novus TxMini-M12 Compact Temperature Transmitter User Guide
- September 12, 2024
- Novus
Table of Contents
TxMini-M12 Compact Temperature Transmitter
“`html
Specifications
- Model: TXMINI-M12
- User Guide Version: V1.0x K
Product Information
1. Introduction
Thank you for choosing the TxMini-M12 transmitter. This user
guide will help you understand how to install, configure, and use
the transmitter effectively.
2. Specifications
2.1 Accuracy
The accuracy of the TxMini-M12 transmitter is detailed in the
specifications provided by the manufacturer.
2.2 Measurement Range
The TxMini-M12 transmitter has a specified measurement range
which should be adhered to for accurate readings.
3. Mechanical Installation
Follow the mechanical installation instructions provided in this
user guide to ensure proper mounting and positioning of the
transmitter.
4. Electrical Installation
Proper electrical installation is crucial for the optimal
functioning of the TxMini-M12 transmitter. Ensure you follow the
recommendations provided in this section.
4.1 Installation Recommendations
Refer to the installation recommendations for best practices
when setting up the transmitter.
4.2 Power Supply and Communication Connection
Connect the TxMini-M12 transmitter to the power supply and
communication devices as instructed in this section.
4.3 Sensor Connection
Instructions on how to connect sensors to the TxMini-M12
transmitter can be found here.
4.4 M12 Cable Connection
Details on how to properly connect the M12 cable to the
TxMini-M12 transmitter are provided in this section.
5. Configuration
Learn how to configure the TxMini-M12 transmitter using factory
settings, a TxConfig-M12 device, or Signow software.
5.1 Factory Settings
Instructions on restoring the transmitter to factory settings
can be found here.
5.2 Using a TxConfig-M12
Utilize a TxConfig-M12 device for configuring the settings of
the transmitter.
5.3 Signow Software
Use Signow software for advanced configuration of the TxMini-M12
transmitter.
5.3.1 Connecting the Device to Your Computer
Follow these steps to establish a connection between the
transmitter and your computer using Signow software.
5.3.2 Configuration Section
Navigate through the configuration section of the Signow
software to adjust specific settings of the transmitter.
5.3.3 Diagnostic Section
Access the diagnostic section in the Signow software for
troubleshooting and monitoring the performance of the TxMini-M12
transmitter.
FAQ
Q: How do I reset the TxMini-M12 transmitter to factory
settings?
A: To reset the transmitter to factory settings, follow the
instructions provided in section 5.1 of this user guide.
“`
TXMINI-M12 TRANSMITTER
USER GUIDE V1.0x K
TxMini-M12
INTRODUCTION………………………………………………………………………………………………………………………………………………………………………3
SPECIFICATIONS ……………………………………………………………………………………………………………………………………………………………………4
2.1
ACCURACY……………………………………………………………………………………………………………………………………………………………..4
2.2
MEASUREMENT RANGE………………………………………………………………………………………………………………………………………….4
MECHANICAL INSTALLATION………………………………………………………………………………………………………………………………………………….5
ELECTRICAL INSTALLATION …………………………………………………………………………………………………………………………………………………..6
4.1
INSTALLATION RECOMMENDATIONS………………………………………………………………………………………………………………………6
4.2
POWER SUPPLY AND COMMUNICATION CONNECTION…………………………………………………………………………………………..6
4.3
SENSOR CONNECTION …………………………………………………………………………………………………………………………………………..6
4.4
M12 CABLE CONNECTION……………………………………………………………………………………………………………………………………….6
CONFIGURATION ……………………………………………………………………………………………………………………………………………………………………7
5.1
FACTORY SETTINGS……………………………………………………………………………………………………………………………………………….7
5.2
USING A TXCONFIG-M12 …………………………………………………………………………………………………………………………………………7
5.3
SIGNOW SOFTWARE ………………………………………………………………………………………………………………………………………………7
5.3.1 CONNECTING THE DEVICE TO YOUR COMPUTER………………………………………………………………………………………8
5.3.2 CONFIGURATION SECTION…………………………………………………………………………………………………………………………9
5.3.3 DIAGNOSTIC SECTION ……………………………………………………………………………………………………………………………….9
5.4
SIGNOW APP…………………………………………………………………………………………………………………………………………………………10
5.4.1 CONNECTING THE DEVICE TO YOUR SMARTPHONE ………………………………………………………………………………..10
5.4.2 RUNNING THE APP……………………………………………………………………………………………………………………………………10
OPERATION ………………………………………………………………………………………………………………………………………………………………………….12
WARRANTY …………………………………………………………………………………………………………………………………………………………………………..13
NOVUS AUTOMATION
2/13
TxMini-M12
1. INTRODUCTION
TxMini-M12 Transmitter is a two-wire 4-20 mA type temperature transmitter
powered by the current loop. To configure it, you must use the SigNow software
or app. The output current is linearized according to the signal applied to
the transmitter input and adjusted according to the configured scale.
NOVUS AUTOMATION
3/13
TxMini-M12
2. SPECIFICATIONS
FEATURES
TXMINI-M12
Sensor input
Configurable. The accepted sensors are listed in Table 2, with their
respective maximum measurement ranges.
Pt100: 3-wire type, 0.8 mA excitation, = 0.00384, according to NBR 13773. IEC
60751 (ITS-90). Pt1000: 3-wire type, 0.8 mA excitation, = 0.00384, according
to NBR 13773. IEC 60751 (ITS-90). To use 2-wire Pt1000, connect terminals 3
and 4.
Time between energizing and < 2.5 s.
stabilizing the measurement
Accuracy is only guaranteed after 15 minutes.
Reference conditions
Environment: 25 °C (77 °F). Power supply: 24 V. Load: 250 . Stabilization time: 15 minutes.
Temperature influence
< ± 0.2 % / 25 °C (77 °C).
Response time
Typically, 1.6 s.
Maximum acceptable voltage at the input terminals on the sensor
3 V.
RTD Current
800 µA.
Effect of RTD cable resistance
0.005 °C / .
Maximum admissible resistance of RTD cable
25 .
Power supply influence
0.006 % / V typically (maximum range percentage).
Output
4-20 mA or 20-4 mA current, 2-wire type. Linear in relation to the temperature measured by the selected sensor.
Output resolution
2 µA.
Power supply
8 to 35 Vdc.
Maximum load (RL)
RL (max.) = (Vdc 8) / 0.02 []. Where: Vdc = Power supply in Volts (from 8 to 35 Vdc).
Operating temperature
-40 to 85 °C (-40 to 185 °F).
Environment humidity
0 to 90 % RH.
Wire size used:
0.14 to 1.5 mm².
Recommended torque
0.8 Nm.
Housing
Polyamide.
No electrical isolation between input and output.
Internal protection against reversal polarity of voltage supply.
Table 1 Technical specifications
2.1 ACCURACY
SENSOR TYPE
TYPICAL ACCURACY MINIMUM ACCURACY
Pt100 / Pt1000
0.1 %
0.2 %
Table 2 Calibration error and measurement range percentages
2.2 MEASUREMENT RANGE
SENSOR TYPE MAXIMUM MEASUREMENT RANGE MINIMUM MEASUREMENT RANGE
Pt100
-200 to 650 °C (-328 to 1202 °F)
40 °C (104 °F)
Pt1000
-200 to 650 °C (-328 to 1202 °F)
40 °C (104 °)
Table 3 Sensors accepted by the transmitter
Order codes: · P/N: 8816021079: TxConfig-M12 Interface. · P/N: 8806065000: PVC sensor cable / 1 m / 4 positions / with M12 female connector (accessory). · P/N: 8806065100: PVC sensor cable / 3 m / 4 positions / with M12 female connector (accessory).
NOVUS AUTOMATION
4/13
TxMini-M12
3. MECHANICAL INSTALLATION
TxMini-M12 Transmitter is suitable for installation in pipes and in places
with limited space. Vibrations, excessive humidity and temperature,
electromagnetic interference, high voltage, and other interference can
permanently damage the transmitter and cause errors in the measured value.
Figure 1 Dimensions
NOVUS AUTOMATION
5/13
TxMini-M12
4. ELECTRICAL INSTALLATION
· The terminal housing is made of polyamide. · Wire size used: 0.14 to 1.5
mm².
4.1 INSTALLATION RECOMMENDATIONS
· Input signal conductors should run through the plant separate from output
and supply conductors. If possible, in grounded conduits. · The power supply
for electronic instruments must come from a network specific to the
instrumentation. · In control applications, it is essential to consider what
can happen when any part of the system fails. · It is recommended to use RC
FILTERS (noise suppressors) in contactor coils, solenoids, etc.
4.2 POWER SUPPLY AND COMMUNICATION CONNECTION
Terminal 2 is used to configure communication with the transmitter (use the TxConfig-M12 Configuration Interface). Terminal 4 is used to configure the connection to the cable mesh (if necessary).
1 2 3 4
Table 4 Power supply
LOOP + COMM LOOP SHIELD
4.3 SENSOR CONNECTION
Terminals 1, 2, and 3 are used to connect the sensor. Terminals 1 and 2 must
be connected, as shown in the figure below:
Figure 2 Pt100 / Pt1000 3-wire input
4.4 M12 CABLE CONNECTION
Below are the guidelines for making or purchasing a M12 cable:
PIN
PIN WIRE COLOR FUNCTION
1
Brown
Vdc
2
Black
D+
3
White
GND
4
Blue
D-
Table 5 Pins
Figure 3 M12 cable
For correct compensation of the RTD cable resistances, they must be equal at
all terminals and must not exceed 25 per cable. To guarantee these conditions,
it is recommended to use 3 or 4-wire cable of the same length and gauge (the
cable is not supplied).
NOVUS AUTOMATION
6/13
TxMini-M12
5. CONFIGURATION
The factory setting of the transmitter is for a Pt100 input with a range of 0
to 100 °C (32 to 212 °F) and output for maximum current in case of error. When
using the transmitter with this setting, no further commissioning is required.
In this case, its installation can be carried out immediately. When it is
necessary to change the configuration of the device, you must use the SigNow
software or app. To configure the device using the software, connect the
TxConfig-M12 Configuration Interface (purchased from the manufacturer or its
authorized representatives) to the USB port of the computer used and run
SigNow (see CONNECTING THE DEVICE TO YOUR COMPUTER section). To configure the
device using the app, you must use an OTG cable with the TxConfig-M12
Configuration Interface and then run the app and proceed with the recognition
process (see CONNECTING THE DEVICE TO YOUR SMARTPHONE section).
The TxConfig-M12 interface is NOT electrically isolated from the input
transmitter.
5.1 FACTORY SETTINGS
TxMini-M12 has the following factory settings: · 3-wire Pt100 sensor, range 0
to 100 °C (32 to 212 °F). · Maximum output for sensor failure. · Zero
correction: 0 °C (32 °F). · Unit: °C. · Output: 4 to 20 mA. In the purchase
order, it is possible to define a specific setting.
5.2 USING A TXCONFIG-M12
To change the configuration of your TxMini-M12, you must use the SigNow
software or app. To configure the device using the software, connect the
TxMini-485 to a TxConfig-M12 and then connect the TxConfig-M12 to the USB port
on the computer being used. To configure the device using the app, you also
need to use an OTG cable with the TxConfig-M12. When connected to the USB port
of the TxConfig-M12, the OTG cable (the other end must be inserted into the
USB port of the smartphone) will allow you to connect the device to your
smartphone. After this, you must run the SigNow app and proceed with the
recognition process (see CONNECTING THE DEVICE TO YOUR SMARTPHONE section).
The transmitter has no electrical insulation between input and output.
5.3 SIGNOW SOFTWARE
SigNow software is the main tool for configuring and analyzing data from
TxMini-M12. To install it, simply run the SigNowSetup.exe file and proceed
with the configuration. The software and its respective manual can be
downloaded for free in the Download Area of our website
www.novusautomation.com. This manual describes the generic functionalities of
SigNow. For more specific instructions on how to operate certain tools, check
the specific user guide.
NOVUS AUTOMATION
7/13
TxMini-M12
5.3.1 CONNECTING THE DEVICE TO YOUR COMPUTER
Once the TxConfig-M12 has been connected to the TxMini-M12, connect the
transmitter to the computer’s USB port and run SigNow, which will display the
following screen:
Figure 4 Home screen
To establish a communication, click on Configuration USB:
Figure 5 USB
NOVUS AUTOMATION
8/13
5.3.2 CONFIGURATION SECTION
By clicking on the General tab, you can configure the device:
TxMini-M12
Figure 6 Configuration Section
The bottom part of the screen displays information about the device, such as
name, serial number, and firmware version. 1. Sensor type: Allows you to
select the type of sensor to be used. 2. Temperature unit: Allows you to set
the temperature unit to be used. 3. Lower limit: Allows you to set the minimum
limit for the measurement range. 4. Upper limit: Allows you to set the maximum
limit for the measurement range. 5. Output status (Sensor failure): Allows you
to establish the behavior of the output when the transmitter indicates a
failure. 6. Output type: Allows you to set the type of output to be used. 7.
Zero correction: Allows you to correct small deviations in the transmitter
output that happen, for example, when the sensor is changed.
5.3.3 DIAGNOSTIC SECTION
By clicking on the Diagnostic tab, you can view the diagnostic data:
Figure 7 Diagnostic section
You can also access the Diagnostic section by clicking on the Diagnostic tab,
located on the left of the configuration screen.
NOVUS AUTOMATION
9/13
TxMini-M12
5.4 SIGNOW APP
The SigNow app is the ideal tool for using the TxMini-M12 on a daily basis.
Available for Android smartphones, it is always easily accessible for
monitoring or configuring the device. SigNow can be downloaded for free from
Google Play Store.
5.4.1 CONNECTING THE DEVICE TO YOUR SMARTPHONE
Android smartphones with On the Go (OTG) technology can be directly connected
to the device via the USB port. Using the TxConfig-M12 Configuration
Interface, TxMini-M12 can be recognized and configured when running the SigNow
app. To do this, you need to observe how to connect the OTG cable to the
device:
Figure 8 OTG Cable
1. If you position the cable end incorrectly, it is possible that the device
will not be recognized by the app. 2. iOS smartphones are not compatible with
the OTG cable.
5.4.2 RUNNING THE APP
When using an OTG cable and a TxConfig-M12 to connect the device to the
smartphone and run the SigNow app (see CONNECTING THE DEVICE TO YOUR
SMARTPHONE section), you must first approve the use of the TxConfig-M12, which
will act as an intermediary for the connection:
Figure 9 Using a TxConfig-M12
NOVUS AUTOMATION
10/13
After that, the app will recognize the device and show the main screen:
TxMini-M12
Figure 10 Main screen
To configure the device, simply click on the Configuration button to display
the main screen of the Configuration section:
Figure 11 Information screen
It displays information about the device, such as its name, serial number and
firmware version. When you open the Config section, you can configure the
parameters displayed in the CONFIGURATION SECTION. By clicking on Diagnostic,
you will be able to view information about the transmitter, according to the
DIAGNOSTIC SECTION. Apart from the particularities of the connection mode, the
parameters and division of information are the same as in the SigNow software.
More specific information about the application’s buttons can be found in the
SigNow manual, available on NOVUS website.
NOVUS AUTOMATION
11/13
TxMini-M12
6. OPERATION
You can use SigNow software or app to change the sensor Offset. The USB
connection can be made even when the transmitter is connected to the process
and operating, without causing errors in the measurement. You must choose the
sensor and range best suited to your process. The chosen range must not exceed
the maximum measurement range defined for the sensor and must not be smaller
than the minimum range for the same sensor. It is important to note that even
when setting an intermediate range, the transmitter’s accuracy is always based
on the maximum range of the sensor used. Example: · If the Pt100 sensor is in
the maximum range of -200 to 650 °C and the accuracy is 0.2 %, there will be a
maximum error of up to 1.7 °C (0.2 %
of 850 °C). · This error does not necessarily decrease as the range configured
for the sensor narrows (e.g. 0 to 100 °C). Note: When checking or calibrating
the transmitter, check that the Pt100 excitation current required by the
calibrator is compatible with the Pt100 excitation current used in this
instrument: 0.8 mA.
NOVUS AUTOMATION
12/13
7. WARRANTY
Warranty conditions are available on our website
www.novusautomation.com/warranty.
TxMini-M12
NOVUS AUTOMATION
13/13
References
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>