BLAUBERG KOMFORT EC DB 160 Heat Recovery Air Handling Unit User Manual
- September 9, 2024
- BLAUBERG
Table of Contents
KOMFORT EC DB 160 Heat Recovery Air Handling Unit
“`html
Specifications:
-
Model: KOMFORT EC DB 160 / KOMFORT EC DB 250 / KOMFORT EC DB
350 -
Power: 50 W / 190 W / 410 W
-
Max Air Flow: 3770 m3/h / 3200 m3/h
-
Efficiency: from 82% up to 94% / from 80% up to 91%
-
Energy Rating: A+
-
Heat Recovery Efficiency: from 80% up to 98% counter-flow
A -
Dimensions: 40 mm
Product Usage Instructions:
Safety Requirements:
When connecting the unit to the mains, ensure it is done through
a disconnecting device as per electrical wiring rules to allow full
disconnection under overvoltage conditions. Replace damaged supply
cords promptly by qualified personnel to prevent safety
hazards.
Disposal:
At the end of its service life, the product must be disposed of
separately and not as unsorted domestic waste.
Purpose:
The air handling unit is designed for efficient heat recovery
and air circulation.
Delivery Set:
-
Air handling unit
-
User’s manual
-
Control panel (for units with S11 and S14 automation)
-
Mounting boxes for wall flush and surface mounting (for units
with S14 automation) -
Fastening kit
-
Packing box
Unit Design and Operating Principle:
The unit operates by circulating air for heat recovery. Refer to
the compatibility table for optional equipment and unit models.
Summer Cooling Mode:
In this mode, the bypass damper is opened, allowing the intake
air to bypass the heat exchanger to maintain a constant
temperature.
FAQ:
Q: Can I connect the unit to an external switching device like
a timer?
A: No, to avoid safety hazards, the unit must not be supplied
through an external switching device.
“`
Heat recovery air Handling unit
KOMFORT EC DB 160 KOMFORT EC DB 250 KOMFORT EC DB 350
EN uSer’S Manual
www.blaubergventilatoren.de
KoMFort ec dB 160/250/350
CONTENTS
Safety requirements………………………………………………………………………………………………………………………………………………… 2
Purpose………………………………………………………………………………………………………………………………………………………………………… 5
Delivery set…………………………………………………………………………………………………………………………………………………………………. 5
Designation key………………………………………………………………………………………………………………………………………………………… 5
Technical data……………………………………………………………………………………………………………………………………………………………. 6
Unit design and operating principle…………………………………………………………………………………………………………………
8 Installation and set-
up……………………………………………………………………………………………………………………………………………. 11 Connection to
power mains ………………………………………………………………………………………………………………………………. 15 Technical
maintenance………………………………………………………………………………………………………………………………………….. 17 Storage
and transportation regulations………………………………………………………………………………………………………….. 18
Manufacturer’s warranty………………………………………………………………………………………………………………………………………..
19 Certificate of
acceptance………………………………………………………………………………………………………………………………………. 20 Seller
information…………………………………………………………………………………………………………………………………………………….. 20
Installation certificate………………………………………………………………………………………………………………………………………………
20 Warranty card……………………………………………………………………………………………………………………………………………………………..
20
This user’s manual is a main operating document intended for technical, maintenance, and operating staff. The manual contains information about purpose, technical details, operating principle, design, and installation of the KOMFORT EC DB 160/250/350 unit and all its modifications. Technical and maintenance staff must have theoretical and practical training in the field of ventilation systems and should be able to work in accordance with workplace safety rules as well as construction norms and standards applicable in the territory of the country.
SAFETY REQUIREMENTS
This unit is not intended for use by persons (including children) with reduced
physical, sensory or mental capabilities, or lack of experience and knowledge,
unless they have been given supervision or instruction concerning use of the
unit by a person responsible for their safety. Children should be supervised
to ensure that they do not play with the unit. This appliance can be used by
children aged from 8 years and above and persons with reduced physical,
sensory or mental capabilities or lack of experience and knowledge if they
have been given supervision or instruction concerning use of the appliance in
a safe way and understand the hazards involved. Cleaning and user maintenance
shall not be done by children without supervision. Children shall not play
with the appliance.
Connection to the mains must be made through a disconnecting device, which is
integrated into the fixed wiring system in accordance with the wiring rules
for design of electrical units, and has a contact separation in all poles that
allows for full disconnection under overvoltage category III conditions.
If the supply cord is damaged, it must be replaced by the manufacturer, its
service agent, or similarly qualified persons in order to avoid a safety
hazard.
2
KoMFort ec dB 160/250/350
www.blaubergventilatoren.de
CAUTION: In order to avoid a safety hazard due to inadvertent resetting of the
thermal cutout, this unit must not be supplied through an external switching
device, such as a timer, or connected to a circuit that is regularly switched
on and off by the utility.
Ensure that the unit is switched off from the supply mains before removing the
guard. WARNING: If there are any unusual oscillating movements, immediately
stop using the unit and contact the manufacturer, its service agent or
suitably qualified persons. The replacement of parts of the safety suspension
system device shall be performed by the manufacturer, its service agent or
suitably qualified persons. Precautions must be taken to avoid the back-flow
of gases into the room from the open flue of gas or other fuel-burning
appliances.
The appliance may adversely affect the safe operation of appliances burning
gas or other fuels (including those in other rooms) due to back flow of
combustion gases. These gases can potentially result in carbon monoxide
poisoning. After installation of the unit the operation of flued gas
appliances should be tested by a competent person to ensure that back flow of
combustion gases does not occur. Fixing means for attachment to the ceiling
such as hooks or other devices shall be fixed with a sufficient strength to
withstand 4 times the weight of the appliance. The mounting of the suspension
system shall be performed by the manufacturer, its service agent or suitably
qualified persons. The appliance is to be installed so that the blades are
more than 2.3m (2,1 m AU) above the floor.
All operations described in this manual must be performed by qualified
personnel only, properly trained and qualified to install, make electrical
connections and maintain ventilation units. Do not attempt to install the
product, connect it to the mains, or perform maintenance yourself. This is
unsafe and impossible without special knowledge. Disconnect the power supply
prior to any operations with the unit. All user’s manual requirements as well
as the provisions of all the applicable local and national construction,
electrical, and technical norms and standards must be observed when installing
and operating the unit. Disconnect the unit from the power supply prior to any
connection, servicing, maintenance, and repair operations. Connection of the
unit to power mains is allowed by a qualified electrician with a work permit
for the electric units up to 1000 V after careful reading of the present
user’s manual. Check the unit for any visible damage of the impeller, the
casing, and the grille before starting installation. The casing internals must
be free of any foreign objects that can damage the impeller blades. While
mounting the unit, avoid compression of the casing! Deformation of the casing
may result in motor jam and excessive noise. Misuse of the unit and any
unauthorised modifications are not allowed. Do not expose the unit to adverse
atmospheric agents (rain, sun, etc.). Transported air must not contain any
dust or other solid impurities, sticky substances, or fibrous
3
www.blaubergventilatoren.de
KoMFort ec dB 160/250/350
materials. Do not use the unit in a hazardous or explosive environment containing spirits, gasoline, insecticides, etc. Do not close or block the intake or extract vents in order to ensure the efficient air flow. Do not sit on the unit and do not put objects on it. The information in this user’s manual was correct at the time of the document’s preparation. The Company reserves the right to modify the technical characteristics, design, or configuration of its products at any time in order to incorporate the latest technological developments. Never touch the unit with wet or damp hands. Never touch the unit when barefoot. BEFORE INSTALLING ADDITIONAL EXTERNAL DEVICES, READ THE RELEVANT USER MANUALS.
THE PRODUCT MUST BE DISPOSED SEPARATELY AT THE END OF ITS SERVICE LIFE.
DO NOT DISPOSE THE UNIT AS UNSORTED DOMESTIC WASTE.
4
KoMFort ec dB 160/250/350
www.blaubergventilatoren.de
PURPOSE
The unit is designed to ensure continuous mechanical air exchange in houses,
offices, hotels, cafes, conference halls, and other utility and public spaces
as well as to recover the heat energy contained in the air extracted from the
premises to warm up the filtered stream of intake air. The unit is not
intended for organizing ventilation in swimming pools, saunas, greenhouses,
summer gardens, and other spaces with high humidity. Due to the ability to
save heating energy by means of energy recovery, the unit is an important
element of energy-efficient premises. The unit is a component part and is not
designed for stand-alone operation. It is rated for continuous operation.
Transported air must not contain any flammable or explosive mixtures,
evaporation of chemicals, sticky substances, fibrous materials, coarse dust,
soot and oil particles or environments favourable for the formation of
hazardous substances (toxic substances, dust, pathogenic germs).
DELIVERY SET
Air handling unit
1 pc.
User’s manual
1 pc.
Control panel (only for units with S11 and S14 automation)
1 pc.
Mounting box for wall flush mounting (only for units with S14 automation)
1 pc.
Mounting box for wall surface mounting (only for units with S14 automation)
1 pc.
Fastening kit
1 pc.
Packing box
1 pc.
DESIGNATION KEY
KOMFORT EC D B X L S14
Control S11/S14/S21 Service side L – left service side R – right service side Rated air flow [m3/h] Additional components B bypass Spigot orientation D suspended mounting, horizontal spigot orientation Motor type EC electronically commutated Unit type
5
www.blaubergventilatoren.de
KoMFort ec dB 160/250/350
TECHNICAL DATA
The unit is designed for indoor application with the ambient temperature
ranging from +1 °C up to +40 °C and relative humidity up to 60 % without
condensation. In cold, damp rooms, there is a possibility of freezing or
condensation inside and outside the casing. In order to prevent condensation
on the internal walls of the unit, it is necessary that the surface
temperature of the casing is 2-3 °C above the dew point temperature of the
transported air. The unit should be operated continuously, and in cases where
ventilation is not necessary, reduce the air flow of the fans to a minimum
(20%). This will ensure a favorable indoor climate and reduce the amount of
condensation inside the unit, which can damage electronic components. Never
use the unit for dehumidification, for example, of new buildings. The unit is
rated as a Class I electrical appliance. Hazardous parts access and water
ingress protection rating: IP22 for the unit connected to the air ducts IP44
for the unit motors The unit design is constantly being improved, thus some
models may be slightly different from those described in this manual.
MODEL
KOMFORT EC DB 160 KOMFORT EC DB 250 KOMFORT EC DB 350
Supply voltage, 50 (60) Hz [V] Nominal power consumption [W] Current [A] Maximum air flow [m3/h] RPM, min-1 Sound pressure level at 3 m distance [dBA] Transported air temperature [°C] Casing material Insulation (mineral wool) [mm] Extract filter Supply filter Connected air duct diameter [mm] Weight [kg] Heat recovery efficiency Heat exchanger type SEC class
50 0.4 190 3770 26
40 mm
Ø 125 48
from 82 up to 94 %
A+
1~ 220 240 101 0.8 270 4480 28
from -25 up to +40 aluzinc steel 40 mm G4 F7 Ø 125 48
from 80 up to 98 % counter-flow A
170 1.3 410 3200 34
40 mm
Ø 160 70
from 80 up to 91 %
A+
6
KoMFort ec dB 160/250/350
ØD
A
B2
B
Ø16
A
A2
A1
B3
B1
B
Ø10,2
8 holes
www.blaubergventilatoren.de
L3 L4
L3 L4 H1
L3 L4
H
LEFT-HANDED MODIFICATION
A view (indoor connection)
L2
L1
L6
B view (outdoor connection)
L5
L
L2
RIGHT-HANDED MODIFICATION
A view (outdoor connection)
L2
L1
L6
B view (indoor connection)
L5
L
L2
L3 L4
Model
KOMFORT EC DB 160 KOMFORT EC DB 250 KOMFORT EC DB 350
Dimensions [mm] ØD A A1 A2 B B1 B2 B3 H H1 L L1 L2 L3 L4 L5 L6 125 1008 1105 1073 754 822 480 410 320 361 386 293 245 31 128 123 216 125 1008 1105 1073 754 822 480 410 320 361 386 293 245 31 128 123 216 160 1138 1235 1203 1044 1112 680 610 320 361 555 417 345 40 119 144 282
7
www.blaubergventilatoren.de
KoMFort ec dB 160/250/350
UNIT DESIGN AND OPERATING PRINCIPLE
The unit has the following operating logic: warm stale extract air from the
room flows into the unit, where it is filtered by the extract filter, then air
flows through the heat exchanger and is exhausted outside by the extract fan.
Cold fresh air from the outside flows into the unit, where it is cleaned by
the supply filter. Then the air flows through the heat exchanger and is
directed to the room with the supply fan. Heat energy of warm extract air is
transferred to clean intake fresh air from the outside and warms it up. The
air flows are fully separated while flowing through the heat exchanger. Heat
recovery minimizes heat losses, which reduces the cost of space heating in the
cold season. The difference between the supply and extract air flow
temperature leads to condensate generation. Condensate is collected in the
drain pan and is removed outside through the drain pipe.
KOMFORT EC DB … L
BOTTOM VIEW
10
1
2 3 11 4 5 6 7 12 8
KOMFORT EC DB … R
9 10
1 cable glands; 2 supply fan; 3 control unit; 4 bypass damper; 5
extract filter; 6 counter-flow heat exchanger; 7 drain pan; 8 detachable
plates for technical maintenance of filters; 9 drain pipe; 10 SETUP MODE
button (for KOMFORT EC DB 160/250/350 A21 units); 11 extract fan; 12
supply filter.
Additional equipment (is not included in the delivery set, can be ordered
separately) Humidity sensor. The FS2 humidity sensor is connected to the
controller in KOMFORT EC DB 160/250/350 A21 models, and to the terminal block
in KOMFORT EC DB 160/250/350 A14 models. The HR-S humidity sensor is connected
to the controller. The unit with the installed humidity sensor maintains a set
indoor humidity point. As the extract air humidity rises above the set point,
the system automatically switches to the maximum speed. As the humidity drops
down below the set point the unit returns to the previous mode. CO2 sensor
(connected to the controller) Measures the level of concentration of carbon
dioxide in the room and generates a signal that controls the performance of
the fan. Air capacity control based on CO2 concentration is an efficient
energy saving solution. VOC sensor (connected to the controller) Qualitative
assessment of air saturation with contaminants (cigarette smoke, exhaled air,
solvent and detergent vapours). The sensor sensitivity can be adjusted with
regards to the expected maximum level of air pollution. Enables on-demand
ventilation which results in considerable energy savings as air is exchanged
only upon reaching the preset level of pollution. Duct preheater. The heater
maintains the duct air temperature at a point that prevents the heat exchanger
freezing. Heater installation and connection to the unit are described in the
heater user’s manual. Duct reheater. The heater maintains the room temperature
set by the user. Heater installation and connection to the unit are described
in the heater user’s manual.
8
KoMFort ec dB 160/250/350
Compatibility table of optional equipment and unit models
www.blaubergventilatoren.de
FS1 internal humidity sensor
FS2 internal humidity sensor CO2-1 room sensor CO2-2 room sensor Room humidity
sensor VOC room sensor
(0-10 V) CO2 room sensor
(0-10 V) Room humidity sensor (0-10 V)
Preheater Reheater
KOMFORT EC DB 160/250/350 S11
—
—
—
—
—
—
—
—
KOMFORT EC DB 160/250/350 S14
—
—
—
—
—
—
KOMFORT EC DB 160/250/350 S21
—
UNIT OPERATION MODES Heat recovery mode: warm stale extract air from the room
flows into the unit, where it is filtered by the extract filter, then air
flows through the heat exchanger and is exhausted outside by the extract fan.
Cold fresh air from the outside flows into the unit, where it is cleaned by
the supply filter. Then the air flows through the heat exchanger and is
directed to the room with the supply fan. Supply air is heated in the heat
exchanger by transferring the heat energy of warm and humid extract air to the
cold fresh air. The air flows are fully separated while flowing through the
heat exchanger. Heat recovery minimizes heat losses, which reduces the cost of
space heating in the cold season.
EXHAUST AIR
SUPPLY AIR
EXTRACT AIR
INTAKE AIR
Freeze protection (danger of freezing appears when the exhaust air temperature downstream of the heat exchanger is lower than +5 °C and intake air temperature upstream of the heat exchanger is lower than -3 °C for the units with preheating, and when exhaust temperature downstream of the heat exchanger is lower than +3 °C for the units without preheating). To protect the heat exchanger from freezing in the cold season, the unit has a Frost Protection mode based on the temperature sensor readings. The sensor is installed in the exhaust air duct downstream of the heat exchanger. The Frost Protection mode is activated at an exhaust air temperature of +3 °. After temperature increase the unit returns to the previous operation mode. In KOMFORT EC DB 160/250/350 S11 units the frost protection mode must be activated, see the User’s manual of the control panel. In case of freezingdanger,thesupplyfanisturnedoffinKOMFORTECDB160/250/350 S14units.Aftertemperatureincreasetheunitreturnstotheprevious operation mode.The KOMFORT EC DB 160/250/350 S21 units have three frost protection modes: – gradual reduction of the supply fan speed – with the bypass – with the electric preheater (if the unit is equipped with a duct preheater). Mode selection and settings are described in the User’s manual for the control system.
9
www.blaubergventilatoren.de
SUPPLY AIR EXTRACT AIR
KoMFort ec dB 160/250/350
EXHAUST AIR
INTAKE AIR
Summer Cooling mode: the bypass damper is opened, the intake air that is
supplied to the premises bypasses the heat exchanger. The intake air
temperature remains constant.
EXHAUST AIR
SUPPLY AIR
EXTRACT AIR
INTAKE AIR
10
KoMFort ec dB 160/250/350
www.blaubergventilatoren.de
INSTALLATION AND SET-UP
HUMIDITY SENSOR MOUNTING Remove the service panel and install the humidity
sensor into the mount from the side of the extract air duct and connect the
humidity sensor connector to the respective contact socket coming from the
control unit. FS2 sensor:
Install the service panel back to the unit.
UNIT INSTALLATION To attain the best performance of the unit and to minimise
turbulence-induced air pressure losses connect the straight air duct section
to the spigots on both sides of the unit while mounting. Minimum straight air
duct length: · equal to 1 air duct diameter on the intake side · equal to 3
air duct diameters on the outlet side If the air ducts are too short or not
connected, protect the unit parts from ingress of foreign objects. To prevent
uncontrollable access to the fans, the spigots may be covered with a
protecting grille or other protecting device with mesh width not more than
12.5 mm. While installing the unit, ensure convenient access for subsequent
maintenance and repair. Fasteners for ceiling mounting are not included in the
delivery set and should be ordered separately. While choosing fasteners
consider the material of the mounting surface as well as the weigh of the
unit, refer to the Technical data section. Fasteners for unit installation
should be selected by a qualified technician.
min 200 mm
min 20 mm
min 350 mm
min 500 mm
Nut Washer Vibration-absorbing rubber Nut and lock-nut
11
www.blaubergventilatoren.de
KoMFort ec dB 160/250/350
Wall and ceiling mounting examples
KOMFORT EC DB … L
EXTRACT AIR
SUPPLY AIR
KOMFORT EC DB … R
SUPPLY AIR
EXTRACT AIR
KOMFORT EC DB … L
EXHAUST AIR
INTAKE AIR
KOMFORT EC DB … R
INTAKE AIR
EXHAUST AIR
INTAKE AIR
EXHAUST AIR
EXHAUST AIR
INTAKE AIR
SUPPLY AIR
EXTRACT AIR
EXTRACT AIR
SUPPLY AIR
12
KoMFort ec dB 160/250/350
www.blaubergventilatoren.de
RIGHT-HANDED AND LEFT-HANDED MODIFICATIONS The figure below shows the arrangement of spigots for left- and right-handed modifications. Choosing the right arrangement can improve the ease of installation, shorten the length of the ducts and reduce the number of air duct bends.
Cable glands
Extract air Supply air Drain pipe Drain pipe Supply air Extract air
KOMFORT EC DB … R KOMFORT EC DB … L
Cable glands
View from above
Intake air Exhaust air
Exhaust air Intake air
Extract air Supply air
KOMFORT EC DB … L
Intake air Exhaust air
KOMFORT EC DB … R
Intake air Exhaust air
Extract air Supply air
13
www.blaubergventilatoren.de
KoMFort ec dB 160/250/350
CONDENSATE DRAINAGE Connect the drain pipe to the sewage system using the SFK
20×32 U-trap kit (available upon separate order). The pipe slope downwards
must be at least 3°.
U-trap
min 3°
Drain hose
Drain hose
Sewage system Sewage system
Drain pipe
Drain hose
Drain hose
U-trap
min 3°
Drain pipe
min 3° min 3°
The condensate drainage system is designed for normal operation in premises with air temperatures above 0 °C! If the expected ambient air temperatures are below 0 °C, the condensate drainage system must be equipped with heat insulation and pre-heating facilities.
14
KoMFort ec dB 160/250/350
CONNECTION TO POWER MAINS
www.blaubergventilatoren.de
ANY TAMPERING WITH THE INTERNAL CONNECTIONS IS PROHIBITED AND WILL VOID THE WARRANTY.
· The unit is rated for connection to 1~230 V/50 (60) Hz power mains according
to the wiring diagram. · The connection must be made using durable, insulated
and heat-resistant conductors (cables, wires). The actual wire cross section
selection must be based on the maximum load current, maximum conductor
temperature depending in the wire type, insulation, length and installation
method. · The external power input must be equipped with a automatic circuit
breaker built into the stationary wiring to open the circuit in the event of
overload or short-circuit. The position of the circuit breaker must ensure
free access for quick unit power-off. The trip current of the automatic
circuit breaker must exceed the maximum current consumption of the unit (refer
to the “Technical data” section or to the unit label). The recommended trip
current of the circuit breaker is the next current in the standard trip
current row following the maximum current of the connected unit. · The
automatic circuit breaker is not included in the delivery set and can be
ordered separately. To access the control unit, remove the service panel.
1 1
External wiring diagram for KOMFORT EC DB 160/250/350 S11 units
23 4
5
6 7 8 9 10 11 12 13 14 15 16
L N PE L
N c no c no +12V GND B A +5V GND Vo
White Green Brown Yellow
t °C
Power input 230 VAC
21 21
LN LN
12
U
(no-contact) +12V Gnd B A
+5V Gnd Vo
SM1*
Designation CCU SM1 SM2 PK1 P1 TE1
Name DX cooler Supply air damper actuator Extract air damper actuator Contact from a fire alarm panel Control panel Outdoor temperature sensor
*Is not included in the delivery set
SM2*
PK1*
P1
TE1
Model N0
LF 230 LF 230
N0
Wire** 2×0.75 mm2 2×0.75 mm2 2×0.75 mm2 2×0.75 mm2
The sensor is installed by the manufacturer in the intake air duct. ** Maximum connecting cable length is 20 m! –ELECTRIC SHOCK HAZARD!
15
www.blaubergventilatoren.de
KoMFort ec dB 160/250/350
External wiring diagram for KOMFORT EC DB 160/250/350 S14 units The unit has an option of additional external controls connection to the X2 terminal block, which is located on the hinged electrical mounting plate of the control unit. Extra connections to the unit are shown in dotted lines in the External wiring diagram.
PK fire alarm panel (remove the jumper while connecting the contact)
Humidity sensor
Power input 230 VAC
+U 3 GND 2 0-10V 1
Control panel
Electric actuators
of the external air dampers
– Tx Rx + External device NO (CO2 sensor))
SM1 SM2 supply exhaust
L1 N L1 N
White Brown Green Yellow
X1 L
12
X2 N PE PK PK +U 0-10VGND N C GND Tx Rx +U SM-L SM-N
3 4 1 2 3 4 5 6 7 8 9 10 11 12 13
–ELECTRIC SHOCK HAZARD!
External wiring diagram for KOMFORT EC DB 160/250/350 S21 units
X1
A1
F1 L N PE L N NO NC NC C NO C Com Out1 NO In1 Com Out1 NO In1 TE_H Gnd Valve1 Valve2 KKB CO2
RS485
2.5A L1 N 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 NO C NO C NO C Gnd 0-10V +24V Gnd A B +24V
31
32
Brown White
CCU*
1 2 3 4
Power input 230 VAC
21 21 PK1 Boost
12 34 N In 90 60
EVH*
12 34 N In 90 60
ENH*
12
RT2 ENH*
**U
**U
2 121
SM1 SM2
Gnd 0-10V 24V GND +24V
CO2*
P1*
Designation S1 S2 1 CCU 1 Boost CO2 ENH ENH RT2 EVH
Name Supply air damper actuator Exhaust air damper actuator Contact from fire alarm control panel Cooler control External control panel Contacts ON/OFF Boost External CO2 sensor Channel heater (afterheater) Channel temperature sensor Channel heater (preheating)
Wire*** Contact type 2 x 0,75 mm2 NO 2 x 0,75 mm2 NO 2 x 0,75 mm2 NC 2 x 0,75 mm2 NO 4 x 0,5 mm2 2 x 0,75 mm2 NO 3 x 0,25 mm2 NO 4 x 0,5 mm2 2 x 0,25 mm2 4 x 0,5 mm2
Note 3 A, 30 V DC/~250 AC 3 A, 30 V DC/~250 AC Remove 31 jumper 3 A, 30 V
DC/~250 AC
With ENH, Remove 32 jumper
Not included in the delivery set. The U supply voltage of the SM1, SM2 external dampers is selected depending on the type of dampers. Maximum connecting cable length is 20 m!
— ELECTRIC SHOCK HAZARD!
16
KoMFort ec dB 160/250/350
www.blaubergventilatoren.de
TECHNICAL MAINTENANCE
Maintenance operations of the unit are required 3-4 times per year.
Maintenance includes general cleaning of the unit and the following
operations:
1. Filter maintenance (3-4 times per year). Dirty filters increase air
resistance in the system and reduce supply air volume. The filters require
cleaning not less than 3-4 times per year. Vacuum cleaning is allowed. After
two consecutive cleanings filters must be replaced. For new filters, contact
the Seller. To clean or replace the filters, detach the removable plates
located on the service side of the unit. After cleaning install the filters
and the detachable plates in the reverse order.
2. Heat exchanger maintenance (once per year). Some dust may accumulate on the heat exchanger even in case of regular maintenance of the filters. To maintain the high heat recovery efficiency, regular cleaning is required. The heat exchanger is connected with the drain pan by the fixing bands that should be removed only in case of heat exchanger replacement. The drain pan is fixed to the unit casing using three screws. To clean the heat exchanger pull it and the drain pan out, drain the water through the pipes, then flush the heat exchanger with warm detergent solution. After cleaning install the dry heat exchanger with the drain pan back to the unit.
17
www.blaubergventilatoren.de
KoMFort ec dB 160/250/350
3. Fan maintenance (once per year). Even in case of regular maintenance of the filters, some dust may accumulate inside the fans and reduce the fan performance and supply air flow. Clean the fans with a soft brush or cloth. Do not use water, aggressive solvents, or sharp objects as they may damage the impeller. 4. Technical maintenance of condensate drainage system (once a year). The condensate drainage (drain line) may get clogged by dirt and dust particles contained in the exhaust air. Pour some water inside the drain pan to check the pipe for clogging. Clean the U-trap and the drain pipe if required. 5. Ductwork system maintenance (once in 5 years). Even regular fulfilling of all the maintenance operations prescribed above may not completely prevent dirt accumulation in the air ducts, which leads to air pollution and reduces the unit capacity. Duct maintenance means regular cleaning or replacement. 6. Control unit maintenance (if necessary). The control unit is positioned inside the unit casing. For accessing the control unit remove the fixing screws on the service panel and remove it. CAUTION! The control unit maintenance must be performed by an expert qualified for unassisted operations with electrical installations with the voltage up to 1000 V after careful reading of the user’s manual.
TROUBLESHOOTING
Problem
Possible reasons
Troubleshooting
The fan(s) do(es) not get started.
No power supply.
Low air flow. Noise, vibration.
Filters, fans or the heat exchanger are soiled.
The ventilation system is soiled or damaged. The fan impeller is soiled. Fan
screw connection is loose.
Make sure the power supply line is connected correctly, otherwise troubleshoot
a connection error.
Clean or replace the filters, clean the fans, and the heat exchanger.
Make sure the air ducts are clean and intact.
Clean the impellers.
Check tightening torques.
Water leakage.
The drainage system is soiled, damaged, or installed incorrectly.
Clean the drain line if necessary. Check the drain line slope angle. Make sure that the U-trap is filled with water and the drain pipes are frost protected.
STORAGE AND TRANSPORTATION REGULATIONS
· Store the unit in the manufacturer’s original packaging box in a dry closed
ventilated premise with temperature range from +5 ° to +40 ° and relative
humidity up to 70 %.
· Storage environment must not contain aggressive vapors and chemical mixtures
provoking corrosion, insulation, and sealing deformation.
· Use suitable hoist machinery for handling and storage operations to prevent
possible damage to the unit. · Follow the handling requirements applicable for
the particular type of cargo. · The unit can be carried in the original
packaging by any mode of transport provided proper protection against
precipitation and
mechanical damage. The unit must be transported only in the working position.
· Avoid sharp blows, scratches, or rough handling during loading and
unloading. · Prior to the initial power-up after transportation at low
temperatures, allow the unit to warm up at operating temperature for at
least 3-4 hours.
18
KoMFort ec dB 160/250/350
www.blaubergventilatoren.de
MANUFACTURER’S WARRANTY
The product is in compliance with EU norms and standards on low voltage
guidelines and electromagnetic compatibility. We hereby declare that the
product complies with the provisions of Electromagnetic Compatibility (EMC)
Directive 2014/30/EU of the European Parliament and of the Council, Low
Voltage Directive (LVD) 2014/35/EU of the European Parliament and of the
Council and CE-marking Council Directive 93/68/EEC. This certificate is issued
following test carried out on samples of the product referred to above. The
manufacturer hereby warrants normal operation of the unit for 24 months after
the retail sale date provided the user’s observance of the transportation,
storage, installation, and operation regulations. Should any malfunctions
occur in the course of the unit operation through the Manufacturer’s fault
during the guaranteed period of operation, the user is entitled to get all the
faults eliminated by the manufacturer by means of warranty repair at the
factory free of charge. The warranty repair includes work specific to
elimination of faults in the unit operation to ensure its intended use by the
user within the guaranteed period of operation. The faults are eliminated by
means of replacement or repair of the unit components or a specific part of
such unit component.
The warranty repair does not include: · routine technical maintenance · unit
installation/dismantling · unit setup To benefit from warranty repair, the
user must provide the unit, the user’s manual with the purchase date stamp,
and the payment paperwork certifying the purchase. The unit model must comply
with the one stated in the user’s manual. Contact the Seller for warranty
service.
The manufacturer’s warranty does not apply to the following cases: · User’s
failure to submit the unit with the entire delivery package as stated in the
user’s manual including submission with missing
component parts previously dismounted by the user. · Mismatch of the unit
model and the brand name with the information stated on the unit packaging and
in the user’s manual. · User’s failure to ensure timely technical maintenance
of the unit. · External damage to the unit casing (excluding external
modifications as required for installation) and internal components caused
by the user. · Redesign or engineering changes to the unit. · Replacement and
use of any assemblies, parts and components not approved by the manufacturer.
· Unit misuse. · Violation of the unit installation regulations by the user. ·
Violation of the unit control regulations by the user. · Unit connection to
power mains with a voltage different from the one stated in the user’s manual.
· Unit breakdown due to voltage surges in power mains. · Discretionary repair
of the unit by the user. · Unit repair by any persons without the
manufacturer’s authorization. · Expiration of the unit warranty period. ·
Violation of the unit transportation regulations by the user. · Violation of
the unit storage regulations by the user. · Wrongful actions against the unit
committed by third parties. · Unit breakdown due to circumstances of
insuperable force (fire, flood, earthquake, war, hostilities of any kind,
blockades). · Missing seals if provided by the user’s manual. · Failure to
submit the user’s manual with the unit purchase date stamp. · Missing payment
paperwork certifying the unit purchase.
FOLLOWING THE REGULATIONS STIPULATED HEREIN WILL ENSURE A LONG AND TROUBLE-
FREE OPERATION OF THE UNIT
USER’S WARRANTY CLAIMS SHALL BE SUBJECT TO REVIEW ONLY UPON PRESENTATION OF
THE UNIT, THE PAYMENT DOCUMENT AND THE USER’S MANUAL
WITH THE PURCHASE DATE STAMP
19
www.blaubergventilatoren.de
KoMFort ec dB 160/250/350
20
KoMFort ec dB 160/250/350
www.blaubergventilatoren.de
21
www.blaubergventilatoren.de
KoMFort ec dB 160/250/350
22
KoMFort ec dB 160/250/350
www.blaubergventilatoren.de
CERTIFICATE OF ACCEPTANCE
Unit Type Model
Serial Number
Manufacture Date Quality Inspector’s Stamp
Heat recovery air handling unit
SELLER INFORMATION
Seller Address Phone Number E-mail Purchase Date This is to certify acceptance
of the complete unit delivery with the user’s manual. The warranty terms are
acknowledged and accepted.
Customer’s Signature
INSTALLATION CERTIFICATE
The _____ unit is installed pursuant to the
requirements stated in the present user’s manual.
Company name
Address
Phone Number
Installation Technician’s Full Name
Installation Date:
Signature:
The unit has been installed in accordance with the provisions of all the applicable local and national construction, electrical and technical codes and standards. The unit operates normally as intended by the manufacturer.
Signature:
WARRANTY CARD
Unit Type Model
Serial Number
Manufacture Date Purchase Date Warranty Period Seller
Heat recovery air handling unit
Seller’s Stamp Installation Stamp
Seller’s Stamp
23