standard Electrical Specifications| Optional Factory Installed VFD
Electrical Specifications
---|---
HP| Volts| HZ| Phase| FLA
per motor
| Min. Cir. Amps| Max. Over current
Protection Device| FLA per motor| Min. Cir. Amps|
Max. Over current
Protection Device
2.0| 120| 60| Single| 20.0| 45.0| 60| | |
2.0| 208-230
208-230
460| 60
60
60| Single
Three
Three| 10.8-10.0
6.6-5.8
2.9| 24.3
14.9
6.5| 35
20
15| 6.6-5.8
6.6-5.8
2.9| 28.3
16.3
7.2| 30
20
15
3.0| 575
208-230
208-230
460
575| 60
60
60
60
60| Three
Single
Three
Three
Three| 2.4
14.7-14
9.4-8.5
4.2
3.3| 5.4
33.1
21.1
9.5
7.4| 15
40
25
15
15| 2.4
9.4-8.5
9.4-8.5
4.2
3.3| 5.9
40.2
23.2
10.5
8.2| 15
45
25
15
15
5.0| 208-230
460
575| 60
60
60| Three
Three
Three| 14.5-13.4
6.7
5.3| 32.6
15.1
11.9| 45
20
15| 14.5-13.4
6.7
5.3| 35.9
16.6
13.1| 45
20
15
ABBREVIATIONS
EA: Exhaust Air to outside
OA: Outside Air intake
RA: Room Air to be exhausted
FA: Fresh Air to inside
INSTALLATION ORIENTATION
Unit must be installed in orientation
shown.
NOTE
- UNLESS OTHERWISE SPECIFIED, DIMENSIONS ARE ROUNDED TO THE NEAREST EIGHTH OF AN INCH.
- SPECIFICATIONS MAY BE SUBJECT TO CHANGE WITHOUT NOTICE.
- MIN. DUCT CLEARANCE FROM DAMPER BLADES WHEN FULLY OPENED TO BE 2″. SMACNA RULES APPLY.
CONFIGURATION CODE
OVERVIEW
1.1 DESCRIPTION
The HE4XINH Energy Recovery Ventilator is a device for recovering both
sensible energy (heat) and latent energy (moisture) from the Exhaust Air from
an Occupied Space and injecting those energies into an incoming Outside Air
stream. It accomplishes this task by forcing the two air streams through
encephalitic cores, where the energy exchange takes place. The two air streams
pass through the encephalitic cores at right angles and the air streams never
mix together. See Section 2.2 Encephalitic Cores in this manual.
Each ERV has two electric blowers, one for each air stream. Fan speeds can be
either single speed, using adjustable sheaves to change fan speed, or they can
be variable speed, controlled by Feds, a Renewal Commercial Controller or by a
MS. There are a number of different control devices available to control the
operation or speed of the unit fans. For further information on available
control accessories, see the HE Renewal catalog.
There are two types of HE4X units, one for indoor installations and one for
rooftop, or outdoor, installation. This manual is for the HE4XINH, which is
the indoor unit with horizontal ducting. For information on the vertically
dusted HE4XIN, see the HE4XINV manual. For information on the outdoor version
of this product, see the HE4XRT manual.
These Er Vs are commonly installed as part of an air handling system that
provides heating and cooling of Supply Air. They can also be installed to
operate as stand-alone devices when ducted directly to and from the Occupied
Space.
Each unit has an integral 24 VAC power supply that is used internally and can
also be used as a power source for other optional control devices.
The HE4XINH units are low-maintenance, requiring periodic replacement of the
air filters, lubrication of the motors and annual vacuuming of the
encephalitic cores. See Section 7.0 Unit Maintenance in this manual.
NOTE: This unit is an Energy Recovery Ventilator, or ERV. It is commonly
referred to throughout this manual as an ERV.
IMPORTANT
It is important to understand and use the equipment air stream terminology as
it is used in this manual. The air streams are defined as:
- OUTSIDE AIR (OA): Air taken from the external atmosphere and, therefore, not previously circulated through the system.
- FRESH AIR (FA): Air that is downstream of the encephalitic cores and is ready for conditioning or for return to the Occupied Space.
- RETURN AIR (RA): Air that is returned to the ERV from a conditioned space.
- EXHAUST AIR (EA): Air that is removed from a heating or cooling appliance or from the Occupied Space and discharged.
1.2 AIRFLOW
The airflow configuration is indicated by digit 9 of the Configuration Code.
MODEL | DESCRIPTION OF DUCT CONNECTION CONFIGURATION |
---|---|
HE4XINH | Room Air [RA] and Outside Air [OA] enter on the same side of the |
unit.
FIGURE 1.2.0 AIRFLOW ORIENTATION
CAUTION
Low air flow can cause fouling of the encephalitic cores. The ERV must never
be operated without clean filters in place and minimum airflow must be greater
than 250 CFM per full-sized core.
COMPONENT DESCRIPTIONS
2.1 CABINET
The cabinet for the HE4XINH is made of 20 gauge galvanized steel and has 1″
thick high density, foil-backed insulation on the inside. Units are available
in either single-wall or double wall construction. Doors are hinged and are
fitted with stainless steel machine screws through the faces to prevent
accidental opening of the doors when the unit is in operation. Doors may be
completely removed by removing the hinge pins. All units are equipped with
adjustable-height leveling legs for purposes of leveling the unit. Duct
flanges are provided at all four air stream openings for connection of field-
supplied duct work.
2.2 ENCEPHALITIC CORES
All HE4XINH Er Vs use four static-plate encephalitic cores. The encephalitic
cores transfer both latent and sensible energies between the air streams.
Cores are bi-directional and may be rotated in their mounting hardware, but
care must be taken to install the correct side of the core toward the unit
door. Gasket is per-installed on the cores and must be positioned to provide a
proper air seal. For information on annual maintenance of the cores, see
Section 7.0 Maintenance in this manual.
2.3 FAN/MOTOR ASSEMBLIES
There are two fan and motor assemblies in each ERV. The fans are belt-driven.
All fans have an adjustable sheave on the electric motor for purposes of
adjusting the fan speed. The motors require periodic inspection and
lubrication. For information on adjusting sheaves, see Section 7.0
Maintenance.
2.4 E-BOX
Every HE4XINH is equipped with what is known as an “E-Box.” High-voltage
supply wiring and low-voltage control wiring is all terminated here. When VFDs
are installed in the unit, the VFD keypads are installed here. If optional
integrated programmable controls are installed, an additional 24 VAC
transformer is installed here to power both the controller and its dedicated
sensors.
NOTE: Every ERV has an attached electrical connection box, known as the
E-Box. It is attached to the outside of the ERV and all electrical connections
are made there. There is a high-voltage side and a low-voltage side. See
Figure 2.4.0.
2.5 FILTERS
All HE4XINH units come equipped with eight each MERV 8 20″ X 20″ X 2″ thick
pleated paper filters. MERV 13 filters can be ordered as an accessory and are
shipped loose.
2.6 FACTORY INSTALLED OPTIONS
All HE4XINH units can be ordered with factory installed options. See Unit
Configuration Code on page 8.
Options will have supplemental manuals shipped with the unit.
For Isolation Dampers, see Isolation Dampers Supplemental Manual.
For Commercial Controls, see Commercial Controls Supplemental Manual.
For Filter Alarm, see Filter Alarm Supplemental Manual.
For Economizer/Bypass, see Bypass Economizer Supplemental Manual.
For Isolation Dampers, see Isolation Dampers Supplemental Manual.
For Variable Frequency Drive, see VFD Supplemental Manual.
SHIPPING/RECEIVING/HANDLING
HE4XINH units are palletized at the factory and then shipped by common
carrier. Upon receipt by the installer, the shipment should be inspected for
shipping damage, prior to unloading. Any discovered shipping damage should be
immediately reported to the Renew Aire sales rep and the damage must be
recorded on the Bill Of Lading, prior to signing for acceptance of the
shipment. The unit can be handled with a fork lift or a crane. Prior to moving
the unit, verify that all latches and securing bolts on the cabinet doors are
tightly fastened.
If a crane is used for moving the HE4XINH unit, unscrew the sheet metal plates
that hold the unit to the pallet. Use two hoisting slings and a spreader bar
to hoist the unit. The hoisting slings must be positioned around the ends of
the unit so they do not touch the unit doors. Unit hoisting weights and Center
of Gravity are detailed in Sections 3.1 and 3.2 in this manual.
Perform a test lift to make sure the unit is being hoisted level and is
secure.
Place the HE4XINH unit on a flat surface where it will be protected from the
weather and incidental damage. Do not remove protective coverings from any
duct openings and keep the doors secured and tightly closed.
3.1 UNIT WEIGHTS AND DIMENSIONS
3.1.1 Unit Dimensions and Weight
72 1/2″ L x 82 3/4″ W x 44″ H
723–1,092 lbs., varies by option(s)
3.1.2 Shipping Dimensions and Weight
80″ L x 90″ W x 50″ H
1,228 lbs.
3.2 RIGGING AND CENTER OF GRAVITY
3.2.1 HE4XINH Hoisting Weights and COG
BASIC UNIT WEIGHTS (lbs.)
Motors| UNIT| LF| LR| RR| RF
2 HP| 809| 229| 195| 176| 209
3 HP| 873| 252| 208| 185| 228
5 HP| 881| 253| 210| 187| 231
ADDITIONAL WEIGHTS FOR OPTIONS (lbs.)
Options| UNIT| LF| LR| RR| RF
Double Wall| 93| 28| 23| 18| 23
By-Pass| 32| 8| 8| 8| 8
VFDs| 8| 4| 4| 0| 0
RA or EA Damper| 39| 3| 3| 16| 17
OA or FA Damper| 39| 3| 3| 17| 16
Total Selected Weights| | | | |
Add the additional weights for options to the Basic Module weights determined
by motor size to determine Module and Corner weights for a specific unit.
INDICATES LOCATIONS AT WHICH CORNER WEIGHTS ARE CALCULATED: ALONG CENTERS OF
CURB RAILS.
Center of gravity: From Left (A) = 26″, From Front (B) = 33″ (+/- 2″)
FIGURE 3.2.0 HE4XINH WEIGHTS AND COG
3.3 RECEIVING
Upon receipt of the HE4XINH, inspect the unit for obvious external damage. If
damage is observed, take digital pictures and report the damage to your Renew
Aire rep. Note the damage on the carrier’s Bill of Lading. Depending on
expected transport and storage conditions, the unit may have only the duct
openings covered, it may be stretch-wrapped or it may be crated. Do not unwrap
the unit at this time. The unit will normally be moved to its final location
while still wrapped and attached to its pallet.
The preferred method of hoisting the HE4XINH from the carrier truck is by
using a construction forklift.
Once the unit is unwrapped, prevent dirt and debris from entering the cabinet
by covering any duct openings that do not have attached dampers. Keep the duct
openings covered until it’s time to connect duct work.
3.4 HANDLING AND STORAGE
Units that must be stored prior to installation should be left on their
pallets and protected from weather and physical damage. Units must be placed
on a level surface to prevent wracking of the pallet and the HE4XINH. All
access doors must be secured with all available hardware (door latches and
securing bolts) and all openings into the cabinet must be sealed to prevent
entry of dust, dirt and debris.
UNIT PLACEMENT
4.1 BEFORE YOU BEGIN
Units that must be stored prior to installation should be left on their
pallets and protected from weather and physical damage. Units must be placed
on a level surface to prevent wracking of the pallet and the HE4XINH. All
access doors must be secured with all available hardware (door latches and
securing bolts) and all openings into the cabinet must be sealed to prevent
entry of dust, dirt and debris.
The HE4XINH is designed for installation in a sheltered location, out of the
weather. The preferred mounting location is to place the unit on a concrete
floor.
For all installations, maintain needed service clearances as shown on the
dimension ed drawings located in Section 4.2 of this manual. In addition, if
the optional Bypass Economizer is ordered, additional clearance will be
required for the extra bypass duct. See the Renew Aire Supplemental Manual for
Bypass or further information and clearance details specific to the HE4XINH
units.
Select a location that is central to the inside duct runs and close to both
the exhaust duct (to the outside) and also to the fresh air duct (from the
outside).
The exhaust outlet and the outside air inlet on the outside of the building
should be at least ten feet apart to avoid cross-contamination. Comply with
all local building codes in the positioning of the duct openings. Do not
position the exhaust air outlet in a location where it will dump exhaust air
into any enclosed or occupied space. The duct inlets and outlets should be
screened against insects and vermin and should be shielded from the weather to
prevent entry of rain or snow.
4.2 SERVICE CLEARANCES
4.3 SOUND ATTENUATION
Take these simple steps to attenuate noise from the unit.
4.3.1 Outside the Building
Exhaust velocity noise is the primary cause of unit-related noise outside the
building. Size the exhaust duct and grille for less than 1000 FPM air
velocity. When practical, orient the exhaust air hood to point away from
houses or public areas.
4.3.2 Ducts
Make sure the ductwork at the unit outlets is stiff enough to resist the
flexure and resulting booming associated with system start-up and shut-off, as
well as the turbulent flow conditions at the blower outlets.
In general, provide smooth transitions from the Erv’s outlets to the duct. The
ducts connecting to the outlets should be straight for a sufficient distance,
with gradual transitions to the final duct size.
These guidelines are consistent with SMACK recommended duct layout practices
for efficient and quiet air movement. Follow SMACK guidelines.
4.3.3 Radiated Noise
The HE4XINH is insulated with high-density fiberglass. This provides
significant attenuation of radiated sound.
The outlet ducts can be significant sources of radiated sound as well. The FA
and EA ducts (outlet ducts) should be insulated for sound control. This
insulation should start at the unit. At a minimum the first ten feet of duct
should be insulated. All parts of the FA and EA ducts located in the
mechanical space should be insulated for sound control, both to minimize sound
radiation out of these ducts and also to control sound radiation into the
ducts.
4.3.4 Aerodynamic (Velocity) Noise
When sound attenuation is a design concern, the primary consideration is
velocity noise at the unit’s Fresh Air blower outlet. The average velocity at
the Fresh Air blower outlet is 2984 FPM when the unit is operating at 3000
CFM.
INSTALLATION
5.1 DUCT WORK
5.1.1 Ducts to the Outside
The exhaust outlet and fresh air inlet on the outside of the building should
be at least 10′ apart to avoid cross-contamination. The exhaust outlet should
not dump air into an enclosed space or any other structure. The inlets and
outlets should be screened against insects and vermin and shielded from the
weather to prevent the entry of rain or snow.
Ducts connecting the HE4XINH to the outside must be insulated, with sealed
vapor barrier on both inside and outside of the insulation. Insulate both the
Outside Air (OA) and Exhaust Air (EA) ducts.
NOTE: Ducts inside a building that are connected to the outside must be
insulated with a sealed vapor barrier on both the inside and the outside of
the insulation.
5.1.2 Inside Duct work System
Ensure Good Duct work Design
Duct work should be designed to allow the unit to provide the required airflow
and reduce pressure drop for efficient, quiet operation. If the inside ducts
run through unconditioned spaces they must be insulated with a sealed vapor
barrier on both inside and outside of insulation.
NOTE: It is the installer’s responsibility to select appropriate
materials capable of safely supporting the weight of the ERV and all attached
hardware, such as duct work. It is the installer’s responsibility to determine
the location of the ERV and the needed supporting threaded rods. All such
installations must be reviewed and approved by an engineer.
5.2 FLOOR INSTALLATION
Most units are installed in a location specified by others. In general, it’s
preferable to install the unit on a flat, reasonably level surface, such as a
concrete floor.
5.3 ELECTRICAL REQUIREMENTS
WARNING
ARC FLASH AND ELECTRIC SHOCK HAZARD
Arc flash and electric shock hazard. Disconnect all electric power supplies,
verify with a voltmeter that electric power is off and wear protective
equipment per NFPA 70E before working within electric control enclosure.
Failure to comply can cause serious injury or death.
Customer must provide earth ground to unit, per NEC, CEC and local codes, as
applicable.
Before proceeding with installation, read all instructions, verifying that all
the parts are included and check the nameplate to be sure the voltage matches
available utility power.
The line side of the disconnect switch contains live high-voltage.
The only way to ensure that there is NO voltage inside the unit is to install
and open a remote disconnect switch and verify that power is off with a volt
meter. Refer to unit electrical schematic.
Follow all local codes.
5.3.1 Factory-Recommended Electric Service Entry
Knockouts are provided in the bottom of the E-box for entry of high-voltage
power supply wiring. Install the wiring in accordance with local codes and
provide strain relief at the E-box opening. Wiring is then terminated on the
top of the disconnect switch.
Low-voltage control wiring is to enter the E-box through the knockout in the
bottom of the E-box. Provide strain relief as needed.
High-voltage supply wiring is to be connected on the top side of the
disconnect switch. See Figure 5.3.0 below.
5.3.2 Low Voltage Control System
This ERV is provided with a Class II 24 VAC power supply system that operates
the unit’s contractor(s) for HE4XINH. The Erv’s 24 VAC Power Supply can also
be used to power the externally-installed controls system: up to 8VA of power
is available.
The unit’s power supply system includes isolation relay(s) so you can use
external controls whose contact ratings are as low as 50 mA (1.2 VA). Also, it
is possible to operate the isolation relays with 24 VAC power from an external
source (with proper wiring connections).
A built-in circuit-breaker prevents damage to the transformer and other low-
voltage components in the event of a short-circuit or overload. In extreme
cases, the transformer itself is designed to fail safely.
Specifications:
- Nominal Output Voltage under load: 24 VAC
- Typical Output Voltage at no load: 29–31 V
- Minimum contact rating for connected control device: 50 mA (1.2 VA)
- Circuit Breaker Trip Point: 3 A
NOTICE If primary-side voltage is 230 VAC, move black primary-side lead
from transformer’s “208 V” terminal to the transformer’s terminal marked “240
V” (“230 V” in some units). Do not move the black primary-side lead that is
connected to the transformer’s “COM” terminal.
5.3.3 How to Reset the 24 VAC Circuit Breaker
If the transformer is subjected to an excessive load or a short circuit, the
circuit breaker will trip to prevent the failure of the transformer. When it
trips the circuit breaker’s button pops up. Shut off the primary-side power to
the unit, and remove the excessive load or the short. The circuit breaker can
be reset about fifteen seconds after it trips by pressing in the button.
**CAUTION**
- Connect only to components intended for use with 24 VAC power.
- Do not undersized the low-voltage wires connected to this device. Observe the wire length and gauge limits indicated in this manual.
- Do not overload this unit’s 24 VAC power supply system. Confirm that the power requirements of devices you connect to this power supply system do not exceed 8 VA in total.
- If an external source of 24 VAC power is used to control the unit, consult the wiring schematics and connect the external power only to the specified terminals in order to avoid damaging the unit or external controls. Connect only CLASS II power to the control terminals of this unit.
- Unit is not equipped to receive analog signals (such as 1–10 vdc or 4–20 mA).
CAUTION
Be careful if the external control system provides 24 VAC power at its control
output: make sure blue and red leads are separately capped and not connected
to any other wires.
5.3.4 Limits of Power Output
If limits on wire gauge and length are observed, you may connect control
devices that draw up to 8 VA to the blue and red wires. More than one device
can be connected as long as total steady-state load does not exceed 8 VA.
Wire Gauge | #22 | #20 | #18 | #16 | #14 | #12 |
---|---|---|---|---|---|---|
Circuit Length | 100′ | 150′ | 250′ | 400′ | 700′ | 1000′ |
“Circuit Length” is distance from ERV to Control Device.
Observe these limits to wire length and gauge in order to ensure reliable
operation of the control system.
5.4 WIRING SCHEMATICS
NOTE: The simplified schematics below show only the relevant portions of
the low-voltage control circuit in the ERV unit and representational external
control approaches. See the complete unit schematics above.
CAUTION
Make sure the control provides no voltage or current at its output terminals.
5.5 EXTERNAL CONTROL CONNECTIONS
5.5.1 Single 2-Wire Control, Powered
See Figure 5.6.0 if the control requires no power from the ERV and acts as a
simple ON/OFF switch. The control must not supply any power to the ERV.
- Install jumper (provided) between terminals 2 and 3.
- Connect the control’s contacts to terminals 1 and 4 to operate the isolation relays for OA/FA blower.
- Install jumper between terminals 4 and 5 to operate the ERV’s isolation relays for the RA/EA blower.
5.5.2 Single 2-Wire Control, Separate Power
Use the schematic shown in Section 5.5 if the control is on a separate power
supply with no power present at control output.
5.5.3 Control Sending 24 VAC “ON” Signal
See Figure 5.6.1 if a 24 VAC “ON” signal is to be sent from an external power
source to the ERV.
- Verify that a jumper is NOT installed between terminals 2 and 3.
- 24 VAC can be safely applied to terminals 3 and 4 to operate the Erv’s isolation relay for the OA/FA blower.
- Install a jumper (provided) between terminals 4 and 5 to operate the Erv’s isolation relay for the RA/EA blower.
- Supply only 24 VAC (not DC) from a Class II power source.
5.5.4 External Control Using ERV Power Supply
See Figure 5.6.2 if external control is to be applied using 24 VAC from the
ERV power supply.
- External control system must not draw more than 8 VA.
- Install jumper (provided) between terminals 2 and 3.
- Connect the switched output of the control to terminal 4 to operate the ERV’s isolation relay for the OA/FA blower.
- Install jumper between terminals 4 and 5 to operate the ERV’s isolation relay for the RA/EA blower.
5.5.5 Control with 2 Non-Powered Relay Contacts
See Figure 5.6.3 if the external control system provides no voltage or current
at its output contacts.
- Install jumper between terminals 2 and 3.
- Connect one side of each of the output contacts to terminal 1.
- Connect the other side of the output contact to terminal 4 in order to control the FA blower.
- Connect the other side of the output contact to terminal 5 in order to control the EA blower.
CAUTION
External control system should not draw more than 8 VA.
5.5.6 Control with 2 “ON” Signals, External Power
See Figure 5.6.4 if the controller is sending two 24 VAC “ON” signals from an
external power source.
- Verify there is NO jumper between terminals 2 and 3.
- Apply one 24 VAC signal to terminals 3 and 4 to operate the isolation relay for the FA blower.
- Apply the second 24 VAC signal to terminals 3 and 5 to operate the isolation relay for the EA blower.
- Verify that the polarity of each wire connected to terminal 3 is the same.
CAUTION
Supply only 24 VAC (not VDC) from a Class II Power Source.
5.6 QUICK-START FOR TESTING CORRECT 3PH WIRING
All units that run on 3 phase power should be test-run immediately after high
voltage wiring connections are made. This will verify that the three phases
are properly connected, that the dampers will open and close properly and the
fans are working properly.
For purposes of testing correct phase connections, the internal 24 VAC power
supply will be used to power-up the fans and all external control devices will
be disabled, when applicable.
UNIT OPERATION
NOTE: Any changes to unit low-voltage wiring should be made with the
disconnect switch in the OFF position.
NOTE: When installing temporary jumpers on the low-voltage termi- nal
strip, use 18 gauge or larger wire.
6.1 PRINCIPLE OF OPERATION
The HE4XINH has one basic purpose: to exhaust air from a structure and bring
in fresh air from outside, while transferring heating or cooling energy from
the exhaust air to the fresh air.
The HE4XINH is a very simple device, and will accomplish this purpose as long
as the blower is able to move air through the enthalpic core.
6.2 PRE-STARTUP
6.2.1 Verify Voltages
Using a voltmeter, test the input voltages as supplied to the disconnect
switch. Refer to Digit 13 of the unit Configuration Code to find the rated
voltage. The supplied voltage must be within +/- 10% of the rated voltage.
6.2.2 Verify Transformer Wiring
Units with 230 VAC power source are shipped with the transformer wired for 208
VAC. If the unit is receiving 230 VAC, make sure the black primary-side wire
on the transformer’s 208 V terminal has been moved to the 230 V terminal.
6.2.3 Inspect Filters
Filters must be installed prior to fan start-up. Filters must be clean and
butted tightly against each other, allowing no air circulation around them.
6.2.4 Inspect Foam Gasketing
Inspect the gasketing to make sure there are no gaps allowing air movement
around the cores or filters.
6.2.5 Inspect Belts and Verify Sheave Alignment
Prior to shipment from the factory, sheaves are carefully aligned and belts
are tensioned.
Inspect the motor mount to verify that it did not shift during shipment of the
unit. Verify that belts are still properly tensioned and that they track
correctly in the sheaves.
6.2.6 Inspect Fans
Prior to start-up, the fans should be rotated by hand to make sure that the
impeller is not rubbing anywhere and that they turn freely.
6.2.7 Inspect and Clean the Cabinet Interior
During the construction and installation phases of a project, dust, dirt and
debris will often accumulate inside a unit. Thoroughly clean the inside of the
unit by vacuuming and/or wiping metal surfaces with a damp rag.
6.2.8 Inspect Ductwork Connections
Ducts attached to the ERV must be firmly attached, sealed and supported in
accordance with installation instructions and SMACNA guidelines.
6.3 UNIT STARTUP
6.3.1 Fixed-Speed Units
Most fixed-speed units do not have any external controlling signals and only
require turning on the disconnect switch, located on the E-Box. When the
disconnect switch is turned ON, any dampers will first move into their correct
operating positions and then power is suppled to the motor contactors, causing
the fans to run.
Some fixed-speed units are wired to receive an actuating signal from an
external source.
If there is an external actuating signal source, verify the type of signal and
that it is wired according to the low-voltage wiring diagrams found in Section
5.6 of this manual. Turn on the disconnect switch and then turn ON the
actuating device. After any dampers have moved into their correct positions,
power is then applied to the motor contactors and the fans will begin running.
IMPORTANT
It is important to balance the airflows after the unit is operational and all
ductwork has been installed. Balancing the airflows is typically required by
state and/or local codes, and is often specified by the HVAC design engineer.
Optimum efficiency of the enthalpic cores is achieved when the airstreams are
properly balanced.
6.4 BALANCING AIRFLOWS
During the construction and installation phases of a project, dust, dirt and
debris will often accumulate inside a unit. Thoroughly clean the inside of the
unit by vacuuming and/or wiping metal surfaces with a damp rag.
All HVAC installations are governed by local and state building codes, some of
which include specific requirements for balancing of airflows. In addition,
the HVAC design engineer typically includes a specification for balancing of
airflows. If there is a conflict between the specification sources, consult
the HVAC design engineer.
A frequent requirement is for the airstreams to be perfectly balanced between
Fresh Air supply and Exhaust Air discharge. In practice, it is generally
preferable to leave a slight imbalance in the airflows, with the Exhaust Air
set for slightly less than Fresh Air intake, producing a slight positive
pressure within the Occupied Space. The reason for doing this is to reduce air
infiltration, which is untempered air. Having an imbalance in the airstreams
results in slightly lower efficiency in the energy transfer in the enthalpic
cores, but it is made up for by the reduction in air infiltration. Whenever
airstreams are adjusted for an imbalance, the imbalance should be no more than
5%. Each job site is different and equipment requirements will vary. Example:
there may be a water heater that is not ducted to the outside and therefore
consumes and discharges large amounts of building air.
The process of balancing airflows is accomplished after all ductwork has been
installed and examined for compliance to SMACNA guidelines. Improperly
designed and installed ductwork will cause turbulence in the airstreams and
restrictions in airflow, all of which will lower the operating efficiency of
the HVAC system.
All airflow adjustments are dependent on taking accurate measurements of
actual airflow by means of a manometer in the test ports on the unit. For some
units, digital controls may have been installed that incorporate airflow
sensors and it will not be necessary to take manometer readings. For further
information on using the information from an integrated commercial controller,
see the manual provided with the controller.
NOTE: ERV airflows are to be balanced after all ductwork is installed.
Balanc- ing of airflows is typically required by local or state building codes
or by the HVAC design engineer.
NOTE: The tubing should extend in the pressure port approx. 1″.
NOTE: These ports are carefully located on the unit to give the most
accurate airflow measurement. Do not relocate pressure ports.
NOTE: Make sure clean filters are installed before balancing airflow.
Dirty or clogged filters reduce airflow through the unit.
6.4.1 All Fixed-Speed Units
For all fixed-speed units, manometer readings are taken and then the
adjustable sheaves on the motors are adjusted to re-set fan speeds.
Equipment Required
- A magnehelic gauge or other device capable of measuring 0–1.0 in. water of differential pressure.
- 2 pieces of natural rubber latex tubing, 1/8″ ID, 1/16″ Wall works the best.
The individual differential static pressures (DP) are measured using the
installed pressure ports located in the front of the units core access doors.
Do not relocate pressure ports. Procedure:
- To read SCFM of Fresh Air (FA) install the “high” pressure side (+) of your measuring device to the Outside Air (OA) port and the “low” pressure side (-) to the Fresh Air (FA) port.
- To read SCFM of Room Air (RA) install the “high” pressure side (+) of your measuring device to the Room Air (RA) port and the “low” pressure side (-) to the Exhaust Air (EA) port.
- Use the reading displayed on your measurement device to cross reference the CFM output using the conversion chart.
DIFFERENTIAL STATIC ACROSS CORE DSP VS. CFM
HE4XINH| DP (H2O)| DSP| 0.20| 0.30| 0.40| 0.50| 0.60| 0.70| 0.80
Fresh Air (FA)| CFM| 1070| 1600| 2130| 2670| 3200| 3740| 4270
Room Air (RA)| CFM| 1140| 1710| 2280| 2850| 3420| 3990| 4560
6.4.2 Filter Pressure Drop
b CAUTION
The proper operating airflow range for this model is 1000–4400 CFM.
NOTE: Clean filter pressure drop is included in unit airflow performance
tables.
6.4.3 Sheave Adjustment
All fan motors that are not controlled by a VFD are equipped with an
adjustable sheave. These adjustable sheaves must be re-set in the field to
attain optimum performance of the ERV. This adjustment is to be done after all
ductwork is connected.
Adjustable sheaves are held in position on the drive motor shaft by a set
screw that is normally hidden until the belt(s) is removed. One flange is
fixed-position, the others are adjustableposition. The adjustable flanges of
the sheave have a set screw located in an exposed position on the collar of
the flange.
To adjust the flanges:
- Remove the drive belt(s)
- Loosen the set screws on both adjustable flanges
- IN HALF-TURN INCREMENTS, turn the adjustable flanges in or out the same number of turns
- Tighten the set screws on the adjustable flanges, making certain that the set screws are landing on the machined “flat” on the sheave.
6.4.4 Variable-Speed Units
The motors on variable-speed units also have adjustable sheaves, but they are
not to be adjusted. Speed control of variable-speed units is accomplished by
adjusting either the VFDs (if present) or the Integrated Commercial Controls
(if present). For more information on adjusting VFDs, see the manual that was
shipped with the unit. For more information on adjusting speeds via commercial
controls, see the Integrated Commercial Controller manual that was shipped
with the unit.
6.5 NORMAL OPERATION
Normal operation of the HE4XINH units involves continuous running of the fans,
shutting down only for periodic maintenance. Various optional control devices
may modulate the speed of the fans or may shut down one or more fans, but the
fans always have power and are ready to run continuously.
Continuous operation is acceptable in virtually all conditions and the unit
will not be damaged as long as air flow occurs. If filters become completely
blocked due to lack of maintenance, airflow will be blocked and the blower
motors may overheat. Continuous operation during extreme cold weather may
lead to frost.
6.6 EXTREME COLD OPERATION
HE4XINH units are capable of operating without internal frosting at
temperatures down to -10° F, with indoor humidity below 40%. The units can
operate under more severe conditions occasionally with little or no impact on
their performance. At lower humidities, they can operate at still lower
outside temperatures without freezing the enthalpic cores.
Some condensation or even frost may form on the outside of the unit or drip
off the cabinet during very cold conditions, especially if the unit runs
continuously. Exterior condensation during extreme cold conditions can be
reduced or prevented by periodically cycling the unit OFF for several minutes
to allow the cabinet to warm up.
UNIT MAINTENANCE
RenewAire ERVs are built to operate with minimal maintenance. After unit
commissioning, the primary areas of attention are the air filters, periodic
lubrication of the fan motors and annual vacuuming of the enthalpic cores.
7.1 MAINTENANCE 24 HRS. AFTER START-UP
24 hours after unit start-up:
- Readjust the tension on the motor drive belts.
- In new installations, check the air filters since they will often collect dust, dirt and debris at the time of start-up.
7.2 MAINTENANCE 30 DAYS AFTER START-UP
After 30 days of operation:
- Tighten all electrical connections, paying special attention to VFD wiring (if present).
- Readjust the tension on motor drive belts.
- Check the air filters as part of the normal monthly maintenance.
7.3 MAINTENANCE SCHEDULE
Experience on the part of the service person is the most important issue in
establishing a maintenance schedule. There will be times of the year when
frequent inspection of the filters will be required, such as spring and summer
when there may be pollen, dust, dirt or debris from budding trees and bushes
that can clog the filters. Also see Section 7.7 Maintenance Records in this
manual.
7.4 FILTERS
Inspection and replacement of air filters is the most frequent maintenance
issue. For units that do not have filter air pressure differential sensors,
filters must be visually inspected monthly, as a minimum. If a filter looks
discolored or dirty, REPLACE IT! When installing new filters, DO NOT USE
filter sprays. Residue from the filter spray could migrate to the enthalpic
core media and damage the cores.
For units that have filter air pressure differential sensors, a dirty filter
alarm will occur on the connected alarm or control device.
Filter cleanliness and replacement is the most important and frequent
maintenance issue. Dirty filters will cause an immediate reduction in
operating efficiency of the ERV. Normally, filters should be inspected and
changed when they are dirty. Paper filters are not to be cleaned, they are to
be replaced. In general, if a filter looks dirty, replace it. The best
indication of dirty filters is to check the pressure drop across the filter
banks with an optional filter monitor. If it is not possible to check the
pressure drop, the rule of thumb would be to change the filters every two
months.
7.5 FAN MOTORS
The most important issues in motor maintenance are:
- Belt condition and belt tension
- Sheave condition
- Motor cleanliness
- Motor lubrication
7.5.1 Belt Tension
Premature or frequent belt failures can be caused by improper belt tension
(either too loose or too tight) or misaligned sheaves. Abnormally high belt
tension or drive misalignment will cause excessive bearing loads and may
result in failure of the fan and/or motor bearings. Conversely, loose belts
will cause squealing on start-up, excessive belt flutter, slippage and
overheated sheaves. Both loose and tight belts can cause fan vibration.
WARNING
Danger of injury if unit starts unexpectedly. Switch power off at service
disconnect. Lock-out/tagout the disconnect.
WARNING
Danger of Electrical Shock when servicing an installed unit.
ALWAYS DISCONNECT POWER SOURCE BEFORE SERVICING! More than one disconnect
switch may be required.
Proper Wiring Size Selection and Wiring Installation are the Responsibility of
the Electrical Contractor.
Do not pry belts on or off the sheave. Loosen belt tension until the belts can
be removed by simply lifting the belts off the sheaves. After replacing belts,
ensure that slack in each belt is on the same side of the drive. Belt dressing
should never be used.
The proper belt setting is the lowest tension at which the belts will not slip
under peak load operation. For initial tensioning, set the belt deflection at
1/64″ for each inch of belt span (measured half-way between sheave centers).
Example: If the belt span is 16″, the belt deflection should be 1/64″, or 1/4″
(using moderate thumb pressure at mid-point of the drive). Check belt tension
two times during the first 24 hours of operation and periodically thereafter.
NOTE: Each motor manufacturer specifies the frequency of maintenance and
the amount and type of grease to use on the bearings. Do not mix different
types of grease. Check the manufacturer’s web site for each specific motor.
CAUTION
DO NOT WASH THE ENTHALPIC CORE. Keep it away from water or fire to avoid
damaging it. Always handle the core carefully.
7.5.2 Sheave Condition
Do not install new belts on worn sheaves. If the sheaves have grooves worn in
them, they must be replaced before new belts are installed.
7.5.3 Motor Cleanliness
Removing dust and grease buildup on the motor housing assists proper cooling.
Never washdown the motor with high pressure spray.
7.5.4 Motor Lubrication
High efficiency motors have unique maintenance requirements that vary from
motor to motor. Many smaller horsepower motors have sealed bearings that do
not require periodic greasing. Larger horsepower motors come equipped with
grease fittings. Before greasing any motor, consult the motor manufacturer’s
web site to determine the correct maintenance and greasing schedule.
7.6 ENTHALPIC CORES
Risk of DAMAGE TO ENTHALPIC CORES
CAUTION
7.6.1 Enthalpic Core Maintenance
The enthalpic core media is a fibrous material that must be kept clean at all
times. As a minimum, cores should be cleaned once per year.
- DO NOT WASH OR ALLOW THE ENTHALPIC CORES TO GET WET.
- DO NOT EXPOSE THE ENTHALPIC CORES TO HIGH HEAT OR FLAMES.
- DO NOT DIRECT COMPRESSED AIR AT THE CORE MEDIA.
- DO NOT REMOVE THE ENTHALPIC CORES FROM THE ERV UNLESS NECESSARY.
- USE CAUTION WHEN WORKING AROUND THE ENTHALPIC CORES. DO NOT DROP TOOLS OR OTHER OBJECTS ON THE CORES, DO NOT BUMP OR TWIST THE CORES.
Whenever working within the ERV cabinet, protect the enthalpic cores from
accidental damage. The core media is subject to damage from dropped tools or
other foreign objects.
7.6.2 Enthalpic Core Removal
Before removing enthalpic cores, switch the main disconnect to OFF. Open the
door to the Energy Recovery Module and simply pull each core straight out of
its guides.
7.6.3 Enthalpic Core Replacement
Cores have foam gasketing on one end of each core. The core should be
reinstalled so that the foam gasketing is toward the back of the ERV and the
core label is facing toward the front.
To access enthalpic cores for cleaning, remove the air filters.
To clean enthalpic cores, all exposed surfaces must be vacuumed with an
attachment having long, soft bristles. The greatest buildup of dirt and dust
will normally be on the leading 1–2 inches of the inlet side (closest to the
air filters).
When cores are removed from the ERV, they should be immediately protected
from accidental damage, water, high heat or flames.
7.7 MAINTENANCE RECORDS
MAINTENANCE LOG
ENTER DATES OF SERVICE
OA FILTER CHANGE| RA FILTER CHANGE| INSPECTION/
CLEANING| CLEAN CORE| CLEAN BLOWERS| INITIALS
| | | | |
| | | | |
| | | | |
| | | | |
| | | | |
7.8 HE4XINH SERVICE PARTS
TROUBLESHOOTING
If problems occur with a RenewAire ERV, the primary resources for trouble- shooting are the unit as-built wiring schematics and the Sequence Of Operation (SOO) for each control scheme.
FACTORY ASSISTANCE
In the unlikely event that you need assistance from the factory for a specific
issue, make sure that you have the information called for in the Unit Records
page in the Owner Information section of this manual. The person you speak
with at the factory will need that information to properly identify the unit
and the installed options.
To contact RenewAire Customer Service:
Call 800-627-4499
Email: RenewAireSupport@RenewAire.com
Remember that RenewAire Customer Service can only assist with the products
sold by RenewAire, it cannot resolve engineering issues that result from air
handling system design by others.
About RenewAire
For over 35 years, RenewAire has been a pioneer in enhancing indoor air
quality (IAQ) in commercial and residential buildings of every size. This is
achieved while maximizing sustainability through our fifth-generation, static-
plate, enthalpic-core Energy Recovery Ventilators (ERVs) that optimize energy
efficiency, lower capital costs via load reduction and decrease operational
expenses by minimizing equipment needs, resulting in significant energy
savings. Our ERVs are competitively priced, simple to install, easy to use and
maintain and have a quick payback. They also enjoy the industry’s best
warranty with the lowest claims due to long-term reliability derived from
innovative design practices, expert workmanship and Quick Response
Manufacturing (QRM).
As the pioneer of static-plate core technology in North America, RenewAire is
the largest ERV producer in the USA. We’re committed to sustainable
manufacturing and lessening our environmental footprint, and to that end our
Waunakee, WI plant is 100% powered by wind turbines. The facility is also one
of the few buildings worldwide to
be LEED® Gold and Green Globes certified, as well as having achieved ENERGY
STAR Building status. In 2010, RenewAire joined the Soler & Palau (S&P)
Ventilation Group in order to provide direct access to the latest in energy-
efficient air-moving technologies.
For more information, visit: renewaire.com
Member of the SandP Group
Family of Brands
2023 © RenewAire LLC
134739_008_FEB23